VER<br />

<strong>Downflow</strong> – Precision <strong>Air</strong> <strong>Conditioning</strong><br />

6 kW - 60 kW<br />

TECHNICAL MANUAL


2<br />

-DF<br />

AB OUT AIR ED AL E<br />

About <strong><strong>Air</strong>edale</strong> Products & Customer Services<br />

WARRANTY<br />

Warranty is only valid in the<br />

event that<br />

CAUTION<br />

SPARES<br />

TRAINING<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

All AIAC products or parts (non consumable) supplied for installation within the UK mainland and<br />

commissioned by an AIAC engineer, carry a full Parts & Labour warranty for a period of 12 months<br />

from the date of commissioning or 18 months from the date of despatch, whichever is the sooner.<br />

Parts or Equipment supplied by AIAC for installation within the UK or for Export that are properly<br />

commissioned in accordance with AIAC standards and specification, not commissioned by an AIAC<br />

engineer; carry a 12 month warranty on non consumable Parts only from the date of commissioning<br />

or 18 months from the date of despatch, whichever is the sooner.<br />

Parts or equipment installed or commissioned not to acceptable AIAC standards or specification<br />

invalidate all warranty.<br />

In the period between delivery and commissioning the equipment: is properly protected & serviced as<br />

per the AIAC installation & maintenance manual provided where applicable the glycol content is<br />

maintained to the correct level.<br />

In the event of a problem being reported and once warranty is confirmed as valid under the given<br />

installation and operating conditions, the Company will provide the appropriate warranty coverage<br />

(as detailed above) attributable to the rectification of any affected <strong><strong>Air</strong>edale</strong> equipment supplied<br />

(excluding costs for any specialist access or lifting equipment that must be ordered by the customer).<br />

Any spare part supplied by <strong><strong>Air</strong>edale</strong> under warranty shall be warranted for the unexpired period of<br />

the warranty or 3 months from delivery, whichever period is the longer.<br />

To be read in conjunction with the <strong><strong>Air</strong>edale</strong> Conditions of Sale - Warranty and Warranty Procedure,<br />

available upon request.<br />

Warranty cover is not a substitute for maintenance. Warranty cover is conditional to maintenance<br />

being carried out in accordance with the recommendations provided during the warranty period.<br />

Failure to have the maintenance procedures carried out will invalidate the warranty and any liabilities<br />

by <strong><strong>Air</strong>edale</strong> <strong>International</strong> <strong>Air</strong> <strong>Conditioning</strong> Ltd.<br />

A spares list for 1, 3 and 5 years will be supplied with every unit and is also available from our<br />

Spares department on request.<br />

As well as our comprehensive range of products, <strong><strong>Air</strong>edale</strong> offers a modular range of Refrigeration<br />

and <strong>Air</strong> <strong>Conditioning</strong> Training courses, for further information please contact <strong><strong>Air</strong>edale</strong>.<br />

CUSTOMER SERVICES For further assistance, please e-mail: enquiries@airedale.com or telephone:<br />

Customer Services<br />

Legal Notices<br />

UK Sales Enquiries + 44 (0) 113 238 7789 enquiries@airedale.com<br />

<strong>International</strong> Enquiries + 44 (0) 113 239 1000 enquiries@airedale.com<br />

Spares Hot Line + 44 (0) 113 238 7878 spares@airedale.com<br />

<strong><strong>Air</strong>edale</strong> Service + 44 (0) 113 239 1000 service@airedale.com<br />

<strong>Technical</strong> Support + 44 (0) 113 239 1000 tech.support@airedale.com<br />

Training Enquiries + 44 (0) 113 239 1000 marketing@airedale.com<br />

For information, visit us at our Web Site: www.airedale.com<br />

AIAC Ltd endeavours to ensure that the information in this document is correct and fairly stated, but<br />

none of the statements are to be relied upon as a statement or representation of fact. AIAC Ltd does<br />

not accept liability for any error or omission, or for any reliance placed on the information contained<br />

in this document.<br />

The development of <strong><strong>Air</strong>edale</strong> products and services is continuous and the information in this<br />

document may not be up to date. It is important to check the current position with AIAC Ltd at the<br />

address stated. This document is not part of a contract or licence unless expressly agreed.<br />

No part of this document may be reproduced or transmitted in any form or by any means, electronic<br />

or mechanical, including photocopying, recording, or information storage and retrieval systems, for<br />

any purpose other than the purchaser’s personal use, without the express written permission of<br />

AIAC Ltd.<br />

2013 <strong><strong>Air</strong>edale</strong> <strong>International</strong> <strong>Air</strong> <strong>Conditioning</strong> Limited. All rights reserved. Printed in the UK.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

CONTENT S<br />

Contents<br />

Warranty ................................................................................................................................................. 2<br />

General Description 4<br />

Unit Identification .................................................................................................................................... 4<br />

Introduction ............................................................................................................................................. 4<br />

Standard Features .................................................................................................................................. 5<br />

Optional Extras - Energy Saving ............................................................................................................. 9<br />

Optional Extras - General........................................................................................................................ 9<br />

Dimensional Data 13<br />

Dimensions ........................................................................................................................................... 13<br />

Weights ................................................................................................................................................ 13<br />

Positioning ............................................................................................................................................ 15<br />

Controls 16<br />

Standard Features ................................................................................................................................ 17<br />

Optional Extras ..................................................................................................................................... 18<br />

Sound Data 20<br />

Method of Sound Measurement ............................................................................................................ 20<br />

Design Features & Information 21<br />

Electronic Expansion Valves (EEV)....................................................................................................... 21<br />

Condensate Pump (Optional Extra)....................................................................................................... 22<br />

Humidification ....................................................................................................................................... 23<br />

AIR COOLED (X) & WATER COOLED (WX) MODELS 24<br />

Performance Data - <strong>Air</strong> & Water Cooled Models 24<br />

Cooling Duties - X Type Models ............................................................................................................ 24<br />

Operating Limits - X Type Models ......................................................................................................... 24<br />

Cooling Duties - WX Type Models ........................................................................................................ 26<br />

Operating Limits - WX Type Models ...................................................................................................... 26<br />

General Specification - <strong>Air</strong> & Water Cooled Models 27<br />

Mechanical Data ................................................................................................................................... 27<br />

Electrical Data ...................................................................................................................................... 31<br />

Sound Data - <strong>Air</strong> & Water Cooled Models 35<br />

Design Data - <strong>Air</strong> & Water Cooled Models 37<br />

Waterside Pressure Drop (kPa) - WX Type Models .............................................................................. 37<br />

Low Pressure Hot Water (Optional Extra) - X & WX Type Models ......................................................... 38<br />

System Pipework Schematic ................................................................................................................. 39<br />

Refrigerant Pipe Sizing Guide - X Type Models .................................................................................... 40<br />

Refrigerant Charging Guide - X Type Models ........................................................................................ 40<br />

Ethylene Glycol Correction Factors ....................................................................................................... 42<br />

Interconnecting Wiring .......................................................................................................................... 43<br />

CHILLED WATER (CW) MODELS 44<br />

Performance Data - Chilled Water Models 44<br />

Cooling Duties ...................................................................................................................................... 44<br />

General Specification - Chilled Water Models 45<br />

Mechanical Data ................................................................................................................................... 45<br />

Electrical Data ...................................................................................................................................... 49<br />

Sound Data - Chilled Water Models 51<br />

Design Data - Chilled Water Models 53<br />

Waterside Pressure Drop (kPa) ............................................................................................................ 53<br />

Low Pressure Hot Water (Optional Extra) ............................................................................................. 53<br />

System Pipework Schematic ................................................................................................................. 54<br />

Ethylene Glycol Correction Factors ....................................................................................................... 55<br />

Interconnecting Wiring .......................................................................................................................... 56<br />

OUTDOOR UNITS - AIR COOLED CONDENSERS 57<br />

General Description 57<br />

Unit Identification .................................................................................................................................. 57<br />

Introduction ........................................................................................................................................... 57<br />

Standard Features ................................................................................................................................ 57<br />

Optional Extras ..................................................................................................................................... 58<br />

Dimensional Data 59<br />

General Specification 62<br />

Mechanical Data ................................................................................................................................... 62<br />

Electrical Data ...................................................................................................................................... 64<br />

Interconnecting Wiring .......................................................................................................................... 64<br />

Performance Data 65<br />

Capacity Data ....................................................................................................................................... 65<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

3


GENERAL<br />

4<br />

-DF<br />

Indoor Unit<br />

General Description<br />

UNIT IDENTIFICATION<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

EASICOOL PRECISION AIR CONDITIONING RANGE<br />

DF <strong>Downflow</strong> Configuration<br />

6-60 Model Size (Expressed as Nominal Cooling in kW)<br />

X <strong>Air</strong> Cooled Remote Condenser<br />

WX Water Cooled<br />

CW Chilled Water<br />

2 Tandem Compressor Set<br />

EZ Series - EasiCool<br />

Example DF22X2-EZ<br />

INTRODUCTION Designed to provide environmental Precision air conditioning for applications such as<br />

Telecommunication Facilities, Computer Rooms, Clean Rooms and laboratories, the<br />

EasiCool range is available 17 models as direct expansion air cooled, 17 models as<br />

Water Cooled or 17 models as chilled water all single circuit. Full function units provide<br />

full control of temperature, humidity and filtration.<br />

CE DIRECTIVE<br />

The modular design of the EasiCool allows for flexible installation by grouping same or<br />

differing models and capacities to be installed side by side, thus providing multi<br />

circuit functionality.<br />

A full range of air cooled condensers is available with the direct expansion indoor units to<br />

provide a matched system with optional performance upgrade, refer to Outdoor Units - <strong>Air</strong><br />

Cooled Condensers.<br />

Also available is a full range of <strong><strong>Air</strong>edale</strong> water chillers to complement the chilled water<br />

indoor units.<br />

The unit is designed for the use of R407C, please refer to Optional Extras - General for<br />

alternative refrigerants.<br />

This manual covers the full range of <strong>Downflow</strong> configured models. For Upflow<br />

configured models, please refer to the Upflow <strong>Technical</strong> <strong>Manual</strong>.<br />

<strong><strong>Air</strong>edale</strong> certify that the equipment detailed in this manual conforms with the following<br />

EC Directives:<br />

Electromagnetic Compatibility Directive (EMC) 2004/108/EC<br />

Low Voltage Directive (LVD) 2006/95/EC<br />

Machinery Directive (MD) 89/392/EEC in the version<br />

2006/42/EC<br />

Pressure Equipment Directive (PED) 97/23/EC<br />

To comply with these directives appropriate national & harmonised standards have been<br />

applied. These are listed on the Declaration of Conformity, supplied with each product.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

General Description<br />

STANDARD FEATURES<br />

Construction The cabinet comprises an anodised aluminium frame with black nylon corners and<br />

removable galvanised sheet steel panels. The unit panels are manufactured from<br />

galvanised sheet steel coated with epoxy baked powder paint to provide a durable finish.<br />

Standard unit colour is Light Grey (RAL 7035).<br />

Cabinets are lined internally with fire resistant foam (UL94 V0) thermal and<br />

acoustic insulation:<br />

30mm deep for removable panels<br />

12mm deep for remaining internal surfaces<br />

As standard, the cabinet doors are full height and secured by M6 bolts, a 4mm Allen key<br />

is provided for access.<br />

Hinged and lock type doors are available as an option, please refer to Optional<br />

Extras - General.<br />

Unit design incorporates a series of M6 fixings to the top and bottom face for offering up<br />

customer ductwork, please contact <strong><strong>Air</strong>edale</strong> for further details.<br />

Sizes 6 - 25 Dependent upon model type, components such as the expansion valve, compressor,<br />

humidifier and sight glass are contained within an acoustically lined enclosure to provide<br />

both ease of maintenance and to minimise sound emission.<br />

Evaporator Large surface area coil(s) ideally positioned to optimise airflow and heat transfer,<br />

manufactured from refrigeration quality copper tube with mechanically bonded<br />

aluminium fins.<br />

The copper tube is internally rifled for improved heat transfer.<br />

Fins are coated with a non-stick acrylic film (hydrophilic) which provides additional<br />

corrosion protection and efficient surface water removal for improved performance.<br />

The cooling coil is mounted over a full width stainless steel condensate tray.<br />

Factory pressure tested to 40Bar.<br />

X Models Only Sweat copper pipe for brazed connection as standard.<br />

Condenser<br />

(WX Models)<br />

Stainless steel high efficiency brazed plate heat exchanger(s) will allow optimum heat<br />

transfer between media.<br />

Factory pressure tested to 40Bar.<br />

Sweat copper pipe for brazed connection as standard. Optional threaded connections<br />

available refer to Optional Extras - General.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

5<br />

GENERAL


GENERAL<br />

6<br />

-DF<br />

General Description<br />

STANDARD FEATURES<br />

Chilled Water Coil<br />

(CW Models)<br />

Fan & Motor Assembly<br />

Size 6 - 25<br />

(Direct Drive)<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Large surface area coil(s) ideally positioned to optimise airflow and heat transfer,<br />

manufactured from refrigeration quality copper tubes with mechanically bonded<br />

aluminium fins.<br />

Fins are coated with a non-stick acrylic film (hydrophilic) which provides additional<br />

corrosion protection and efficient surface water removal for improved performance.<br />

The cooling coil is mounted over a full width stainless steel condensate tray.<br />

For control of water flow, a 3 port, raise/lower type, modulating mixing control valve is<br />

fitted as standard.<br />

Maximum operating pressure 10bar. Factory pressure tested to 20Bar.<br />

Sweat copper pipe for brazed connection as standard. Optional threaded connections<br />

available refer to Optional Extras - General.<br />

Units utilise a double inlet, forward curved, direct drive centrifugal fan with integral shaft<br />

mounted motor which is statically and dynamically balanced for quiet operation. Impellers<br />

and casings are galvanised for protection against corrosion. The integral motor runs in<br />

sealed for life, lubricated bearings and features automatic thermal overload protection.<br />

Fan speed, airflow and external static pressure are controlled by the use of a manually<br />

adjustable voltage controller via the microprocessor display keypad which offers easy on<br />

site adjustment.<br />

Adjustable by increments of 1% within + / - 10% of the set point.<br />

Sizes 6 - 17 Units have a single fan and motor assembly.<br />

Sizes 22 - 25 Units have 2 fan and motor assemblies.<br />

Size 26 - 60<br />

(Belt & Pulley)<br />

Double inlet forward curved centrifugal fan(s) with galvanised impellers and casing.<br />

Mild steel fan shaft with lifetime lubricated ball bearings.<br />

Fan and drive assembly design is based on a minimum of 25,000 hours life expectancy.<br />

Each fan assembly is separately driven by a high efficiency air cooled motor through a<br />

pulley and ‘V’ belt drive. The complete motor assembly is mounted on a fully adjustable<br />

platform for belt tensioning. Motor specification conforms to Efficiency Class 2 (EFF2).<br />

With integrated plummer block bearings (4kW motors only).<br />

Sizes 26 - 45 Units have a single fan and motor assembly.<br />

Sizes 50 - 60 Units have 2 fan and motor assemblies.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

General Description<br />

STANDARD FEATURES<br />

<strong>Air</strong>flow Switch An adjustable differential pressure switch activates a visual alarm at the status panel and<br />

breaks the power supply in the event of a fan or motor failure.<br />

Compressor Compressor(s) are mounted on the base via the use of vibration isolators. Each<br />

compressor is designed for use with R407C refrigerant.<br />

X & WX Models Utilise a single hermetic scroll compressor fitted as standard with:<br />

Thermal motor protection Internal or external (dependent upon model size)<br />

High temperature discharge protection<br />

X2 & WX2 Models Utilise a Tandem hermetic scroll compressor set, to provide 2 stages of control, fitted as<br />

standard with:<br />

Thermal motor protection Internal or external (dependent upon model size)<br />

High temperature discharge protection<br />

Sight glass<br />

For further details, refer to Design Features & Information, Tandem Compressors.<br />

Refrigeration Each refrigeration circuit features as standard:<br />

X Models Externally equalised thermostatic expansion valve (TEV)<br />

Sight glass<br />

Filter drier (loose)<br />

Low pressure switch - manual reset<br />

High pressure switch - manual reset<br />

Liquid line pressure transducer<br />

Holding charge of Inert Gas<br />

WX Models Externally equalised thermostatic expansion valve (TEV)<br />

Sight glass<br />

Head Pressure Control (3 way mechanical)<br />

Filter drier<br />

Low pressure switch - manual reset<br />

High pressure switch - manual reset<br />

Liquid line pressure transducer<br />

Full operating charge of R407C<br />

Bleed valve<br />

Binder points<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

7<br />

GENERAL


GENERAL<br />

8<br />

-DF<br />

General Description<br />

STANDARD FEATURES<br />

Head Pressure Control -<br />

Intelligent Modulation<br />

(X Models)<br />

Head Pressure Control<br />

(WX Models)<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

The system is fitted with a voltage regulating fan speed controller which allows set point<br />

adjustment and system monitoring via the indoor unit<br />

microprocessor controller.<br />

A pressure transducer is fitted to the liquid line which in turn feeds back the head<br />

pressure to the microprocessor. The condenser fan speed can then modulate via the<br />

controller to provide optimum control under varying ambient conditions. The head<br />

pressure can be monitored via the display keypad.<br />

Units fitted with thermostatic expansion valves have the head pressure factory set to<br />

17 barg (247 psig).<br />

Units fitted with optional electronic expansion valves have the head pressure factory set<br />

to 14 barg (203 psig).<br />

A 3 way mechanical regulating valve senses the compressor head pressure and allows<br />

cooling water to flow to the condenser, to by-pass the condenser, or to allow water flow to<br />

both condenser and by-pass line in order to maintain correct refrigerant head pressure.<br />

A pressure transducer is fitted to the liquid line which enables the head pressure to be<br />

monitored via the display keypad.<br />

Filters Pleated disposable panel filters in a rigid frame. Conform to BS EN 779-G4.<br />

Access and removal from unit front.<br />

As standard the microprocessor provides an alarm following a pre set run<br />

time limit being exceeded, refer to Controls -Filter Change Alarm.<br />

Electrical The control panel contains the necessary compressor starter contactors, transformer, sub<br />

circuit protection, volt free contacts for a common alarm and mains and inter-connecting<br />

terminals. The panel is situated within the cabinet and can be removed for essential<br />

maintenance of other components within the unit. The electrical control panels are wired<br />

to the latest European standards and codes of practice.<br />

Sub Fusing The electrical mains supply for the system’s outdoor unit(s) is supplied via the indoor unit.<br />

MCBs are fitted for protection.<br />

Main Electric Isolator To ensure complete unit isolation of the electrical panel during adjustment and<br />

maintenance a door interlocking isolator is provided as standard.<br />

Controls Units are fitted with the microprocessor controller which offers powerful<br />

analogue and digital control to meet a wide range of monitoring and control. Features a<br />

communication port plus networking and BMS connections.<br />

A 4 x 20 character backlit LCD display keypad assembly is used to view the unit status<br />

and allow operator adjustment.<br />

For full details, please refer to the Controls section.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

General Description<br />

OPTIONAL EXTRAS - ENERGY SAVING<br />

Electronic Expansion<br />

Valves (EEV)<br />

(X & WX Models)<br />

OPTIONAL EXTRAS - GENERAL<br />

Low Noise Feature for<br />

Condenser Fan<br />

(X Models)<br />

Humidifier - Intelligent<br />

Modulation<br />

Electronic expansion valves differ to the normal thermostatic expansion valves in their<br />

ability to maintain control of the suction superheat at reduced head pressures. This can<br />

lead to significant energy savings particularly at reduced loading and low<br />

ambient temperatures.<br />

EEV step position, superheat setpoint, head pressure set point and other features can be<br />

viewed and adjusted via the microprocessor display.<br />

Factory fitted, for full details refer to Design Features & Information section, Electronic<br />

Expansion Valves.<br />

Specifically designed for night time operation as optimum low noise levels are achieved<br />

with reduced ambient temperature and room loads, this feature is also ideal for residential<br />

and other outdoor noise critical applications.<br />

Initiated by setting the microprocessor programmable time clock, the head pressure set<br />

point changes from the standard 14 barg (203 psig) (TEV) or 17 barg (247 psig) (optional<br />

EEV) to 22 barg (319 psig), reducing the outdoor unit fan speed and corresponding<br />

operating sound levels.<br />

This feature is enabled by the inclusion of an optional clock card within<br />

the microprocessor.<br />

Humidification is provided by an electrode boiler. The sealed humidifier design ensures<br />

that only clean sterile steam is supplied to the conditioned area and corrosive salts and<br />

minerals are held in the disposable bottle. The steam is distributed through a sparge pipe<br />

fitted to the coil assembly.<br />

Featuring modulating capacity output control as standard, the system provides<br />

continuous modulation of steam output in response to a proportional control signal. The<br />

output control range is 20%-100% of the humidifier rated value and is designed to give an<br />

approximate steam output of +/- 3% at 25°C at the sensor, thus ensuring precise control<br />

of the conditioned space.<br />

The cylinder operating life time is automatically optimised via the integrated water<br />

conductivity sensor, which combined with the controls monitors and regulates<br />

the water refill cycle to reduce excessive salt deposits and the progressive wear of the<br />

cylinder. For further details, refer to Design Features & Information section, Humidification.<br />

All humidifier parameters and alarms are accessible and adjustable via the<br />

microprocessor display keypad unit, main features include:<br />

Supply water conductivity (S/cm)<br />

Actual steam output (kg/h)<br />

Required steam output (kg/h)<br />

Actual current rating (A)<br />

Required current rating (A)<br />

Status mode (Start Up, Running, Filling, Draining)<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

9<br />

GENERAL


GENERAL<br />

10<br />

-DF<br />

General Description<br />

OPTIONAL EXTRAS - GENERAL<br />

Water Conductivity &<br />

Cylinder Type<br />

Heating Options<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Conductivity is a measure of the ability of water to pass an electric current, measured in<br />

micro Siemens / centimetre (S/cm). 3 different cylinders are available which correspond<br />

to the supply water conductivity.<br />

Matching the correct cylinder type with the conductivity of the supply water ensures<br />

optimum performance and increases the life span of the cylinder.<br />

1 Low Conductivity (Soft Water) 100 to 350 S/cm<br />

2 Standard Conductivity (Moderate/Hard Water) 350 to 750 S/cm<br />

3 High Conductivity (Very Hard Water) 750 to 1250 S/cm<br />

As standard the humidifier is fitted with the standard conductivity cylinder which covers<br />

the majority of water supplies. Where the water conductivity is known, please specify at<br />

order. For further details please contact <strong><strong>Air</strong>edale</strong>.<br />

CAUTION The supply water pressure to the humidifier assembly must be between 1 - 8 barg.<br />

Electric Heating Multi-stage finned electric heating elements complete with auto and manual reset<br />

overheat cut-out protection.<br />

Electric Heating Thyristor<br />

Control<br />

Sizes 26 - 60<br />

Standard electric heating elements are phase balanced for increased efficiency.<br />

Offers precision control between 0 - 100% via the microprocessor.<br />

Or<br />

Low Pressure Hot Water A low pressure hot water coil constructed of refrigeration quality copper tube and<br />

mechanically bonded aluminium fins can be factory fitted.<br />

Filter Change Switch<br />

Sizes 26 - 60<br />

Frost protection is fitted to prevent freezing of the low pressure hot water coil assembly.<br />

Proportional heating control is provided by a factory fitted 3 port, raise/lower type,<br />

modulating valve.<br />

Access to the RHS of the unit is required to set up the regulating valve, refer to<br />

Installation Data - Positioning.<br />

A solid state filter differential pressure switch can be fitted to provide an alarm at the<br />

controller to indicate the need for filter maintenance. The microprocessor is<br />

upgraded to facilitate this feature and in doing so offers further improved alarm handling,<br />

refer to Controls - Upgraded Controller.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

General Description<br />

OPTIONAL EXTRAS - GENERAL<br />

Larger Fan & Motor<br />

Assembly<br />

Condensate Pump<br />

For applications where higher static air pressures are required, a larger fan and motor<br />

assembly size can be fitted to replace the standard assembly.<br />

Refer to Mechanical Data for availability.<br />

Sizes 6 - 25 The condensate pump has a 3 litre reservoir with a capacity of 5 l/m at a head of 8m and<br />

is mounted in the unit base, for pump performance, refer to Condensate Pump (Optional<br />

Extra).<br />

Sizes 26 - 60 The condensate pump has a 6 litre reservoir with a capacity of 5 l/m at a head of 10.8m<br />

and is mounted in the unit base, for pump performance; refer to Condensate Pump<br />

(Optional Extra).<br />

Easy Access Doors For improved ease of access, hinged and lock type doors can be fitted.<br />

Plain Doors - No Display<br />

Keypad<br />

Open & Enclosed<br />

Floorstand<br />

Discharge <strong>Air</strong><br />

Configuration<br />

Networking is a standard option of the <strong>Air</strong>eTronix microprocessor, refer to<br />

Controls - Optional Extras section for full details. To reduce costs, the “slave” units can be<br />

supplied with plain doors (no display keypad), in all door types, please specify at order.<br />

