<strong>Premier</strong> <strong>48</strong>, <strong>88</strong>, <strong>168</strong> & <strong>640</strong> <strong>Installation</strong> <strong>Manual</strong> Programming the Control Panel<br />
22 - R/R=Reset Only<br />
When 0V is applied to the control panel R/R input, any areas<br />
programmed for anti-code reset (see page 41 for details) that<br />
are in alarm, will be reset.<br />
R/R=Silence/RST<br />
When 0V is applied to the control panel R/R input any areas<br />
programmed for anti-code reset (see page 41 for details) that<br />
are in alarm, will be silenced. When 0V is applied to the R/R<br />
input a second time, the areas will be reset (this would<br />
normally be used when Audio Verification is required).<br />
23 - User Code Pulse<br />
The control panel will see a zone that is in the short circuit<br />
condition as ‘Active’.<br />
User Code Latch<br />
The control panel will see a zone that is in the short circuit<br />
condition as a ‘Tamper’.<br />
24 - Timed Test Call<br />
A test call to the Alarm Receiving Centre will occur every time<br />
the ‘Test Call Every’ timer expires.<br />
Test Call = CT7<br />
A test call to the Alarm Receiving Centre will occur every time<br />
‘Control Timer 7’ activates.<br />
25 - Batt Test Timed<br />
A battery test will occur every time the ‘Batt Test Period’ timer<br />
expires.<br />
Batt Test = Disarm<br />
A battery test will occur every time the system is disarmed or<br />
after the ‘Batt Test Period’ timer has expired (whichever<br />
occurs first).<br />
26 - Bell = 1st Alarm<br />
The ‘Bell’ and ‘Strobe’ outputs will activate after an Intruder<br />
alarm (1st Alarm) occurs.<br />
Bell = 2nd Alarm<br />
The ‘Bell’ and ‘Strobe’ outputs will activate after a Confirmed<br />
alarm (2nd Alarm) occurs.<br />
27 - SNDR = 1st Alarm<br />
The internal sounders will sound after an Intruder alarm (1st<br />
Alarm) occurs.<br />
SNDR = 2nd Alarm<br />
The internal sounders will sound after a Confirmed alarm<br />
(2nd Alarm) occurs.<br />
28 - Conf. = Instant<br />
Following the arming of the system/area, if two zones activate<br />
(causing a Confirmed alarm), the signal will be reported to the<br />
Alarm Receiving Centre immediately.<br />
Conf. = Delayed<br />
Following the arming of the system/area, if two zones activate<br />
(causing a Confirmed alarm), the signal will only be reported<br />
to the Alarm Receiving Centre after the ‘Abort’ time has<br />
expired.<br />
29 - Abort=Eng.Reset<br />
An Intruder alarm that is aborted can only be reset by an<br />
Engineer/Anti-code.<br />
Abort=User Reset<br />
An Intruder alarm that is aborted can be reset by any User.<br />
30 – Auto AV Output<br />
When using the AV Module, if a microphone is remotely<br />
selected, the corresponding output automatically activates.<br />
<strong>Manual</strong> AV Output<br />
When using the AV Module, if a microphone is remotely<br />
selected, the corresponding output must be activated<br />
manually.<br />
31 - Clock = 50Hz<br />
The internal clock on the control panel runs from the 50Hz<br />
main frequency.<br />
Clock = Crystal<br />
The internal clock on the control panel runs from the built-in<br />
crystal.<br />
32 - 80 Column Print<br />
Select this option when connecting an 80 Column printer to<br />
the control panel.<br />
40 Column Print<br />
Select this option when connecting an 40 Column printer to<br />
the control panel.<br />
33 - Disable Text<br />
Areas that are armed are displayed as letters on the bottom<br />
line of the display i.e. ‘Armed: AB.D…’<br />
Enable Text<br />
Areas that are armed are displayed using their assigned text<br />
on the bottom line of the display i.e. ‘Armed: Garage’, ‘Office’<br />
etc. (a different area is displayed every second).<br />
34 - EN50131 Disabled<br />
The Control Panels EN50131 options are disabled.<br />
EN50131 Enabled<br />
The Control Panels EN50131 options are enabled.<br />
INS176 47<br />
<br />
This options must be enabled to comply with EN50131<br />
35 - 2nd Zone = Confirm<br />
After the entry timer has expired, activation of 2 more zones is<br />
required to generate a Confirmed alarm<br />
1st Zone = Confirm<br />
After the entry timer has expired, activation of 1 more zone is<br />
required to generate a Confirmed alarm<br />
36 - Keypads Global<br />
Keypads show information for all areas.<br />
Keypads Local<br />
Keypads only show information that is relative to the area that<br />
the keypad is assigned to.