A User's Manual for DELSOL3 - prod.sandia.gov - Sandia National ...
A User's Manual for DELSOL3 - prod.sandia.gov - Sandia National ...
A User's Manual for DELSOL3 - prod.sandia.gov - Sandia National ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
.<br />
furthermore, that the assumed turbine efficiency is a worst case estimate (see<br />
Sections 1II.G-5 and 1V.A-7). Thus, the capacity factor value calculated and dis-<br />
played during a DELSOL optimization is only an estimate at best. By optimizing<br />
the physical storage size, the user will be changing the actual capacity factor, as<br />
well as storage and energy costs, because the amount of available stored energy<br />
will change without changing solar multiple. DELSOL will not recalculate the ca-<br />
pacity factor.<br />
1V.C-6. Heliostat Field Boundaries-The user has no control over this part of<br />
the system optimization. DELSOL will optimize the boundaries of the heliostat<br />
field as described in Section 1V.B-1. The heliostat field is always constrained to<br />
lie within the zoning defined by the variables RADMIN and RADMAX, and may<br />
be further subjected to a land constraint as described in Section 1V.D-2.<br />
IV. C- 7. Heliostat Spacings-DELSOL has an option <strong>for</strong> optimizing the spacing<br />
of heliostats within each zone (IHOPT-1 in Namelist OPT). The optimization<br />
has three constraints: (1) the layout pattern is always a radial stagger pattern;<br />
(2) the optimized densities and aspect ratios cannot be more than 3~20% from the<br />
initial densities and aspect ratios defined in Namelist FIELD (the range is set by<br />
the variable DHOPT in Namelist BASIC): and (3) the tower height cannot be<br />
optimized simultaneously with optimizing heliostat spacings (see Chapter VI).<br />
1V.D. Constraints on System Optimization/Desipn<br />
During system optimization, DELSOL can design systems which meet flux<br />
limitations on the receiver or which have land availability constraints. In this<br />
case, no system will be accepted as an optimum unless the appropriate con-<br />
straints are satisfied.<br />
I V. D-1. Receiver Flux Constraint During Optimization-DELSOL has an op-<br />
tion to calculate and monitor the flux at the design point at up to four points<br />
on the receiver surface (NFLXMXs4). The maximum allowable values at these<br />
points are specified by FLXLIM(1) watts/m2, where I=l, NFLXMX. If the flux<br />
limit at one of the points exceeds its limit, field buildup during optimization is<br />
halted <strong>for</strong> that combination of receiver and tower dimensions.<br />
The flux values which are calculated during optimization are only approxima-<br />
tions of actual peak flux levels, <strong>for</strong> at least three reasons. First, the design point<br />
insolation is assumed to be REFSOL (Namelist BASIC), which may not match ei-<br />
ther a measured insolation at a design point time or a calculated insolation using<br />
one of the insolation models available in DELSOL during a per<strong>for</strong>mance calcula-<br />
tion. Second, in calculating the flux during optimization, DELSOL assumes that<br />
the relative shape of the flux profile at the design point is the same as the relative<br />
shape of the annual average flux profile as described by an initial per<strong>for</strong>mance<br />
calculation. This assumption is more correct <strong>for</strong> surround fields than <strong>for</strong> north<br />
biased fields, but in any case it depends on the choice of the design point by the<br />
user. This assumption usually causes the optimization calculation of flux to over-<br />
predict the actual flux level at a point on the receiver. Third, the peak flux on<br />
111