Open or enclosed floorstands are available, complete with adjustable feet and floor tile<br />

lip. Enclosed floorstands incorporate an air turning vane. Height of the floorstand; please<br />

specify at order, refer to Installation Data - Minimum Unit Clearance.<br />

Standard configuration is forward air discharge. Reverse air discharge is available,<br />

please specify at order, refer to Positioning.<br />

Ceiling Duct Extension Straight and ‘L’ shaped duct extensions up to a height of 1350mm constructed and<br />

finished to match the unit are available.<br />

Services Side Access<br />

Gland Plate<br />

For extensions greater than 1350mm, please contact <strong><strong>Air</strong>edale</strong>.<br />

Height; please specify at order.<br />

As standard services can be routed through the gland plate in the base of the units. A<br />

gland plate can be optionally located to the lower left hand side face of the unit, if<br />

required, refer to Dimensions.<br />

Water Detector 2 methods are available:<br />

1 A solid state (probe) sensor is supplied loose for remote mounting on site.<br />

2 Tape suitable for sensing water droplets is supplied loose for remote mounting on<br />

site. Standard tape length 10m.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 11<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

GENERAL


GENERAL<br />

12<br />

-DF<br />

General Description<br />

OPTIONAL EXTRAS - GENERAL<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Firestat Installed in the return air stream to shut down the unit in the event of an unusually high<br />

return air temperature.<br />

Smoke Detector Supplied loose for remote mounting to shut down the unit and activate the alarm upon<br />

sensing the presence of smoke.<br />

Chilled Water Bypass<br />

Balancing Valves<br />

2 Port Chilled Water<br />

Control Valve<br />

0-10 Volt DC Chilled<br />

Water Regulating Valve<br />

Threaded Connection<br />

(WX & CW Models)<br />

Phase Rotation<br />

Protection<br />

(X & WX Models)<br />

Bypass balancing valves can be fitted to aid commissioning and unit operation by<br />

creating the same pressure drop through the bypass as through the chilled water coil.<br />

For systems with variable speed pumps and water flow, a 2 port control valve can be<br />

fitted in place of the standard 3 port valve.<br />

Designed to optimise the regulation of water flow for special applications. A 0-10 volt DC<br />

chilled water regulating valve can be fitted in place of the standard raise/lower<br />

regulating valve.<br />

BSP brass male taper threaded connections can be factory fitted.<br />

A phase sequence relay is available for units containing 3 phase scroll compressors, to<br />

prevent possible damage by running the compressor in the wrong direction.<br />

Alternative Refrigerant For applications outside the EU, units can be supplied for use with R22, please specify<br />

at order.<br />

Export Packing Units can be supplied packed inside a case to provide additional protection during<br />

transportation, (not required for container delivery).<br />

Standard construction material is solid wood.<br />

Optionally, construction can be of pest treated manufactured board (Stirling Board).<br />

Please specify at order.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Dimensional Data<br />

DIMENSIONS<br />

DF6 - DF25<br />

Standard <strong>Air</strong>flow Configuration (mm)<br />

670<br />

670<br />

640<br />

15<br />

640<br />

15<br />

1940<br />

1940<br />

270<br />

270<br />

200<br />

200<br />

C<br />

6 - 10 13 - 17 22 - 25<br />

670<br />

D<br />

B<br />

A<br />

F<br />

G<br />

200<br />

15<br />

990<br />

B<br />

A<br />

200<br />

15<br />

B<br />

1310<br />

C D<br />

C D<br />

E<br />

D<br />

4<br />

A<br />

5<br />

B<br />

200<br />

15<br />

1 2<br />

H x W x D A B (6) C (7) D (7) E F (8) G (7)<br />

DF6 X/WX/CW mm 1940 x 670 x 670 640 270 216 (183) 238 (304) N/A 50 (157) 268 (268)<br />

DF8 X/WX/CW mm 1940 x 670 x 670 640 270 183 (167) 304 (337) N/A 50 (157) 268 (295)<br />

DF10 X/WX/CW mm 1940 x 670 x 670 640 270 167 (167) 337 (337) N/A 50 (186) 295 (295)<br />

DF13 X/WX/CW mm 1940 x 990 x 670 960 590 326 (326) 337 (337) N/A 50 (186) 295 (295)<br />

DF15 X/WX/CW mm 1940 x 990 x 670 960 590 294 (N/A) 401 (N/A) N/A 50 (210) 347 (N/A)<br />

DF17 X/WX/CW mm 1940 x 990 x 670 960 590 294 (N/A) 401 (N/A) N/A 50 (210) 347 (N/A)<br />

DF22 X2/WX2/CW mm 1940 x 1310 x 670 1280 455 166 (166) 337 (337) 303 50 (186) 295 (295)<br />

DF25 X2/WX2/CW mm 1940 x 1310 x 670 1280 455 166 (N/A) 337 (N/A) 303 50 (186) 295 (N/A)<br />

(1) Standard Forward <strong>Air</strong>flow Direction.<br />

(2) Optional Reverse <strong>Air</strong>flow Direction.<br />

(3) Optional Gland Plate and Panel for side services access via the right side of unit.<br />

(4) Base Mains Cable Entry.<br />

(5) Standard Base Gland Plate Entry for Refrigeration/Water Services.<br />

(6) M6 fixing hole positions.<br />

(7) Figures in brackets represent position of Fan Discharge Aperture when Larger Fan Motor Option is fitted.<br />

(8) Figures in brackets represent optional reverse air discharge configuration.<br />

WEIGHTS<br />

DF6 - DF25<br />

Machine /<br />

Machine (1)<br />

Operating<br />

DF6X kg 185 DF6WX kg 200 / 202 DF6CW kg 155<br />

DF8X kg 196 DF8WX kg 214 / 216 DF8CW kg 165<br />

DF10X kg 200 DF10WX kg 218 / 220 DF10CW kg 168<br />

DF13X kg 222 DF13WX kg 243 / 244 DF13CW kg 195<br />

DF15X kg 235 DF15WX kg 262 / 264 DF15CW kg 200<br />

DF17X kg 238 DF17WX kg 268 / 270 DF17CW kg 200<br />

DF22X2 kg 304 DF22WX2 kg 341 / 344 DF22CW kg 252<br />

DF25X2 kg 304 DF25WX2 kg 341 / 344 DF25CW kg 252<br />

(1) Machine weight includes a refrigerant charge / Operating weight includes calculated water volume, refer to Mechanical Data.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 13<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

3<br />

Machine<br />

GENERAL


GENERAL<br />

14<br />

-DF<br />

Dimensional Data<br />

750<br />

750<br />

DIMENSIONS<br />

DF26 - DF60<br />

Standard <strong>Air</strong>flow Configuration (mm)<br />

710<br />

20<br />

710<br />

20<br />

1940<br />

210<br />

330<br />

1940<br />

210<br />

330<br />

26 - - 31<br />

C<br />

1460<br />

D<br />

B B<br />

B<br />

A<br />

F<br />

G<br />

210<br />

20<br />

35 - - 45<br />

C<br />

1835<br />

D<br />

B B<br />

B<br />

A<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

F<br />

G<br />

210<br />

20<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

4<br />

C<br />

50 - - 60<br />

D<br />

2170<br />

E<br />

B B B<br />

B<br />

A<br />

D<br />

5<br />

F<br />

G<br />

210<br />

20<br />

3<br />

1 2<br />

H x W x D A B (6) C (7) D (7) E F (8) G (7)<br />

DF26 X/WX/CW mm 1940 x 1460 x 750 1420 347 540 379 N/A 91 (113) 546<br />

DF28 X/WX/CW mm 1940 x 1460 x 750 1420 347 540 379 N/A 91 (113) 546<br />

DF31 X/WX/CW mm 1940 x 1460 x 750 1420 347 540 379 N/A 91 (113) 546<br />

DF35 X/WX/CW mm 1940 x 1835 x 750 1795 472 679 477 N/A 91 (113) 546<br />

DF40 X/WX/CW mm 1940 x 1835 x 750 1795 472 679 477 N/A 91 (113) 546<br />

DF45 X/WX/CW mm 1940 x 1835 x 750 1795 472 679 477 N/A 91 (113) 546<br />

DF50 X2/WX2/CW mm 1940 x 2170 x 750 2130 438 206 401 543 76 (257) 345<br />

DF55 X2/WX2/CW mm 1940 x 2170 x 750 2130 438 206 401 543 76 (257) 345<br />

DF60 X2/WX2/CW mm 1940 x 2170 x 750 2130 438 206 401 543 76 (257) 345<br />

(1) Standard Forward <strong>Air</strong>flow Direction.<br />

(2) Optional Reverse <strong>Air</strong>flow Direction.<br />

(3) Optional Gland Plate and Panel for side services access via the right side of unit.<br />

(4) Base Mains Cable Entry.<br />

(5) Standard Base Gland Plate Entry for Refrigeration/Water Services.<br />

(6) M6 fixing hole positions.<br />

(7) Figures in brackets represent position of Fan Discharge Aperture when Larger Fan Motor Option is fitted.<br />

(8) Figures in brackets represent optional reverse air discharge configuration.<br />

WEIGHTS<br />

DF26 - DF60<br />

Machine /<br />

Machine (1)<br />

Operating<br />

Machine<br />

DF26X kg 452 DF26WX kg 503 / 509 DF26CW kg 351<br />

DF28X kg 452 DF28WX kg 503 / 509 DF28CW kg 351<br />

DF31X kg 459 DF31WX kg 510 / 516 DF31CW kg 354<br />

DF35X kg 501 DF35WX kg 555 / 561 DF35CW kg 410<br />

DF40X kg 522 DF40WX kg 581 / 587 DF40CW kg 431<br />

DF45X kg 550 DF45WX kg 628 / 638 DF45CW kg 442<br />

DF50X2 kg 665 DF50WX2 kg 747 / 756 DF50CW kg 486<br />

DF55X2 kg 678 DF55WX2 kg 761 / 771 DF55CW kg 499<br />

DF60X2 kg 674 DF60WX2 kg 757 / 767 DF60CW kg 495<br />

(1) Machine weight includes a refrigerant charge / Operating weight includes calculated water volume, refer to Mechanical Data.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Dimensional Data<br />

POSITIONING Standard Return<br />

Minimum Unit Clearance<br />

(2)<br />

(1)<br />

A B C - Floorstand (4) D (5)<br />

DF6 - DF10 mm 670 610 Min 200 - Max 750<br />

Min 300<br />

DF13 - DF17 mm 990 610 (+ 50mm Feet<br />

Min 300<br />

DF25 - DF25 mm 1310 610 Adjustable +/- 20mm)<br />

Min 300<br />

DF26 - DF31 mm 1460 700 Min 300 - Max 800<br />

N/A<br />

DF35 - DF45 mm 1835 700 (+ 50mm Feet<br />

N/A<br />

DF50 - DF60 mm 2170 700 Adjustable +/- 20mm)<br />

N/A<br />

Minimum Ceiling Clearance (2)<br />

Forward Only Forward & 1 Side Forward & 2 Sides All Faces<br />

DF6 - DF10 mm 470 240 160 120<br />

DF13 - DF17 mm 550 330 240 170<br />

DF22 - DF25 mm 560 370 280 190<br />

DF26 - DF31 mm 620 410 310 210<br />

DF35 - DF45 mm 640 450 350 230<br />

DF50 - DF60 mm 640 480 380 240<br />

(1) Shown with optional open floor stand.<br />

(2) Minimum Ceiling Clearance, refer to table.<br />

(3) Shaded area indicates minimum service and maintenance requirements.<br />

(4) Dimension C denotes recommended minimum/maximum floorstand height, refer to <strong><strong>Air</strong>edale</strong> for special applications.<br />

(5) Dimension D refers to units fitted with LPHW which require access to the RHS of the unit to set up the regulating valve.<br />

(6) SERVICES SIDE ACCESS GLAND PLATE, OPTIONAL POSITION; ensure appropriate clearance is available to the base of the RHS of the<br />

unit if this option is selected.<br />

(6)<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 15<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

GENERAL


GENERAL<br />

16<br />

-DF<br />

Controls<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

GENERAL As standard the units are supplied with an microprocessor controller<br />

connected to a 4x20 back-lit LCD display keypad.<br />

TEMPERATURE<br />

CONTROL<br />

The microprocessor controller can be linked together locally to provide<br />

run/standby operation. Windows based supervisor software is also available for local or<br />

remote networking. This modular approach provides great flexibility while at the same<br />

time reducing installation and maintenance costs.<br />

The display keypad features a simple array of keys to navigate through the in<br />

built menus.<br />

For enhanced alarm monitoring, an upgraded controller can be fitted, refer to Controls -<br />

Optional Extras.<br />

A temperature sensor is mounted in the return air with an option for a humidity sensor on<br />

full function units.<br />

The temperature sensor is a NTC type thermistor accurate up to +/- 0.25°C and the<br />

humidity sensor accurate to +/- 3% at 25°C at the sensor.<br />

The microprocessor senses the return air conditions and maintains the return<br />

air temperature and humidity conditions by controlling cooling, heating, humidification and<br />

dehumidification outputs accordingly.<br />

The microprocessor monitors and displays the following values:<br />

Return <strong>Air</strong> Temperature<br />

Return <strong>Air</strong> Humidity (Optional on Full Function units)<br />

Condensing Pressure (Optional on DX units only)<br />

Coil Temperature Sensor (Indoor)<br />

ALARM HANDLING A visual alarm will be generated under the following conditions:<br />

Return air temperature high limit<br />

Return air temperature low limit<br />

Return air humidity high limit (Optional on Full Function units)<br />

Return air humidity low limit (Optional on Full Function units)<br />

Frost protection low limit (LPHW option only)<br />

<strong>Air</strong>flow failure<br />

Compressor failure (Optional on DX units only)<br />

Low pressure trip (Optional on DX units only)<br />

Electric Heating Overheat cut-out<br />

Filter change alarm<br />

<strong>Manual</strong> override<br />

Common alarm<br />

Power fail reset<br />

Communications failure<br />

Humidifier alarm (Full Function units only)<br />

Maintenance - fan and compressor (once hours run limit exceeded)


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

STANDARD FEATURES<br />

User Friendly Display<br />

Keypad<br />

Controls<br />

The default screen shows the unit status and room condition (°C/RH %) without the need<br />

for interrogation and an easy to navigate menu structure for further interrogation<br />

and adjustment.<br />

The controller logs and allows viewing of the last 100 conditions recorded in descending<br />

chronological order through the keypad display<br />

Password Protection The control system integrity can be maintained by restricting access with a password<br />

PIN number.<br />

CAUTION<br />

IMPORTANT: To change the PIN number, please contact <strong><strong>Air</strong>edale</strong> at time of order<br />

with the preferred 4 digit number.<br />

Remote On/Off Terminals for interlocking are provided to enable or disable the unit remotely.<br />

Fire Shut Down Terminals for interlocking are provided to shut down the unit in the event of fire.<br />

Compressor Anti-Cycle<br />

Control<br />

Programmed to provide automatic anti-cycling delays of up to 10 starts per hour with a<br />

minimum off time of 3 minutes.<br />

Compressor Rotation On tandem compressor units the controller is programmed to provide automatic<br />

compressor rotation to ensure equal compressor running times. In the event of a<br />

compressor fault on networked systems the controller is programmed to automatically<br />

select the next compressor in order of running hours.<br />

Compressor Hours Run<br />

Log & Reset<br />

Allows the user to monitor the running times of each compressor and reset<br />

after maintenance.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 17<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

GENERAL


GENERAL<br />

18<br />

-DF<br />

STANDARD FEATURES<br />

Evaporator Fan Hours<br />

Run Log & Reset<br />

Head Pressure Control<br />

and Condenser Fan<br />

Speed Controller<br />

Evaporator Fan Speed<br />

Controller<br />

Sizes 6 - 25<br />

Controls<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Allows the user to monitor the running times of the evaporator fans and reset<br />

after maintenance.<br />

Each refrigerant circuit (TEV or EEV) is fitted with condenser pressure transducers and a<br />

modulating condenser fan speed controller to allow the designed head pressure to be<br />

monitored and maintained under varying ambient conditions. Condenser fan speed<br />

control settings are input via the display keypad.<br />

Evaporator fan speed control is easily set via the display keypad and can be<br />

incrementally increased or decreased to meet on site airflow and external static<br />

pressure requirements.<br />

Filter Change Alarm Filter change is managed by the <strong>Air</strong>eTronix software, and is based on fan(s) hours run<br />

with an alarm being generated when the pre-set run time limit has been exceeded. The<br />

set-point value can be adjusted to suit each application and is factory set to 2000 hours.<br />

LPHW Frost Protection<br />

(DX units with LPHW<br />

option)<br />

OPTIONAL EXTRAS<br />

Upgraded Controller<br />

Sizes 26 - 60<br />

The coil temperature sensor is mounted on the DX coil and has a fixed 3°C low limit<br />

setting to disable DX cooling.<br />

The microprocessor controller is upgraded when the Filter Change Switch<br />

option is selected, refer to Indoor Unit, Optional Extras - General, Filter Change Switch.<br />

However, the controller can also be upgraded to provide for applications requiring specific<br />

alarm handling such as; filter dirty, fire, flood, phase failure, critical / non critical alarms<br />

and the ability to disable heating and humidification. Please contact <strong><strong>Air</strong>edale</strong> for details.<br />

Real Time Clock A real time clock card can be fitted to the microprocessor to provide date and<br />

time stamping on alarms. Occupied and unoccupied set points can also be configured for<br />

temperature, humidity and head pressure control settings.<br />

This option is enabled by the inclusion of a clock card within the microprocessor, supplied<br />

as standard with this option.<br />

Networking A Local Area Network ( ) can be used to connect upto 6 units to offer<br />

intercommunication and Duty/Standby control. This also allows the connection of<br />

computers, printers and modems on the same communications ring. For further details,<br />

please contact <strong><strong>Air</strong>edale</strong> Controls.<br />

CAUTION<br />

When adding to an existing network, please consult <strong><strong>Air</strong>edale</strong> to ensure strategy<br />

compatibility.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

OPTIONAL EXTRAS<br />

Controls<br />

Duty/Standby Operation The controller enables units to operate in run/standby mode, with up to 6 units networked<br />

together, without the need for additional hardware or controllers. Standby units can be<br />

configured to start when the run unit has a critical alarm and/or a high/low return air<br />

temperature alarm.<br />

Duty Rotation Networked units can be configured to duty rotate, providing equal hours run of fans<br />

and compressors.<br />

BMS Interface Card Enables Controlled units to be interfaced with most BMS, factory fitted,<br />

please contact <strong><strong>Air</strong>edale</strong>.<br />

Plain Doors - No Display<br />

Keypad<br />

A wide range of protocols can be accommodated through the use of interface devices.<br />

Available as a standard option are: ModBus/Jbus, Carel and Trend.<br />

For interfaces such as SNMP, LonWorks, Metasys and BACnet, please contact <strong><strong>Air</strong>edale</strong>.<br />

To reduce costs, the “slave” units can be supplied with plain doors (no display keypad),<br />

please specify at order.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 19<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

GENERAL


GENERAL<br />

Sound Data<br />

20<br />

-DF<br />

METHOD OF SOUND MEASUREMENT<br />

Measurement of Sound<br />

Data<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

All sound data quoted has been measured in the third-octave band limited values, using<br />

a Real Time Analyser calibrated sound intensity meter in accordance with<br />

BS EN ISO9614 Part 1 : 1995.<br />

All Sound Power Levels quoted are calculated from measured sound intensity according<br />

BS EN ISO9614 Part 1 : 1995.<br />

Semi Hemispherical Sound Pressure Levels are calculated from sound power using the semi-hemispherical<br />

method where the noise source is in junction with 2 boundaries i.e. the floor and 1 wall.<br />

Free Field For comparison, the semi hemispherical figures can typically be reduced by 3dB to<br />

provide free field conditions.<br />

IMPORTANT<br />

The sound data quoted is based on the unit having a ducted return air and ducted<br />

(or underfloor) discharge air application.<br />

Case breakout sound data is therefore independent of the discharge air and return<br />

air sound data.<br />

For non-ducted return air applications, the overall case breakout sound levels may<br />

increase, due to the return air sound being predominant.<br />

Within the conditioned space, sound from in-room ducted discharge air grilles and<br />

other equipment will contribute to the overall sound level and should therefore be<br />

considered as part of sound calculations.<br />

Specialist acoustic advice is recommended for noise critical applications.<br />

(1)<br />

(2)<br />

(3)<br />

(1)Return <strong>Air</strong><br />

(2)Case Breakout<br />

(3)Discharge <strong>Air</strong><br />

(1) Return <strong>Air</strong><br />

(2) Case Breakout<br />

(3) Discharge <strong>Air</strong>


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Design Features & Information<br />

ELECTRONIC EXPANSION VALVES (EEV)<br />

Thermostatic<br />

Expansion Valves (TEV)<br />

Electronic Expansion<br />

Valves (EEV)<br />

Reduced Condensing<br />

Pressure<br />

Evaporating Pressure<br />

Whilst offering versatile control at the full design duty of the unit, standard TEVs do not<br />

automatically optimise themselves to all operating conditions. Therefore, if the<br />

refrigeration system is operating at 40% or 50% of full load, especially at a lower ambient<br />

temperature than that for which the valve was sized, the conventional TEV must have the<br />

design head pressure available to ensure good refrigerant control. Maintaining an<br />

artificially high condensing pressure is normal in conventional systems.<br />

Using an EEV allows for good refrigeration control whilst operating at part load and lower<br />

ambient conditions with a reduced condensing pressure. By fitting an EEV and adjusting<br />

the head pressure control setting an increase in the system EER (Energy Efficiency<br />

Ratio) of up to 30% can typically be seen. The Mollier diagram shown below helps to<br />

illustrate how this increase in efficiency is achieved.<br />

EEV’s differ to normal thermostatic expansion valves in their ability to maintain control of<br />

refrigerant flow and the suction superheat at reduced head pressures. The turn-down rate<br />

of a typical EEV is superior to that of it’s thermostatic equivalent, such that a reduced<br />

optimum condensing pressure can be maintained at low compressor load. However low<br />

the load is on the compressor, from zero to 100%, there will not be a problem with turn<br />

down, even down to 10% of the valves rated capacity.<br />

1<br />

Pressure (Bara)<br />

Key<br />

3<br />

Increase in<br />

Cooling Duty<br />

Bubble<br />

4<br />

2<br />

Enthalpy (kJ/kg)<br />

Dew<br />

1<br />

Reduction in<br />

Compressor<br />

Input Power<br />

1 Compression<br />

2 Condensation<br />

3 Expansion<br />

4 Evaporation<br />

Cooling Cycle @ 22°C ambient with a conventional TEV fitted.<br />

Cooling cycle @ 22°C ambient, demonstrating a typical EEV condensing<br />

temperature taking full advantage of lower ambient air temperatures (below 35°C).<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 21<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

GENERAL


GENERAL<br />

22<br />

-DF<br />

Design Features & Information<br />

CONDENSATE PUMP (OPTIONAL EXTRA)<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Performance The following graphs illustrate the TOTAL static (head) pressure available. The system<br />

horizontal pipe losses and vertical lift should be factored in when calculating the<br />

condensate pump performance.<br />

Sizes 6 - 25<br />

Sizes 26 - 60<br />

IMPORTANT<br />

Head (m)<br />

Head (m)<br />

12<br />

10<br />

8<br />

6<br />

4<br />

2<br />

0<br />

12<br />

10<br />

8<br />

6<br />

4<br />

2<br />

0<br />

5 7 9 11 13 15<br />

Pump Flow Rate (l/min)<br />

5 7 9 11 13 15<br />

Pump Flow Rate (l/min)<br />

Use only 10mm (3/8”) copper tube when connecting the discharge stub to the<br />

condensate pump. The discharge line from the pump should rise no more than 6<br />

meters vertically and no more than 8 metres in total length before being<br />

interrupted with a swan neck air break and tundish.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Design Features & Information<br />

HUMIDIFICATION<br />

Control Principles In a humidifier with electrodes, steam is produced by passing a current between electrode<br />

plates to generate heat. The higher the current being passed between the electrodes, the<br />

greater the quantity of steam that is produced.<br />

To modulate the rate of steam production, this system varies the level of water within the<br />

cylinder, thereby increasing the immersion level of the electrodes and the current being<br />

passed between them. The more conducting area that is available to pass current<br />

between the electrodes, the larger the amount of steam that is produced.<br />

Modulated by the controller, the water level is varied so that the level of<br />

steam being produced ensures that the room humidity set-point is continually maintained<br />

within a tight tolerance.<br />

Optimised Lifetime The life span of the <strong><strong>Air</strong>edale</strong> humidification system is optimised by the inclusion of a water<br />

conductivity sensor into the bottle feed. This sensor determines the conductivity level of<br />

the supply water and by using an algorithm embedded in the software,<br />

determines the frequency that the bottle should be drained.<br />

Example:<br />

(Optimised Lifetime with<br />

High Water Conductivity<br />

Supply)<br />

TANDEM<br />

COMPRESSORS<br />

As liquid water is boiled off into steam, mineral deposits are left in solution increasing the<br />

conductivity of the water. To counter this, the intelligent software increases the frequency<br />

of drain meaning that the replenishing supply water keeps the concentration of minerals<br />

diluted. By maintaining an acceptable mineral concentration, the bottle life span<br />

is maximised.<br />

Comprising of 2 scroll type compressors linked together by refrigerant pipework to one<br />

common circuit.<br />

Tandem compressors provide variable control of the system performance by activating<br />

individual compressors as required. Multiple steps of unloading allow external load<br />

demands to be met with greater precision, eliminating unnecessary temperature and<br />

humidity variations. Consequently, system efficiency and reliability are much improved by<br />

extending major component working hours.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 23<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

