03.03.2013 Views

Premier 48, 88, 168 & 640 Installation Manual - PVK

Premier 48, 88, 168 & 640 Installation Manual - PVK

Premier 48, 88, 168 & 640 Installation Manual - PVK

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>Premier</strong> <strong>48</strong>, <strong>88</strong>, <strong>168</strong> & <strong>640</strong> <strong>Installation</strong> <strong>Manual</strong> Commissioning and Troubleshooting<br />

3. Commissioning and Troubleshooting<br />

Commissioning<br />

Once ALL connections have been made to the control panel<br />

and power is ready to be applied, you should read this<br />

section before continuing.<br />

When applying power for the first time, the factory default<br />

settings must be loaded. The default settings ensure that<br />

the control panel software is reset and all programming<br />

information is loaded into memory. For a complete list of<br />

factory default settings, see page 28<br />

The factory default settings are loaded by applying power to<br />

the control panel whilst at the same time, holding down the<br />

Factory Default button.<br />

To default the control panel, proceed as follows:<br />

• Connect the black battery lead to the negative (–)<br />

terminal of the standby battery and the red battery lead<br />

to the positive (+) terminal of the standby battery<br />

• Press and hold the Factory Default button<br />

• Press the battery kick-start button to connect the battery<br />

and ensure that the green heartbeat light illuminates<br />

• After the heartbeat light has illuminated, let go of the<br />

Factory Default button (the heartbeat light will continue<br />

to flash whilst the factory default settings are being<br />

loaded, this can take up to 30 seconds)<br />

• If the system goes into alarm, enter the default<br />

Engineer code , and the alarm<br />

tone will stop<br />

• To access the Engineer Programming Menu, enter the<br />

default Engineer code <br />

• Program the system as described in section 6<br />

•<br />

(Programming the Control Panel)<br />

Perform a zone test as described on 86. Remember that<br />

some powered detectors (e.g. PIR’s and combined<br />

technology detectors) take several minutes to warm up<br />

and become operational<br />

• Test the internal sounder, external sounder and strobe as<br />

described on page 87<br />

• Replace the lid and secure with the lid screw supplied<br />

• Press followed by YES to leave the programming<br />

menu, the system will return to normal<br />

• The display will be showing that there is a ‘Mains Power<br />

Off’ condition. Switch on the AC mains supply to the<br />

control panel<br />

• The normal banner message (if programmed) will now<br />

be displayed<br />

<strong>Installation</strong> is now complete and the system is<br />

ready for use.<br />

Trouble-Shooting<br />

Control Panel<br />

No Power to unit (mains only)<br />

• Check the mains block fuse and replace if blown<br />

• Check for loose wires at the mains block, the transformer<br />

and the AC terminals on the PCB<br />

• Check the mains block is connected correctly; live to live<br />

(brown), neutral to neutral (blue)<br />

No Power to unit (battery only)<br />

• Don’t forget to press the battery kick-start button<br />

• Check the battery fuse F2 and replace if blown<br />

• Check for loose wires at the BATT terminals on the PCB<br />

• Check that the battery wires are connected correctly; red<br />

from BATT+ to the battery positive (+), black from<br />

BATT- to the battery negative (-)<br />

Heartbeat LED is not flashing<br />

• Remove ALL power (AC Mains and Battery) and then<br />

reapply power again<br />

Network Data LED’s are not flashing<br />

• Remove ALL power (AC Mains and Battery) and remove<br />

ALL wires from the network terminals. Then<br />

re-apply power again before referring to the Network<br />

Diagnostics table on page 12<br />

Keypads<br />

Keypad does not operate<br />

• Check that the keypad is wired correctly from the control<br />

panel (see page 12 for wiring details)<br />

• Check the network fuses F3 and F5 and replace if blown<br />

• Use the network diagnostics (see page 12 for details)<br />

Keypad does not accept codes<br />

• If the system has more than one keypad check that each<br />

keypad is addressed differently, see page 14 for details<br />

• If the keypad is on a long cable run, check the voltage<br />

between the ‘+’ and ‘–’ terminals at the keypad and<br />

ensure that it measures no less than 10.0V<br />

• Check that you are using the correct User codes. The<br />

default Engineer code is and the<br />

default Master User code is <br />

• Check that the User code you are using is not ‘Time<br />

Locked’, if the User code is time locked then the access<br />

code will only be accepted when Control Timer 1 is off<br />

(see pages 49 and 83 for details)<br />

Keypad zones do not operate<br />

• Each keypad zone has to be mapped onto the system<br />

before it can be used (see page 54 for details)<br />

• The zone is not programmed (see page 33 for details)<br />

Keypad emergency keys do not operate<br />

• Each keypad can be configured so that the emergency<br />

keys PA, FIRE and MEDICAL can be enabled or<br />

disabled. Check that the keypad has been programmed<br />

correctly (see page 54 for details)<br />

INS176 25

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!