Technical Standards - Scottish Government
Technical Standards - Scottish Government
Technical Standards - Scottish Government
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>Technical</strong> <strong>Standards</strong><br />
For compliance with the Building <strong>Standards</strong><br />
(Scotland) Regulations 1990, as amended by<br />
the Building <strong>Standards</strong> (Scotland) Amendment<br />
Regulations 1993, the Building <strong>Standards</strong><br />
(Scotland) Amendment Regulations 1994, the<br />
Building <strong>Standards</strong> (Scotland) Amendment<br />
Regulations 1996, the Building (Scotland)<br />
Amendment Regulations 1997, the Building<br />
<strong>Standards</strong> and Procedure Amendment<br />
(Scotland) Regulations 1999, and the Building<br />
<strong>Standards</strong> Amendment (Scotland) Regulations<br />
2001.<br />
This publication presents the <strong>Technical</strong> <strong>Standards</strong> which are the ‘relevant<br />
standards’ for compliance with the Building <strong>Standards</strong> (Scotland) Regulations<br />
1990, as amended. The <strong>Technical</strong> <strong>Standards</strong> have full Statutory force by virtue<br />
of Regulation 9.<br />
Although presented in separate Parts to relate to particular regulations, the<br />
<strong>Technical</strong> <strong>Standards</strong> and the Regulations must be considered and applied as a<br />
whole; more than one standard or regulation may bear on a particular building<br />
element or design decision. Where this is relevant the most onerous standard<br />
applies [see for example Regulation 6 (4)or Regulation 7 (3)].<br />
i<br />
Amdt: September 2001
Amdt: September 2001<br />
© Text: Crown Copyright 2001<br />
© Typographic Design: The Stationery Office Limited 2001<br />
First Published 2001<br />
British Library Cataloguing in Publication Data<br />
A catalogue record for this book is available from the British Library<br />
ISBN 0 11 497294 X (Book Bound)<br />
0 11 497295 8 (Looseleaf)<br />
ii
Contents<br />
Introduction: The building control system in Scotland<br />
Part A: General including:<br />
Definitions<br />
References to published standards<br />
Regulations 3 to 9<br />
Schedules 1 to 5<br />
Part B: Fitness of materials and workmanship (Regulation 10)<br />
Part C: Structure (Regulation 11)<br />
Part D: Structural fire precautions (Regulation 12)<br />
Part E: Means of escape from fire, facilities for fire-fighting and means of<br />
warning of fire (Regulation 13)<br />
Part F: Combustion appliance installations and Storage of liquid and<br />
gaseous fuels (Regulations 14 and 15)<br />
Part G: Preparation of sites, Resistance to moisture and Resistance to<br />
condensation (Regulations 16, 17 and 18)<br />
Part H: Resistance to transmission of sound (Regulations 19 to 21)<br />
Part J: Conservation of fuel and power (Regulation 22)<br />
Part K: Ventilation of buildings (Regulation 23)<br />
Part M: Drainage and Sanitary facilities (Regulations 24 and 25)<br />
Part N: Electrical installations and Aids to assist the hard of hearing<br />
(Regulations 26 and 26A)<br />
Part P: Miscellaneous hazards (Regulations 27 to 28)<br />
Part Q: Access and Facilities for dwellings (Regulation 29)<br />
Part R: Storage of waste (Regulations 30 to 31)<br />
Part S: Access to and movement within buildings, and protective barriers<br />
(Regulation 32)<br />
Appendix: Publications referred to in the <strong>Technical</strong> <strong>Standards</strong><br />
Index Index to <strong>Technical</strong> <strong>Standards</strong> as revised September 2001<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A, General.<br />
iii<br />
vii<br />
Amdt: September 2001
INTRODUCTION: TITLE?<br />
THE BUILDING CONTROL SYSTEM<br />
IN SCOTLAND
Amdt: December 1999<br />
vi
vii<br />
Introduction:<br />
The Building Control System<br />
in Scotland<br />
BACKGROUND<br />
Local authorities administer building control in Scotland,<br />
enforcing regulations made by the <strong>Scottish</strong> Ministers subject<br />
to approval by the <strong>Scottish</strong> Parliament.<br />
Building control applies to the construction, alteration,<br />
extension or demolition of a building or part of a building, or<br />
to any change of use which attracts additional or more<br />
onerous requirements under the regulations.<br />
The essential purpose is to safeguard people in and around<br />
buildings. To this has been added the conservation of fuel<br />
and power used in buildings, and the provision of facilities<br />
for the disabled in and around buildings. It is a pre-emptive<br />
system, ensuring as far as practically possible that the<br />
proposed buildings will not contravene the regulations and<br />
that on completion the buildings do in fact comply.<br />
The <strong>Scottish</strong> Ministers hope that users of the regulations and<br />
those affected by them, including members of the public,<br />