GENERAL


24<br />

-DF<br />

AIR COOLED (X) & W AT ER C OOL ED (W X) MOD ELS<br />

Performance Data - <strong>Air</strong> & Water Cooled Models<br />

COOLING DUTIES - X TYPE MODELS<br />

Standard Condenser Match<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Cooling Capacity (1) Ambient<br />

<strong>Air</strong> On °C DB<br />

25°C 30°C 35°C 40°C<br />

/%RH TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)<br />

DF6X-EZ<br />

C11<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

6.6<br />

6.8<br />

7.0<br />

5.9<br />

6.5<br />

7.0<br />

6.1<br />

6.3<br />

6.4<br />

5.7<br />

6.3<br />

6.4<br />

6.1<br />

6.3<br />

6.4<br />

5.7<br />

6.3<br />

6.4<br />

5.9<br />

6.0<br />

6.2<br />

5.6<br />

6.0<br />

6.2<br />

DF8X-EZ<br />

C15<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

9.3<br />

9.5<br />

9.8<br />

8.1<br />

8.7<br />

9.4<br />

8.6<br />

8.9<br />

9.2<br />

7.7<br />

8.4<br />

9.1<br />

8.6<br />

8.9<br />

9.1<br />

7.7<br />

8.4<br />

9.1<br />

8.3<br />

8.5<br />

8.8<br />

7.6<br />

8.2<br />

8.8<br />

DF10X-EZ<br />

C15<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

10.5<br />

10.8<br />

11.2<br />

9.6<br />

10.4<br />

11.1<br />

9.9<br />

10.3<br />

10.7<br />

9.2<br />

10.0<br />

10.7<br />

9.8<br />

10.1<br />

10.5<br />

9.2<br />

9.9<br />

10.5<br />

9.4<br />

9.7<br />

10.1<br />

8.9<br />

9.6<br />

10.1<br />

DF13X-EZ<br />

C20<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

13.9<br />

14.3<br />

14.6<br />

11.6<br />

12.6<br />

13.9<br />

13.0<br />

13.4<br />

13.7<br />

11.2<br />

12.2<br />

13.6<br />

12.8<br />

13.2<br />

13.4<br />

11.1<br />

12.1<br />

13.4<br />

12.2<br />

12.6<br />

12.8<br />

10.9<br />

11.8<br />

12.8<br />

DF15X-EZ<br />

C25<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

16.7<br />

17.0<br />

17.4<br />

13.9<br />

15.0<br />

16.3<br />

15.7<br />

16.2<br />

16.6<br />

13.4<br />

14.7<br />

16.0<br />

15.3<br />

15.7<br />

16.0<br />

13.3<br />

14.5<br />

15.7<br />

14.5<br />

15.0<br />

15.4<br />

12.9<br />

14.2<br />

15.4<br />

DF17X-EZ<br />

C35<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

20.0<br />

20.5<br />

20.9<br />

17.4<br />

18.8<br />

20.3<br />

18.6<br />

19.2<br />

19.6<br />

16.7<br />

18.2<br />

19.6<br />

18.5<br />

19.0<br />

19.4<br />

16.6<br />

18.1<br />

19.4<br />

17.6<br />

18.1<br />

18.5<br />

16.2<br />

17.6<br />

18.5<br />

DF22X2-EZ<br />

C45<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

25.5<br />

26.6<br />

27.4<br />

20.5<br />

22.4<br />

24.2<br />

23.4<br />

24.7<br />

25.5<br />

19.6<br />

21.5<br />

23.3<br />

23.4<br />

24.7<br />

25.4<br />

19.6<br />

21.5<br />

23.3<br />

22.4<br />

23.6<br />

24.2<br />

19.2<br />

21.0<br />

22.8<br />

DF25X2-EZ<br />

C45<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

26.6<br />

27.4<br />

28.1<br />

22.4<br />

24.4<br />

26.6<br />

24.7<br />

25.5<br />

26.2<br />

21.5<br />

23.6<br />

25.7<br />

24.7<br />

25.4<br />

26.1<br />

21.5<br />

23.5<br />

25.6<br />

23.5<br />

24.3<br />

24.9<br />

20.9<br />

23.0<br />

24.9<br />

DF26X-EZ<br />

C45<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

28.0<br />

28.7<br />

29.3<br />

25.0<br />

27.0<br />

29.1<br />

26.0<br />

26.8<br />

27.4<br />

23.9<br />

26.0<br />

27.4<br />

25.8<br />

26.5<br />

27.1<br />

23.8<br />

25.8<br />

27.1<br />

24.5<br />

25.2<br />

25.7<br />

23.1<br />

25.1<br />

25.7<br />

DF28X-EZ<br />

C45<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

28.7<br />

29.4<br />

29.2<br />

26.7<br />

29.0<br />

29.2<br />

26.7<br />

27.4<br />

27.4<br />

25.6<br />

27.4<br />

27.4<br />

26.4<br />

27.1<br />

27.1<br />

25.5<br />

27.1<br />

27.1<br />

25.0<br />

25.7<br />

26.1<br />

24.8<br />

25.7<br />

26.1<br />

DF31X-EZ<br />

C45<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

31.9<br />

32.9<br />

33.4<br />

30.4<br />

32.9<br />

33.4<br />

30.2<br />

31.1<br />

31.8<br />

29.4<br />

31.1<br />

31.8<br />

29.5<br />

30.3<br />

30.9<br />

29.0<br />

30.3<br />

30.9<br />

27.9<br />

28.7<br />

29.3<br />

27.9<br />

28.7<br />

29.3<br />

DF35X-EZ<br />

CS50<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

38.1<br />

39.1<br />

40.0<br />

36.1<br />

39.1<br />

40.0<br />

36.1<br />

37.1<br />

38.0<br />

34.9<br />

37.1<br />

38.0<br />

35.2<br />

36.3<br />

37.0<br />

34.4<br />

36.3<br />

37.0<br />

33.6<br />

34.6<br />

35.3<br />

33.6<br />

34.6<br />

35.3<br />

DF40X-EZ<br />

CS50<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

41.6<br />

43.4<br />

44.3<br />

40.0<br />

43.4<br />

44.3<br />

39.7<br />

41.7<br />

42.7<br />

38.9<br />

41.7<br />

42.7<br />

38.5<br />

40.4<br />

41.4<br />

38.3<br />

40.4<br />

41.4<br />

37.1<br />

38.8<br />

39.8<br />

37.1<br />

38.8<br />

39.8<br />

DF45X-EZ<br />

CS50<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

46.2<br />

47.4<br />

48.4<br />

42.4<br />

45.8<br />

48.4<br />

44.5<br />

45.6<br />

46.6<br />

41.5<br />

44.9<br />

46.6<br />

42.6<br />

43.8<br />

44.7<br />

40.5<br />

43.8<br />

44.7<br />

40.7<br />

41.8<br />

42.7<br />

39.4<br />

41.8<br />

42.7<br />

DF50X2-EZ<br />

CS65<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

54.6<br />

54.6<br />

57.1<br />

49.1<br />

52.8<br />

57.1<br />

51.9<br />

51.8<br />

54.6<br />

47.7<br />

51.3<br />

54.6<br />

50.6<br />

50.5<br />

52.9<br />

46.9<br />

50.5<br />

52.9<br />

48.4<br />

48.6<br />

50.8<br />

45.6<br />

48.6<br />

50.8<br />

DF55X2-EZ<br />

CS80<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

60.8<br />

62.3<br />

63.8<br />

52.5<br />

56.5<br />

60.8<br />

57.4<br />

59.0<br />

60.4<br />

50.8<br />

54.8<br />

59.1<br />

56.3<br />

57.8<br />

59.1<br />

50.2<br />

54.2<br />

58.4<br />

54.0<br />

55.4<br />

56.7<br />

48.9<br />

53.0<br />

56.7<br />

DF60X2-EZ<br />

CS80<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

64.4<br />

65.9<br />

68.6<br />

56.2<br />

60.7<br />

66.2<br />

61.0<br />

62.6<br />

66.0<br />

54.5<br />

59.0<br />

64.9<br />

59.5<br />

61.1<br />

64.4<br />

53.7<br />

58.1<br />

64.0<br />

57.0<br />

58.4<br />

62.2<br />

52.3<br />

56.8<br />

62.2<br />

AIR & WATER COOLED<br />

TC = Total Cooling SC = Sensible Cooling<br />

(1) All data quoted is gross.<br />

(2) Deduct fan motor gain for nett duties, refer to Mechanical Data in this section.<br />

OPERATING LIMITS - X TYPE MODELS<br />

Cooling<br />

Indoor <strong>Air</strong> Temperature +18°C to +28°C<br />

Indoor RH% +40% to +55%<br />

Outdoor Temperature -30°C to +48°C<br />

(1) For conditions outside those quoted, please contact <strong><strong>Air</strong>edale</strong>.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Performance Data - <strong>Air</strong> & Water Cooled Models<br />

COOLING DUTIES - X TYPE MODELS<br />

Upgraded Condenser Match<br />

Cooling Capacity (1) Ambient<br />

<strong>Air</strong> On °C DB 25°C 30°C 35°C 40°C 45°C<br />

/%RH TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)<br />

DF6X-EZ<br />

C15<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

6.8<br />

7.0<br />

7.1<br />

6.0<br />

6.6<br />

7.1<br />

6.1<br />

6.3<br />

6.4<br />

5.7<br />

6.3<br />

6.4<br />

6.1<br />

6.3<br />

6.4<br />

5.7<br />

6.3<br />

6.4<br />

6.0<br />

6.2<br />

6.3<br />

5.7<br />

6.2<br />

6.3<br />

5.7<br />

5.9<br />

6.0<br />

5.6<br />

5.9<br />

6.0<br />

DF8X-EZ<br />

C20<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

9.4<br />

9.7<br />

9.9<br />

8.1<br />

8.8<br />

9.5<br />

8.6<br />

8.9<br />

9.2<br />

7.7<br />

8.4<br />

9.1<br />

8.6<br />

8.9<br />

9.2<br />

7.7<br />

8.4<br />

9.1<br />

8.4<br />

8.7<br />

8.9<br />

7.6<br />

8.3<br />

8.9<br />

8.1<br />

8.3<br />

8.6<br />

7.5<br />

8.1<br />

8.6<br />

DF10X-EZ<br />

C20<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

10.7<br />

11.0<br />

11.3<br />

9.7<br />

10.5<br />

11.2<br />

9.9<br />

10.3<br />

10.7<br />

9.2<br />

10.0<br />

10.7<br />

9.9<br />

10.3<br />

10.7<br />

9.2<br />

10.0<br />

10.7<br />

9.6<br />

9.9<br />

10.3<br />

9.1<br />

9.8<br />

10.3<br />

9.2<br />

9.6<br />

10.0<br />

8.8<br />

9.5<br />

10.0<br />

DF13X-EZ<br />

C25<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

14.1<br />

14.5<br />

14.8<br />

11.7<br />

12.7<br />

14.0<br />

13.0<br />

13.4<br />

13.7<br />

11.2<br />

12.2<br />

13.6<br />

13.0<br />

13.3<br />

13.6<br />

11.2<br />

12.2<br />

13.6<br />

12.4<br />

12.7<br />

13.0<br />

10.9<br />

11.9<br />

13.0<br />

11.7<br />

12.1<br />

12.3<br />

10.6<br />

11.6<br />

12.3<br />

DF15X-EZ<br />

C35<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

17.2<br />

17.7<br />

18.0<br />

14.1<br />

15.3<br />

16.6<br />

15.7<br />

16.2<br />

16.6<br />

13.4<br />

14.7<br />

16.0<br />

15.7<br />

16.2<br />

16.6<br />

13.4<br />

14.7<br />

16.0<br />

15.1<br />

15.5<br />

15.9<br />

13.2<br />

14.4<br />

15.7<br />

14.3<br />

15.0<br />

15.2<br />

12.9<br />

14.2<br />

15.2<br />

DF17X-EZ<br />

C45<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

20.5<br />

21.0<br />

21.4<br />

17.6<br />

19.1<br />

20.6<br />

18.6<br />

19.2<br />

19.6<br />

16.7<br />

18.2<br />

19.6<br />

18.6<br />

19.2<br />

19.6<br />

16.7<br />

18.2<br />

19.6<br />

18.2<br />

18.7<br />

19.1<br />

16.5<br />

17.9<br />

19.1<br />

17.3<br />

17.7<br />

18.2<br />

16.0<br />

17.5<br />

18.2<br />

DF22X2-EZ<br />

CS50<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

25.6<br />

26.8<br />

27.6<br />

20.6<br />

22.5<br />

24.3<br />

23.4<br />

24.7<br />

25.5<br />

19.6<br />

21.5<br />

23.3<br />

23.4<br />

24.7<br />

25.5<br />

19.6<br />

21.5<br />

23.3<br />

22.7<br />

23.9<br />

24.6<br />

19.3<br />

21.2<br />

22.9<br />

21.8<br />

22.9<br />

23.5<br />

18.9<br />

20.7<br />

22.5<br />

DF25X2-EZ<br />

CS50<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

26.8<br />

27.6<br />

28.3<br />

22.5<br />

24.5<br />

26.7<br />

24.7<br />

25.5<br />

26.2<br />

21.5<br />

23.6<br />

25.7<br />

24.7<br />

25.5<br />

26.2<br />

21.5<br />

23.6<br />

25.7<br />

23.8<br />

24.6<br />

25.3<br />

21.1<br />

23.1<br />

25.2<br />

22.8<br />

23.6<br />

24.2<br />

20.6<br />

22.7<br />

24.2<br />

DF26X-EZ<br />

CS50<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

28.2<br />

29.0<br />

29.6<br />

25.1<br />

27.1<br />

29.3<br />

26.0<br />

26.8<br />

27.4<br />

23.9<br />

26.0<br />

27.4<br />

26.0<br />

26.8<br />

27.4<br />

23.9<br />

26.0<br />

27.4<br />

25.0<br />

25.7<br />

26.3<br />

23.4<br />

25.4<br />

26.3<br />

23.8<br />

24.5<br />

25.1<br />

22.8<br />

24.5<br />

25.1<br />

DF28X-EZ<br />

CS50<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

28.9<br />

29.7<br />

29.6<br />

26.9<br />

29.1<br />

29.6<br />

26.7<br />

27.4<br />

27.4<br />

25.6<br />

27.4<br />

27.4<br />

26.7<br />

27.4<br />

27.4<br />

25.6<br />

27.4<br />

27.4<br />

25.5<br />

26.3<br />

26.5<br />

25.0<br />

26.3<br />

26.5<br />

24.3<br />

25.0<br />

25.7<br />

24.3<br />

25.0<br />

25.7<br />

DF31X-EZ<br />

CS50<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

32.3<br />

33.3<br />

33.8<br />

30.6<br />

33.1<br />

33.8<br />

30.2<br />

31.1<br />

31.8<br />

29.4<br />

31.1<br />

31.8<br />

29.9<br />

30.8<br />

31.5<br />

29.3<br />

30.8<br />

31.5<br />

28.6<br />

29.5<br />

30.2<br />

28.5<br />

29.5<br />

30.2<br />

27.3<br />

28.1<br />

28.8<br />

27.3<br />

28.1<br />

28.8<br />

DF35X-EZ<br />

CS65<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

39.0<br />

40.1<br />

41.0<br />

36.6<br />

39.7<br />

41.0<br />

36.0<br />

37.1<br />

38.0<br />

34.9<br />

37.1<br />

38.0<br />

36.0<br />

37.1<br />

38.0<br />

34.9<br />

37.1<br />

38.0<br />

34.6<br />

35.7<br />

36.4<br />

34.1<br />

35.7<br />

36.4<br />

33.0<br />

34.0<br />

34.8<br />

33.0<br />

34.0<br />

34.8<br />

DF40X-EZ<br />

CS65<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

42.7<br />

44.3<br />

45.3<br />

40.6<br />

44.3<br />

45.3<br />

39.7<br />

41.7<br />

42.8<br />

38.9<br />

41.7<br />

42.8<br />

39.5<br />

41.5<br />

42.5<br />

38.9<br />

41.5<br />

42.5<br />

38.1<br />

40.0<br />

41.0<br />

38.1<br />

40.0<br />

41.0<br />

36.7<br />

38.3<br />

39.3<br />

36.7<br />

38.3<br />

39.3<br />

DF45X-EZ<br />

CS65<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

47.5<br />

48.7<br />

49.7<br />

43.1<br />

46.5<br />

49.7<br />

44.6<br />

45.9<br />

46.9<br />

41.6<br />

45.1<br />

46.9<br />

44.1<br />

45.2<br />

46.2<br />

41.3<br />

44.7<br />

46.2<br />

42.2<br />

43.3<br />

44.3<br />

40.3<br />

43.3<br />

44.3<br />

40.3<br />

41.3<br />

42.3<br />

39.3<br />

41.3<br />

42.3<br />

DF50X2-EZ<br />

CS80<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

55.3<br />

55.5<br />

57.8<br />

49.5<br />

53.3<br />

57.5<br />

52.0<br />

51.9<br />

54.6<br />

47.6<br />

51.3<br />

54.6<br />

51.5<br />

51.4<br />

53.9<br />

47.4<br />

51.0<br />

53.9<br />

49.4<br />

49.5<br />

51.8<br />

46.2<br />

49.5<br />

51.8<br />

47.2<br />

47.6<br />

49.6<br />

45.0<br />

47.6<br />

49.6<br />

DF55X2-EZ<br />

CS105<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

62.0<br />

63.7<br />

65.1<br />

53.3<br />

57.2<br />

61.5<br />

57.4<br />

59.0<br />

60.4<br />

50.7<br />

54.8<br />

59.1<br />

57.4<br />

59.0<br />

60.4<br />

50.7<br />

54.8<br />

59.1<br />

55.4<br />

56.9<br />

58.2<br />

49.7<br />

53.7<br />

57.9<br />

52.9<br />

54.4<br />

55.6<br />

48.4<br />

52.5<br />

55.6<br />

DF60X2-EZ<br />

CS105<br />

22 / 50<br />

24 / 45<br />

26 / 40<br />

65.8<br />

67.4<br />

69.9<br />

57.0<br />

61.4<br />

66.9<br />

61.0<br />

62.7<br />

66.0<br />

54.5<br />

59.0<br />

64.8<br />

61.0<br />

62.7<br />

65.8<br />

54.5<br />

59.0<br />

64.7<br />

58.6<br />

60.1<br />

63.7<br />

53.2<br />

57.7<br />

63.6<br />

55.9<br />

57.4<br />

61.5<br />

51.8<br />

56.3<br />

61.5<br />

TC = Total Cooling SC = Sensible Cooling<br />

(1) All data quoted is gross.<br />

(2) Deduct fan motor gain for nett duties, refer to Mechanical Data in this section.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 25<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

AIR & WATER COOLED


AIR & WATER COOLED<br />

26<br />

-DF<br />

Performance Data - <strong>Air</strong> & Water Cooled Models<br />

COOLING DUTIES - WX TYPE MODELS<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Cooling Capacity (1) Condenser Entering / Leaving Temperature - Based on ΔT of 5°C<br />

25°C /30°C 30°C /35°C 35°C/40°C 40°C/45°C<br />

<strong>Air</strong> On °C DB TC SC THR TC SC THR TC SC THR TC SC THR<br />

/%RH (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW) (kW)<br />

22 / 50 6.7 6.0 8.9 6.5 5.9 8.5 6.2 5.7 8.2 5.9 5.6 7.9<br />

DF6WX-EZ<br />

24 / 45 6.9 6.6 9.0 6.6 6.4 8.7 6.4 6.3 8.4 6.1 6.1 8.1<br />

26 / 40 7.1 7.1 9.2 6.8 6.8 8.9 6.5 6.5 8.5 6.2 6.2 8.2<br />

22 / 50 9.4 8.1 11.6 9.1 8.0 11.5 8.7 7.8 11.3 8.4 7.6 11.2<br />

DF8WX-EZ<br />

24 / 45 9.7 8.8 11.9 9.4 8.6 11.8 9.0 8.5 11.6 8.7 8.3 11.5<br />

26 / 40 10.0 9.5 12.2 9.6 9.4 12.0 9.3 9.2 11.9 8.9 8.9 11.7<br />

22 / 50 10.8 9.7 13.0 10.4 9.5 13.0 10.0 9.3 12.9 9.6 9.1 12.8<br />

DF10WX-EZ<br />

24 / 45 11.1 10.5 13.4 10.7 10.3 13.3 10.4 10.1 13.3 10.0 9.8 13.2<br />

26 / 40 11.4 11.3 13.7 11.1 11.0 13.7 10.8 10.8 13.6 10.4 10.4 13.6<br />

22 / 50 14.3 11.7 16.7 13.7 11.5 16.6 13.2 11.2 16.5 12.5 11.0 16.4<br />

DF13WX-EZ<br />

24 / 45 14.7 12.8 17.1 14.1 12.6 17.0 13.5 12.3 16.9 12.9 12.0 16.7<br />

26 / 40 15.0 14.1 17.4 14.4 13.9 17.3 13.8 13.7 17.2 13.2 13.2 17.0<br />

22 / 50 17.4 14.2 19.7 16.7 13.8 19.7 16.0 13.6 19.8 15.3 13.2 19.8<br />

DF15WX-EZ<br />

24 / 45 17.9 15.4 20.2 17.0 15.0 20.2 16.5 14.8 20.2 15.7 14.5 20.2<br />

26 / 40 18.3 16.7 20.6 17.4 16.3 20.6 16.9 16.1 20.6 16.1 15.8 20.6<br />

22 / 50 20.4 17.6 22.9 19.6 17.2 23.2 19.0 16.9 23.5 18.1 16.4 23.9<br />

DF17WX-EZ<br />

24 / 45 20.9 19.0 23.4 20.2 18.7 23.8 19.5 18.3 24.1 18.6 17.9 24.5<br />

26 / 40 21.4 20.6 23.9 20.6 20.2 24.2 19.9 19.8 24.6 19.1 19.1 24.9<br />

22 / 50 25.8 20.6 28.5 24.6 20.1 29.0 23.6 19.7 29.5 22.5 19.2 30.0<br />

DF22WX2-EZ<br />

24 / 45 27.0 22.6 29.8 25.9 22.1 30.3 24.9 21.6 30.7 23.8 21.1 31.2<br />

26 / 40 27.8 24.4 30.6 26.7 23.9 31.0 25.7 23.4 31.5 24.5 22.9 31.9<br />

22 / 50 27.0 22.6 29.8 25.9 22.0 30.2 24.9 21.6 30.6 23.7 21.0 31.1<br />

DF25WX2-EZ<br />

24 / 45 27.8 24.6 30.6 26.7 24.1 31.1 25.7 23.7 31.5 24.5 23.1 32.0<br />

26 / 40 28.6 26.9 31.4 27.5 26.3 31.9 26.5 25.8 32.2 25.2 25.1 32.7<br />

22 / 50 28.3 25.2 31.3 27.3 24.6 31.9 26.3 24.1 32.6 25.1 23.5 33.2<br />

DF26WX-EZ<br />

24 / 45 29.1 27.2 32.1 28.1 26.6 32.7 27.0 26.1 33.3 25.8 25.5 34.0<br />

26 / 40 29.8 29.3 32.8 28.7 28.7 33.4 27.6 27.6 34.0 26.5 26.5 34.7<br />

22 / 50 29.0 26.9 32.0 28.0 26.4 32.6 26.9 25.8 33.2 25.7 25.1 33.9<br />

DF28WX-EZ<br />

24 / 45 29.8 29.2 32.9 28.8 28.6 33.4 27.7 27.7 34.0 26.5 26.5 34.6<br />

26 / 40 29.7 29.7 32.8 28.6 28.6 33.6 27.5 27.5 34.3 26.6 26.6 35.1<br />

22 / 50 32.6 30.8 35.8 31.5 30.2 36.7 30.3 29.5 37.6 29.0 28.8 38.5<br />

DF31WX-EZ<br />

24 / 45 33.6 33.3 36.8 32.5 32.5 37.7 31.3 31.3 38.6 30.0 30.0 39.4<br />

26 / 40 34.2 34.2 37.5 33.1 33.1 38.4 31.9 31.9 39.2 30.6 30.6 40.2<br />

22 / 50 38.9 36.5 42.5 37.5 35.7 43.6 36.0 34.9 44.7 34.4 34.0 45.8<br />

DF35WX-EZ<br />

24 / 45 40.0 39.6 43.7 38.6 38.6 44.8 37.1 37.1 45.9 35.5 35.5 47.0<br />

26 / 40 40.9 40.9 44.6 39.5 39.5 45.7 38.0 38.0 46.7 36.3 36.3 47.8<br />

22 / 50 42.7 40.6 46.8 41.1 39.8 48.0 39.6 38.9 49.4 38.1 38.1 50.7<br />

DF40WX-EZ<br />

24 / 45 44.4 44.4 48.4 43.1 43.1 49.8 41.6 41.6 51.2 40.0 40.0 52.7<br />

26 / 40 45.4 45.4 49.4 44.1 44.1 50.8 42.7 42.7 52.3 41.1 41.1 53.8<br />

22 / 50 48.1 43.4 51.8 46.5 42.6 53.4 44.9 41.7 55.0 43.1 40.7 56.7<br />

DF45WX-EZ<br />

24 / 45 49.4 46.9 53.2 47.8 46.1 54.7 46.1 45.2 56.4 44.3 44.2 57.9<br />

26 / 40 50.4 50.4 54.3 48.9 48.9 55.8 47.1 47.1 57.4 45.3 45.3 59.0<br />

22 / 50 55.7 49.7 60.0 54.0 48.8 61.9 52.0 47.7 63.9 50.0 46.6 65.8<br />

DF50WX2-EZ<br />

24 / 45 56.0 53.6 60.5 54.0 52.5 62.3 51.9 51.3 64.2 50.0 50.0 66.0<br />

26 / 40 58.4 57.8 62.8 56.6 56.6 64.7 54.6 54.6 66.6 52.6 52.6 68.5<br />

22 / 50 61.6 53.0 66.4 59.6 51.9 68.4 57.3 50.7 70.5 54.9 49.4 72.6<br />

DF55WX2-EZ<br />

24 / 45 63.3 57.0 68.2 61.2 55.9 70.1 58.9 54.7 72.2 56.5 53.5 74.2<br />

26 / 40 64.8 61.3 69.7 62.6 60.2 71.6 60.2 59.0 73.6 57.8 57.8 75.6<br />

22 / 50 65.5 56.9 70.6 63.3 55.7 72.7 60.8 54.4 74.9 58.3 53.0 77.1<br />

DF60WX2-EZ<br />

24 / 45 67.1 61.3 72.3 64.9 60.1 74.4 62.4 58.8 76.6 59.9 57.5 78.7<br />

26 / 40 69.8 66.8 75.2 67.8 65.8 77.7 65.7 64.7 80.2 63.6 63.6 82.8<br />

TC = Total Cooling SC = Sensible Cooling THR = Total Heat of Rejection<br />

(1) All data quoted is gross.<br />

(2) Deduct fan motor gain for nett duties, refer to Mechanical Data in this section.<br />

