GENERAL<br />

18<br />

-DF<br />

STANDARD FEATURES<br />

Evaporator Fan Hours<br />

Run Log & Reset<br />

Head Pressure Control<br />

and Condenser Fan<br />

Speed Controller<br />

Evaporator Fan Speed<br />

Controller<br />

Sizes 6 - 25<br />

Controls<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Allows the user to monitor the running times of the evaporator fans and reset<br />

after maintenance.<br />

Each refrigerant circuit (TEV or EEV) is fitted with condenser pressure transducers and a<br />

modulating condenser fan speed controller to allow the designed head pressure to be<br />

monitored and maintained under varying ambient conditions. Condenser fan speed<br />

control settings are input via the display keypad.<br />

Evaporator fan speed control is easily set via the display keypad and can be<br />

incrementally increased or decreased to meet on site airflow and external static<br />

pressure requirements.<br />

Filter Change Alarm Filter change is managed by the <strong>Air</strong>eTronix software, and is based on fan(s) hours run<br />

with an alarm being generated when the pre-set run time limit has been exceeded. The<br />

set-point value can be adjusted to suit each application and is factory set to 2000 hours.<br />

LPHW Frost Protection<br />

(DX units with LPHW<br />

option)<br />

OPTIONAL EXTRAS<br />

Upgraded Controller<br />

Sizes 26 - 60<br />

The coil temperature sensor is mounted on the DX coil and has a fixed 3°C low limit<br />

setting to disable DX cooling.<br />

The microprocessor controller is upgraded when the Filter Change Switch<br />

option is selected, refer to Indoor Unit, Optional Extras - General, Filter Change Switch.<br />

However, the controller can also be upgraded to provide for applications requiring specific<br />

alarm handling such as; filter dirty, fire, flood, phase failure, critical / non critical alarms<br />

and the ability to disable heating and humidification. Please contact <strong><strong>Air</strong>edale</strong> for details.<br />

Real Time Clock A real time clock card can be fitted to the microprocessor to provide date and<br />

time stamping on alarms. Occupied and unoccupied set points can also be configured for<br />

temperature, humidity and head pressure control settings.<br />

This option is enabled by the inclusion of a clock card within the microprocessor, supplied<br />

as standard with this option.<br />

Networking A Local Area Network ( ) can be used to connect upto 6 units to offer<br />

intercommunication and Duty/Standby control. This also allows the connection of<br />

computers, printers and modems on the same communications ring. For further details,<br />

please contact <strong><strong>Air</strong>edale</strong> Controls.<br />

CAUTION<br />

When adding to an existing network, please consult <strong><strong>Air</strong>edale</strong> to ensure strategy<br />

compatibility.