Contact with engine oil, antifreeze and fuel can result in damage<br />

to health. Therefor:<br />

• Avoid skin contact with engine oil, fuel and antifreeze.<br />

• Remove oil and fuel splashes and antifreeze from the skin<br />

immediately.<br />

• Do not inhale oil and fuel vapours.<br />

Danger for Life. Improper handling, operation, installation and<br />

maintenance can result in severe personal injury and/or material<br />

damage.<br />

Electrical voltages above 48 volts (battery chargers greater than 36 volts)<br />

are always dangerous to life). The rules of the respective regional authority<br />

must be adhered to. Only an electrician may carry out installation of the electrical<br />

connections for safety reasons.<br />

Generator, oil and antifreeze can be hot during/after operation.<br />

Risk of severe burns.<br />

During Installation/maintenance personal protective equipment<br />

is required to minimize the health hazards.<br />

• Protective clothing<br />

• safety boots<br />

• protective gloves<br />

• Ear defender<br />

• safety glasses<br />

Disconnect all load during the work at the generator to avoid<br />

damages at the load.<br />

7.3 Overloading the Generator<br />

Danger!: Danger of poisoning<br />

ATTENTION!: Danger to Life - High voltage<br />

Warning!: Hot surface/material<br />

Generator Failure<br />

Instruction!: Personal protective equipment necessary.<br />

Attention!: Disconnect all load<br />

Please ensure that the genset is not overloaded. This is especially the case with multi-power aggregates. Overloading<br />

occurs when the electrical load (demand) induces a load torque in the generator which is higher than what<br />

the diesel drive motor can provide. Overloading causes the engine to run rough, burn oil, create excessive exhaust<br />

(environmentally unfriendly) and even to stall.<br />

The generator should only be loaded at the peak rated power for short periods only! A high peak current is required<br />

to start many electrical devices, especially electric motors and compressors (from a still stand state).<br />

In order to prolong the gensets life expectancy, the nominal electrical demand on the system should not be more<br />

than 70% of the rated genset power.<br />

Bear this in mind when switching on electrical devices. This ensures a longer life expectancy.<br />

Continuous performance is the uninterrupted running of the generator for many hours. The genset can be run for<br />

several hours at partial load (i.e. 2/3 of rated power), however it is not advised that it is run for more than 2-3 hours<br />

Seite/Page 116 Panda_4000s_PMS_SCB_FCB_eng.R04 - Kapitel/Chapter 7: Generator Failure 7.5.12