(3) Interpolate for water temperatures between those quoted, do not extrapolate.<br />

(4) Water flow rate (l/s) = THR ÷ (4.19 x T) at 100% Water. For glycol use, refer to Ethylene Glycol Correction Factors in this section.<br />

OPERATING LIMITS - WX TYPE MODELS<br />

Cooling<br />

Indoor <strong>Air</strong> Temperature +18°C to +28°C<br />

Indoor RH% +40% to +55%<br />

Condenser Minimum Entering Temperature °C +25°C<br />

Condenser Maximum Leaving Water Temperature °C +45°C<br />

(1) Conditions quoted at 100% Water.<br />

(2) For conditions outside those quoted, please refer to <strong><strong>Air</strong>edale</strong>.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

General Specification - <strong>Air</strong> & Water Cooled Models<br />

MECHANICAL DATA<br />

DF6X-EZ DF8X-EZ DF10X-EZ DF13X-EZ<br />

DF6WX-EZ DF8WX-EZ DF10WX-EZ DF13WX-EZ<br />

Standard Matched Condenser - X<br />

Capacity<br />

C11 C15 C15 C20<br />

Nom Cooling (Gross) - X (1) kW 6.3 8.9 10.1 13.2<br />

Nom Cooling (Gross) - WX (2) kW 6.3 8.9 10.3 13.4<br />

Total Heat of Rejection - WX (2) kW 8.1 11.7 13.5 17.4<br />

Capacity Steps 1 1 1 1<br />

Fan Gain kW 0.33 0.60 0.65 0.65<br />

Dimensions - H x W x D mm 1940 x 670 x 670 1940 x 670 x 670 1940 x 670 x 670 1940 x 990 x 670<br />

Weight - Machine - X kg 185 196 200 222<br />

Weight - Machine / Operating - WX (3) kg 200 / 202 214 / 216 218 / 220 243 / 244<br />

Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey, (RAL 7035)<br />

Material/Colour<br />

Frame: Anodised Aluminium Frame with Black Nylon Corners<br />

Evaporator Rifled Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins<br />

Cooling/Dehum Stages 1/1 1/1 1/1 1/1<br />

Condenser - WX Stainless Steel Brazed Plate<br />

Water Volume l 1.1 1.4 1.4 1.4<br />

Fan & Motor Centrifugal Direct Drive- Designed to 25Pa ESP<br />

Quantity / Motor Size kW 1 x 0.30 1 x 0.55 1 x 0.60 1 x 0.60<br />

Maximum ESP Pa 196 140 118 294<br />

Nominal <strong>Air</strong>flow m³/s 0.55 0.75 0.95 1.00<br />

Compressor - Scroll Single<br />

Quantity 1 1 1 1<br />

Oil Charge Volume (Total) l 1.00 1.10 1.10 1.36<br />

Oil Type Polyol Ester<br />

Refrigeration Single Circuit<br />

Refrigeration Control Thermostatic Expansion Valve (Optional EEV)<br />

Refrigeration Type (4) R407C<br />

Holding Charge - X Inert Gas<br />

Charge (Total) - WX<br />

Connections<br />

kg 2.4 2.5 2.5 3.7<br />

Liquid (Sweat) - X in 3/8 3/8 3/8 1/2<br />

Discharge (Sweat) - X in 5/8 5/8 5/8 3/4<br />

Water Inlet / Outlet - WX mm 22 22 22 22<br />

Condensate Drain Hose mm 19 19 19 19<br />

Filtration Disposable to BS EN 779 - G4 - 50mm<br />

Quantity<br />

OPTIONAL EXTRAS<br />

Upgraded Condenser Match - X<br />

1 1 1 2<br />

Nom Cooling (Gross) (1) kW 6.3 8.9 10.3 13.3<br />

Electric Heating (Total)<br />

Humidifier<br />

kW 7.5 7.5 7.5 7.5<br />

Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0<br />

Feed/Drain<br />

Condensate Pump<br />

3/4” BSPF Braided flexible hose / 19mm hose connection<br />

Head m 8 8 8 8<br />

Flow l/m 5 5 5 5<br />

Drain 10mm S/Steel Stub Connection<br />

Larger / Next Larger Fan Motor Size<br />

Quantity / Motor Size kW 1 x 0.55 / N/A 1 x 0.60 / N/A N/A / N/A N/A / N/A<br />

Maximum ESP Pa 254 / N/A 253 / N/A N/A / N/A N/A / N/A<br />

Fan Gain rpm 0.60 / N/A 0.65 / N/A N/A / N/A N/A / N/A<br />

Low Pressure Hot Water Copper Tube/Aluminium Fin<br />

Capacity Gross (5) kW 6.50 7.50 8.40 11.50<br />

Water Flow (Nominal) l/s 0.14 0.17 0.19 0.26<br />

LPHW Connection Sizes<br />

Threaded Connection - WX<br />

mm 22 22 22 22<br />

Brass Male Taper in 3/4 3/4 3/4 3/4<br />

(1) Entering air 24°C/45% RH ambient 35°C.<br />

(2) Entering air 24°C/45% RH condensing water in / out: 30°C /35°C.<br />

(3) Machine weight includes a refrigerant charge / Operating weight includes calculated water volume.<br />

(4) For refrigerant charges, refer to the Refrigerant Charging Guide - X Type Models table in this section.<br />

(5) Based upon low pressure hot water 82°C inlet/71°C outlet. <strong>Air</strong> on 20°C. Refer to the Low Pressure Hot Water (Optional Extra) - X & WX Type<br />

Models in this section.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 27<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

AIR & WATER COOLED


AIR & WATER COOLED<br />

28<br />

-DF<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

General Specification - <strong>Air</strong> & Water Cooled Models<br />

MECHANICAL DATA<br />

DF15X-EZ DF17X-EZ DF22X2-EZ DF25X2-EZ<br />

DF15WX-EZ DF17WX-EZ DF22WX2-EZ DF25WX2-EZ<br />

Standard Matched Condenser - X<br />

Capacity<br />

C25 C35 C45 C45<br />

Nom Cooling (Gross) - X (1) kW 15.7 19.0 24.7 25.4<br />

Nom Cooling (Gross) - WX (2) kW 16.2 29.2 24.7 25.5<br />

Total Heat of Rejection - WX (2) kW 21.2 25.6 32.6 33.4<br />

Capacity Steps 1 1 2 2<br />

Fan Gain kW 1.20 1.20 1.31 1.31<br />

Dimensions - H x W x D mm 1940 x 990 x 670 1940 x 990 x 670 1940 x 1310 x 670 1940 x 1310 x 670<br />

Weight - Machine - X kg 235 238 308 308<br />

Weight - Machine / Operating - WX (3) kg 262 / 264 268 / 270 341 / 344 341 / 344<br />

Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey, (RAL 7035)<br />

Material/Colour<br />

Frame: Anodised Aluminium Frame with Black Nylon Corners<br />

Evaporator Rifled Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins<br />

Cooling/Dehum Stages 1/1 1/1 1/1 1/1<br />

Condenser - WX Stainless Steel Brazed Plate<br />

Water Volume l 2.0 2.5 2.5 2.5<br />

Fan & Motor Centrifugal Direct Drive- Designed to 25Pa ESP<br />

Quantity / Motor Size kW 1 x 1.10 1 x 1.10 2 x 0.60 2 x 0.60<br />

Maximum ESP Pa 120 34 194 43<br />

Nominal <strong>Air</strong>flow m³/s 1.20 1.40 1.70 2.00<br />

Compressor - Scroll Single Tandem<br />

Quantity 1 1 2 2<br />

Oil Charge Volume (Total) l 1.85 1.65 2.72 2.72<br />

Oil Type Polyol Ester<br />

Refrigeration Single Circuit<br />

Refrigeration Control Thermostatic Expansion Valve (Optional EEV)<br />

Refrigeration Type (4) R407C<br />

Holding Charge - X Inert Gas<br />

Charge (Total) - WX<br />

Connections<br />

kg 4.1 4.1 5.1 5.1<br />

Liquid (Sweat) - X in 1/2 1/2 5/8 5/8<br />

Discharge (Sweat) - X in 3/4 3/4 7/8 7/8<br />

Water Inlet / Outlet - WX mm 22 28 28 28<br />

Condensate Drain Hose mm 19 19 19 19<br />

Filtration Disposable to BS EN 779 - G4 - 50mm<br />

Quantity<br />

OPTIONAL EXTRAS<br />

Upgraded Condenser Match - X<br />

2 2 3 3<br />

Nom Cooling (Gross) (1) kW 16.2 19.2 24.5 25.5<br />

Electric Heating (Total)<br />

Humidifier<br />

kW 7.5 7.5 15.0 15.0<br />

Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0<br />

Feed/Drain<br />

Condensate Pump<br />

3/4” BSPF Braided flexible hose / 19mm hose connection<br />

Head m 8 8 8 8<br />

Flow l/m 5 5 5 5<br />

Drain 10mm S/Steel Stub Connection<br />

Larger / Next Larger Fan Motor Size<br />

Quantity / Motor Size kW N/A / N/A N/A / N/A N/A / N/A N/A / N/A<br />

Maximum ESP Pa N/A / N/A N/A / N/A N/A / N/A N/A / N/A<br />

Fan Gain rpm N/A / N/A N/A / N/A N/A / N/A N/A / N/A<br />

Low Pressure Hot Water Copper Tube/Aluminium Fin<br />

Capacity Gross (5) kW 12.50 13.30 16.10 16.60<br />

Water Flow (Nominal) l/s 0.28 0.30 0.36 0.37<br />

LPHW Connection Sizes<br />

Threaded Connection - WX<br />

mm 22 22 22 22<br />

Brass Male Taper in 3/4 1 1 1<br />

(1) Entering air 24°C/45% RH ambient 35°C.<br />

(2) Entering air 24°C/45% RH condensing water in / out: 30°C /35°C.<br />

(3) Machine weight includes a refrigerant charge / Operating weight includes calculated water volume.<br />

(4) For refrigerant charges, refer to the Refrigerant Charging Guide - X Type Models table in this section.<br />

(5) Based upon low pressure hot water 82°C inlet/71°C outlet. <strong>Air</strong> on 20°C. Refer to the Low Pressure Hot Water (Optional Extra) - X & WX Type<br />

Models in this section.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

General Specification - <strong>Air</strong> & Water Cooled Models<br />

MECHANICAL DATA<br />

DF26X-EZ DF28X-EZ DF31X-EZ DF35X-EZ<br />

DF26WX-EZ DF28WX-EZ DF31WX-EZ DF35WX-EZ<br />

Standard Matched Condenser - X<br />

Capacity<br />

C45 C45 C45 CS50<br />

Nom Cooling (Gross) - X (1) kW 26.5 27.1 30.3 36.4<br />

Nom Cooling (Gross) - WX (2) kW 26.8 27.5 31.1 37.1<br />

Total Heat of Rejection - WX (2) kW 35.5 36.2 41.0 49.2<br />

Capacity Steps 1 1 1 1<br />

Fan Gain kW 0.98 1.43 2.60 2.60<br />

Dimensions - H x W x D mm 1940 x 1460 x 750 1940 x 1460 x 750 1940 x 1460 x 750 1940 x 1835 x 750<br />

Weight - Machine - X kg 452 452 459 501<br />

Weight - Machine / Operating- WX (3) kg 503 / 509 503 / 509 510 / 516 555 / 561<br />

Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey, (RAL 7035)<br />

Material/Colour<br />

Frame: Anodised Aluminium Frame with Black Nylon Corners<br />

Evaporator Rifled Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins<br />

Cooling/Dehum Stages 1/1 1/1 1/1 1/1<br />

Condenser - WX Stainless Steel Brazed Plate<br />

Water Volume l 6.1 6.1 6.1 6.1<br />

Fan & Motor Centrifugal Belt & Pulley- Designed to 25Pa ESP<br />

Quantity / Motor Size kW 1 x 1.5 1 x 2.2 1 x 4.0 1 x 4.0<br />

Speed @ 25Pa / Maximum ESP rpm 775 / 801 871 / 909 1008 /1171 980 /1078<br />

Maximum ESP Pa 65 75 265 165<br />

Nominal <strong>Air</strong>flow m³/s 2.1 2.4 2.8 3.3<br />

Compressor - Scroll Single<br />

Quantity 1 1 1 1<br />

Oil Charge Volume (Total) l 4.10 4.10 4.10 3.25<br />

Oil Type Polyol Ester<br />

Refrigeration Single Circuit<br />

Refrigeration Control Thermostatic Expansion Valve (Optional EEV)<br />

Refrigeration Type (4) R407C<br />

Holding Charge - X Inert Gas<br />

Charge (Total) - WX<br />

Connections<br />

kg 7.2 7.2 7.2 8.9<br />

Liquid (Sweat) - X in 5/8 5/8 5/8 5/8<br />

Discharge (Sweat) - X in 7/8 7/8 7/8 7/8<br />

Water Inlet / Outlet - WX mm 35 35 35 35<br />

Condensate Drain Hose mm 19 19 19 19<br />

Filtration Disposable to BS EN 779 - G4 - 75mm<br />

Quantity<br />

OPTIONAL EXTRAS<br />

Upgraded Condenser Match - X<br />

3 3 3 3<br />

Nom Cooling (Gross) (1) kW 26.8 27.5 31.0 37.0<br />

Electric Heating (Total)<br />

Humidifier<br />

kW 20 20 20 20<br />

Capacity kg/hr 1.6 - 8.0 1.6 - 8.0 1.6 - 8.0 3.0 - 15.0<br />

Feed/Drain<br />

Condensate Pump<br />

3/4” BSPF Braided flexible hose / 19mm hose connection<br />

Head m 10.8 10.8 10.8 10.8<br />

Flow l/m 5 5 5 5<br />

Drain 10mm S/Steel Stub Connection<br />

Larger / Next Larger Fan Motor Size<br />

Quantity / Motor Size kW 1 x 2.2 / 1 x 3.0 1 x 3.0 / 1 x 4.0 N/A / N/A 1 x 5.5 / N/A<br />

Maximum ESP Pa 345 / 665 362 / 722 N/A / N/A 322 / N/A<br />

Speed @ Maximum ESP rpm 1057 / 1350 1144 / 1439 N/A / N/A 1196 / N/A<br />

Fan Gain kW 1.43 / 1.95 1.95 / 2.60 N/A / N/A 3.58 / N/A<br />

Low Pressure Hot Water Copper Tube/Aluminium Fin<br />

Capacity Gross (5) kW 20.10 21.30 22.70 30.00<br />

Water Flow (Nominal) l/s 0.45 0.48 0.51 0.67<br />

LPHW Connection Sizes<br />

Threaded Connection - WX<br />

mm 22 22 22 22<br />

Brass Male Taper in 1 1/4 1 1/4 1 1/4 1 1/4<br />

(1) Entering air 24°C/45% RH ambient 35°C.<br />

(2) Entering air 24°C/45% RH condensing water in / out: 30°C /35°C.<br />

(3) Machine weight includes a refrigerant charge / Operating weight includes calculated water volume.<br />

(4) For refrigerant charges, refer to the Refrigerant Charging Guide - X Type Models table in this section.<br />

(5) Based upon low pressure hot water 82°C inlet/71°C outlet. <strong>Air</strong> on 20°C. Refer to the Low Pressure Hot Water (Optional Extra) - X & WX Type<br />

Models in this section.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 29<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

AIR & WATER COOLED


AIR & WATER COOLED<br />

30<br />

-DF<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

General Specification - <strong>Air</strong> & Water Cooled Models<br />

MECHANICAL DATA<br />

DF40X-EZ DF45X-EZ DF50X2-EZ DF55X2-EZ DF60X2-EZ<br />

DF40WX-EZ DF45WX-EZ DF50WX2-EZ DF55WX2-EZ DF60WX2-EZ<br />

Standard Matched Condenser - X<br />

Capacity<br />

CS50 C50 CS65 CS80 CS80<br />

Nom Cooling (Gross) - X (1) kW 40.6 43.9 50 57.4 60.7<br />

Nom Cooling (Gross) - WX (2) kW 41.7 45.9 51.2 59.0 62.7<br />

Total Heat of Rejection - WX (2) kW 54.9 60.9 51.9 77.6 82.3<br />

Capacity Steps 1 1 2 2 2<br />

Fan Gain kW 3.58 3.58 2.86 2.86 3.90<br />

Dimensions - H x W x D mm 1940 x 1835 x 1940 x 1835 x 1940 x 2170 x 1940 x 2170 x 1940 x 2170 x<br />

750<br />

750<br />

750<br />

750<br />

750<br />

Weight - Machine - X kg 522 550 665 678 674<br />

Weight - Machine / Operating - WX (3) kg 581 / 587 628 / 638 747 / 756 761 / 771 757 / 767<br />

Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey, (RAL 7035)<br />

Material/Colour<br />

Frame: Anodised Aluminium Frame with Black Nylon Corners<br />

Evaporator Rifled Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins<br />

Cooling/Dehum Stages 1/1 1/1 2/2 2/2 2/2<br />

Condenser - WX Stainless Steel Brazed Plate<br />

Water Volume l 6.1 9.9 9.9 9.9 9.9<br />

Fan & Motor Centrifugal Belt & Pulley- Designed to 25Pa ESP<br />

Quantity / Motor Size kW 1 x 5.5 1 x 5.5 2 x 2.2 2 x 2.2 2 x 3.0<br />

Speed @ 25Pa / Maximum ESP rpm 1094 / 1186 1094 / 1186 1167 / 1170 1167 / 1170 1307 / 1311<br />

Maximum ESP Pa 175 175 35 35 75<br />

Nominal <strong>Air</strong>flow m³/s 3.7 3.7 4.2 4.2 4.6<br />

Compressor - Scroll Single Tandem<br />

Quantity 1 1 2 2 2<br />

Oil Charge Volume (Total) l 3.30 6.20 6.50 7.60 7.60<br />

Oil Type Polyol Ester<br />

Refrigeration Single Circuit<br />

Refrigeration Control Thermostatic Expansion Valve (Optional EEV)<br />

Refrigeration Type (4) R407C<br />

Holding Charge - X Inert Gas<br />

Charge (Total) - WX<br />

Connections<br />

kg 8.9 11.7 11.6 13.3 13.3<br />

Liquid (Sweat) - X in 7/8 7/8 7/8 7/8 7/8<br />

Discharge (Sweat) - X in 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8<br />

Water Inlet / Outlet - WX mm 35 42 42 42 42<br />

Condensate Drain Hose mm 19 19 19 19 19<br />

Filtration Disposable to BS EN 779 - G4 - 75mm<br />

Quantity<br />

OPTIONAL EXTRAS<br />

Upgraded Condenser Match - X<br />

3 3 4 4 4<br />

Nom Cooling (Gross) (1) kW 41.2 44.8 51.2 58.5 61.8<br />

Electric Heating (Total)<br />

Humidifier<br />

kW 20 20 30 30 30<br />

Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0<br />

Feed/Drain<br />

Condensate Pump<br />

3/4” BSPF Braided flexible hose / 19mm hose connection<br />

Head m 10.8 10.8 10.8 10.8 10.8<br />

Flow l/m 5 5 5 5 5<br />

Drain 10mm S/Steel Stub Connection<br />

Larger / Next Larger Fan Motor Size<br />

Quantity / Motor Size kW N/A / N/A N/A / N/A 2 x 3.0 / 2 x 4.0 2 x 3.0 / 2 x 4.0 2 x 4.0 / N/A<br />

Maximum ESP Pa N/A / N/A N/A / N/A 310 / 360 310 / 360 275 / N/A<br />

Speed @ Maximum ESP rpm N/A / N/A N/A / N/A 1448 / 1498 1448 / 1498 1497 / N/A<br />

Fan Gain kW N/A / N/A N/A / N/A 3.90 / 5.20 3.90 / 5.20 5.20 / N/A<br />

Low Pressure Hot Water Copper Tube/Aluminium Fin<br />

Capacity Gross (5) kW 31.50 31.50 38.30 38.30 39.80<br />

Water Flow (Nominal) l/s 0.70 0.70 0.85 0.85 0.89<br />

LPHW Connection Sizes<br />

Threaded Connection - WX<br />

mm 22 22 22 22 22<br />

Brass Male Taper in 1 1/4 1 1/2 1 1/2 1 1/2 1 1/2<br />

(1) Entering air 24°C/45% RH ambient 35°C.<br />

(2) Entering air 24°C/45% RH condensing water in / out: 30°C /35°C.<br />

(3) Machine weight includes a refrigerant charge / Operating weight includes calculated water volume.<br />

(4) For refrigerant charges, refer to the Refrigerant Charging Guide - X Type Models table in this section.<br />

(5) Based upon low pressure hot water 82°C inlet/71°C outlet. <strong>Air</strong> on 20°C. Refer to the Low Pressure Hot Water (Optional Extra) - X & WX Type<br />

Models in this section.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

General Specification - <strong>Air</strong> & Water Cooled Models<br />

ELECTRICAL DATA<br />

DF6X-EZ DF8X-EZ DF10X-EZ DF13X-EZ<br />

DF6WX-EZ DF8WX-EZ DF10WX-EZ DF13WX-EZ<br />

Standard Matched Condensers - X C11 C15 C15 C20<br />

Unit Data - X (1)<br />

Nominal Run Amps A 17.90 22.40 25.70 26.70<br />

Maximum Start Amps A 38.40 57.70 66.20 70.20<br />

Recommended Mains Fuse Size A 25 32 32 32<br />

Max Mains Incoming Cable Size mm² 6 6 6 6<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit VAC 24 24 24 24<br />

Unit Data - WX (1)<br />

Nominal Run Amps A 17.90 22.40 25.70 26.70<br />

Maximum Start Amps A 38.40 57.70 66.20 70.20<br />

Recommended Mains Fuse Size A 25 32 32 32<br />

Max Mains Incoming Cable Size mm² 6 6 6 6<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit VAC 24 24 24 24<br />

