Technical Manual Downflow - Airedale International Air Conditioning
Technical Manual Downflow - Airedale International Air Conditioning
Technical Manual Downflow - Airedale International Air Conditioning
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
AIR & WATER COOLED<br />
32<br />
-DF<br />
Precision <strong>Air</strong> <strong>Conditioning</strong><br />
<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />
Precision <strong>Air</strong> <strong>Conditioning</strong><br />
General Specification - <strong>Air</strong> & Water Cooled Models<br />
ELECTRICAL DATA<br />
DF15X-EZ DF17X-EZ DF22X2-EZ DF25X2-EZ<br />
DF15WX-EZ DF17WX-EZ DF22WX2-EZ DF25WX2-EZ<br />
Standard Matched Condensers - X C25 C35 C45 C45<br />
Unit Data - X (1)<br />
Nominal Run Amps A 29.20 30.10 44.10 44.10<br />
Maximum Start Amps A 86.90 94.90 87.60 87.60<br />
Recommended Mains Fuse Size A 40 40 50 50<br />
Max Mains Incoming Cable Size mm² 35 35 35 35<br />
Mains Supply V 400V / 3PH + N / 50Hz<br />
Control circuit VAC 24 24 24 24<br />
Unit Data - WX (1)<br />
Nominal Run Amps A 29.20 30.10 44.10 44.10<br />
Maximum Start Amps A 86.90 94.90 87.60 87.60<br />
Recommended Mains Fuse Size A 40 40 50 50<br />
Max Mains Incoming Cable Size mm² 35 35 35 35<br />
Mains Supply V 400V / 3PH + N / 50Hz<br />
Control circuit VAC 24 24 24 24<br />
Evaporator Fan - Per Fan<br />
Quantity/Motor Size kW 1 x 1.1 1 x 1.1 2 x 0.6 2 x 0.6<br />
Full Load Amps A 10.0 10.0 7.7 7.7<br />
Locked Rotor Amps A 25.0 25.0 20.5 20.5<br />
Compressor - Per Compressor<br />
Quantity 1 1 2 2<br />
Nominal Run Amps A 8.3 9.2 6.5 6.5<br />
Locked Rotor Amps A 66.0 74.0 50.0 50.0<br />
Motor Size kW 5.6 6.5 4.7 4.7<br />
Type of Start Direct On Line<br />
Matched Outdoor Condenser - Per Fan<br />
Quantity/Motor Size kW 1 x 0.6 1 x 0.6 2 x 0.6 2 x 0.6<br />
Full Load Amps A 2.62 2.62 2.62 2.62<br />
OPTIONAL EXTRAS<br />
Electric Heating<br />
Stage of Reheat 1 1 2 2<br />
Number of Elements 3 3 6 6<br />
Rating (Total) kW 7.5 7.5 15.0 15.0<br />
Current Per Phase A 10.9 10.9 21.8 21.8<br />
Humidifier<br />
Capacity kg/hr 0.60 - 3.00 0.60 - 3.00 0.60 - 3.00 0.60 - 3.00<br />
Rating kW 2.25 2.25 2.25 2.25<br />
Full Load Amps A 3.50 3.50 3.50 3.50<br />
Larger Fan Motor - Per Fan<br />
Quantity / Motor Size kW N/A N/A N/A N/A<br />
Full Load Amps A N/A N/A N/A N/A<br />
Locked Rotor Amps A N/A N/A N/A N/A<br />
(1) Values given for full function units (incl. electric heating, humidification and matched condenser) at ARI conditions with standard fan motors, for<br />
optional data, please contact <strong><strong>Air</strong>edale</strong>.