GENERAL<br />

12<br />

-DF<br />

General Description<br />

OPTIONAL EXTRAS - GENERAL<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Firestat Installed in the return air stream to shut down the unit in the event of an unusually high<br />

return air temperature.<br />

Smoke Detector Supplied loose for remote mounting to shut down the unit and activate the alarm upon<br />

sensing the presence of smoke.<br />

Chilled Water Bypass<br />

Balancing Valves<br />

2 Port Chilled Water<br />

Control Valve<br />

0-10 Volt DC Chilled<br />

Water Regulating Valve<br />

Threaded Connection<br />

(WX & CW Models)<br />

Phase Rotation<br />

Protection<br />

(X & WX Models)<br />

Bypass balancing valves can be fitted to aid commissioning and unit operation by<br />

creating the same pressure drop through the bypass as through the chilled water coil.<br />

For systems with variable speed pumps and water flow, a 2 port control valve can be<br />

fitted in place of the standard 3 port valve.<br />

Designed to optimise the regulation of water flow for special applications. A 0-10 volt DC<br />

chilled water regulating valve can be fitted in place of the standard raise/lower<br />

regulating valve.<br />

BSP brass male taper threaded connections can be factory fitted.<br />

A phase sequence relay is available for units containing 3 phase scroll compressors, to<br />

prevent possible damage by running the compressor in the wrong direction.<br />

Alternative Refrigerant For applications outside the EU, units can be supplied for use with R22, please specify<br />

at order.<br />

Export Packing Units can be supplied packed inside a case to provide additional protection during<br />

transportation, (not required for container delivery).<br />

Standard construction material is solid wood.<br />

Optionally, construction can be of pest treated manufactured board (Stirling Board).<br />

Please specify at order.