Evaporator Fan - Per Fan<br />

Quantity/Motor Size kW 1 x 0.30 1 x 0.55 1 x 0.60 1 x 0.60<br />

Full Load Amps A 3.50 6.80 7.70 7.70<br />

Locked Rotor Amps A 8.75 17.00 20.50 20.50<br />

Compressor - Per Compressor<br />

Quantity 1 1 1 1<br />

Nominal Run Amps A 3.2 4.7 5.5 6.5<br />

Locked Rotor Amps A 24.0 40.0 46.0 50.0<br />

Motor Size kW 2.0 2.6 3.9 4.7<br />

Type of Start Direct On Line<br />

Matched Outdoor Condenser - Per Fan<br />

Quantity/Motor Size kW 1 x 0.15 1 x 0.15 1 x 0.15 1 x 0.15<br />

Full Load Amps A 0.65 0.65 0.65 0.65<br />

OPTIONAL EXTRAS<br />

Electric Heating<br />

Stage of Reheat 1 1 1 1<br />

Number of Elements 3 3 3 3<br />

Rating (Total) kW 7.5 7.5 7.5 7.5<br />

Current Per Phase A 10.9 10.9 10.9 10.9<br />

Humidifier<br />

Capacity kg/hr 0.60 - 3.00 0.60 - 3.00 0.60 - 3.00 0.60 - 3.00<br />

Rating kW 2.25 2.25 2.25 2.25<br />

Full Load Amps A 3.50 3.50 3.50 3.50<br />

Larger Fan Motor - Per Fan<br />

Quantity / Motor Size kW 1 x 0.55 1 x 0.60 N/A N/A<br />

Full Load Amps A 6.80 7.70 N/A N/A<br />

Locked Rotor Amps A 17.00 20.50 N/A N/A<br />

(1) Values given for full function units (incl. electric heating, humidification and matched condenser) at ARI conditions with standard fan motors, for<br />

optional data, please contact <strong><strong>Air</strong>edale</strong>.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 31<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

AIR & WATER COOLED


AIR & WATER COOLED<br />

32<br />

-DF<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

General Specification - <strong>Air</strong> & Water Cooled Models<br />

ELECTRICAL DATA<br />

DF15X-EZ DF17X-EZ DF22X2-EZ DF25X2-EZ<br />

DF15WX-EZ DF17WX-EZ DF22WX2-EZ DF25WX2-EZ<br />

Standard Matched Condensers - X C25 C35 C45 C45<br />

Unit Data - X (1)<br />

Nominal Run Amps A 29.20 30.10 44.10 44.10<br />

Maximum Start Amps A 86.90 94.90 87.60 87.60<br />

Recommended Mains Fuse Size A 40 40 50 50<br />

Max Mains Incoming Cable Size mm² 35 35 35 35<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit VAC 24 24 24 24<br />

Unit Data - WX (1)<br />

Nominal Run Amps A 29.20 30.10 44.10 44.10<br />

Maximum Start Amps A 86.90 94.90 87.60 87.60<br />

Recommended Mains Fuse Size A 40 40 50 50<br />

Max Mains Incoming Cable Size mm² 35 35 35 35<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit VAC 24 24 24 24<br />

Evaporator Fan - Per Fan<br />

Quantity/Motor Size kW 1 x 1.1 1 x 1.1 2 x 0.6 2 x 0.6<br />

Full Load Amps A 10.0 10.0 7.7 7.7<br />

Locked Rotor Amps A 25.0 25.0 20.5 20.5<br />

Compressor - Per Compressor<br />

Quantity 1 1 2 2<br />

Nominal Run Amps A 8.3 9.2 6.5 6.5<br />

Locked Rotor Amps A 66.0 74.0 50.0 50.0<br />

Motor Size kW 5.6 6.5 4.7 4.7<br />

Type of Start Direct On Line<br />

Matched Outdoor Condenser - Per Fan<br />

Quantity/Motor Size kW 1 x 0.6 1 x 0.6 2 x 0.6 2 x 0.6<br />

Full Load Amps A 2.62 2.62 2.62 2.62<br />

OPTIONAL EXTRAS<br />

Electric Heating<br />

Stage of Reheat 1 1 2 2<br />

Number of Elements 3 3 6 6<br />

Rating (Total) kW 7.5 7.5 15.0 15.0<br />

Current Per Phase A 10.9 10.9 21.8 21.8<br />

Humidifier<br />

Capacity kg/hr 0.60 - 3.00 0.60 - 3.00 0.60 - 3.00 0.60 - 3.00<br />

Rating kW 2.25 2.25 2.25 2.25<br />

Full Load Amps A 3.50 3.50 3.50 3.50<br />

Larger Fan Motor - Per Fan<br />

Quantity / Motor Size kW N/A N/A N/A N/A<br />

Full Load Amps A N/A N/A N/A N/A<br />

Locked Rotor Amps A N/A N/A N/A N/A<br />

(1) Values given for full function units (incl. electric heating, humidification and matched condenser) at ARI conditions with standard fan motors, for<br />

optional data, please contact <strong><strong>Air</strong>edale</strong>.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

General Specification - <strong>Air</strong> & Water Cooled Models<br />

ELECTRICAL DATA<br />

DF26X-EZ DF28X-EZ DF31X-EZ DF35X-EZ<br />

DF26WX-EZ DF28WX-EZ DF31WX-EZ DF35WX-EZ<br />

Standard Matched Condensers - X C45 C45 C45 CS50<br />

Unit Data - X (1)<br />

Nominal Run Amps A 57.10 58.30 64.30 66.10<br />

Maximum Start Amps A 165.30 166.50 181.00 192.00<br />

Recommended Mains Fuse Size A 63 63 80 80<br />

Max Mains Incoming Cable Size mm² 35 35 35 35<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit VAC 24 24 24 24<br />

Unit Data - WX (1)<br />

Nominal Run Amps A 51.5 52.7 58.7 60.5<br />

Maximum Start Amps A 159.7 160.9 175.4 186.4<br />

Recommended Mains Fuse Size A 63 63 80 80<br />

Max Mains Incoming Cable Size mm² 35 35 35 35<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit VAC 24 24 24 24<br />

Evaporator Fan - Per Fan<br />

Quantity/Motor Size kW 1 x 1.5 1 x 2.2 1 x 4.0 1 x 4.0<br />

Full Load Amps A 3.5 4.7 8.2 8.2<br />

Locked Rotor Amps A 21.0 32.9 57.4 57.4<br />

Compressor - Per Compressor<br />

Quantity 1 1 1 1<br />

Nominal Run Amps A 14.8 14.8 17.3 19.1<br />

Locked Rotor Amps A 123.0 123.0 134.0 145.0<br />

Motor Size kW 8.3 8.3 9.7 11.0<br />

Type of Start Direct On Line<br />

Matched Outdoor Condenser - Per Fan<br />

Quantity/Motor Size kW 2 x 0.6 2 x 0.6 2 x 0.6 2 x 0.6<br />

Full Load Amps A 2.62 2.62 2.62 2.62<br />

OPTIONAL EXTRAS<br />

Electric Heating<br />

Stage of Reheat 3 3 3 3<br />

Number of Elements 8 8 8 8<br />

Rating (Total) kW 20 20 20 20<br />

Current Per Phase A 32.4 32.4 32.4 32.4<br />

Humidifier<br />

Capacity kg/hr 1.60 - 8.00 1.60 - 8.00 1.60 - 8.00 3.00 - 15.00<br />

Rating kW 6.00 6.00 6.00 11.25<br />

Full Load Amps A 8.70 8.70 8.70 15.80<br />

Larger Fan Motor - Per Fan<br />

Quantity / Motor Size kW 1 x 2.2 1 x 3.0 N/A 1 x 5.5<br />

Full Load Amps A 4.7 6.3 N/A 10.9<br />

Locked Rotor Amps A 32.9 44.1 N/A 76.3<br />

Next Larger Fan Motor - Per Fan<br />

Quantity / Motor Size kW 1 x 3.0 1 x 4.0 N/A N/A<br />

Full Load Amps A 6.3 8.2 N/A N/A<br />

Locked Rotor Amps A 44.1 57.4 N/A N/A<br />

(1) Values given for full function units (incl. electric heating, humidification and matched condenser) at ARI conditions with standard fan motors, for<br />

optional data, please contact <strong><strong>Air</strong>edale</strong>.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 33<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

AIR & WATER COOLED


AIR & WATER COOLED<br />

34<br />

-DF<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

General Specification - <strong>Air</strong> & Water Cooled Models<br />

ELECTRICAL DATA<br />

DF40X-EZ DF45X-EZ DF50X2-EZ DF55X2-EZ DF60X2-EZ<br />

DF40WX-EZ DF45WX-EZ DF50WX2-EZ DF55WX2-EZ DF60WX2-EZ<br />

Standard Matched Condensers - X CS50 CS50 CS65 CS80 CS80<br />

Unit Data - X (1)<br />

Nominal Run Amps A 72.60 75.70 90.50 91.20 97.60<br />

Maximum Start Amps A 194.70 224.70 204.80 196.70 201.50<br />

Recommended Mains Fuse Size A 80 100 100 100 125<br />

Max Mains Incoming Cable Size mm² 35 35 35 35 35<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit VAC 24 24 24 24 24<br />

Unit Data - WX (1)<br />

Nominal Run Amps A 67 70.1 82.1 82.5 88.9<br />

Maximum Start Amps A 189.1 219.1 197.8 188 192.8<br />

Recommended Mains Fuse Size A 80 80 100 100 100<br />

Max Mains Incoming Cable Size mm² 35 35 35 35 35<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit VAC 24 24 24 24 24<br />

Evaporator Fan - Per Fan<br />

Quantity/Motor Size kW 1 x 5.5 1 x 5.5 2 x 2.2 2 x 2.2 2 x 3.0<br />

Full Load Amps A 10.9 10.9 4.7 4.7 6.3<br />

Locked Rotor Amps A 76.3 76.3 32.9 32.9 44.1<br />

Compressor - Per Compressor<br />

Quantity 1 1 2 2 2<br />

Nominal Run Amps A 22.9 26.0 14.3 14.5 16.1<br />

Locked Rotor Amps A 145.0 175.0 130.0 120.0 120.0<br />

Motor Size kW 11.9 13.2 7.8 8.5 9.7<br />

Type of Start Direct On Line<br />

Matched Outdoor Condenser - Per Fan<br />

Quantity/Motor Size kW 2 x 0.78 2 x 0.78 3 x 0.78 3 x 0.78 3 x 0.78<br />

Full Load Amps A 3.50 3.50 3.50 3.50 3.50<br />

OPTIONAL EXTRAS<br />

Electric Heating<br />

Stage of Reheat 3 3 3 3 3<br />

Number of Elements 8 8 12 12 12<br />

Rating (Total) kW 20.0 20.0 30.0 30.0 30.0<br />

Current Per Phase A 32.4 32.4 43.6 43.6 43.6<br />

Humidifier<br />

Capacity kg/hr 3.00 - 15.00 3.00 - 15.00 3.00 - 15.00 3.00 - 15.00 3.00 - 15.00<br />

Rating kW 11.25 11.25 11.25 11.25 11.25<br />

Full Load Amps A 15.80 15.80 15.80 15.80 15.80<br />

Larger Fan Motor - Per Fan<br />

Quantity / Motor Size kW N/A N/A 2 x 3.0 2 x 3.0 2 x 4.0<br />

Full Load Amps A N/A N/A 6.3 6.3 8.2<br />

Locked Rotor Amps A N/A N/A 44.1 44.1 57.4<br />

Next Larger Fan Motor - Per Fan<br />

Quantity / Motor Size kW<br />

Motor Size kW N/A N/A 2 x 4.0 2 x 4.0 N/A<br />

Full Load Amps A N/A N/A 8.2 8.2 N/A<br />

Locked Rotor Amps A N/A N/A 57.4 57.4 N/A<br />

(1) Values given for full function units (incl. electric heating, humidification and matched condenser) at ARI conditions with standard fan motors and<br />

filters, for optional data, please contact <strong><strong>Air</strong>edale</strong>.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Sound Data - <strong>Air</strong> & Water Cooled Models<br />

SOUND DATA<br />

DF6X-EZ<br />

DF6WX-EZ<br />

DF8X-EZ<br />

DF8WX-EZ<br />

DF10X-EZ<br />

DF10WX-EZ<br />

DF13X-EZ<br />

DF13WX-EZ<br />

DF15X-EZ<br />

DF15WX-EZ<br />

DF17X-EZ<br />

DF17WX-EZ<br />

DF22X2-EZ<br />

DF22WX2-EZ<br />

DF25X2-EZ<br />

DF22WX2-EZ<br />

IMPORTANT To be read in conjunction with Method of Sound Measurement.<br />

Sound<br />

Overall<br />

Frequency (Hz) dB<br />

Measurement<br />

dB(A) 63 125 250 500 1000 2000 4000 8000<br />

Discharge <strong>Air</strong> Power 71 65 69 67 67 67 66 58 54<br />

Return <strong>Air</strong> Power 62 68 68 66 59 54 51 49 39<br />

Case Breakout Power 58 64 66 58 55 52 47 44 38<br />

Sound @ 3m Pressure 43 50 51 43 40 37 33 29 24<br />

Discharge <strong>Air</strong> Power 77 70 74 73 72 72 71 64 59<br />

Return <strong>Air</strong> Power 68 73 74 72 65 59 56 54 44<br />

Case Breakout Power 63 70 71 63 60 56 53 50 43<br />

Sound @ 3m Pressure 48 55 57 49 45 42 38 36 29<br />

Discharge <strong>Air</strong> Power 80 73 77 76 75 75 74 67 62<br />

Return <strong>Air</strong> Power 71 76 77 75 68 62 59 57 47<br />

Case Breakout Power 66 73 74 66 63 59 55 53 47<br />

Sound @ 3m Pressure 51 58 60 52 48 45 41 38 32<br />

Discharge <strong>Air</strong> Power 77 71 74 72 72 72 71 64 59<br />

Return <strong>Air</strong> Power 67 73 74 72 65 59 56 54 44<br />

Case Breakout Power 63 70 71 63 60 56 52 50 44<br />

Sound @ 3m Pressure 48 56 57 49 45 42 38 36 30<br />

Discharge <strong>Air</strong> Power 73 70 75 72 69 68 67 62 57<br />

Return <strong>Air</strong> Power 66 73 74 71 62 55 52 53 42<br />

Case Breakout Power 62 70 72 63 57 54 49 51 44<br />

Sound @ 3m Pressure 47 55 57 49 43 39 34 36 29<br />

Discharge <strong>Air</strong> Power 77 74 78 76 73 72 70 66 61<br />

Return <strong>Air</strong> Power 70 77 78 75 66 59 55 56 46<br />

Case Breakout Power 65 73 76 67 61 57 52 53 46<br />

Sound @ 3m Pressure 50 59 61 52 46 43 38 39 31<br />

Discharge <strong>Air</strong> Power 81 74 78 77 76 77 75 68 63<br />

Return <strong>Air</strong> Power 72 77 78 76 69 63 60 59 48<br />

Case Breakout Power 67 74 76 68 64 61 56 54 48<br />

Sound @ 3m Pressure 52 59 61 53 49 46 42 40 34<br />

Discharge <strong>Air</strong> Power 85 79 83 81 80 81 79 72 67<br />

Return <strong>Air</strong> Power 76 81 82 80 73 67 64 63 52<br />

Case Breakout Power 71 78 80 72 68 65 60 58 52<br />

Sound @ 3m Pressure 56 64 65 57 54 50 46 43 37<br />

(1) dB(A) is the overall sound level, measured on the A scale.<br />

(2) All sound data measured at nominal conditions.<br />

The Sound Pressure data quoted is only valid where the unit is installed on a false floor and against a rear wall. If the equipment is<br />

placed adjacent to any other vertical reflective walls, values may vary to those stated, typically increasing by 3dB for each side<br />

added. Values stated do not include for room reverberation conditions.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 35<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

AIR & WATER COOLED


AIR & WATER COOLED<br />

36<br />

-DF<br />

Sound Data - <strong>Air</strong> & Water Cooled Models<br />

SOUND DATA<br />

DF26X-EZ<br />

DF26WX-EZ<br />

DF28X-EZ<br />

DF28WX-EZ<br />

DF31X-EZ<br />

DF31WX-EZ<br />

DF35X-EZ<br />

DF35WX-EZ<br />

DF40X-EZ<br />

DF40WX-EZ<br />

DF45X-EZ<br />

DF45WX-EZ<br />

DF50X2-EZ<br />

DF50WX2-EZ<br />

DF55X2-EZ<br />

DF55WX2-EZ<br />

DF60X2-EZ<br />

DF60WX2-EZ<br />

IMPORTANT To be read in conjunction with Method of Sound Measurement.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Sound<br />

Overall<br />

Frequency (Hz) dB<br />

Measurement<br />

dB(A) 63 125 250 500 1000 2000 4000 8000<br />

Discharge <strong>Air</strong> Power 84 75 76 77 79 79 79 76 72<br />

Return <strong>Air</strong> Power 66 75 68 60 65 61 55 54 44<br />

Case Breakout Power 68 77 67 61 66 64 57 54 45<br />

Sound @ 3m Pressure 53 62 52 46 51 50 43 39 31<br />

Discharge <strong>Air</strong> Power 87 77 80 79 81 81 82 79 76<br />

Return <strong>Air</strong> Power 68 77 71 63 66 63 58 56 47<br />

Case Breakout Power 70 79 70 63 67 67 60 57 48<br />

Sound @ 3m Pressure 55 64 56 49 53 52 45 42 34<br />

Discharge <strong>Air</strong> Power 91 78 84 83 85 84 85 83 80<br />

Return <strong>Air</strong> Power 71 77 75 66 69 66 61 60 52<br />

Case Breakout Power 73 79 74 67 70 69 63 60 52<br />

Sound @ 3m Pressure 58 65 59 52 55 55 48 46 38<br />

Discharge <strong>Air</strong> Power 90 77 83 82 87 83 84 82 79<br />

Return <strong>Air</strong> Power 71 76 74 65 71 65 60 59 51<br />

Case Breakout Power 72 78 73 66 71 68 61 60 51<br />

Sound @ 3m Pressure 58 64 58 51 57 53 47 45 37<br />

Discharge <strong>Air</strong> Power 92 80 86 85 89 86 86 85 81<br />

Return <strong>Air</strong> Power 73 78 76 67 73 67 62 62 53<br />

Case Breakout Power 75 80 75 68 74 70 64 62 54<br />

Sound @ 3m Pressure 60 65 61 54 59 56 49 48 40<br />

Discharge <strong>Air</strong> Power 92 80 86 85 89 86 86 85 81<br />

Return <strong>Air</strong> Power 73 78 76 67 73 67 62 62 54<br />

Case Breakout Power 75 80 75 68 74 70 64 62 54<br />

Sound @ 3m Pressure 60 65 61 54 59 56 49 48 40<br />

Discharge <strong>Air</strong> Power 89 78 84 86 82 83 84 81 76<br />

Return <strong>Air</strong> Power 69 76 75 69 66 64 59 58 48<br />

Case Breakout Power 71 79 74 69 67 68 61 58 49<br />

Sound @ 3m Pressure 56 64 59 55 52 53 47 43 34<br />

Discharge <strong>Air</strong> Power 89 78 84 86 82 83 84 81 76<br />

Return <strong>Air</strong> Power 70 77 75 69 67 64 60 58 48<br />

Case Breakout Power 71 79 74 69 68 68 62 58 49<br />

Sound @ 3m Pressure 57 64 59 55 53 53 47 44 35<br />

Discharge <strong>Air</strong> Power 91 80 85 89 84 85 86 83 79<br />

Return <strong>Air</strong> Power 71 79 76 72 69 66 62 60 51<br />

Case Breakout Power 73 81 75 73 69 69 63 60 52<br />

Sound @ 3m Pressure 58 66 60 58 55 54 49 46 37<br />

(1) dB(A) is the overall sound level, measured on the A scale.<br />

(2) All sound data measured at nominal conditions.<br />

The Sound Pressure data quoted is only valid where the unit is installed on a false floor and against a rear wall. If the equipment is<br />

placed adjacent to any other vertical reflective walls, values may vary to those stated, typically increasing by 3dB for each side<br />

added. Values stated do not include for room reverberation conditions.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Design Data - <strong>Air</strong> & Water Cooled Models<br />

WATERSIDE PRESSURE DROP (KPA) - WX TYPE MODELS<br />

DF6WX - DF25WX2<br />

DF26WX - DF60WX2<br />

PRESSURE DROP (kPa)<br />

PRESSURE DROP (kPa)<br />

200<br />

150<br />

100<br />

50<br />

0<br />

250<br />

200<br />

150<br />

100<br />

50<br />

0<br />

200<br />

150<br />

100<br />

50<br />

6 8 - 13 15 17 -25<br />

0<br />

0 0.25 0.5 0.75 1 1.25 1.5 1.75 2<br />

0.00 0.25 0.50 0.75 1.00 1.25 1.50 1.75 2.00<br />

250<br />

200<br />

150<br />

100<br />

50<br />

WATERFLOW (l/s)<br />

26 - 35 40<br />

45 - 60<br />

0<br />

1 1.5 2 2.5 3 3.5 4 4.5 5<br />

1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0<br />

WATERFLOW (l/s)<br />

(1) Includes coil, 3 port valve and pipework.<br />

(2) To calculate 3 port valve pressure drop:<br />

P valve =<br />

2<br />

Q <br />

<br />

M <br />

(3) Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors.<br />

Kv <br />

where P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M = <br />

36 <br />

M Values<br />

Model Sizes 6 - 15 17 - 25 26 - 35 40 - 60<br />

Water Cooled Valve 0.13 0.22 0.28 0.46<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 37<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

AIR & WATER COOLED


AIR & WATER COOLED<br />

38<br />

-DF<br />

Design Data - <strong>Air</strong> & Water Cooled Models<br />

LOW PRESSURE HOT WATER (OPTIONAL EXTRA) - X & WX TYPE MODELS<br />

DF6 - DF25<br />

DF26 - DF60<br />

PRESSURE DROP (kPa)<br />

PRESSURE DROP (kPa)<br />

(1) Includes coil, 3 port valve and pipework.<br />

(2) To calculate 3 port valve pressure drop:<br />

P valve =<br />

2<br />

Q <br />

<br />

M <br />

M Values<br />

Model Sizes 6 - 60<br />

LPHW 0.18<br />

20<br />

15<br />

10<br />

5<br />

20<br />

15<br />

10<br />

5<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

6 - 10<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

13 - 17<br />

22 - 25<br />

0<br />

0 0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45<br />

0.00 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

26 - 31<br />

WATERFLOW (l/s)<br />

35 - 45<br />

50 - 60<br />

0<br />

0 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0<br />

0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0<br />

WATERFLOW (l/s)<br />

Kv <br />

where P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M = <br />

36


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Design Data - <strong>Air</strong> & Water Cooled Models<br />

SYSTEM PIPEWORK<br />

SCHEMATIC<br />

X Type<br />

19<br />

17<br />

16<br />

21<br />

20 SPT<br />

4<br />

TT<br />

LP<br />

HP<br />

4<br />

15<br />

12<br />

WX Type<br />

19<br />

17<br />

21<br />

20<br />

4<br />

T T<br />

S P T<br />

LP<br />

16 H P<br />

4<br />

28<br />

HC<br />

23<br />

22<br />

23<br />

22<br />

24<br />

B<br />

27<br />

15<br />

1<br />

3<br />

18<br />

2<br />

14<br />

3<br />

1<br />

BV 29<br />

4<br />

18<br />

13/2 13/1<br />

26<br />

7<br />

7<br />

25<br />

24 B<br />

B 24<br />

Design should be in accordance with good refrigeration practice to ensure good oil return<br />

to the compressor under all normal operating conditions to prolong the life of your unit.<br />

4<br />

4<br />

TEV<br />

5<br />

6<br />

EEV 8<br />

T EV<br />

9<br />

4<br />

HPT 10<br />

11<br />

12<br />

13<br />

5<br />

6<br />

E EV 8<br />

9<br />

4<br />

HPT 10<br />

11<br />

4<br />

1 Indoor Unit<br />

2 Outdoor Unit(s)<br />

3 Evaporator Coil<br />

4 Schrader Point<br />

5 Liquid Expansion Line<br />

6 Thermostatic Expansion Valve (TEV) - Standard<br />

7 Equalisation Line - Standard with TEV<br />

8 Electronic Expansion valve (EEV) - Optional in place of TEV<br />

9 Sight Glass<br />

10 Head Pressure Transducer<br />

11 Filter Drier (Supplied Loose)<br />

12 Shut Off Valve (Supplied loose) - Optional with Outdoor Units<br />

13 Liquid Line<br />

14 Condenser Coil & Fan<br />

15 Discharge Line<br />

16 High Pressure Switch<br />

17 Scroll Compressor<br />

18 Additional Scroll Compressor (Tandem Set)<br />

19 Low Pressure Switch<br />

20 Suction Pressure Transducer - Optional with EEV<br />

21 Temperature Transmitter - Optional with EEV<br />

22 TEV Bulb - Standard with TEV<br />

23 Suction Line<br />

1 Indoor Unit<br />

3 Evaporator Coil<br />

4 Schrader Point<br />

5 Liquid Expansion Line<br />

6 Thermostatic Expansion Valve (TEV) - Standard<br />

7 Equalisation Line - Standard with TEV<br />

8 Electronic Expansion valve (EEV) - Optional in place of TEV<br />

9 Sight Glass<br />

10 Head Pressure Transducer<br />

11 Filter Drier (Supplied Loose)<br />

13 Liquid Line 1 & 2<br />

15 Discharge Line<br />

16 High Pressure Switch<br />

17 Scroll Compressor<br />

18 Additional Scroll Compressor (Tandem Set)<br />

19 Low Pressure Switch<br />

20 Suction Pressure Transducer - Optional with EEV<br />

21 Temperature Transmitter - Optional with EEV<br />

22 TEV Bulb - Standard with TEV<br />

23 Suction Line<br />

24 Binder Point<br />

25 Plate Condenser<br />

26 Bypass Leg & Ball Valve<br />

27 Liquid Receiver<br />

28 Head Pressure Control Valve<br />

29 Bleed Valve<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 39<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

