AIR & WATER COOLED<br />

26<br />

-DF<br />

Performance Data - <strong>Air</strong> & Water Cooled Models<br />

COOLING DUTIES - WX TYPE MODELS<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Cooling Capacity (1) Condenser Entering / Leaving Temperature - Based on ΔT of 5°C<br />

25°C /30°C 30°C /35°C 35°C/40°C 40°C/45°C<br />

<strong>Air</strong> On °C DB TC SC THR TC SC THR TC SC THR TC SC THR<br />

/%RH (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)<br />

22 / 50 6.7 6.0 8.9 6.5 5.9 8.5 6.2 5.7 8.2 5.9 5.6 7.9<br />

DF6WX-EZ<br />

24 / 45 6.9 6.6 9.0 6.6 6.4 8.7 6.4 6.3 8.4 6.1 6.1 8.1<br />

26 / 40 7.1 7.1 9.2 6.8 6.8 8.9 6.5 6.5 8.5 6.2 6.2 8.2<br />

22 / 50 9.4 8.1 11.6 9.1 8.0 11.5 8.7 7.8 11.3 8.4 7.6 11.2<br />

DF8WX-EZ<br />

24 / 45 9.7 8.8 11.9 9.4 8.6 11.8 9.0 8.5 11.6 8.7 8.3 11.5<br />

26 / 40 10.0 9.5 12.2 9.6 9.4 12.0 9.3 9.2 11.9 8.9 8.9 11.7<br />

22 / 50 10.8 9.7 13.0 10.4 9.5 13.0 10.0 9.3 12.9 9.6 9.1 12.8<br />

DF10WX-EZ<br />

24 / 45 11.1 10.5 13.4 10.7 10.3 13.3 10.4 10.1 13.3 10.0 9.8 13.2<br />

26 / 40 11.4 11.3 13.7 11.1 11.0 13.7 10.8 10.8 13.6 10.4 10.4 13.6<br />

22 / 50 14.3 11.7 16.7 13.7 11.5 16.6 13.2 11.2 16.5 12.5 11.0 16.4<br />

DF13WX-EZ<br />

24 / 45 14.7 12.8 17.1 14.1 12.6 17.0 13.5 12.3 16.9 12.9 12.0 16.7<br />

26 / 40 15.0 14.1 17.4 14.4 13.9 17.3 13.8 13.7 17.2 13.2 13.2 17.0<br />

22 / 50 17.4 14.2 19.7 16.7 13.8 19.7 16.0 13.6 19.8 15.3 13.2 19.8<br />

DF15WX-EZ<br />

24 / 45 17.9 15.4 20.2 17.0 15.0 20.2 16.5 14.8 20.2 15.7 14.5 20.2<br />

26 / 40 18.3 16.7 20.6 17.4 16.3 20.6 16.9 16.1 20.6 16.1 15.8 20.6<br />

22 / 50 20.4 17.6 22.9 19.6 17.2 23.2 19.0 16.9 23.5 18.1 16.4 23.9<br />

DF17WX-EZ<br />

24 / 45 20.9 19.0 23.4 20.2 18.7 23.8 19.5 18.3 24.1 18.6 17.9 24.5<br />

26 / 40 21.4 20.6 23.9 20.6 20.2 24.2 19.9 19.8 24.6 19.1 19.1 24.9<br />

22 / 50 25.8 20.6 28.5 24.6 20.1 29.0 23.6 19.7 29.5 22.5 19.2 30.0<br />

DF22WX2-EZ<br />

24 / 45 27.0 22.6 29.8 25.9 22.1 30.3 24.9 21.6 30.7 23.8 21.1 31.2<br />

26 / 40 27.8 24.4 30.6 26.7 23.9 31.0 25.7 23.4 31.5 24.5 22.9 31.9<br />

22 / 50 27.0 22.6 29.8 25.9 22.0 30.2 24.9 21.6 30.6 23.7 21.0 31.1<br />

DF25WX2-EZ<br />

24 / 45 27.8 24.6 30.6 26.7 24.1 31.1 25.7 23.7 31.5 24.5 23.1 32.0<br />

26 / 40 28.6 26.9 31.4 27.5 26.3 31.9 26.5 25.8 32.2 25.2 25.1 32.7<br />

22 / 50 28.3 25.2 31.3 27.3 24.6 31.9 26.3 24.1 32.6 25.1 23.5 33.2<br />

DF26WX-EZ<br />

24 / 45 29.1 27.2 32.1 28.1 26.6 32.7 27.0 26.1 33.3 25.8 25.5 34.0<br />

26 / 40 29.8 29.3 32.8 28.7 28.7 33.4 27.6 27.6 34.0 26.5 26.5 34.7<br />

