12 I.B. 8926-1A<br />
OVERCURRENT PROTECTION<br />
All ungrounded conductors in a motor control center<br />
(MCC) installation require some form of overcurrent<br />
protection in order to comply with Section 240-20 of<br />
the NEC. Such overcurrent protection for the<br />
incoming lines to the MCC is in the form of fuses or<br />
a circuit breaker located at the transformer<br />
secondary that supplies the MCC. The conductors<br />
from the transformer secondary constitute the feeder<br />
to the MCC, and the “10-foot rule” and the “25-foot<br />
rule” of NEC, 240-21 apply. These latter exceptions<br />
to the general rule allow the disconnect means and<br />
Fig 17 Main Disconnect with Stab Load<br />
Connections<br />
overcurrent protection to be located in the MCC,<br />
provided the feeder taps from the transformer are<br />
sufficiently short and other requirements are met.<br />
MAIN DISCONNECTS<br />
A circuit breaker or a circuit interrupter combined<br />
with fuses controlling the power to the entire MCC<br />
may provide the over-current protection required as<br />
described above or may be a supplementary<br />
disconnect (isolation) means. See Figures 17, 18,<br />
and 19.<br />
Part 5<br />
INCOMING LINE CONNECTIONS<br />
Fig. 18 Main Circuit Breaker with Reverse Feed<br />
Fig. 19 Main Circuit Breaker