Generator Failure<br />

Change this fuse (1,6A slow to blow)<br />

Fig. 7.4.4-1: VCS<br />

The generator can’t be damaged by an overload because the winding is overload- and short-circuit safety. But<br />

damages are possible in the periphery. Especially connected consumers are endangered because a lower voltage<br />

can damage them by order<br />

The Mini VCS has no fuse to change<br />

.Notice!:<br />

7.4.4.1 Possible disturbances in the area of the rev regulation „VCS“<br />

Failure Cause<br />

The spindle of the actuator jams not regularly lubricated.<br />

surface is mechanical damaged.<br />

actuator is defect.<br />

defect of the VCS control (short of winding).<br />

signal 230V AC missing.<br />

limiting nut jams the spindle.<br />

Fuse on the printed circuit board of the VCS control constant overload of the generator.<br />

is melted.<br />

7.4.4.2 Steps to check the voltage control by a disturbance:<br />

1. Switch off all electrical consumers.<br />

2. Disconnect the plug of the actuator.<br />

3. Turn the actuator manually to check if the adjusting nut is jammed to the limit stop points.<br />

4. Turn the actuator manually to check if the adjusting nut on the spindle runs faultless.<br />

If there is no result by these steps the actuator is working mechanically correct. After this the electrical components<br />

must be checked:<br />

1. Connect the plug of the actuator.<br />

2. Start the generator.<br />

3. Turn the actuator by hand and check if the spindle turns back by the motor.<br />

4. If the motor react on the turn by manual strongly (the motor can normally hold with the fingers) the drive will be<br />

working faultless. If there are nevertheless faults in the voltage control there is a fault in the control VCS.<br />

7.4.4.3 If the actuator is not moving the following points are necessary:<br />

7.5.12 Panda_4000s_PMS_SCB_FCB_eng.R04 - Kapitel/Chapter 7: Generator Failure Seite/Page 121