GENERAL<br />

16<br />

-DF<br />

Controls<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

GENERAL As standard the units are supplied with an microprocessor controller<br />

connected to a 4x20 back-lit LCD display keypad.<br />

TEMPERATURE<br />

CONTROL<br />

The microprocessor controller can be linked together locally to provide<br />

run/standby operation. Windows based supervisor software is also available for local or<br />

remote networking. This modular approach provides great flexibility while at the same<br />

time reducing installation and maintenance costs.<br />

The display keypad features a simple array of keys to navigate through the in<br />

built menus.<br />

For enhanced alarm monitoring, an upgraded controller can be fitted, refer to Controls -<br />

Optional Extras.<br />

A temperature sensor is mounted in the return air with an option for a humidity sensor on<br />

full function units.<br />

The temperature sensor is a NTC type thermistor accurate up to +/- 0.25°C and the<br />

humidity sensor accurate to +/- 3% at 25°C at the sensor.<br />

The microprocessor senses the return air conditions and maintains the return<br />

air temperature and humidity conditions by controlling cooling, heating, humidification and<br />

dehumidification outputs accordingly.<br />

The microprocessor monitors and displays the following values:<br />

Return <strong>Air</strong> Temperature<br />

Return <strong>Air</strong> Humidity (Optional on Full Function units)<br />

Condensing Pressure (Optional on DX units only)<br />

Coil Temperature Sensor (Indoor)<br />

ALARM HANDLING A visual alarm will be generated under the following conditions:<br />

Return air temperature high limit<br />

Return air temperature low limit<br />

Return air humidity high limit (Optional on Full Function units)<br />

Return air humidity low limit (Optional on Full Function units)<br />

Frost protection low limit (LPHW option only)<br />

<strong>Air</strong>flow failure<br />

Compressor failure (Optional on DX units only)<br />

Low pressure trip (Optional on DX units only)<br />

Electric Heating Overheat cut-out<br />

Filter change alarm<br />

<strong>Manual</strong> override<br />

Common alarm<br />

Power fail reset<br />

Communications failure<br />

Humidifier alarm (Full Function units only)<br />

Maintenance - fan and compressor (once hours run limit exceeded)