GENERAL<br />

22<br />

-DF<br />

Design Features & Information<br />

CONDENSATE PUMP (OPTIONAL EXTRA)<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Performance The following graphs illustrate the TOTAL static (head) pressure available. The system<br />

horizontal pipe losses and vertical lift should be factored in when calculating the<br />

condensate pump performance.<br />

Sizes 6 - 25<br />

Sizes 26 - 60<br />

IMPORTANT<br />

Head (m)<br />

Head (m)<br />

12<br />

10<br />

8<br />

6<br />

4<br />

2<br />

0<br />

12<br />

10<br />

8<br />

6<br />

4<br />

2<br />

0<br />

5 7 9 11 13 15<br />

Pump Flow Rate (l/min)<br />

5 7 9 11 13 15<br />

Pump Flow Rate (l/min)<br />

Use only 10mm (3/8”) copper tube when connecting the discharge stub to the<br />

condensate pump. The discharge line from the pump should rise no more than 6<br />

meters vertically and no more than 8 metres in total length before being<br />

interrupted with a swan neck air break and tundish.