01.03.2013 Views

A User's Manual for DELSOL3 - prod.sandia.gov - Sandia National ...

A User's Manual for DELSOL3 - prod.sandia.gov - Sandia National ...

A User's Manual for DELSOL3 - prod.sandia.gov - Sandia National ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

This approximate method of calculating PLAVG is used during system optimization.<br />

However, during a final per<strong>for</strong>mance calculation (IPROB=O) the parasitic<br />

losses are calculated and averaged over the days and times <strong>for</strong> which energy<br />

calculation is accomplished, rather than depending on the approximation of hours<br />

of storage and hours of receiver operation.<br />

The parasitic losses described above are only calculated when the plant (i.e.,<br />

turbine) is generating energy. However, the total power plant also requires en-<br />

ergy at other times, to run such mundane things as lighting and building heat, as<br />

well as to start and shut down equipment, such as unstowing the heliostat field<br />

or preheating the receiver. Reference 33 provides empirical relationships <strong>for</strong> non-<br />

operating parasitic losses as a function of rated gross electric power Pe,gross <strong>for</strong><br />

several different plant status conditions, such as at night, during maintenance<br />

outages, and during startup and shutdown of the plant. Specifically,<br />

startup/shutdown loss (MWe)<br />

I 8 = PARLlq,+ PARL2 x Pe,gross<br />

prestartup/postshutdown IOSS (MW,) = PARL3 + PARL4 x Pe,gross<br />

nighttime loss (MWe) = PARL5 + PARL6 x Pe,gross<br />

weather loss (MWe) = PARL7 + PARLS x Pe,gross<br />

outage (PF) loss (MWe) = PARLS + PARLlO x Pe,gross<br />

(I1I.G - 24)<br />

All of the above parasitic losses need to be associated with some length of<br />

time in order to calculate the lost energy. It is assumed that the time of the PF<br />

outage (Namelist NLEFF) is (1 - PF) x 365 x 24 hours. Weather is assumed to<br />

be a fraction of all remaining time of the year as defined by (1 - WEATH). Al-<br />

though in reality weather only affects daytime operations, this approximation<br />

is acceptable as long as the weather parasitic loss coefficients are not signifi-<br />

cantly different from night time loss coefficients. Times <strong>for</strong> startup/shutdown<br />

and prestartup/postshutdown operations are input by the user <strong>for</strong> the variables<br />

TSTRT and TPRE (Namelist BASIC) as the average time to per<strong>for</strong>m one oper-<br />

ation (either startup or shutdown, or either prestartup or postshutdown) <strong>for</strong> one<br />

day, in hours. Night time is defined to be the time left after all other times are<br />

accounted <strong>for</strong>, including startup/shutdown, prestartup/postshutdown, mainte-<br />

nance outages, weather outages, times when the receiver is operating (HROP),<br />

and times when the receiver is shut down but energy is being generated from<br />

storage. Note that startup and prestartup times do not reduce the hours of op-<br />

eration, since hours of operation of the receiver are fixed by the user’s choice of<br />

the variable ASTART.<br />

88<br />

Defaults <strong>for</strong> all parasitic loss variables are as follows:<br />

PLREF (REFPRL) = 0.103<br />

fa (FSP) = 0.66

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!