7.4.3 Lubrication of the spiral thread spindle (not ND models)<br />

Generator Failure<br />

The spiral thread spindle must be lubricated carefully and regularly. Please only use a temperature independence<br />

lubricant (up to 100°C) witch is also equipped with „emergency run qualities“. Spread also lubricant to the end of the<br />

nuts.<br />

It is possible that the spindle could clamp if the spindle is not enough lubricated. Then the generator can be switched<br />

off by over- or under voltage.<br />

All screws at the actuator and the spindle must be ensured „solvable“ with a screw safety grease.<br />

1. Speed actuator<br />

2. Spiral thread spindle<br />

7.4.4 Effects of a overload to the actuator (not ND models)<br />

Fig. 7.4.3-1: Actuator<br />

If the generator is overloaded the voltage falls on account of a not adequate motor power under the nominal value.<br />

The actuator stays at the upper keystroke and tries to rev up the diesel engine. An internal regulation limits the current<br />

to the actuator, nevertheless a longer overload can damage the winding of the actuator. (short of the winding).<br />

The motor gets not strictly inoperative but it can happen that the cranking torque of the actuator is getting weak. This<br />

has the consequence that the rev spindle can not be turned to all positions faultless. Therefore the voltage of the<br />

generator is regulated not good or sometimes not at all.<br />

If you notice that the spindle of the actuator doesn't run faultless, first check if the aggregate was overloaded for a<br />

short time and if thereby the winding of the actuator was damaged. Then the actuator has to be changed.<br />

Check the electrical fuse (miniature slow-to-blow fuse<br />

1,6A) on the control printed circuit board if the actuator<br />

will not turn at all.<br />

1 2<br />

Seite/Page 120 Panda_4000s_PMS_SCB_FCB_eng.R04 - Kapitel/Chapter 7: Generator Failure 7.5.12