• Measure the electrolyte density of individual cells with a<br />

commercial hydrometer. The hydrometer reading (see table<br />

on following page) indicates the battery’s state of charge.<br />

During measurement, the temperature of the electrolyte<br />

should preferably be 20 C.<br />

The gases emitted by the battery are explosive! Keep sparks<br />

and naked flames away from the battery!<br />

Do not allow battery acid to come into contact with skin or<br />

clothing!<br />

Wear protective goggles!<br />

Do not rest tools on the battery!<br />

6.11 Ventilating the fuel system<br />

Attention<br />

Maintenance Instructions<br />

Fig. 6.10.1.3-1: Battery<br />

Electrolyte density<br />

in [kg/ l] Charge status<br />

Normal Tropical<br />

1.28 1.23 well charged<br />

1.20 1.12 semi-charged, re-charge<br />

1.12 1.08 discharged, immediately charge<br />

Normally, the fuel system is designed to ventilate air itself i.e. as soon as the electric starter motor starts operation<br />

the fuel pump starts working and the fuel system will be de-aerated after some time automatically. It is nevertheless<br />

essential to ventilate the system as follows prior to the first operation (as all hoses are empty):<br />

Generators with iControl system do not need a Failure<br />

bypass switch. At these generators the fuel pump can be<br />

activated by an option of the control panel. See Control<br />

panel manual.<br />

1. Main power switch „OFF“<br />

Attention:<br />

Seite/Page 110 Panda_4000s_PMS_SCB_FCB_eng.R04 - Kapitel/Chapter 6: Maintenance Instructions 7.5.12