Manual
Manual
Manual
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Generator Failure<br />
1. The motor turns not strongly rather weak:<br />
The actuator has shorts in the winding and must be changed. (pay attention that the generator is not overloaded<br />
anymore.)<br />
2. The actuator does not move but the spindle can be turned manually. Disconnect the plug of the actuator. Connect<br />
provisional an external voltage source 12V-DC to the motor.<br />
The actuator don’t turns with the external voltage source. The actuator is defect and have to be changed.<br />
The control must be inspected by the following steps if the actuator turns and works faultless with the external<br />
voltage source:<br />
1. Check the fuse on the VCS printed circuit board.<br />
2. Check if the sense voltage is wired to the VCS printed circuit board.<br />
3. Check if the VCS supply voltage is wired to the VCS.<br />
4. Check if the VCS outlet signal for the actuator is wired.<br />
Change the VCS printed circuit board if the points above carries no clearance.<br />
7.4.4.4 The mechanical voltage limitation must be checked regularly. The following steps<br />
have to be done:<br />
1. Disconnect the plug of the actuator.<br />
2. Switch off all consumers.<br />
3. Connect an electrical voltmeter.<br />
4. Start the generator.<br />
5. Turn the actuator manually to the lower limit stop point.<br />
6. The voltage must be 220V.<br />
7. Turn the actuator manually to the upper limit stop point. The max. voltage is 270V.<br />
8. A new adjustment is necessary in case of deviants.<br />
7.5 Low Generator-Output Voltage<br />
If the produced alternating voltage is too low, switch the consumers off, in order to relieve the generator. Mostly the<br />
problem already solved. If the output voltage is still too low, even if all consumers are switched off, the generator<br />
runs without load, you can assume one or more condensers are defective.<br />
7.6 Testing generator stator windings<br />
7.6.1 Checking the generator voltage<br />
In order to test, whether the fixed winding produces enough voltage, proceed in such a way:<br />
1. Guarantee that the connection to the electrical system is interrupted.<br />
2. Remove all conductions in the power terminal box of the generator.<br />
3. Starter battery must be connected with the generator.<br />
4. Start the generator start.<br />
5. Measure with a voltmeter the voltage between the phase(s) and N. If the measured values are under the substantially<br />
values in Table 9.4-5, “Voltage values stator coil,” on Page 200, a coil damage is to be accepted.<br />
During the measurement in the 60Hz version both partial coils must be interconnected, i.e. a connection must be<br />
provided between line 1 and line 3. (see wiring diagram)<br />
Seite/Page 122 Panda_4000s_PMS_SCB_FCB_eng.R04 - Kapitel/Chapter 7: Generator Failure 7.5.12