will not hesitate to make their views known where they feel<br />
the regulations are either inadequate or are too wide in their<br />
scope or too onerous in any respect. Suggestions for<br />
improving any aspect of building control will always be<br />
given careful consideration.<br />
BUILDING STANDARDS (SCOTLAND) REGULATIONS<br />
The building standards regulations are made by the <strong>Scottish</strong><br />
Ministers under powers in section 3 of the Building<br />
(Scotland) Act 1959 as amended, (in particular by the<br />
Scotland Act 1998, which transferred the powers from the<br />
Secretary of State for Scotland). The regulations do not<br />
Amdt: December 1999
apply retrospectively to existing buildings unless there are<br />
exceptional circumstances (such as danger to the public), but<br />
do apply to parts of existing buildings that are altered or<br />
extended.<br />
A number of separate supporting regulations set out the<br />
procedures, forms and related matters which regulate the<br />
operation of the building control system. Local authorities<br />
can advise on what is applicable in relation to any particular<br />
project.<br />
<strong>Scottish</strong> Ministers, in framing building standards<br />
regulations, are required to consult the Building <strong>Standards</strong><br />
Advisory Committee (see below) and such other bodies as<br />
appear to them to be representative of the interests<br />
concerned. Regulations are published in the form of<br />
Statutory Instruments, which are subject to the approval of<br />
the <strong>Scottish</strong> Parliament.<br />
BUILDING STANDARDS ADVISORY COMMITTEE<br />
This committee, established by statute, keeps a watching eye<br />
on the building control system and reports to <strong>Scottish</strong><br />
Ministers on aspects that need attention because of<br />
developments in the industry or changes in the expectations<br />
of society. The committee must also be consulted on all<br />
proposed amendments to the legislation. The secretariat to<br />
the committee is provided by the <strong>Scottish</strong> Executive, which<br />
can be approached to put matters before the committee.<br />
COMPLIANCE WITH THE REGULATIONS<br />
Regulation 9 stipulates that the requirements of the<br />
regulations can be satisfied only by compliance with the<br />
relevant standards. The relevant standards are set out in this<br />
document, the <strong>Technical</strong> <strong>Standards</strong> for compliance with the<br />
Building <strong>Standards</strong> (Scotland) Regulations 1990, as<br />
amended.<br />
Without prejudice to any other way of meeting the standards,<br />
complying with the provisions that are deemed to satisfy the<br />
requirements of the regulations, as given in this document,<br />
constitutes compliance.<br />
To satisfy the regulations therefore the design, materials and<br />
methods of construction must be at least to the standards set<br />
in this publication. The provisions deemed to satisfy the<br />
standards are provided for the convenience of designers only<br />
if they choose to adopt them. There is no obligation to do so,<br />
but if used properly deemed to satisfy solutions must be<br />
accepted by the local authority.<br />
An important point to recognise is the full acceptance of<br />
solutions based on standards and technical specifications<br />
recognised in other Member States of the European<br />
Economic Area (EEA), or to the growing number of<br />
European standards, where these provide equivalent<br />
standards of protection or performance. (See Part A:<br />
Reference to published standards, and Part B: Fitness of<br />
Materials and Workmanship). These regulations must not<br />
contravene the Construction Products Directive by causing<br />
barriers to trade within the EEA.<br />
Amdt: September 2001<br />
viii
ix<br />
BUILDING WARRANTS<br />
All building work must comply with the standards<br />
prescribed by the regulations except the classes of building<br />
exempted by the definition of building or listed in schedule<br />
1 (see Part A). It is an offence for anyone to carry out<br />
building works, other than those specifically exempted,<br />
without a warrant from the local authority. It is the<br />
responsibility of the building owner to apply for and obtain<br />
the warrant. Apart from the exempted classes of building<br />
described above certain fixtures, listed in schedule 2, may<br />
not require a warrant, although compliance with the<br />
standards is still required. The building control officers of<br />
the local authority will advise on what drawings,<br />
specifications and other information are required to enable<br />
them to check for compliance with the regulations. For very<br />
minor work only limited plans may be needed, but large<br />
projects require extensive information. A fee is payable at<br />
the time of application for a warrant based on the estimated<br />
cost of the building works.<br />
