25 I.B. 8926-1A<br />

To provide for padlocking the circuit breaker<br />

operator in the “on” position, drill the appropriate<br />

size hole through the drill point located on the<br />

operator mechanism.<br />

D. Unit Interlock<br />

The unit interlock is provided to assure that the<br />

unit circuit breaker is:<br />

- Open before the stab clips can contact the<br />

vertical bus.<br />

Lock Plate<br />

DOOR INTERLOCK HOOK<br />

(6 Inch Units)<br />

Fig. 35 6-Inch Breaker Unit Slider Operator Mechanism<br />

MCC Slider Operator Mechanism Padlocking<br />

(C)<br />

UNIT INTERLOCK<br />

(ROD)<br />

ON POSITION (LEFT)<br />

30-150 AMP<br />

Fig. 36<br />

(A) Rectangular slot for scissors.<br />

(B) One 1/4 in. or 5/16 in. diameter padlock hasp.<br />

DOOR INTERLOCK<br />

OFF PADLOCKS<br />

(A)<br />

(B)<br />

- Open before the stab clips can be disengaged<br />

from the vertical bus.<br />

The unit interlock and bracket does not need field<br />

adjustment. The interlock bracket will be adjusted to<br />

almost touch the side of the unit interlock rod when<br />

the operator is in the “on” position.<br />

DEFEATER SCREW<br />

ON PADLOCK AREA<br />

OFF POSITION (RIGHT)<br />

ON ON<br />

30-150 AMP<br />

Fig. 37<br />

(C) Rotate lock plate for one to three 3/8 in.<br />

diameter padlock hasp locks.