Maintenance Instructions<br />

2. Press failure bypass switch and keep firmly pressed.<br />

The electrical fuel pump must be audible. Switching on<br />

and off the solenoid valve at the generator will be audible<br />

by pressing the failure bypass switch (if capsule<br />

removed).<br />

3. Pressing the failure bypass switch for approx 3 - 4 minutes<br />

will loosen the ventilation screw located at the fuel<br />

solenoid valve. The button must continue to be pressed,<br />

whilst opening the screw. A large cloth or Kleenex tissue<br />

must be laid beneath the connection to prevent escaping<br />

fuel running into the capsule. If the fuel runs out without<br />

air bubbles, then the ventilation screw can be closed.<br />

Only then may the button be released.<br />

Use spanner size 10mm.<br />

Not all generator models has a fuel solenoid valve. At generators<br />

without fuel solenoid valve, a single ventilation screw is<br />

installed.<br />

4. Pressing the starter button can now start the machine.<br />

The machine should start after a short period.<br />

5. If this does not occur, then a connecting nut fitted to the<br />

injection line must be loosened and starting procedure<br />

repeated. Retighten the washers after successfully starting.<br />

The injection line must be raised by several millimetres.<br />

Use spanner size 17mm.<br />

6. Switch main switch „OFF“<br />

Note!:<br />

Fig. 6.11-1: Failure bypass switch<br />

Fig. 6.11-2: Ventilation screw at the fuel solenoid valve<br />

Fig. 6.11-3: Injection nozzles<br />

7.5.12 Panda_4000s_PMS_SCB_FCB_eng.R04 - Kapitel/Chapter 6: Maintenance Instructions Seite/Page 111