<strong>Premier</strong> <strong>48</strong>, <strong>88</strong>, <strong>168</strong> & <strong>640</strong> <strong>Installation</strong> <strong>Manual</strong> <strong>Installation</strong><br />

Zone Connections<br />

Any zones that are not being used must be linked out or<br />

programmed as ‘Not Used’ (see page 33 for details).<br />

When using End Of Line wiring, ensure that no more than 5<br />

detectors are connected to each zone.<br />

A zone short can be programmed for ‘Active’ or ‘Tamper’<br />

response (see page 46 for details).<br />

Double Pole<br />

Use this wiring configuration when connecting normally<br />

closed or normally open detection devices to the zone using<br />

4-Wires.<br />

When using Double Pole wiring, the system will respond as<br />

follows:<br />

<br />

Zone Status System Response<br />

‘A’ Closed Zone Secure<br />

‘A’ Open Zone Active<br />

‘T’ Closed Tamper Secure<br />

‘T’ Open Tamper Active<br />

Short Circuit * Zone Active or Tamper<br />

* Can be programmed for ‘Active’ or ‘Tamper’<br />

response (see page 46 for details).<br />

When using this configuration, no more than 10<br />

detectors can be connected to each zone.<br />

When wiring device as normally open contacts, ensure<br />

that system Config. option 21 is set to ‘Zone Short =<br />

Active’ (see page 46 for details).<br />

End Of Line<br />

Use this wiring configuration when connecting normally<br />

closed or normally open detection devices to the zone using<br />

2-Wires.<br />

When Configuration Option 21 (see page 46 for details) is<br />

programmed as ‘Short = Tamper’ the system will respond as<br />

follows:<br />

Zone Status System Response<br />

0 - 2k Zone Tamper<br />

2k1 - 4k6 (EOL) Zone Secure<br />

4k7 - 20k Zone Active<br />

21k+ Zone Tamper<br />

INS176 19<br />

<br />

When using this configuration, no more than 3<br />

detectors can be connected to each zone.<br />

When Configuration Option 21 (see page 46 for details) is<br />

programmed as ‘Short = Active’ the system will respond as<br />

follows:<br />

<br />

Zone Status System Response<br />

0 - 2k Zone Active<br />

2k1 - 4k6 (EOL) Zone Secure<br />

4k7 - 30k Zone Active<br />

31k+ Zone Tamper<br />

When using this configuration, no more than 5<br />

detectors can be connected to each zone.<br />

For details on testing zones, see page 86.