25 I.B. 8926-1A<br />
To provide for padlocking the circuit breaker<br />
operator in the “on” position, drill the appropriate<br />
size hole through the drill point located on the<br />
operator mechanism.<br />
D. Unit Interlock<br />
The unit interlock is provided to assure that the<br />
unit circuit breaker is:<br />
- Open before the stab clips can contact the<br />
vertical bus.<br />
Lock Plate<br />
DOOR INTERLOCK HOOK<br />
(6 Inch Units)<br />
Fig. 35 6-Inch Breaker Unit Slider Operator Mechanism<br />
MCC Slider Operator Mechanism Padlocking<br />
(C)<br />
UNIT INTERLOCK<br />
(ROD)<br />
ON POSITION (LEFT)<br />
30-150 AMP<br />
Fig. 36<br />
(A) Rectangular slot for scissors.<br />
(B) One 1/4 in. or 5/16 in. diameter padlock hasp.<br />
DOOR INTERLOCK<br />
OFF PADLOCKS<br />
(A)<br />
(B)<br />
- Open before the stab clips can be disengaged<br />
from the vertical bus.<br />
The unit interlock and bracket does not need field<br />
adjustment. The interlock bracket will be adjusted to<br />
almost touch the side of the unit interlock rod when<br />
the operator is in the “on” position.<br />
DEFEATER SCREW<br />
ON PADLOCK AREA<br />
OFF POSITION (RIGHT)<br />
ON ON<br />
30-150 AMP<br />
Fig. 37<br />
(C) Rotate lock plate for one to three 3/8 in.<br />
diameter padlock hasp locks.