The local authority is responsible for the enforcement of the<br />
regulations and in most cases difficulties or disagreements<br />
over interpretation are resolved by discussion with the local<br />
authority. There is, however, a right of appeal to the Sheriff<br />
Court in the event of refusal to grant warrant and certain<br />
other actions of the local authority.<br />
The time required for checking may depend on the size or<br />
complexity of the project, and any adjustments required, so<br />
no time limit is set in Statute. Most authorities however<br />
operate to targets for responding, and report performance to<br />
the Accounts Commission which publishes annual reports.<br />
A warrant is valid for three years from issue, but this period<br />
can be extended if a request is made within that period.<br />
A warrant is required for the demolition of a building<br />
(sections 6 and 16 of the Act refer).<br />
INSPECTION<br />
During construction building control staff may inspect the<br />
works, and the local authority must be notified when<br />
building work begins and subsequently at specified stages.<br />
Tests (e.g. of drains) may be required to establish<br />
compliance with the regulations (section 18 of the Act<br />
refers).<br />
COMPLETION<br />
Before the building may be occupied it is necessary to obtain<br />
from the local authority a certificate of completion. This<br />
provides formal confirmation that the building work has<br />
been carried out in accordance with the warrant and with the<br />
building standards regulations, so far as the local authority<br />
can ascertain from their inspection (section 9 of the Act<br />
refers).<br />
Quite apart from the legal implications, failure to obtain<br />
warrants and completion certificates can have serious<br />
practical consequences, e.g. for householders seeking to sell<br />
Amdt: December 1999
their homes. Buyers’ solicitors and lending institutions often<br />
wish to see these documents in connection with property<br />
sales, mortgages etc. Where work has been carried out that<br />
does not comply with the regulations the local authority can<br />
require changes to be made to bring it up to standard. This<br />
can impose considerable additional expense on the owner.<br />
ADDITIONAL ARRANGEMENTS<br />
The summary above outlines the arrangements and legal<br />
obligations that apply in most cases. There are additional<br />
arrangements that may be appropriate in particular<br />
circumstances.<br />
Relaxations: Any set of rules for such a complex and<br />
evolving subject as building must incorporate a degree of<br />
elasticity to cope with exceptional circumstances. In such<br />
cases there are arrangements to permit relaxation from or<br />
dispensation of requirements in the regulations. The power<br />
to decide these cases has been devolved fully to local<br />
authorities, which can advise on how to apply for a<br />
relaxation (and on how to appeal if an applicant feels<br />
particularly aggrieved by a refusal or the conditions attached<br />
to a decision to relax). In the case of relaxations only, appeal<br />
is to the <strong>Scottish</strong> Executive, not the Sheriff Court.<br />
Reasons for relaxation can include, for example, difficulties<br />
posed in alteration work. The key consideration is whether,<br />
in a particular case, it is unreasonable for specific<br />
requirements to apply. If a relaxation application concerns a<br />
departure from regulation 13 on means of escape from fire<br />
the local authority must consult the fire authority before<br />
issuing a decision (section 4 of the Act refers).<br />
Class relaxations: Exceptionally, <strong>Scottish</strong> Ministers can<br />
issue class relaxation directions permitting the use of<br />
products or elements of buildings that do not comply with<br />
the published standards. Class relaxations characteristically<br />
relate to products or building elements or forms that<br />
incorporate new technical features not envisaged when the<br />
regulations were made, but which nevertheless embody<br />
adequate safeguards for public health and safety (section 4 of<br />
the Act refers).<br />
Class warrants: The Act sets out a procedure for giving a<br />
class of building a warrant, which would apply in subsequent<br />
applications. This procedure has never been implemented as<br />
local authorities in Scotland have set up the <strong>Scottish</strong><br />
Building Control Organisation to issue type approvals.<br />
Information is available from the Convention of <strong>Scottish</strong><br />
Local Authorities.<br />
Staged warrants: Local authorities are empowered to issue a<br />
warrant subject to agreement on later phases of work. This<br />
procedure, often known as a staged warrant, allows<br />
construction to begin before design is complete. The<br />
applicant choosing to build in this way will be required to<br />