AIR & WATER COOLED


AIR & WATER COOLED<br />

40<br />

-DF<br />

Design Data - <strong>Air</strong> & Water Cooled Models<br />

REFRIGERANT PIPE<br />

SIZING GUIDE -<br />

X TYPE MODELS<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Pipe lengths calculated for Indoor unit with standard Outdoor CE Condenser match. For<br />

Condenser unit connections sizes, please refer to Condenser Installation <strong>Manual</strong>.<br />

Indoor Outdoor Indoor Unit<br />

Equivalent Pipe Lengths with R407C<br />

Connection Size<br />

0-15m 15-40m<br />

Liquid Discharge Liquid<br />

Discharge<br />

Horizontal<br />

Liquid<br />

Discharge<br />

(1) Vertical (2) Horizontal (1) Vertical (2)<br />

DF6X C11 3/8” 5/8” 3/8” 5/8” 5/8” 1/2” 3/4” 3/4”<br />

DF8X C15 3/8” 5/8” 3/8” 5/8” 5/8” 1/2” 3/4” 3/4”<br />

DF10X C15 3/8” 5/8” 3/8” 5/8” 5/8” 1/2” 3/4” 3/4”<br />

DF13X C20 1/2” 3/4” 1/2” 3/4” 3/4” 5/8” 7/8” 7/8”<br />

DF15X C25 1/2” 3/4” 1/2” 3/4” 3/4” 5/8” 7/8” 7/8”<br />

DF17X C35 1/2” 3/4” 1/2” 3/4” 3/4” 5/8” 7/8” 7/8”<br />

DF22X2 C45 5/8” 7/8” 5/8” 7/8” 7/8” 5/8” 7/8” 7/8”<br />

DF25X2 C45 5/8” 7/8” 5/8” 7/8” 7/8” 5/8” 1 1/8” 7/8”<br />

DF26X C45 5/8” 7/8” 5/8” 1 1/8” 1 1/8” 3/4” 1 1/8” 1 1/8”<br />

DF28X C45 5/8” 7/8” 5/8” 1 1/8” 1 1/8” 3/4” 1 1/8” 1 1/8”<br />

DF31X C45 5/8” 7/8” 5/8” 1 1/8” 1 1/8” 3/4” 1 1/8” 1 1/8”<br />

DF35X CS50 5/8” 7/8” 5/8” 1 1/8” 1 1/8” 3/4” 1 3/8” 1 1/8”<br />

DF40X CS50 7/8” 1 1/8” 7/8” 1 3/8” 1 3/8” 3/4” 1 3/8” 1 3/8”<br />

DF45X CS50 7/8” 1 1/8” 7/8” 1 3/8” 1 3/8” 7/8” 1 3/8” 1 3/8”<br />

DF50X2 CS65 7/8” 1 3/8” 7/8” 1 3/8” 1 3/8” 7/8” 1 5/8” 1 3/8”<br />

DF55X2 CS80 7/8” 1 3/8” 7/8” 1 5/8” 1 3/8” 7/8” 1 5/8” 1 5/8”<br />

DF60X2 CS80 7/8” 1 3/8” 7/8” 1 5/8” 1 5/8” 1 1/8” 1 5/8” 1 5/8”<br />

(1) For interconnecting pipework with a predominantly horizontal layout.<br />

(2) For interconnecting pipework with a predominantly vertical layout.<br />

REFRIGERANT<br />

CHARGING GUIDE -<br />

X TYPE MODELS<br />

Unit Refrigerant Charge<br />

(kg/Circuit)<br />

The following information can be used to estimate the refrigerant quantity required in a<br />

typical split system installation.<br />

The following table shows the refrigerant charge / circuit for the indoor and outdoor units.<br />

Indoor Unit Standard Condenser Upgraded Condenser<br />

(IR) kg/Circuit (OR) kg/Circuit (OR) kg/Circuit<br />

DF6X-EZ 2.0 C11 2.1 C15 2.1<br />

DF8X-EZ 2.0 C15 2.1 C20 2.3<br />

DF10X-EZ 2.0 C15 2.1 C20 2.3<br />

DF13X-EZ 3.2 C20 2.3 C25 3.1<br />

DF15X-EZ 3.2 C25 3.1 C35 6.1<br />

DF17X-EZ 3.2 C35 6.1 C45 6.1<br />

DF22X2-EZ 4.1 C45 6.1 CS50 4.3<br />

DF25X2-EZ 4.1 C45 6.1 CS50 4.3<br />

DF26X-EZ 4.9 C45 6.1 CS50 4.3<br />

DF28X-EZ 4.9 C45 6.1 CS50 4.3<br />

DF31X-EZ 4.9 C45 6.1 CS50 4.3<br />

DF35X-EZ 6.5 CS50 4.3 CS65 8.5<br />

DF40X-EZ 6.5 CS50 4.3 CS65 8.5<br />

DF45X2-EZ 7.9 CS50 4.3 CS65 8.5<br />

DF50X2-EZ 7.7 CS65 8.5 CS80 7.3<br />

DF55X2-EZ 9.4 CS80 7.3 CS105 14.6<br />

DF60X2-EZ 9.4 CS80 7.3 CS105 14.6


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Design Data - <strong>Air</strong> & Water Cooled Models<br />

REFRIGERANT PIPE SIZING GUIDE - X TYPE MODELS<br />

Liquid Line Refrigerant<br />

Charge (kg/m)<br />

IMPORTANT<br />

To Calculate the Liquid<br />

Line Refrigerant Charge<br />

(kg)<br />

To Calculate the System<br />

Refrigerant Charge (kg)<br />

The following table shows the refrigerant charge / metre for the liquid line, using R407C<br />

and assuming liquid line temperature of 40°C.<br />

Liquid Line (m) kg/m<br />

3/8” 0.05<br />

1/2” 0.11<br />

5/8” 0.16<br />

3/4” 0.24<br />

7/8” 0.34<br />

The pipe sizes/refrigerant charges quoted are for guidance only. It is the<br />

responsibility of the installing contractor/site engineer to check the pipe<br />

sizes/refrigerant charge is correct for each system installation and application.<br />

Split systems may require additional oil which should be added to the low side of<br />

each compressor.<br />

Design should be in accordance with accepted refrigeration practice to ensure<br />

good oil return to the compressor(s) under all normal operating conditions.<br />

The liquid line refrigerant charge can be calculated using the following equation:<br />

LR = L x m<br />

Where:<br />

LR = Total Liquid Line Refrigerant charge (kg)<br />

L = Length of Interconnecting pipework (metres)<br />

m = Liquid Line Refrigerant charge / metre. Refer to Liquid Line Refrigerant Charge (kg/m)<br />

in this section<br />

The system refrigerant charge can be calculated using the following equation:<br />

SR = LR + IR + OR<br />

Where:<br />

SR = Total System Refrigerant charge (kg)<br />

LR = Total Liquid Line Refrigerant charge. (As calculated from above)<br />

IR = Indoor Unit Refrigerant Charge. Refer to Unit Refrigerant Charge (kg/Circuit) in this<br />

section<br />

OR = Outdoor Unit Refrigerant Charge. Refer to Unit Refrigerant Charge (kg/Circuit) in this<br />

section<br />

Example Indoor Unit Model Ref. = DF25X2-EZ (Tandem Set)<br />

Outdoor Unit Model Ref. = C45-H Condenser<br />

Interconnecting Pipework = 10 metres<br />

Selecting The Liquid Line Size<br />

From the Liquid Line Refrigerant Charge (kg/m) table in this section, the liquid line size given for<br />

pipework length of 10 metres is:<br />

Liquid Line Size = 5/8”<br />

Liquid Line Refrigerant Charge<br />

LR = L x m Where:<br />

L = 10 metres<br />

m = 0.16 kg/m<br />

LR = 10 x 0.16 Liquid Line Charge = 1.6 kg<br />

System Refrigerant Charge<br />

SR = LR + IR + OR Where:<br />

LR = 1.6 kg. (As calculated from above)<br />

IR = 4.1 kg<br />

OR = 6.1 kg<br />

SR = 1.6 + 4.1 + 5.2 System Refrigerant Charge = 11.8 kg / Circuit<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 41<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

AIR & WATER COOLED


AIR & WATER COOLED<br />

42<br />

-DF<br />

Design Data - <strong>Air</strong> & Water Cooled Models<br />

ETHYLENE GLYCOL CORRECTION FACTORS<br />

WX Type Models<br />

For conditions outside those quoted, please refer to <strong><strong>Air</strong>edale</strong>.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

The Use of Glycol Glycol is recommended when a supply water temperature of +5°C or below is required or<br />

when static water can be exposed to freezing temperatures.<br />

The effect of glycol in the system has a direct effect upon the Cooling Duty, the Design<br />

Flow Rate and the unit Pressure Drop.<br />

To approximate the effect of glycol on unit performance, the following correction factors<br />

when applied can be used as a guide.<br />

Where:<br />

V = Corrected Flow Rate.<br />

THR = Equivalent Total Heat of Rejection (THR) (kW), refer to Cooling Duties - WX Type<br />

Models (the change in THR values as glycol concentration is increased is<br />

negligible.)<br />

T = Temperature difference between Water/Glycol Inlet/Outlet (°C).<br />

P = Maximum Water/ Glycol Pressure Drop for the indoor unit (kPa).<br />

Pw = Equivalent Water Pressure Drop for indoor unit (kPa), use the corrected flow<br />

rate V . Refer to Waterside Pressure Drop (kPa) - WX Type Models.<br />

Ethylene Glycol (Volume) / Freezing Point °C<br />

10% / -4°C 20% / -9°C 30% / -15°C 40% / -23°C<br />

V P<br />

Corrected Flow Rate<br />

Corrected Pressure Drop<br />

= THR / T<br />

= Pw<br />

Flow Rate<br />

Pressure Drop<br />

x by<br />

0.240<br />

1.041<br />

0.250<br />

1.083<br />

0.250<br />

1.133<br />

0.260<br />

1.200<br />

Example: DF26WX-EZ Condensing Entering / Leaving at 30°C/35°C, Based on ΔT of 5°C,<br />

24°C/45% RH Ambient, 20% Ethylene Glycol<br />

Ethylene Glycol (Volume) / Freezing Point °C<br />

10% / -4°C 20% / -9°C 30% / -15°C 40% / -23°C<br />

V 1.64 l/s<br />

THR (32.7) / T<br />

=<br />

(12 – 7 = 5T) =<br />

6.54<br />

x by<br />

0.240 0.250 0.250 0.260<br />

P 70.4 kPa = Pw 65 kPa 1.041 1.083 1.133 1.200


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Design Data - <strong>Air</strong> & Water Cooled Models<br />

INTERCONNECTING WIRING<br />

X Type Matched System<br />

WX Type<br />

X & WX Type<br />

Indoor Controls Only<br />

INDOOR UNIT<br />

INDOOR UNIT<br />

INDOOR UNIT<br />

Remote On/Off INDOOR UNIT<br />

Run/Standby Network<br />

INDOOR UNIT<br />

L1 <br />

L2 <br />

L3 <br />

N <br />

PE <br />

C1 <br />

N1 <br />

PE <br />

L1 <br />

L2 <br />

L3 <br />

N <br />

PE <br />

Mains Incoming Supply 400V / 3PH / +N / 50Hz<br />

Mains sub fused supply 230vac 50Hz<br />

- (must be wired from indoor unit)<br />

Link<br />

Mains Incoming Supply 400V / 3PH / +N / 50Hz<br />

560 Volt Free Alarm N/O<br />

561 Volt Free Alarm Common<br />

562 Volt Free Alarm N/C<br />

502 Fire Shutdown input<br />

583 Healthy in N/C Condition<br />

502 Remote On/OFF<br />

522 <br />

TK<br />

TK<br />

U1<br />

U2<br />

PE<br />

Common Alarm<br />

Rx-/Tx- <br />

Use Awg20/22 twisted pair (with overall shield)<br />

Rx-/Tx-<br />

Rx+/Tx+ cable, Belden ref. 8762 (<strong><strong>Air</strong>edale</strong> ref: 017-415), Rx+/Tx+<br />

GND <br />

or equivalent, for network<br />

GND<br />

OUTDOOR<br />

UNIT<br />

INDOOR UNIT<br />

N + 1<br />

CABLE INSTALLATION In line with IEE Wiring Regulations, the following should be observed:<br />

Extra low voltage control cables (ELV) and mains power cable should be segregated<br />

by a minimum distance of 50mm.<br />

If cables must cross, it is recommended that they cross at right angles.<br />

<strong><strong>Air</strong>edale</strong> recommends that ELV cables are screened at one end to<br />

earthed enclosures.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 43<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

AIR & WATER COOLED


CHILLED WATER<br />

44<br />

-DF<br />

CHILLED W AT ER (CW ) MODEL S<br />

Performance Data - Chilled Water Models<br />

COOLING DUTIES<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Cooling Capacity (1) Chilled Water Inlet/Outlet °C<br />

<strong>Air</strong> On ºC DB<br />

5/10°C 7/12°C 8/14°C 10/16°C<br />

/ % RH TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)<br />

22 / 50 8.5 6.9 6.7 6.0 5.1 5.1 4.1 4.1<br />

DF6CW-EZ<br />

24 / 45 9.8 8.1 8.0 7.1 6.3 6.3 5.3 5.3<br />

26 / 40 11.1 9.4 8.9 8.4 7.6 7.6 6.6 6.6<br />

22 / 50 10.6 8.9 7.7 7.7 6.6 6.6 5.3 5.3<br />

DF8CW-EZ<br />

24 / 45 12.3 10.5 9.2 9.2 8.1 8.1 6.8 6.8<br />

26 / 40 13.9 12.2 10.9 10.9 9.8 9.8 8.4 8.4<br />

22 / 50 12.4 10.8 9.3 9.3 7.9 7.9 6.3 6.3<br />

DF10CW-EZ<br />

24 / 45 14.6 12.9 11.1 11.1 9.8 9.8 8.1 8.1<br />

26 / 40 16.4 14.7 13.1 13.1 11.7 11.7 10.2 10.2<br />

22 / 50 16.2 13.0 12.4 11.3 9.7 9.7 7.7 7.7<br />

DF13CW-EZ<br />

24 / 45 18.7 15.2 14.8 13.5 12.0 12.0 10.1 10.1<br />

26 / 40 21.2 17.6 17.2 15.8 14.4 14.4 12.4 12.4<br />

22 / 50 18.5 15.2 14.0 14.0 11.3 11.3 9.0 9.0<br />

DF15CW-EZ<br />

24 / 45 21.4 17.7 17.5 15.6 13.9 13.9 11.7 11.7<br />

26 / 40 24.3 20.5 19.4 18.4 16.7 16.7 14.4 14.4<br />

22 / 50 20.7 17.2 15.0 15.0 12.9 12.9 10.2 10.2<br />

DF17CW-EZ<br />

24 / 45 23.9 20.1 19.6 17.7 15.8 15.8 13.2 13.2<br />

26 / 40 27.2 23.3 21.9 21.1 19.0 19.0 16.4 16.4<br />

22 / 50 26.0 21.3 20.5 18.5 15.9 15.9 12.7 12.7<br />

DF22CW-EZ<br />

24 / 45 30.1 24.9 24.6 22.0 19.6 19.6 16.4 16.4<br />

26 / 40 34.2 29.0 27.5 26.1 23.6 23.6 20.3 20.3<br />

22 / 50 29.2 24.4 21.3 21.3 18.1 18.1 14.4 14.4<br />

DF25CW-EZ<br />

24 / 45 33.8 28.6 27.8 25.1 22.3 22.3 18.7 18.7<br />

26 / 40 38.5 33.2 30.7 29.9 26.9 26.9 23.2 23.2<br />

22 / 50 34.3 27.0 26.5 23.6 20.8 20.8 16.8 16.8<br />

DF26CW-EZ<br />

24 / 45 39.4 31.4 31.3 27.9 25.3 25.3 21.3 21.3<br />

26 / 40 44.6 36.4 36.4 32.9 30.1 30.1 26.1 26.1<br />

22 / 50 37.8 30.2 29.1 26.3 23.2 23.2 18.7 18.7<br />

DF28CW-EZ<br />

24 / 45 43.5 35.1 34.5 31.1 28.1 28.1 23.6 23.6<br />

26 / 40 49.2 40.6 39.8 36.4 33.5 33.5 29.1 29.1<br />

22 / 50 42.3 34.1 32.4 29.8 26.1 26.1 21.1 21.1<br />

DF31CW-EZ<br />

24 / 45 48.6 39.8 38.4 35.3 31.8 31.8 26.8 26.8<br />

26 / 40 55.1 46.1 44.6 41.7 37.9 37.9 32.8 32.8<br />

22 / 50 49.4 40.5 39.1 35.1 30.6 30.6 24.5 24.5<br />

DF35CW-EZ<br />

24 / 45 57.0 47.2 44.8 42.1 37.4 37.4 31.3 31.3<br />

26 / 40 64.8 54.9 52.2 49.5 44.8 44.8 38.7 38.7<br />

22 / 50 53.6 44.4 42.9 38.9 33.5 33.5 26.8 26.8<br />

DF40CW-EZ<br />

24 / 45 61.8 51.9 50.8 45.8 40.9 40.9 34.3 34.3<br />

26 / 40 70.3 60.2 56.4 54.3 49.1 49.1 42.4 42.4<br />

22 / 50 58.9 47.1 45.1 41.0 35.7 35.7 28.6 28.6<br />

DF45CW-EZ<br />

24 / 45 67.9 54.8 53.6 48.5 43.6 43.6 36.6 36.6<br />

26 / 40 77.7 68.2 61.5 61.5 55.1 55.1 47.4 47.4<br />

22 / 50 58.5 50.1 43.4 43.4 36.8 36.8 29.1 29.1<br />

DF50CW-EZ<br />

24 / 45 68.1 58.6 51.9 51.9 45.6 45.6 37.9 37.9<br />

26 / 40 77.0 63.7 62.0 56.7 52.3 52.3 45.2 45.2<br />

22 / 50 65.1 53.1 45.9 45.9 39.5 39.5 31.2 31.2<br />

DF55CW-EZ<br />

24 / 45 75.4 62.0 59.0 55.1 48.6 48.6 40.5 40.5<br />

26 / 40 85.0 71.6 64.8 64.8 58.6 58.6 50.4 50.4<br />

22 / 50 69.6 57.3 49.5 49.5 42.5 42.5 33.6 33.6<br />

DF60CW-EZ<br />

24 / 45 80.7 66.9 59.2 59.2 52.4 52.4 43.8 43.8<br />

26 / 40 90.3 77.3 70.0 70.0 63.1 63.1 54.4 54.4<br />

TC = Total Cooling SC = Sensible Cooling<br />

(1) Deduct fan motor gain for nett duties, refer to Mechanical Data in this section.<br />

(2) Water flow rate (l/s) = TC (4.19 x T) at 100% Water. For glycol use, refer to Ethylene Glycol Correction Factors.<br />

(3) Refer to the Waterside Pressure Drop (kPa) in this section.<br />

OPERATING LIMITS<br />

Cooling<br />

Indoor <strong>Air</strong> Temperature +18°C to +28°C<br />

Indoor RH% +40% to +55%<br />

Water Entering Temperature +5°C to +10°C<br />

Water Leaving Temperature +10°C to +16°C<br />

(1) Conditions quoted at 100% Water.<br />

(2) For conditions outside those quoted, please refer to <strong><strong>Air</strong>edale</strong>.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

General Specification - Chilled Water Models<br />

MECHANICAL DATA<br />

DF6CW-EZ DF8CW-EZ DF10CW-EZ DF13CW-EZ<br />

Capacity (1)<br />

Nom Cooling (Gross) kW 8.0 9.2 11.1 14.8<br />

Fan Gain<br />

Dimensions<br />

kW 0.33 0.60 0.65 0.65<br />

H x W x D<br />

Weight<br />

mm 1940 x 670 x 670 1940 x 670 x 670 1940 x 670 x 670 1940 x 990 x 670<br />

Machine kg 155 165 168 195<br />

Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey, (RAL 7035)<br />

Material/Colour<br />

Frame: Anodised Aluminium Frame with Black Nylon Corners<br />

Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins<br />

Cooling/Dehum Stages 1 (Modulated) / 1<br />

Fan & Motor Centrifugal - Designed to 25Pa ESP<br />

Quantity / Motor Size kW 1 x 0.30 1 x 0.55 1 x 0.60 1 x 0.60<br />

Maximum ESP Pa 196 140 118 294<br />

Nominal <strong>Air</strong>flow<br />

Connections<br />

m³/s 0.55 0.75 0.95 1.00<br />

Inlet/Outlet mm 22 22 22 28<br />

Condensate Drain Hose mm 19 19 19 19<br />

Filtration Disposable to BS EN 779 - G4 - 50mm<br />

Quantity<br />

OPTIONAL EXTRAS<br />

1 1 1 2<br />

Electric Heating (Total)<br />

Humidifier<br />

kW 7.5 7.5 7.5 7.5<br />

Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0<br />

Feed/Drain<br />

Condensate Pump<br />

3/4” BSPF Braided flexible hose/19mm hose connection<br />

Head m 8 8 8 8<br />

Flow l/m 5 5 5 5<br />

Drain 10mm S/Steel Stub Connection<br />

Larger / Next Larger Fan Motor Size<br />

Quantity / Motor Size kW 1 x 0.55 / N/A 1 x 0.60 / N/A N/A / N/A N/A / N/A<br />

Maximum ESP Pa 254 / N/A 253 / N/A N/A / N/A N/A / N/A<br />

Fan Gain rpm 0.60 / N/A 0.65 / N/A N/A / N/A N/A / N/A<br />

Low Pressure Hot Water Copper Tube/Aluminium Fin<br />

Capacity Gross (2) kW 6.50 7.50 8.40 11.50<br />

Water Flow (Nominal) l/s 0.14 0.17 0.19 0.26<br />

LPHW Connection Sizes<br />

Threaded Connections<br />

mm 22 22 22 22<br />

Brass Male Taper in 3/4 3/4 3/4 1<br />

(1) Entering air 24°C/45% RH water 7°C/12°C.<br />

(2) Based upon low pressure hot water 82°C inlet/71°C outlet. <strong>Air</strong> on 20°C. Refer to the Low Pressure Hot Water (Optional Extra) - X & WX Type<br />

Models in this section.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 45<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

CHILLED WATER


CHILLED WATER<br />

46<br />

-DF<br />

General Specification - Chilled Water Models<br />

MECHANICAL DATA<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

DF15CW-EZ DF17CW-EZ DF22CW-EZ DF25CW-EZ<br />

Capacity (1)<br />

Nom Cooling (Gross) kW 17.5 19.6 24.6 27.8<br />

Fan Gain<br />

Dimensions<br />

kW 1.31 1.20 1.31 1.31<br />

H x W x D<br />

Weight<br />

mm 1940 x 990 x 670 1940 x 990 x 670 1940 x 1310 x 670 1940 x 1310 x 670<br />

Machine kg 200 200 252 252<br />

Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey, (RAL 7035)<br />

Material/Colour<br />

Frame: Anodised Aluminium Frame with Black Nylon Corners<br />

Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins<br />

Cooling/Dehum Stages 1 (Modulated) / 1<br />

Fan & Motor Centrifugal Direct Drive - Designed to 25Pa ESP<br />

Quantity / Motor Size kW 1 x 1.10 1 x 1.10 2 x 0.60 2 x 0.60<br />

Maximum ESP Pa 120 34 194 43<br />

Nominal <strong>Air</strong>flow<br />

Connections<br />

m³/s 1.20 1.40 1.70 2.00<br />

Inlet/Outlet mm 28 28 28 28<br />

Condensate Drain Hose mm 19 19 19 19<br />

Filtration Disposable to BS EN 779 - G4 - 50mm<br />

Quantity<br />

OPTIONAL EXTRAS<br />

2 2 3 3<br />

Electric Heating (Total)<br />

Humidifier<br />

kW 7.5 7.5 15.0 15.0<br />

Capacity kg/hr 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0 0.6 - 3.0<br />

Feed/Drain<br />

Condensate Pump<br />

3/4” BSPF Braided flexible hose/19mm hose connection<br />

Head m 8 8 8 8<br />

Flow l/m 5 5 5 5<br />

Drain 10mm S/Steel Stub Connection<br />

Larger / Next Larger Fan Motor Size<br />

Quantity / Motor Size kW N/A / N/A N/A / N/A N/A / N/A N/A / N/A<br />

Maximum ESP Pa N/A / N/A N/A / N/A N/A / N/A N/A / N/A<br />

Fan Gain rpm N/A / N/A N/A / N/A N/A / N/A N/A / N/A<br />

Low Pressure Hot Water Copper Tube/Aluminium Fin<br />

Capacity Gross (2) kW 12.50 13.30 16.10 16.60<br />

Water Flow (Nominal) l/s 0.28 0.30 0.36 0.37<br />

LPHW Connection Sizes<br />

Threaded Connections<br />

mm 22 22 22 22<br />

Brass Male Taper in 1 1 1 1<br />

(1) Entering air 24°C/45% RH water 7°C/12°C.<br />

(2) Based upon low pressure hot water 82°C inlet/71°C outlet. <strong>Air</strong> on 20°C. Refer to the Low Pressure Hot Water (Optional Extra) - X & WX Type<br />

