Premier 48, 88, 168 & 640 Installation Manual - PVK
Premier 48, 88, 168 & 640 Installation Manual - PVK
Premier 48, 88, 168 & 640 Installation Manual - PVK
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Premier</strong> <strong>48</strong>, <strong>88</strong>, <strong>168</strong> & <strong>640</strong> <strong>Installation</strong> <strong>Manual</strong> Commissioning and Troubleshooting<br />
3. Commissioning and Troubleshooting<br />
Commissioning<br />
Once ALL connections have been made to the control panel<br />
and power is ready to be applied, you should read this<br />
section before continuing.<br />
When applying power for the first time, the factory default<br />
settings must be loaded. The default settings ensure that<br />
the control panel software is reset and all programming<br />
information is loaded into memory. For a complete list of<br />
factory default settings, see page 28<br />
The factory default settings are loaded by applying power to<br />
the control panel whilst at the same time, holding down the<br />
Factory Default button.<br />
To default the control panel, proceed as follows:<br />
• Connect the black battery lead to the negative (–)<br />
terminal of the standby battery and the red battery lead<br />
to the positive (+) terminal of the standby battery<br />
• Press and hold the Factory Default button<br />
• Press the battery kick-start button to connect the battery<br />
and ensure that the green heartbeat light illuminates<br />
• After the heartbeat light has illuminated, let go of the<br />
Factory Default button (the heartbeat light will continue<br />
to flash whilst the factory default settings are being<br />
loaded, this can take up to 30 seconds)<br />
• If the system goes into alarm, enter the default<br />
Engineer code , and the alarm<br />
tone will stop<br />
• To access the Engineer Programming Menu, enter the<br />
default Engineer code <br />
• Program the system as described in section 6<br />
•<br />
(Programming the Control Panel)<br />
Perform a zone test as described on 86. Remember that<br />
some powered detectors (e.g. PIR’s and combined<br />
technology detectors) take several minutes to warm up<br />
and become operational<br />
• Test the internal sounder, external sounder and strobe as<br />
described on page 87<br />
• Replace the lid and secure with the lid screw supplied<br />
• Press followed by YES to leave the programming<br />
menu, the system will return to normal<br />
• The display will be showing that there is a ‘Mains Power<br />
Off’ condition. Switch on the AC mains supply to the<br />
control panel<br />
• The normal banner message (if programmed) will now<br />
be displayed<br />
<strong>Installation</strong> is now complete and the system is<br />
ready for use.<br />
Trouble-Shooting<br />
Control Panel<br />
No Power to unit (mains only)<br />
• Check the mains block fuse and replace if blown<br />
• Check for loose wires at the mains block, the transformer<br />
and the AC terminals on the PCB<br />
• Check the mains block is connected correctly; live to live<br />
(brown), neutral to neutral (blue)<br />
No Power to unit (battery only)<br />
• Don’t forget to press the battery kick-start button<br />
• Check the battery fuse F2 and replace if blown<br />
• Check for loose wires at the BATT terminals on the PCB<br />
• Check that the battery wires are connected correctly; red<br />
from BATT+ to the battery positive (+), black from<br />
BATT- to the battery negative (-)<br />
Heartbeat LED is not flashing<br />
• Remove ALL power (AC Mains and Battery) and then<br />
reapply power again<br />
Network Data LED’s are not flashing<br />
• Remove ALL power (AC Mains and Battery) and remove<br />
ALL wires from the network terminals. Then<br />
re-apply power again before referring to the Network<br />
Diagnostics table on page 12<br />
Keypads<br />
Keypad does not operate<br />
• Check that the keypad is wired correctly from the control<br />
panel (see page 12 for wiring details)<br />
• Check the network fuses F3 and F5 and replace if blown<br />
• Use the network diagnostics (see page 12 for details)<br />
Keypad does not accept codes<br />
• If the system has more than one keypad check that each<br />
keypad is addressed differently, see page 14 for details<br />
• If the keypad is on a long cable run, check the voltage<br />
between the ‘+’ and ‘–’ terminals at the keypad and<br />
ensure that it measures no less than 10.0V<br />
• Check that you are using the correct User codes. The<br />
default Engineer code is and the<br />
default Master User code is <br />
• Check that the User code you are using is not ‘Time<br />
Locked’, if the User code is time locked then the access<br />
code will only be accepted when Control Timer 1 is off<br />
(see pages 49 and 83 for details)<br />
Keypad zones do not operate<br />
• Each keypad zone has to be mapped onto the system<br />
before it can be used (see page 54 for details)<br />
• The zone is not programmed (see page 33 for details)<br />
Keypad emergency keys do not operate<br />
• Each keypad can be configured so that the emergency<br />
keys PA, FIRE and MEDICAL can be enabled or<br />
disabled. Check that the keypad has been programmed<br />
correctly (see page 54 for details)<br />
INS176 25