show that any work to be commenced does comply, and that<br />
later phases comply before being permitted to proceed with<br />
them.<br />
Amdt: December 1999<br />
x
xi<br />
Limited warrants: There is provision for gaining a warrant<br />
for buildings to have a stated limited life not exceeding five<br />
years. The warrant is issued on condition that the building<br />
will be demolished before the end of the stated period unless<br />
the local authority grants an extension of the period. It will<br />
be apparent that this provision has significance only where<br />
the regulations accept lesser standards for a short life<br />
building (section 6(4) and (5) of the Act refers). Such<br />
standards might be resistance to moisture, say, which can be<br />
relaxed without increasing risks to the building users for the<br />
limited time involved.<br />
Self-certification: This procedure has been adopted to allow<br />
chartered engineers to certify structural design work rather<br />
than submit detailed calculations (section 6AA of the Act<br />
refers). There are no plans at present to extend the use of<br />
self-certification.<br />
ALTERATIONS AND EXTENSIONS<br />
The application of the building standards regulations to<br />
alterations and extensions sometimes presents difficulties.<br />
The basic principle is that the regulations apply to the<br />
alteration or extension but not to the existing unaffected parts<br />
of the building even where these do not comply with present<br />
regulations. However the alteration or extension must not<br />
directly cause the existing part of the building to fail to<br />
conform, or to fail to conform to a greater degree (for<br />
example if an extension is built over a window needed to<br />
provide light, ventilation or escape). In those instances a<br />
warrant may be refused unless the existing building is<br />
brought up to the standard previously attained (sections<br />
6(2)(a), 6(8)(c) and 29(2) of the Act refer).<br />
CHANGE OF USE<br />
Change of use of a building or part of a building can bring<br />
into force all relevant regulations in the case of a building<br />
previously exempted, or additional or more onerous<br />
requirements in the case of a building already subject to the<br />
regulations. For example, a house changed into a nursing<br />
home would attract more onerous means of escape<br />
requirements. Such changes of use require a warrant even if<br />
no building work is proposed. Or again, if a house is split<br />
into flats the floor will become a separating floor and more<br />
fire resistance is required.<br />
The key is whether a more onerous requirement applies to<br />
the new use of the building or any part or component of the<br />
building. It may relate to only one regulation or many, or<br />
one part of a building and nothing else (for example the use<br />
of a gas flue for a solid fuel appliance).<br />
A building does not necessarily need to change from one<br />
purpose group to another to attract more onerous<br />
requirements. The local authority can advise on particular<br />
cases (section 6(2)(b) of the Act refers).<br />
Change of use for building control purposes must be<br />
carefully distinguished from change of use for planning<br />
purposes.<br />
Amdt: December 1999
ENFORCEMENT<br />
Local authorities have powers to enforce the regulations<br />
where buildings have been constructed without a warrant or<br />
in contravention of the regulations or conditions of a<br />
warrant. Regardless of whether or not work requiring<br />
warrant is proposed, they can also require an existing<br />
building to conform to certain regulations if this should be<br />
necessary to safeguard the occupants or the public generally.<br />
In such cases a notice is served on the owner of the building<br />
stating the operations required. If the owner fails to react<br />
within a defined period the authority may order him to carry<br />
out the work. In the event of failure to comply with the order<br />
within a specified period the owner is guilty of an offence<br />
and the local authority may then carry out the work and<br />
recover the cost from the owner as a debt (sections 10 and 11<br />
of the Act refer).<br />
DANGEROUS BUILDINGS<br />
If the local authority considers that a building is dangerous it<br />
can require immediate evacuation and require, or itself take,<br />
any action (including demolition) necessary to protect the<br />
public and adjacent property. The authority can then serve<br />
on the owner a notice requiring remedial action or<br />
demolition within a stated period and, if no action is taken,<br />
serve an enforcement order. If this is not complied with the<br />
authority can itself carry out the repair or demolition and<br />
then recover its expenses from the owner (sections 13, 14<br />
and 15 of the Act refer).<br />
THE BUILDING CONTROL FORUM<br />
The <strong>Scottish</strong> Executive and the Convention of <strong>Scottish</strong> Local<br />