Models in this section.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

General Specification - Chilled Water Models<br />

MECHANICAL DATA<br />

DF26CW-EZ DF28CW-EZ DF31CW-EZ DF35CW-EZ<br />

Capacity<br />

Nom Cooling (Gross) (1) kW 31.3 34.5 38.4 44.8<br />

Fan Gain<br />

Dimensions<br />

kW 0.98 1.43 2.60 2.60<br />

H x W x D<br />

Weight<br />

mm 1940 x 1460 x 750 1940 x 1460 x 750 1940 x 1460 x 750 1940 x 1835 x 750<br />

Machine kg 351 351 354 410<br />

Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey, (RAL 7035)<br />

Material/Colour<br />

Frame: Anodised Aluminium Frame with Black Nylon Corners<br />

Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins<br />

Cooling/Dehum Stages 1 (Modulated) / 1<br />

Fan & Motor Centrifugal - Designed to 25Pa ESP<br />

Quantity / Motor Size kW 1 x 1.5 1 x 2.2 1 x 4.0 1 x 4.0<br />

Speed @ 25Pa / Maximum ESP rpm 775 / 801 871 / 909 1008 / 1171 980 / 1078<br />

Maximum ESP Pa 65 75 265 165<br />

Nominal <strong>Air</strong>flow<br />

Connections<br />

m³/s 2.1 2.4 2.8 3.3<br />

Inlet/Outlet mm 42 42 42 42<br />

Condensate Drain Hose mm 19 19 19 19<br />

Filtration Disposable to BS EN 779 - G4 - 75mm<br />

Quantity<br />

OPTIONAL EXTRAS<br />

3 3 3 3<br />

Electric Heating (Total)<br />

Humidifier<br />

kW 20 20 20 20<br />

Capacity kg/hr 1.6 - 8.0 1.6 - 8.0 1.6 - 8.0 3.0 - 15.0<br />

Feed/Drain<br />

Condensate Pump<br />

3/4” BSPF Braided flexible hose / 19mm hose connection<br />

Head m 10.8 10.8 10.8 10.8<br />

Flow l/m 5 5 5 5<br />

Drain 10mm S/Steel Stub Connection<br />

Larger / Next Larger Fan Motor Size<br />

Quantity / Motor Size kW 1 x 2.20 / 1 x 3.00 1 x 3.00 / 1 x 4.00 N/A / N/A 1 x 5.50 / N/A<br />

Maximum ESP Pa 345 / 665 362 / 722 N/A / N/A 322 / N/A<br />

Speed @ Maximum ESP rpm 1057 / 1350 1144 / 1439 N/A / N/A 1196 / N/A<br />

Fan Gain kW 1.43 / 1.95 1.95 / 2.60 N/A / N/A 3.58 / N/A<br />

Low Pressure Hot Water Copper Tube/Aluminium Fin<br />

Capacity Gross (2) kW 20.10 21.30 22.70 30.00<br />

Water Flow (Nominal) l/s 0.45 0.48 0.51 0.67<br />

LPHW Connection Sizes<br />

Threaded Connections<br />

mm 22 22 22 22<br />

Brass Male Taper in 1 1/2 1 1/2 1 1/2 1 1/2<br />

(1) Entering air 24°C/45% RH water 7°C/12°C.<br />

(2) Based upon low pressure hot water 82°C inlet/71°C outlet. <strong>Air</strong> on 20°C. Refer to the Low Pressure Hot Water (Optional Extra) - X & WX Type<br />

Models in this section.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 47<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

CHILLED WATER


CHILLED WATER<br />

48<br />

-DF<br />

General Specification - Chilled Water Models<br />

MECHANICAL DATA<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

DF40CW-EZ DF45CW-EZ DF50CW-EZ DF55CW-EZ DF60CW-EZ<br />

Capacity<br />

Nom Cooling (Gross) (1) kW 50.8 53.6 51.9 59.0 59.2<br />

Fan Gain kW 3.58 3.58 2.86 2.86 3.90<br />

Dimensions 1940 x 1835 x 1940 x 1835 x 1940 x 2170 x 1940 x 2170 x 1940 x 2170 x 750<br />

H x W x D<br />

Weight<br />

mm<br />

750<br />

750<br />

750<br />

750<br />

Machine kg 431 442 486 499 495<br />

Construction Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey, (RAL 7035)<br />

Material/Colour<br />

Frame: Anodised Aluminium Frame with Black Nylon Corners<br />

Cooling Coil Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins<br />

Cooling/Dehum Stages 1 (Modulated) / 1<br />

Fan & Motor Centrifugal - Designed to 25Pa ESP<br />

Quantity / Motor Size kW 1 x 5.5 1 x 5.5 2 x 2.2 2 x 2.2 2 x 3.0<br />

Speed @ 25Pa / Maximum ESP rpm 1094 / 1186 1094 / 1186 1167 / 1170 1167 / 1170 1307 / 1311<br />

Maximum ESP Pa 175 175 35 35 75<br />

Nominal <strong>Air</strong>flow<br />

Connections<br />

m³/s 3.7 3.7 4.2 4.2 4.6<br />

Inlet/Outlet mm 42 42 42 42 42<br />

Condensate Drain Hose mm 19 19 19 19 19<br />

Filtration Disposable to BS EN 779 - G4 - 75mm<br />

Quantity<br />

Optional Extras<br />

3 3 4 4 4<br />

Electric Heating (Total)<br />

Humidifier<br />

kW 20 20 30 30 30<br />

Capacity kg/hr 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0 3.0 - 15.0<br />

Feed/Drain<br />

Condensate Pump<br />

3/4” BSPF Braided flexible hose / 19mm hose connection<br />

Head m 10.8 10.8 10.8 10.8 10.8<br />

Flow l/m 5 5 5 5 5<br />

Drain 10mm S/Steel Stub Connection<br />

Larger / Next Larger Fan Motor Size<br />

Quantity / Motor Size kW N/A / N/A N/A / N/A 2 x 3.0 / 2 x 4.0 2 x 3.0 / 2 x 4.0 2 x 4.0 / N/A<br />

Maximum ESP Pa N/A / N/A N/A / N/A 310 / 360 310 / 360 275 / N/A<br />

Speed @ Maximum ESP rpm N/A / N/A N/A / N/A 1448 / 1498 1448 / 1498 1497 / N/A<br />

Fan Gain kW N/A / N/A N/A / N/A 3.9 / 5.2 3.9 / 5.2 5.2 / N/A<br />

Low Pressure Hot Water Copper Tube/Aluminium Fin<br />

Capacity Gross (2) kW 31.50 31.50 38.30 38.30 39.80<br />

Water Flow (Nominal) l/s 0.70 0.70 0.85 0.85 0.89<br />

LPHW Connection Sizes<br />

Threaded Connections<br />

mm 22 22 22 22 22<br />

Brass Male Taper in 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2<br />

(1) Entering air 24°C/45% RH ambient 35°C.<br />

(2) Based upon low pressure hot water 82°C inlet/71°C outlet. <strong>Air</strong> on 20°C. Refer to the Low Pressure Hot Water (Optional Extra) - X & WX Type<br />

Models in this section.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

General Specification - Chilled Water Models<br />

ELECTRICAL DATA<br />

DF6CW-EZ DF8CW-EZ DF10CW-EZ DF13CW-EZ<br />

Unit Data (1)<br />

Nominal Run Amps A 17.9 21.2 23.7 23.7<br />

Maximum Start Amps A 17.9 21.2 24.8 24.8<br />

Recommended Mains Fuse Size A 25 32 32 32<br />

Max Mains Incoming Cable Size mm² 6 6 6 6<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit<br />

Evaporator Fan - Per Fan<br />

VAC 24 24 24 24<br />

Quantity / Motor Size kW 1 x 0.30 1 x 0.55 1 x 0.60 1 x 0.60<br />

Full Load Amps A 3.50 6.80 7.70 7.70<br />

Locked Rotor Amps<br />

OPTIONAL EXTRAS<br />

Electric Heating<br />

A 8.75 17.00 20.50 20.50<br />

Stage of Reheat 1 1 1 1<br />

Number of Elements 3 3 3 3<br />

Rating (Total) kW 7.5 7.5 7.5 7.5<br />

Current Per Phase<br />

Humidifier<br />

A 10.9 10.9 10.9 10.9<br />

Capacity kg/hr 0.60 - 3.00 0.60 - 3.00 0.60 - 3.00 0.60 - 3.00<br />

Rating kW 2.25 2.25 2.25 2.25<br />

Full Load Amps<br />

Larger Fan Motor - Per Fan<br />

A 3.50 3.50 3.50 3.50<br />

Quantity / Motor Size kW 1 x 0.55 1 x 0.60 N/A N/A<br />

Full Load Amps A 6.80 7.70 N/A N/A<br />

Locked Rotor Amps A 17.00 20.50 N/A N/A<br />

DF15CW-EZ DF17CW-EZ DF22CW-EZ DF25CW-EZ<br />

Unit Data (1)<br />

Nominal Run Amps A 24.4 24.4 34.6 34.6<br />

Maximum Start Amps A 25 25 34.6 34.6<br />

Recommended Mains Fuse Size A 32 32 40 40<br />

Max Mains Incoming Cable Size mm² 6 6 35 35<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit<br />

Evaporator Fan - Per Fan<br />

VAC 24 24 24 24<br />

Quantity / Motor Size kW 1 x 1.1 1 x 1.1 2 x 0.6 2 x 0.6<br />

Full Load Amps A 10.0 10.0 7.7 7.7<br />

Locked Rotor Amps<br />

OPTIONAL EXTRAS<br />

Electric Heating<br />

A 25.0 25.0 20.5 20.5<br />

Stage of Reheat 1 1 2 2<br />

Number of Elements 3 3 6 6<br />

Rating (Total) kW 7.5 7.5 15.0 15.0<br />

Current Per Phase<br />

Humidifier<br />

A 10.9 10.9 21.8 21.8<br />

Capacity kg/hr 0.60 - 3.00 0.60 - 3.00 0.60 - 3.00 0.60 - 3.00<br />

Rating kW 2.25 2.25 2.25 2.25<br />

Full Load Amps<br />

Larger Fan Motor - Per Fan<br />

A 3.50 3.50 3.50 3.50<br />

Quantity / Motor Size kW N/A N/A N/A N/A<br />

Full Load Amps A N/A N/A N/A N/A<br />

Locked Rotor Amps A N/A N/A N/A N/A<br />

(1) Values given for full function units (incl. electric heating and humidification) at ARI conditions with standard fan motors, for optional data, please<br />

contact <strong><strong>Air</strong>edale</strong>.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 49<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

CHILLED WATER


CHILLED WATER<br />

50<br />

-DF<br />

General Specification - Chilled Water Models<br />

ELECTRICAL DATA<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

DF26CW-EZ DF28CW-EZ DF31CW-EZ DF35CW-EZ<br />

Unit Data (1)<br />

Nominal Run Amps A 45.4 46.6 50.1 57.2<br />

Maximum Start Amps A 45.4 46.6 57.9 57.9<br />

Recommended Mains Fuse Size A 50 50 63 63<br />

Max Mains Incoming Cable Size mm² 35 35 35 35<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit<br />

Evaporator Fan - Per Fan<br />

VAC 24 24 24 24<br />

Quantity / Motor Size kW 1 x 1.5 1 x 2.2 1 x 4.0 1 x 4.0<br />

Full Load Amps A 3.5 4.7 8.2 8.2<br />

Locked Rotor Amps<br />

OPTIONAL EXTRAS<br />

Electric Heating<br />

A 21.0 32.9 57.4 57.4<br />

Stage of Reheat 3 3 3 3<br />

Number of Elements 8 8 8 8<br />

Rating (Total) kW 20.0 20.0 20.0 20.0<br />

Current Per Phase<br />

Humidifier<br />

A 32.4 32.4 32.4 32.4<br />

Capacity kg/hr 1.60 - 8.00 1.60 - 8.00 1.60 - 8.00 3.00 - 15.00<br />

Rating kW 6.00 6.00 6.00 11.25<br />

Full Load Amps<br />

Larger Fan Motor - Per Fan<br />

A 8.70 8.70 8.70 15.80<br />

Quantity / Motor Size kW 1 x 2.2 1 x 3.0 N/A 1 x 5.5<br />

Full Load Amps A 4.7 6.3 N/A 10.9<br />

Locked Rotor Amps<br />

Next Larger Fan Motor - Per Fan<br />

A 32.9 44.1 N/A 76.3<br />

Quantity / Motor Size kW 1 x 3.0 1 x 4.0 N/A N/A<br />

Full Load Amps A 6.3 8.2 N/A N/A<br />

Locked Rotor Amps A 44.1 57.4 N/A N/A<br />

DF40CW-EZ DF45CW-EZ DF50CW-EZ DF55CW-EZ DF60CW-EZ<br />

Unit Data (1)<br />

Nominal Run Amps A 59.9 59.9 69.3 69.3 72.5<br />

Maximum Start Amps A 76.8 76.8 69.3 69.3 88.7<br />

Recommended Mains Fuse Size A 80 80 80 80 80<br />

Max Mains Incoming Cable Size mm² 35 35 35 35 35<br />

Mains Supply V 400V / 3PH + N / 50Hz<br />

Control circuit<br />

Evaporator Fan - Per Fan<br />

VAC 24 24 24 24 24<br />

Quantity / Motor Size kW 1 x 5.5 1 x 5.5 2 x 2.2 2 x 2.2 2 x 3.0<br />

Full Load Amps A 10.9 10.9 4.7 4.7 6.3<br />

Locked Rotor Amps<br />

OPTIONAL EXTRAS<br />

Electric Heating<br />

A 76.3 76.3 32.9 32.9 44.1<br />

Stage of Reheat 3 3 3 3 3<br />

Number of Elements 8 8 12 12 12<br />

Rating (Total) kW 20.0 20.0 30.0 30.0 30.0<br />

Current Per Phase<br />

Humidifier<br />

A 32.4 32.4 43.6 43.6 43.6<br />

Capacity kg/hr 3.00 - 15.00 3.00 - 15.00 3.00 - 15.00 3.00 - 15.00 3.00 - 15.00<br />

Rating kW 11.25 11.25 11.25 11.25 11.25<br />

Full Load Amps<br />

Larger Fan Motor - Per Fan<br />

A 15.80 15.80 15.80 15.80 15.80<br />

Quantity / Motor Size kW N/A N/A 2 x 3.0 2 x 3.0 2 x 4.0<br />

Full Load Amps A N/A N/A 6.3 6.3 8.2<br />

Locked Rotor Amps<br />

Next Larger Fan Motor - Per Fan<br />

A N/A N/A 44.1 44.1 57.4<br />

Quantity / Motor Size kW N/A N/A 2 x 4.0 2 x 4.0 N/A<br />

Full Load Amps A N/A N/A 8.2 8.2 N/A<br />

Locked Rotor Amps A N/A N/A 57.4 57.4 N/A<br />

(1) Values given for full function units (incl. electric heating and humidification) at ARI conditions with standard fan motors, for optional data, please<br />

contact <strong><strong>Air</strong>edale</strong>.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Sound Data - Chilled Water Models<br />

SOUND DATA<br />

DF6CW-EZ<br />

DF8CW-EZ<br />

DF10CW-EZ<br />

DF13CW-EZ<br />

DF15CW-EZ<br />

DF17CW-EZ<br />

DF22CW-EZ<br />

DF25CW-EZ<br />

IMPORTANT To be read in conjunction with Method of Sound Measurement.<br />

Sound<br />

Overall<br />

Frequency (Hz) dB<br />

Measurement<br />

dB(A) 63 125 250 500 1000 2000 4000 8000<br />

Discharge <strong>Air</strong> Power 71 65 69 67 67 67 66 58 54<br />

Return <strong>Air</strong> Power 62 68 68 66 59 54 51 49 39<br />

Case Breakout Power 57 64 66 58 54 51 47 43 37<br />

Sound @ 3m Pressure 43 50 51 43 40 36 32 29 23<br />

Discharge <strong>Air</strong> Power 77 70 74 73 72 72 71 64 59<br />

Return <strong>Air</strong> Power 68 73 74 72 65 59 56 54 44<br />

Case Breakout Power 63 70 71 63 60 56 52 49 43<br />

Sound @ 3m Pressure 48 55 57 49 45 41 37 34 28<br />

Discharge <strong>Air</strong> Power 80 73 77 76 75 75 74 67 62<br />

Return <strong>Air</strong> Power 71 76 77 75 68 62 59 57 47<br />

Case Breakout Power 66 73 74 66 63 59 55 52 46<br />

Sound @ 3m Pressure 51 58 60 52 48 44 40 37 31<br />

Discharge <strong>Air</strong> Power 77 71 74 72 72 72 71 64 59<br />

Return <strong>Air</strong> Power 67 73 74 72 65 59 56 54 44<br />

Case Breakout Power 62 70 71 63 60 56 52 48 42<br />

Sound @ 3m Pressure 48 56 57 49 45 41 37 34 28<br />

Discharge <strong>Air</strong> Power 73 70 75 72 69 68 67 62 57<br />

Return <strong>Air</strong> Power 66 73 74 71 62 55 52 53 42<br />

Case Breakout Power 61 70 72 63 57 52 48 47 40<br />

Sound @ 3m Pressure 46 55 57 48 42 37 33 32 26<br />

Discharge <strong>Air</strong> Power 77 74 78 76 73 72 70 66 61<br />

Return <strong>Air</strong> Power 70 77 78 75 66 59 55 56 46<br />

Case Breakout Power 65 73 76 67 60 56 51 50 44<br />

Sound @ 3m Pressure 50 59 61 52 46 41 37 36 30<br />

Discharge <strong>Air</strong> Power 81 74 78 77 76 77 75 68 63<br />

Return <strong>Air</strong> Power 72 77 78 76 69 63 60 59 48<br />

Case Breakout Power 67 74 76 68 64 60 56 53 47<br />

Sound @ 3m Pressure 52 59 61 53 49 46 41 38 32<br />

Discharge <strong>Air</strong> Power 85 79 83 81 80 81 79 72 67<br />

Return <strong>Air</strong> Power 76 81 82 80 73 67 64 63 52<br />

Case Breakout Power 71 78 80 72 68 64 60 57 51<br />

Sound @ 3m Pressure 56 64 65 57 54 50 46 42 36<br />

(1) dB(A) is the overall sound level, measured on the A scale.<br />

(2) All sound data measured at nominal conditions.<br />

The Sound Pressure data quoted is only valid where the unit is installed on a false floor and against a rear wall. If the equipment is<br />

placed adjacent to any other vertical reflective walls, values may vary to those stated, typically increasing by 3dB for each side<br />

added. Values stated do not include for room reverberation conditions.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 51<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

CHILLED WATER


CHILLED WATER<br />

52<br />

-DF<br />

Sound Data - Chilled Water Models<br />

SOUND DATA<br />

DF26CW-EZ<br />

DF28CW-EZ<br />

DF31CW-EZ<br />

DF35CW-EZ<br />

DF40CW-EZ<br />

DF45CW-EZ<br />

DF50CW-EZ<br />

DF55CW-EZ<br />

DF60CW-EZ<br />

IMPORTANT To be read in conjunction with Method of Sound Measurement.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Sound<br />

Overall<br />

Frequency (Hz) dB<br />

Measurement<br />

dB(A) 63 125 250 500 1000 2000 4000 8000<br />

Discharge <strong>Air</strong> Power 84 75 76 77 79 79 79 76 72<br />

Return <strong>Air</strong> Power 65 75 68 61 64 60 54 53 44<br />

Case Breakout Power 67 76 67 61 65 63 56 53 45<br />

Sound @ 3m Pressure 52 61 52 46 50 49 42 39 30<br />

Discharge <strong>Air</strong> Power 87 77 80 79 81 81 82 79 76<br />

Return <strong>Air</strong> Power 68 77 71 64 66 63 57 56 47<br />

Case Breakout Power 69 78 70 63 67 66 59 56 48<br />

Sound @ 3m Pressure 55 63 56 49 52 51 45 42 33<br />

Discharge <strong>Air</strong> Power 91 78 84 83 85 84 85 83 80<br />

Return <strong>Air</strong> Power 71 77 75 67 69 66 60 60 52<br />

Case Breakout Power 73 78 74 67 70 69 62 60 52<br />

Sound @ 3m Pressure 58 64 59 52 55 55 48 46 38<br />

Discharge <strong>Air</strong> Power 90 77 83 82 87 83 84 82 79<br />

Return <strong>Air</strong> Power 71 76 74 66 70 64 59 59 51<br />

Case Breakout Power 72 77 73 66 71 67 61 59 51<br />

Sound @ 3m Pressure 58 62 58 51 57 53 47 45 37<br />

Discharge <strong>Air</strong> Power 92 80 86 85 89 86 86 85 81<br />

Return <strong>Air</strong> Power 73 78 76 68 73 67 61 62 53<br />

Case Breakout Power 74 79 75 68 74 70 63 62 54<br />

Sound @ 3m Pressure 60 64 61 54 59 55 49 47 40<br />

Discharge <strong>Air</strong> Power 92 80 86 85 89 86 86 85 81<br />

Return <strong>Air</strong> Power 73 78 76 68 73 67 61 62 53<br />

Case Breakout Power 74 79 75 68 74 70 63 62 54<br />

Sound @ 3m Pressure 60 64 61 54 59 55 49 47 40<br />

Discharge <strong>Air</strong> Power 89 78 84 86 82 83 84 81 76<br />

Return <strong>Air</strong> Power 69 76 75 70 66 64 59 57 48<br />

Case Breakout Power 71 77 74 69 67 67 61 58 49<br />

Sound @ 3m Pressure 56 63 59 55 53 53 46 43 34<br />

Discharge <strong>Air</strong> Power 89 78 84 86 82 83 84 81 76<br />

Return <strong>Air</strong> Power 69 76 75 70 66 64 59 57 48<br />

Case Breakout Power 71 77 74 69 67 67 61 58 49<br />

Sound @ 3m Pressure 56 63 59 55 53 53 46 43 34<br />

Discharge <strong>Air</strong> Power 91 80 85 89 84 85 86 83 79<br />

Return <strong>Air</strong> Power 71 78 76 73 68 66 61 60 51<br />

Case Breakout Power 73 79 75 73 69 69 63 60 51<br />

Sound @ 3m Pressure 58 65 60 58 55 54 49 45 37<br />

(1) dB(A) is the overall sound level, measured on the A scale.<br />

(2) All sound data measured at nominal conditions.<br />

The Sound Pressure data quoted is only valid where the unit is installed on a false floor and against a rear wall. If the equipment is<br />

placed adjacent to any other vertical reflective walls, values may vary to those stated, typically increasing by 3dB for each side<br />

added. Values stated do not include for room reverberation conditions.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Design Data - Chilled Water Models<br />

WATERSIDE PRESSURE DROP (KPA)<br />

Chilled Water System<br />

DF6 - DF25<br />

DF26 - DF60<br />

PRESSURE DROP (kPa)<br />

PRESSURE DROP (kPa)<br />

300<br />

250<br />

200<br />

150<br />

100<br />

50<br />

0<br />

500<br />

500<br />

400<br />

300<br />

200<br />

100<br />

0<br />

0<br />

6 - 10 13 - 17 22 - 25<br />

0.0 0 0.5 0.5 1.0 1.0 1.5 2.0 2.0 2.5 3.0 3.5<br />

WATERFLOW (l/s)<br />

26-31 35-40 45<br />

0.0 0 1.0 1.0 2.0 2.0 3.0 3.0 4.0 5.0 5.0 6.0 6.0 7.0 7.0 8.0 8.0<br />

(1) Includes coil, 3 port valve and pipework.<br />

(2) To calculate 3 port valve pressure drop:<br />

P valve =<br />

2<br />

Q <br />

<br />

M <br />

(3) Fluid 100% water, for glycol use, refer to Ethylene Glycol Correction Factors.<br />

WATERFLOW (l/s)<br />

Kv <br />

where P = Pressure Drop in kPa, Q = Water Flow Rate in l/s and M = <br />

36 <br />

M Values<br />

Model Sizes 6 - 10 13 - 25 26 - 45 50 - 60<br />

Chilled Water Valve 0.17 0.28 0.51 0.80<br />

LOW PRESSURE HOT WATER (OPTIONAL EXTRA)<br />

Refer to Low Pressure Hot Water (Optional Extra) - X & WX Type Models.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 53<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

50<br />

55-60<br />

CHILLED WATER


CHILLED WATER<br />

54<br />

-DF<br />

Design Data - Chilled Water Models<br />

SYSTEM PIPEWORK<br />

SCHEMATIC<br />

8<br />

4<br />

6<br />

7<br />

9<br />

1<br />

5<br />

2<br />

3<br />

6<br />

7<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Design should be in accordance with good refrigeration practice to ensure good oil return<br />

to the compressor under all normal operating conditions to prolong the life of your unit.<br />

