03.03.2013 Views

Manual

Manual

Manual

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Generator Failure<br />

1. The motor turns not strongly rather weak:<br />

The actuator has shorts in the winding and must be changed. (pay attention that the generator is not overloaded<br />

anymore.)<br />

2. The actuator does not move but the spindle can be turned manually. Disconnect the plug of the actuator. Connect<br />

provisional an external voltage source 12V-DC to the motor.<br />

The actuator don’t turns with the external voltage source. The actuator is defect and have to be changed.<br />

The control must be inspected by the following steps if the actuator turns and works faultless with the external<br />

voltage source:<br />

1. Check the fuse on the VCS printed circuit board.<br />

2. Check if the sense voltage is wired to the VCS printed circuit board.<br />

3. Check if the VCS supply voltage is wired to the VCS.<br />

4. Check if the VCS outlet signal for the actuator is wired.<br />

Change the VCS printed circuit board if the points above carries no clearance.<br />

7.4.4.4 The mechanical voltage limitation must be checked regularly. The following steps<br />

have to be done:<br />

1. Disconnect the plug of the actuator.<br />

2. Switch off all consumers.<br />

3. Connect an electrical voltmeter.<br />

4. Start the generator.<br />

5. Turn the actuator manually to the lower limit stop point.<br />

6. The voltage must be 220V.<br />

7. Turn the actuator manually to the upper limit stop point. The max. voltage is 270V.<br />

8. A new adjustment is necessary in case of deviants.<br />

7.5 Low Generator-Output Voltage<br />

If the produced alternating voltage is too low, switch the consumers off, in order to relieve the generator. Mostly the<br />

problem already solved. If the output voltage is still too low, even if all consumers are switched off, the generator<br />

runs without load, you can assume one or more condensers are defective.<br />

7.6 Testing generator stator windings<br />

7.6.1 Checking the generator voltage<br />

In order to test, whether the fixed winding produces enough voltage, proceed in such a way:<br />

1. Guarantee that the connection to the electrical system is interrupted.<br />

2. Remove all conductions in the power terminal box of the generator.<br />

3. Starter battery must be connected with the generator.<br />

4. Start the generator start.<br />

5. Measure with a voltmeter the voltage between the phase(s) and N. If the measured values are under the substantially<br />

values in Table 9.4-5, “Voltage values stator coil,” on Page 200, a coil damage is to be accepted.<br />

During the measurement in the 60Hz version both partial coils must be interconnected, i.e. a connection must be<br />

provided between line 1 and line 3. (see wiring diagram)<br />

Seite/Page 122 Panda_4000s_PMS_SCB_FCB_eng.R04 - Kapitel/Chapter 7: Generator Failure 7.5.12

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!