<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

General Specification - <strong>Air</strong> & Water Cooled Models<br />

ELECTRICAL DATA<br />

DF15X-EZ DF17X-EZ DF22X2-EZ DF25X2-EZ<br />

DF15WX-EZ DF17WX-EZ DF22WX2-EZ DF25WX2-EZ<br />

Standard Matched Condensers - X C25 C35 C45 C45<br />

Unit Data - X (1)<br />

Nominal Run Amps A 29.20 30.10 44.10 44.10<br />

Maximum Start Amps A 86.90 94.90 87.60 87.60<br />

Recommended Mains Fuse Size A 40 40 50 50<br />

Max Mains Incoming Cable Size mm² 35 35 35 35<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit VAC 24 24 24 24<br />

Unit Data - WX (1)<br />

Nominal Run Amps A 29.20 30.10 44.10 44.10<br />

Maximum Start Amps A 86.90 94.90 87.60 87.60<br />

Recommended Mains Fuse Size A 40 40 50 50<br />

Max Mains Incoming Cable Size mm² 35 35 35 35<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit VAC 24 24 24 24<br />

Evaporator Fan - Per Fan<br />

Quantity/Motor Size kW 1 x 1.1 1 x 1.1 2 x 0.6 2 x 0.6<br />

Full Load Amps A 10.0 10.0 7.7 7.7<br />

Locked Rotor Amps A 25.0 25.0 20.5 20.5<br />

Compressor - Per Compressor<br />

Quantity 1 1 2 2<br />

Nominal Run Amps A 8.3 9.2 6.5 6.5<br />

Locked Rotor Amps A 66.0 74.0 50.0 50.0<br />

Motor Size kW 5.6 6.5 4.7 4.7<br />

Type of Start Direct On Line<br />

Matched Outdoor Condenser - Per Fan<br />

Quantity/Motor Size kW 1 x 0.6 1 x 0.6 2 x 0.6 2 x 0.6<br />

Full Load Amps A 2.62 2.62 2.62 2.62<br />

OPTIONAL EXTRAS<br />

Electric Heating<br />

Stage of Reheat 1 1 2 2<br />

Number of Elements 3 3 6 6<br />

Rating (Total) kW 7.5 7.5 15.0 15.0<br />

Current Per Phase A 10.9 10.9 21.8 21.8<br />

Humidifier<br />

Capacity kg/hr 0.60 - 3.00 0.60 - 3.00 0.60 - 3.00 0.60 - 3.00<br />

Rating kW 2.25 2.25 2.25 2.25<br />

Full Load Amps A 3.50 3.50 3.50 3.50<br />

Larger Fan Motor - Per Fan<br />

Quantity / Motor Size kW N/A N/A N/A N/A<br />

Full Load Amps A N/A N/A N/A N/A<br />

Locked Rotor Amps A N/A N/A N/A N/A<br />

(1) Values given for full function units (incl. electric heating, humidification and matched condenser) at ARI conditions with standard fan motors, for<br />

optional data, please contact <strong><strong>Air</strong>edale</strong>.