Programming the Control Panel <strong>Premier</strong> <strong>48</strong>, <strong>88</strong>, <strong>168</strong> & <strong>640</strong> <strong>Installation</strong> <strong>Manual</strong><br />

05 Global Bell Time<br />

When all areas are armed, the system uses the ‘Global Bell<br />

Delay’ and ‘Global Bell Duration’ timers (see page 44 for details).<br />

Area Bell Time<br />

When all areas are armed, the system uses the ‘Area Bell<br />

Delay’ and ‘Area Bell Duration’ timers (see page 37 for details).<br />

06 - 24Hr Omit Global<br />

‘24-Hour’ type zones can be omitted from any keypad.<br />

24Hr Omit Local<br />

Only keypads assigned to the same area as the<br />

‘24-Hour’ type zones can be used to omit the zone.<br />

07 - Remove Omits<br />

When zones have been ‘Omitted’ by a user, the zones will be<br />

automatically reinstated by the system when the area they<br />

are assigned to is next disarmed.<br />

Leave Omits<br />

When zones have been ‘Omitted’ by a user, the zones will<br />

remain omitted until the user reinstates them.<br />

08 - Override Com Dly<br />

If an area is ‘Fully’ armed and an Intruder alarm occurs in that<br />

area, Intruder alarm events (for that area) are reported to the<br />

Alarm Receiving Centre immediately.<br />

Enforce Com Dly<br />

If an area is ‘Fully’ armed and an Intruder alarm occurs in that<br />

area, Intruder alarm events (for that area) are reported to the<br />

Alarm Receiving Centre after any programmed ‘Coms delay’<br />

has expired (see page 37 for details).<br />

09 - NVM is Unlocked<br />

The factory default settings can be reloaded by pressing the<br />

Factory Restart button during power up.<br />

NVM is Locked<br />

The factory default settings cannot be reloaded by pressing<br />

the factory default button during power up.<br />

<br />

If the NVM is locked and the Engineer User code has<br />

been lost or forgotten, the control panel will have to be<br />

returned to Texecom to be unlocked.<br />

10 - Engineer Only<br />

Access to the Engineers Programming menus can be<br />

obtained by just entering the Engineer User code.<br />

User + Engineer<br />

Access to the Engineers Programming mode can only be<br />

obtained, if a User (with the ‘Engineer Access’ attribute) has<br />

authorised engineer access (see page 83 for details).<br />

11 - Chime Audible<br />

Zones programmed with the ‘Chime 2 or 3’ attribute will only<br />

generate a Chime tone.<br />

Chime Visible (Default)<br />

Zones programmed with the ‘Chime 2 or 3’ attribute will<br />

generate a Chime tone. The keypad will also display the<br />

number of the zone that was activated.<br />

12 - Omit Tampers No<br />

A user cannot omit Tamper faults on a zone.<br />

Omit Tampers Yes<br />

A user can omit Tamper faults on a zone.<br />

13 - Offline Printing<br />

If a printer is plugged onto the control panel, nothing will be<br />

printed unless a printout is requested (see page 90 for<br />

details).<br />

Online Printing<br />

If a printer is plugged onto the control panel, anything that is<br />

logged in the event log is also printed at the same time.<br />

14 - Hide Act. Fault<br />

If a zone with the ‘Activity’ attribute is not activated during the<br />

‘Activity Delay’ time window, the area that the zone is<br />

assigned to can still be armed. However, this fault will be<br />

indicated to the user when they try to arm the area.<br />

View Act. Fault<br />

If a zone with the ‘Activity’ attribute is not activated during the<br />

‘Activity Delay’ time window, the area that the zone is<br />

assigned to cannot be armed. This situation can only be<br />

overcome by activating the zone.<br />

15 - Hide Exit Errors<br />

If a user tries to arm an area and there are zones activated,<br />

the exit mode will continue (giving a visual and audible<br />

indication that there is a problem).<br />

View Exit Error<br />

If a user tries to arm an area and there are zones activated,<br />

the exit mode is suspended until all of the zones are secure.<br />

16 - Enable Code Tampers<br />

24 invalid key presses on a keypad will cause a Code Tamper<br />

condition (see option 17).<br />

No Code Tampers<br />

A Code Tamper condition will never occur when the keys on<br />

a keypad are pressed more than 24 times.<br />

17 - Code Tamper Alarm<br />

A Code Tamper condition will cause a Tamper alarm in the<br />

areas that the keypad is assigned to.<br />

Code Tamper Lockout<br />

A Code Tamper condition will cause the keypad to lockout for<br />

5 minutes.<br />

18 - Areas A-H & I-P<br />

The first 8 areas will be displayed as letters A through to H and<br />

the last 8 areas will be displayed as letters I through to P.<br />

Areas 1-8 & I-P<br />

The first 8 areas will be displayed as numbers<br />

1 through to 8 and the last 8 areas will be displayed as letters<br />

I through to P.<br />

19 - Auto Area Select<br />

When an Engineers code is entered to gain access to the<br />

programming mode, ALL Zones and Tampers are disabled<br />

i.e. if any Tampers, PA, Fire or Medical Alarms are activated -<br />

NOTHING WILL HAPPEN.<br />

Man. Area Select<br />

When an Engineers code is entered to gain access to the<br />

programming mode, the Engineer will have to select which<br />

areas are going to be worked on.<br />

46 INS176<br />

<br />

Zones and Tampers are only disabled for the selected<br />

areas all other areas will respond to zone activations<br />

and tampers as normal.<br />

20 - Predictive Text<br />

When in text editing mode, the control panel will<br />

automatically select predictive text.<br />

<strong>Manual</strong> Text Edit<br />

When in text editing mode, the control panel will<br />

automatically select normal text.<br />

21 - Short = Tamper<br />

The control panel will see a zone that is in the short circuit<br />

condition as a ‘Tamper’.<br />

Short = Active<br />

The control panel will see a zone that is in the short circuit<br />

condition as ‘Active’.