22 / 50 29.0 26.9 32.0 28.0 26.4 32.6 26.9 25.8 33.2 25.7 25.1 33.9<br />

DF28WX-EZ<br />

24 / 45 29.8 29.2 32.9 28.8 28.6 33.4 27.7 27.7 34.0 26.5 26.5 34.6<br />

26 / 40 29.7 29.7 32.8 28.6 28.6 33.6 27.5 27.5 34.3 26.6 26.6 35.1<br />

22 / 50 32.6 30.8 35.8 31.5 30.2 36.7 30.3 29.5 37.6 29.0 28.8 38.5<br />

DF31WX-EZ<br />

24 / 45 33.6 33.3 36.8 32.5 32.5 37.7 31.3 31.3 38.6 30.0 30.0 39.4<br />

26 / 40 34.2 34.2 37.5 33.1 33.1 38.4 31.9 31.9 39.2 30.6 30.6 40.2<br />

22 / 50 38.9 36.5 42.5 37.5 35.7 43.6 36.0 34.9 44.7 34.4 34.0 45.8<br />

DF35WX-EZ<br />

24 / 45 40.0 39.6 43.7 38.6 38.6 44.8 37.1 37.1 45.9 35.5 35.5 47.0<br />

26 / 40 40.9 40.9 44.6 39.5 39.5 45.7 38.0 38.0 46.7 36.3 36.3 47.8<br />

22 / 50 42.7 40.6 46.8 41.1 39.8 48.0 39.6 38.9 49.4 38.1 38.1 50.7<br />

DF40WX-EZ<br />

24 / 45 44.4 44.4 48.4 43.1 43.1 49.8 41.6 41.6 51.2 40.0 40.0 52.7<br />

26 / 40 45.4 45.4 49.4 44.1 44.1 50.8 42.7 42.7 52.3 41.1 41.1 53.8<br />

22 / 50 48.1 43.4 51.8 46.5 42.6 53.4 44.9 41.7 55.0 43.1 40.7 56.7<br />

DF45WX-EZ<br />

24 / 45 49.4 46.9 53.2 47.8 46.1 54.7 46.1 45.2 56.4 44.3 44.2 57.9<br />

26 / 40 50.4 50.4 54.3 48.9 48.9 55.8 47.1 47.1 57.4 45.3 45.3 59.0<br />

22 / 50 55.7 49.7 60.0 54.0 48.8 61.9 52.0 47.7 63.9 50.0 46.6 65.8<br />

DF50WX2-EZ<br />

24 / 45 56.0 53.6 60.5 54.0 52.5 62.3 51.9 51.3 64.2 50.0 50.0 66.0<br />

26 / 40 58.4 57.8 62.8 56.6 56.6 64.7 54.6 54.6 66.6 52.6 52.6 68.5<br />

22 / 50 61.6 53.0 66.4 59.6 51.9 68.4 57.3 50.7 70.5 54.9 49.4 72.6<br />

DF55WX2-EZ<br />

24 / 45 63.3 57.0 68.2 61.2 55.9 70.1 58.9 54.7 72.2 56.5 53.5 74.2<br />

26 / 40 64.8 61.3 69.7 62.6 60.2 71.6 60.2 59.0 73.6 57.8 57.8 75.6<br />

22 / 50 65.5 56.9 70.6 63.3 55.7 72.7 60.8 54.4 74.9 58.3 53.0 77.1<br />

DF60WX2-EZ<br />

24 / 45 67.1 61.3 72.3 64.9 60.1 74.4 62.4 58.8 76.6 59.9 57.5 78.7<br />

26 / 40 69.8 66.8 75.2 67.8 65.8 77.7 65.7 64.7 80.2 63.6 63.6 82.8<br />

TC = Total Cooling SC = Sensible Cooling THR = Total Heat of Rejection<br />

(1) All data quoted is gross.<br />

(2) Deduct fan motor gain for nett duties, refer to Mechanical Data in this section.<br />

(3) Interpolate for water temperatures between those quoted, do not extrapolate.<br />

(4) Water flow rate (l/s) = THR ÷ (4.19 x T) at 100% Water. For glycol use, refer to Ethylene Glycol Correction Factors in this section.<br />

OPERATING LIMITS - WX TYPE MODELS<br />

Cooling<br />

Indoor <strong>Air</strong> Temperature +18°C to +28°C<br />

Indoor RH% +40% to +55%<br />

Condenser Minimum Entering Temperature °C +25°C<br />

Condenser Maximum Leaving Water Temperature °C +45°C<br />