CONDENSATE PUMP (OPTIONAL EXTRA)<br />
Precision <strong>Air</strong> <strong>Conditioning</strong><br />
<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />
Precision <strong>Air</strong> <strong>Conditioning</strong><br />
Performance The following graphs illustrate the TOTAL static (head) pressure available. The system<br />
horizontal pipe losses and vertical lift should be factored in when calculating the<br />
condensate pump performance.<br />
Sizes 6 - 25<br />
Sizes 26 - 60<br />
IMPORTANT<br />
Head (m)<br />
Head (m)<br />
12<br />
10<br />
8<br />
6<br />
4<br />
2<br />
0<br />
12<br />
10<br />
8<br />
6<br />
4<br />
2<br />
0<br />
5 7 9 11 13 15<br />
Pump Flow Rate (l/min)<br />
5 7 9 11 13 15<br />
Pump Flow Rate (l/min)<br />
Use only 10mm (3/8”) copper tube when connecting the discharge stub to the<br />
condensate pump. The discharge line from the pump should rise no more than 6<br />
meters vertically and no more than 8 metres in total length before being<br />
interrupted with a swan neck air break and tundish.