4<br />

1 Chilled Water Unit<br />

2 Bleed Valve<br />

3 3 Way Valve<br />

4 Binder Point<br />

5 Double Regulating Valve (Optional Extra)<br />

6 Shut Off Valve (Supplied by Others)<br />

7 Customer’s Chilled Water Supply<br />

8 Regulating Valve (Supply by Others)<br />

9 Chilled Water Coil


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Design Data - Chilled Water Models<br />

ETHYLENE GLYCOL CORRECTION FACTORS<br />

For conditions outside those quoted, please refer to <strong><strong>Air</strong>edale</strong>.<br />

The Use of Glycol Glycol is recommended when a supply water temperature of +5°C or below is required or<br />

when static water can be exposed to freezing temperatures.<br />

Q Corrected Cooling Duty = Qw Cooling Capacity<br />

The effect of glycol in the system has a direct effect upon the Cooling Duty, the Design<br />

Flow Rate and the unit Pressure Drop.<br />

To approximate the effect of glycol on unit performance, the following correction factors<br />

when applied can be used as a guide.<br />

Where:<br />

Q = Total Cooling Capacity (TC) (kW)<br />

Qw = Equivalent Water Cooling Capacity (kW), refer to Cooling Duties, TC (kW) in<br />

this section.<br />

V = Corrected Flow Rate.<br />

T = Temperature difference between Water/Glycol Inlet/Outlet (°C).<br />

P = Maximum Water/ Glycol Pressure Drop for the indoor unit (kPa).<br />

Pw = Equivalent Water Pressure Drop for indoor unit (kPa), use the corrected flow<br />

rate V . Refer to Waterside Pressure Drop (kPa).<br />

Ethylene Glycol (Volume) / Freezing Point °C<br />

10% / -4°C 20% / -9°C 30% / -15°C 40% / -23°C<br />

0.980 0.940 0.890 0.830<br />

V x by<br />

Corrected Flow Rate = Qw/T Flow Rate 0.242 0.248 0.252 0.251<br />

P Corrected Pressure Drop = Pw Pressure Drop 1.041 1.083 1.133 1.200<br />

Example: DF26CW-EZ operating at 7/12, 24°C/45% RH Ambient, 20% Ethylene Glycol<br />

Ethylene Glycol (Volume) / Freezing Point °C<br />

10% / -4°C 20% / -9°C 30% / -15°C 40% / -23°C<br />

Q 29.4 kW = Qw 31.3 kW<br />

0.980 0.940 0.890 0.830<br />

V x by<br />

1.55 l/s = Qw/T<br />

(12 – 7 = 5T) =<br />

6.26 0.242 0.248 0.252 0.251<br />

P 86.6 kPa = Pw 80 kPa 1.041 1.083 1.133 1.200<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 55<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

CHILLED WATER


CHILLED WATER<br />

56<br />

-DF<br />

Design Data - Chilled Water Models<br />

INTERCONNECTING WIRING<br />

Indoor Controls Only<br />

INDOOR UNIT<br />

INDOOR UNIT<br />

Remote On/Off INDOOR UNIT<br />

Run/Standby Network<br />

INDOOR UNIT<br />

L1 <br />

L2 <br />

L3 <br />

N <br />

PE <br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

Mains Incoming Supply 400V / 3PH / +N / 50Hz<br />

560 Volt Free Alarm N/O<br />

561 Volt Free Alarm Common<br />

562 Volt Free Alarm N/C<br />

502 Fire Shutdown input<br />

583 Healthy in N/C Condition<br />

502 Remote On/OFF<br />

522 <br />

Common Alarm<br />

Rx-/Tx- <br />

Use Awg20/22 twisted pair (with overall shield)<br />

Rx-/Tx-<br />

Rx+/Tx+ cable, Belden ref. 8762 (<strong><strong>Air</strong>edale</strong> ref: 017-415), Rx+/Tx+<br />

GND or equivalent, for network GND<br />

INDOOR UNIT<br />

N + 1<br />

CABLE INSTALLATION In line with IEE Wiring Regulations, the following should be observed:<br />

Extra low voltage control cables (ELV) and mains power cable should be segregated<br />

by a minimum distance of 50mm.<br />

If cables must cross, it is recommended that they cross at right angles.<br />

<strong><strong>Air</strong>edale</strong> recommends that ELV cables are screened at one end to<br />

earthed enclosures.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Outdoor Un its - <strong>Air</strong> Co oled Cond en sers<br />

General Description<br />

UNIT IDENTIFICATION<br />

C Condensers<br />

AIR COOLED CONDENSERS<br />

11-105 Model Size (Expressed as Nominal Cooling in kW)<br />

A Aluminium/Magnesium Case<br />

P Pre-Painted Aluminium Fins (Option)<br />

-H Horizontal <strong>Air</strong> Discharge or;<br />

-V Vertical <strong>Air</strong> Discharge<br />

Example C11AP-H<br />

INTRODUCTION The range is custom designed for a small footprint, low sound level, slimline and<br />

aesthetically pleasing appearance for use with <strong><strong>Air</strong>edale</strong>’s comprehensive range of<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> units.<br />

CE Directive<br />

STANDARD FEATURES<br />

<strong><strong>Air</strong>edale</strong> certify that the equipment detailed in this manual conforms with the following<br />

EC Directives:<br />

Electromagnetic Compatibility Directive (EMC) 2004/108/EC<br />

Low Voltage Directive (LVD) 2006/95/EC<br />

Machinery Directive (MD) 89/392/EEC in the version<br />

2006/427/EC<br />

Pressure Equipment Directive (PED) 97/23/EC<br />

To comply with these directives appropriate national & harmonised standards have been<br />

applied. These are listed on the Declaration of Conformity, supplied with each product.<br />

Construction Unit cabinets are manufactured from sheet aluminium magnesium unpainted which<br />

provides a high corrosion resistant finish.<br />

As standard the unit is unpainted aluminium magnesium self coloured.<br />

Removable panels are fitted on both the return bend and header end of the condensers to<br />

facilitate installation and allow access during adjustment and maintenance.<br />

Available in horizontal or vertical airflow, please specify at order.<br />

Lifting brackets are supplied as standard.<br />

Condenser Large surface area coil(s) ideally positioned to optimise airflow and heat transfer,<br />

manufactured from refrigeration quality copper cross hatched tubes with mechanically<br />

bonded louvred aluminium fins.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 57<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

OUTDOOR UNIT


OUTDOOR UNIT<br />

58<br />

-DF<br />

General Description<br />

STANDARD FEATURES<br />

Fan & Motor Assembly Axial flow fan assembly with low noise blades.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

The motor has inbuilt thermal overload protection and the assembly is supplied complete<br />

with a finger guard for protection.<br />

The external rotor motor allows the use of a low power output single phase speed<br />

controllable motor to power the fan.<br />

Standard air discharge is horizontal or vertical, please specify at order.<br />

Refrigeration Each unit features as standard:<br />

Holding Charge of inert gas<br />

Head Pressure Control Is provided by the indoor unit, refer to Indoor Unit, Head Pressure Control - Intelligent.<br />

OPTIONAL EXTRAS<br />

Upgraded Condenser To improve operational efficiency, reduce sound levels or to allow operation in high<br />

ambient conditions, the next condenser size can be selected. Improved efficiency (EER)<br />

comes from reduced head pressure, whilst lower sound levels come from reduced fan<br />

speed at the same design head pressure.<br />

Phenolic Coated Coils In atmospheres where high corrosion is anticipated phenolic coated aluminium finned<br />

coils can be supplied.<br />

Mains Electric Isolator A weatherproof mains isolator is available for on site fitting either directly to the outdoor<br />

unit or remotely wall mounted. Supplied loose with indoor unit.<br />

Shut Off Valves Where unit isolation for easier maintenance is required, shut off valves can be supplied.<br />

Shipped loose with the indoor unit for on site fitment.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Dimensional Data<br />

DIMENSIONS C11 – C35<br />

Horizontal Unit (mm)<br />

B<br />

(3)<br />

500<br />

(2)<br />

(6)<br />

(7)<br />

500<br />

(2)<br />

D<br />

A<br />

(1)<br />

(1)<br />

3000<br />

(2)<br />

500<br />

(2)<br />

(4)<br />

(5a)<br />

(1)<br />

(5b)<br />

C<br />

(1)<br />

150 E 150<br />

Condenser A B C D Mass (kg)<br />

C11 mm 1275 648 550 1212 51<br />

C15 mm 1275 648 550 1212 63<br />

C20 mm 1100 648 645 1037 58<br />

C25 mm 1100 648 645 1037 65<br />

C35 Mm 1650 1048 645 1587 97<br />

Vertical Unit (mm)<br />

B<br />

(3)<br />

(6)<br />

D<br />

A<br />

(1)<br />

(1)<br />

(4)<br />

(5b)<br />

3000<br />

(2)<br />

E<br />

C<br />

(5a)<br />

500<br />

(2)<br />

500<br />

(2)<br />

500<br />

(2)<br />

500<br />

(2)<br />

(1) <strong>Air</strong>flow<br />

(2) Minimum Clearances<br />

(3) 12.7mm Fixing Holes<br />

(4) Mains Electric Isolator.<br />

(5) Service connections<br />

a) Liquid Outlet<br />

b) Discharge Inlet<br />

(6) 40mm Lifting Holes<br />

(1) <strong>Air</strong>flow<br />

(2) Minimum Clearances<br />

(3) 12.7mm Fixing Holes<br />

(4) Mains Electric Isolator.<br />

(5) Service connections<br />

a) Liquid Outlet<br />

b) Discharge Inlet<br />

(6) 40mm Lifting Holes<br />

Condenser A B C D E F Mass (kg)<br />

C11 mm 1275 997 700 N/A 467 87<br />

C15 mm 1275 997 700 467<br />

C20 mm 1100 1092 900 467<br />

C25 mm 1100 1092 900 467<br />

C35 mm 1650 1092 1100 467<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 59<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

OUTDOOR UNIT


OUTDOOR UNIT<br />

60<br />

-DF<br />

DIMENSIONS C45, CS50 – CS65<br />

Horizontal Unit (mm)<br />

Condenser A B C D Mass (kg)<br />

C45 mm 1650 1048 645 1587 110<br />

CS50H-0 mm 2184 1167 1000 2121 132<br />

CS65H-0 mm 2184 1167 1000 2121 162<br />

Vertical Unit (mm)<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

(1) <strong>Air</strong>flow<br />

(2) Minimum Clearances<br />

(3) 12.7mm Fixing Holes<br />

(4) Mains Electric Isolator.<br />

(5) Service connections<br />

a) Liquid Outlet<br />

b) Discharge Inlet<br />

(6) 40mm Lifting Holes<br />

(1) <strong>Air</strong>flow<br />

(2) Minimum Clearances<br />

(3) 12.7mm Fixing Holes<br />

(4) Mains Electric Isolator.<br />

(5) Service connections<br />

a) Liquid Outlet<br />

b) Discharge Inlet<br />

(6) 40mm Lifting Holes<br />

Condenser A B C D E F Mass (kg)<br />

C45 mm 1650 1092 1100 1587 1040 467 110<br />

CS50V-0 mm 2184 1090 1167 2124 1107 467 132<br />

CS65V-0 mm 2184 1090 1167 2124 1107 467 162


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

DIMENSIONS CS80 - 105<br />

Horizontal Unit (mm)<br />

Condenser A B C D Mass (kg)<br />

CS80H-0 mm 3565 1167 1000 1752 208<br />

CS105H-0 mm 3565 1167 1000 1752 260<br />

Vertical Unit (mm)<br />

(1) <strong>Air</strong>flow<br />

(2) Minimum Clearances<br />

(3) 12.7mm Fixing Holes<br />

(4) Mains Electric Isolator.<br />

(5) Service connections<br />

a) Liquid Outlet<br />

b) Discharge Inlet<br />

(6) 40mm Lifting Holes<br />

(1) <strong>Air</strong>flow<br />

(2) Minimum Clearances<br />

(3) 12.7mm Fixing Holes<br />

(4) Mains Electric Isolator.<br />

(5) Service connections<br />

a) Liquid Outlet<br />

b) Discharge Inlet<br />

(6) 40mm Lifting Holes<br />

Condenser A B C D E F Mass (kg)<br />

CS80V-0 mm 3565 1090 1167 1752 1107 501 208<br />

CS105V-0 mm 3565 1090 1167 1752 1107 501 260<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 61<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

OUTDOOR UNIT


OUTDOOR UNIT<br />

62<br />

-DF<br />

General Specification<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

MECHANICAL DATA<br />

C11 C15 C20 C25 C35<br />

Total Heat of Rejection (1) kW 10.98 16.49 20.18 25.57 30.29<br />

Dimensions - Horizontal (2)<br />

Height mm 648 648 848 848 1048<br />

Width mm 550 550 645 645 645<br />

Length mm 1275 1275 1100 1100 1650<br />

Dimensions - Vertical (2)<br />

Height mm 997 997 1092 1092 1092<br />

Width mm 700 700 900 900 1100<br />

Length<br />

Weight<br />

mm 1275 1275 1100 1100 1650<br />

Machine<br />

Construction<br />

kg 51 63 58 65 97<br />

Material/Colour Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey (RAL 7035)<br />

Condenser <strong>Air</strong> Cooled - Rifled Copper Tube/Turbulated Aluminium Fins<br />

Quantity 1 1 1 1 1<br />

Total Face Area m² 0.675 0.675 0.800 0.800 1.600<br />

Nominal <strong>Air</strong>flow m³/s 1.20 1.90 2.00 2.25 2.35<br />

Discharge -H Horizontal or -V Vertical (Please Specify at Order)<br />

Fan & Motor Axial<br />

Quantity 1 2 1 1 1<br />

Diameter mm 450 450 630 630 630<br />

Maximum Speed rpm 930 930 900 900 900<br />

Refrigeration Single Circuit<br />

Refrigerant Type R407C (Optional R22)<br />

Holding Charge Inert Gas<br />

Coil Volume l 5.3 5.3 6.1 8.1 15.7<br />

Refrigerant Charge<br />

Connections<br />

(3) kg 2.1 2.1 2.3 3.1 6.1<br />

Liquid Line - Sweat in 1/2 1/2 5/8 5/8 7/8<br />

Discharge Line - Sweat<br />

OPTIONAL EXTRAS<br />

in 5/8 5/8 7/8 7/8 7/8<br />

Short Case Axial Fan<br />

Dimensions - Horizontal<br />

Designed to 75 Pa ESP<br />

Height mm 648 648 848 848 1048<br />

Width mm 675 675 735 735 711<br />

Length<br />

Dimensions - Vertical<br />

mm 1275 1275 1100 1100 1650<br />

Height mm 1112 1112 1162 1162 1162<br />

Width mm 700 700 900 900 1100<br />

Length<br />

Weight<br />

mm 1275 1275 1100 1100 1650<br />

Machine kg 61 73 70 77 109<br />

(1) Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.<br />

(2) Overall dimensions for clearance; refer to Error! Reference source not found. for detail.<br />

(3) For guidance only.


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

General Specification<br />

MECHANICAL DATA<br />

C45 CS50 CS65 CS80 CS105<br />

Total Heat of Rejection (1) kW 46.09 45.69 61.70 74.63 99.26<br />

Dimensions - Horizontal (2)<br />

Height mm 1048 1167 1167 1167 1167<br />

Width mm 645 1000 1000 1000 1000<br />

Length mm 1650 2184 2184 3565 3565<br />

Dimensions - Vertical (2)<br />

Height mm 1092 1090 1090 1090 1090<br />

Width mm 1100 1167 1167 1167 1167<br />

Length mm 1650 2184 2184 3565 3565<br />

Weight<br />

Machine kg 110 132 162 208 260<br />

Construction<br />

Material/Colour Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey (RAL 7035)<br />

Condenser <strong>Air</strong> Cooled - Rifled Copper Tube/Turbulated Aluminium Fins<br />

Quantity 1 1 1 1 1<br />

Total Face Area m² 1.60 2.11 2.11 3.63 3.63<br />

Nominal <strong>Air</strong>flow m³/s 4.45 4.80 4.20 7.20 6.60<br />

Discharge H Horizontal or V Vertical (Please Specify at Order)<br />

Fan & Motor Axial<br />

Quantity 2 2 2 3 3<br />

Diameter mm 630 630 630 630 630<br />

Maximum Speed rpm 900 900 900 900 900<br />

Refrigeration Single Circuit<br />

Refrigerant Type R407C<br />

Holding Charge Inert Gas<br />

Coil Volume L 15.7 10.7 21.5 18.3 36.7<br />

Refrigerant Charge (3) kg 6.1 4.3 8.5 7.3 14.6<br />

Connections<br />

Liquid Line - Sweat in 7/8 3/4 3/4 7/8 7/8<br />

Discharge Line - Sweat in 7/8 1 1/8 1 1/8 1 3/8 1 3/8<br />

OPTIONAL EXTRAS<br />

Short Case Axial Fan Designed to 75 Pa ESP<br />

Dimensions - Horizontal<br />

Height mm 1048 1167 1167 1167 1167<br />

Width mm 711 1000 1000 1000 1000<br />

Length mm 1650 2184 2184 3565 3565<br />

Dimensions - Vertical<br />

Height mm 1162 1130 1130 1130 1130<br />

Width mm 1100 1167 1167 1167 1167<br />

Length mm 1650 2184 2184 3565 3565<br />

Weight<br />

Machine kg 134 145 175 228 280<br />

(1) Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.<br />

(2) Overall dimensions for clearance; refer to Error! Reference source not found. for detail.<br />

(3) For guidance only.<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 63<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

OUTDOOR UNIT


OUTDOOR UNIT<br />

64<br />

-DF<br />

General Specification<br />

ELECTRICAL DATA<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

C11 C15 C20 C25 C35<br />

Unit Data (1)<br />

Nominal Run Amps A 0.65 1.30 2.80 2.80 2.80<br />

Maximum Start Amps A 2.6 5.2 5.6 5.6 5.6<br />

Recommended Mains Fuse A 10 10 10 10 10<br />

Max Mains Cable Incoming mm² 10 10 10 10 10<br />

Mains Supply<br />

Fan - Per Fan<br />

230V / 1Ph + N / 50Hz<br />

Quantity 1 2 1 1 1<br />

Motor Size kW 0.15 0.15 0.59 0.59 0.59<br />

Full Load Amps A 0.65 0.65 2.80 2.80 2.80<br />

Locked Rotor Amps<br />

OPTIONAL EXTRAS<br />

Short Case Axial Fan - Per Fan<br />

A 2.6 2.6 5.6 5.6 5.6<br />

Quantity 1 2 1 1 1<br />

Motor Size kW 0.61 0.61 1.40 1.40 1.40<br />

Full Load Amps A 2.8 2.8 6.0 6.0 6.0<br />

Locked Rotor Amps A 7.0 7.0 18.0 18.0 18.0<br />

C45HI CS50 CS65 CS80 CS105<br />

Unit Data (1)<br />

Nominal Run Amps A 5.60 5.80 5.80 8.70 8.70<br />

Maximum Start Amps A 11.20 11.20 11.20 16.80 16.80<br />

Recommended Mains Fuse A 10 10 10 16 16<br />

Max Mains Cable Incoming mm² 10 6 6 6 6<br />

Mains Supply<br />

Fan - Per Fan<br />

230V / 1Ph + N / 50Hz<br />

Quantity 2 2 2 3 3<br />

Motor Size kW 0.59 0.63 0.63 0.63 0.63<br />

Full Load Amps A 2.8 2.9 2.9 2.9 2.9<br />

Locked Rotor Amps<br />

OPTIONAL EXTRAS<br />

Short Case Axial Fan - Per Fan<br />

A 5.6 5.6 5.6 5.6 5.6<br />

Quantity kW 2 2 2 3 3<br />

Motor Size kW 1.4 1.4 1.4 1.4 1.4<br />

Full Load Amps A 6.0 6.0 6.0 6.0 6.0<br />

Locked Rotor Amps A 18.0 18.0 18.0 18.0 18.0<br />

(1) Nominal data based on 35°C ambient and a 50°C mean condensing temperature and using standard fan.<br />

INTERCONNECTING<br />

WIRING<br />

C11 - 105<br />

L1<br />

Mains Incoming 230V / 1Ph + N / 50Hz


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Performance Data<br />

CAPACITY DATA<br />

Standard Condenser Fan<br />

C11<br />

C15<br />

C20<br />

C25<br />

C35<br />

C45<br />

CS50<br />

CS65<br />

CS80<br />

CS105<br />

Ambient<br />

Mean Condensing 25°C 30°C 35°C 40°C 45°C 48°C<br />

Temperature °C Output kW Output kW Output kW Output kW Output kW Output kW<br />

35 6.90 3.24 - - - -<br />

40 10.81 6.94 3.26 - - -<br />

45 15.05 10.93 6.97 3.27 - -<br />

50 19.31 15.11 10.98 6.99 3.28 -<br />

55 23.66 19.41 15.18 11.02 7.02 4.78<br />

35 10.27 4.76 - - - -<br />

40 16.21 10.37 4.80 - - -<br />

45 22.28 16.36 10.45 4.83 - -<br />

50 28.49 22.51 16.49 10.51 4.85 -<br />

55 34.95 28.81 22.73 16.61 10.57 7.14<br />

35 12.52 5.79 - - - -<br />

40 19.63 12.70 5.86 - - -<br />

45 26.76 19.93 12.84 5.91 - -<br />

50 34.70 27.23 20.18 12.96 5.95 -<br />

55 42.79 35.22 27.65 20.42 13.07 8.82<br />

35 15.98 7.41 - - - -<br />

40 25.35 16.06 7.44 - - -<br />

45 35.17 25.47 16.13 7.47 - -<br />

50 45.22 35.31 25.57 16.18 7.49 -<br />

55 55.50 45.47 35.47 25.66 16.22 10.99<br />

35 19.01 8.84 - - - -<br />

40 29.39 19.02 8.84 - - -<br />

45 40.15 29.54 19.21 8.84 - -<br />

50 50.81 40.15 29.66 19.28 8.84 -<br />

55 61.77 51.08 40.53 29.93 19.34 13.04<br />

35 28.88 13.47 - - - -<br />

40 45.10 29.22 13.60 - - -<br />

45 61.55 45.64 29.47 13.70 - -<br />

50 78.93 62.34 46.09 29.69 13.79 -<br />

55 96.91 79.84 63.05 46.51 29.89 20.28<br />

35 24.56 5.43 - - - -<br />

40 44.44 25.09 5.74 - - -<br />

45 63.96 45.02 25.68 6.06 - -<br />

50 83.54 64.67 45.69 26.35 6.52 -<br />

55 103.35 84.42 65.49 46.49 27.15 15.41<br />

35 35.31 10.89 - - - -<br />

40 60.70 35.83 11.14 - - -<br />

45 85.43 61.15 36.40 11.46 - -<br />

50 110.21 85.94 61.70 37.06 12.97 -<br />

55 135.25 110.83 86.59 62.39 37.85 23.03<br />

35 40.50 9.63 - - - -<br />

40 72.57 41.37 10.09 - - -<br />

45 104.00 73.54 42.33 10.66 - -<br />

50 135.52 105.17 74.63 43.42 12.00 -<br />

55 167.37 136.96 106.52 75.90 44.71 25.77<br />

35 57.17 18.12 - - - -<br />

40 97.76 57.97 18.53 - - -<br />

45 137.30 98.44 58.85 19.02 - -<br />

50 176.90 138.04 99.26 59.87 21.24 -<br />

55 216.94 177.83 139.02 100.31 61.10 37.44<br />

(1) Output kW refers to the condenser heat of rejection.<br />

OPERATING LIMITS<br />

Standard On/Off Head Pressure Control<br />

Minimum Ambient <strong>Air</strong> DB °C -0°C<br />

Maximum Ambient <strong>Air</strong> DB °C +48<br />

Optional Variable Speed Head Pressure Control<br />

Minimum Ambient <strong>Air</strong> DB °C -20°C<br />

Maximum Ambient <strong>Air</strong> DB °C +48<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 65<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

OUTDOOR UNIT


OUTDOOR UNIT<br />

66<br />

-DF<br />

Precision <strong>Air</strong> <strong>Conditioning</strong><br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

Precision <strong>Air</strong> <strong>Conditioning</strong>


Precision <strong>Air</strong> <strong>Conditioning</strong> -DF<br />

Precision <strong>Air</strong> <strong>Conditioning</strong> 67<br />

<strong>Technical</strong> <strong>Manual</strong> : 6259014 v1.3.0 02_2013<br />

OUTDOOR UNIT


W here to Fin d U s<br />

LITER ATUR E ORDER COD E<br />

PART NO: ISSUE DATE<br />

6259014 (TM E) A 01/03/07<br />

B 13/04/2010<br />

C 03/2011<br />

ITER ATUR E ORDER C ODE<br />

Head Office:<br />

<strong><strong>Air</strong>edale</strong> <strong>International</strong> <strong>Air</strong> <strong>Conditioning</strong> Ltd<br />

Leeds Road<br />

Rawdon<br />

Leeds LS19 6JY<br />

United Kingdom<br />

Tel: +44 (0) 113 239 1000<br />

Fax: +44 (0) 113 250 7219<br />

e-mail: enquiries@airedale.com<br />

website: www.airedale.com<br />

V1.3.0 02_2013

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!