Maintenance Instructions<br />
Unscrew the filter element from the mount (left hand rotation).<br />
Screw the new filter element into the mount.<br />
Lubricate the sight glasses o-ring with a heat resistant grease (Specification:<br />
Antiseize) and screw the sight glass back into its mount (right hand rotation).<br />
6.11.2Check and discharge the capacitors<br />
NEVER check the capacitors whilst the generator motor is running!<br />
Charged capacitors can be lethal. Do not contact the<br />
capacitors with bare fingers or non-insulated metallic objects!<br />
In order to test the capacitors, the terminal lead wires have to<br />
be disconnected using pliers or a screwdriver with insulated<br />
handle(s). Once the wires have been removed, the capacitors<br />
must be discharged by bridging the capacitor terminals with a<br />
discharge reactor.<br />
Attention!:<br />
The capacitors can be checked using a multimeter with capacitor measuring.<br />
Fig. 6.11.1.1-3: Fuel filter<br />
Fig. 6.11.1.1-4: Fuel filter<br />
The capacitors fitted inside the cabinet are discharged over the soldered resistor at every capacitor. The discharge<br />
over the discharge reactor (see special tools) is security because the capacitor voltage is lethal.<br />
7.5.12 Panda_4000s_PMS_SCB_FCB_eng.R04 - Kapitel/Chapter 6: Maintenance Instructions Seite/Page 113