Generator Failure<br />

This period can be reduced by pushing the button on the front of the generator. The generator can be started by<br />

means of the remote control as long as the button is depressed. The switch/button bypasses any faults allowing the<br />

generator to run.<br />

Before depressing the button, a manual check of the oil dip stick must be carried out to determine whether the generator<br />

has sufficient oil, as it is possible that the oil pressure switch causes the generator to cut out. If it has been<br />

ascertained that the reason for the motor cutting out is overheating and not lack of oil, the generator can be run for<br />

several minutes without load, so that the motor is cooled by the circulating coolant.<br />

BEWARE:<br />

If the temperature is the reason for the generator cutting out when it is running under load, then an immediate check<br />

must be made to determine the cause. It could be a fault with the cooling system, one of the fans, the air-intake or a<br />

fault with the external cooling system.<br />

Continual use of the starter-failure bypass switch should be avoided, while the generator cuts out during operation.<br />

The generator must always run without load for several minutes before being switched off, so that a temperature<br />

compensation occurs. Heat accumulation can cause the generator to overheat, even after it has been switched off.<br />

Should the overheating alarm be set off, caused by heat accumulation, after the generator has been switched off,<br />

then this can also be bypassed using the switch.<br />

7.7.3 Stop solenoid<br />

There are two different variations:<br />

A. Energized to stop<br />

By pressing the „OFF“-button on the remote control panel the stop solenoid is supplied with voltage and operate,<br />

through this the injection nozzles resets to zero position and the generator stops.<br />

B. Energized to run<br />

This version is equipped with two solenoids an actuating and a stop solenoid. After being fed with current, the actuating<br />

solenoid attracts the adjusting lever of the fuel injection pump, through which the fuel can flow. The actuating<br />

solenoid is switched off once the final position has been reached, which is maintained by the stop solenoid for as<br />

long as the generator is running<br />

When starting the „START“-button may not be pressed longer than 5 sec.,<br />

because the stop solenoid pulls too much current over the starter. Otherwise<br />

the stop solenoid must be disconnected.<br />

.Notice!:<br />

7.5.12 Panda_4000s_PMS_SCB_FCB_eng.R04 - Kapitel/Chapter 7: Generator Failure Seite/Page 125