Authorities (COSLA) meet regularly to promote common<br />
interpretation and administration of the building standards<br />
regulations. This Forum brings together senior local<br />
authority and central government officials about 3 times a<br />
year to resolve difficulties in the operation of the building<br />
control system, so far as is possible without changing<br />
legislation. It also provides an opportunity for consideration<br />
of representations from industry, commerce and the building<br />
professions on problems of general concern. Anyone<br />
wishing to make such representations should approach either<br />
the <strong>Scottish</strong> Executive or COSLA.<br />
The minutes of the meetings and occasional information<br />
papers agreed by the Forum are distributed to all local<br />
authorities, providing a direct channel of communication to<br />
deal with problems arising on the operation of the system.<br />
Amdt: December 1999<br />
xii
GENERAL INCLUDING:<br />
DEFINITIONS, REFERENCES,<br />
REGULATIONS 3-9, AND SCHEDULES 1-5A
Contents<br />
INTRODUCTION<br />
DEFINITIONS<br />
REFERENCES TO PUBLISHED STANDARDS<br />
REGULATIONS 3 TO 9<br />
3 Exempted classes of buildings<br />
4 Fixtures not requiring a warrant<br />
5 Limited life buildings<br />
6 Classification of buildings by purpose<br />
7 Occupancy capacity<br />
8 Measurements<br />
9 Compliance with building standards<br />
SCHEDULES 1 TO 5<br />
1 Exempted classes of buildings<br />
2 Fixtures not requiring a warrant<br />
3 Classification of buildings by purpose<br />
4 Occupancy load factors<br />
5 Rules of measurement<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A, General.<br />
3A<br />
Amdt: September 2001<br />
A
5A<br />
Introduction<br />
1 The intention of this Part of the <strong>Technical</strong> <strong>Standards</strong> is to<br />
give information on the general application of the Building<br />
<strong>Standards</strong> (Scotland) Regulations 1990 as amended. (These<br />
regulations are made under the powers given by The Building<br />
(Scotland) Act 1959).<br />
2 Part A contains:<br />
a. a full list of the defined terms used both in the Regulations<br />
and in these <strong>Technical</strong> <strong>Standards</strong>;<br />
b. instructions on the interpretation of references to other<br />
published documents;<br />
c. a complete extract of Regulations 3-9, which deal with<br />
the general way in which the Regulations are applied and<br />
which cover: exempted buildings; fixtures not requiring<br />
a warrant; limited life buildings; classification of buildings<br />
by purpose; occupancy capacity; rules of measurement;<br />
and means of compliance; and<br />
d. a set of the Schedules to the Regulations which are<br />
essential to interpret and apply the Regulations, i.e.<br />
Schedules 1-5.<br />
3 The material in Part A is included to enable the reader to<br />
interpret the provisions in the <strong>Technical</strong> <strong>Standards</strong> without<br />
the constant need to cross-refer to the Regulations. For the<br />
same reason, all other Parts of the <strong>Technical</strong> <strong>Standards</strong> are<br />
prefaced by verbatim copies of the Regulations for which<br />
they provide the relevant standards.<br />
4 Applications for warrants for the construction or change<br />
of use* of a building made before the date of coming into<br />
force of these Regulations or any relevant amending Regulations<br />
and applications for extension of the period of validity<br />
or amendment of warrant remain subject to the Building<br />
<strong>Standards</strong> (Scotland) Regulations in operation at the time the<br />
application for warrant was made.<br />
*Change of use is defined in the Building (Scotland) Act and<br />
‘in relation to a building means such change in the use or<br />
occupation of the building as will bring it within a class of<br />
building to which the building standards regulations apply,<br />
or, if it is already within such a class, within a class to which<br />
additional or more onerous provisions of the building standards<br />
regulations apply, and "change the use" shall be construed<br />
accordingly’. It applies to any part or component of a<br />
building as well as whole buildings, and is different in<br />
concept from a change of use in common parlance or in<br />
terms of planning legislation.<br />
Amdt: September 2001<br />
A
A<br />
Definitions<br />
Note:<br />
This is a list of terms used in the <strong>Technical</strong> <strong>Standards</strong> that have a specific meaning. The list also includes all<br />
the terms defined in Regulation 2, ‘Interpretation’, of the Building <strong>Standards</strong> (Scotland) Regulations 1990 as<br />
amended (indicated by an asterisk). The definitions of ‘building’ and ‘construct’ derive from the Act. All the<br />
terms listed below are in italics throughout the <strong>Technical</strong> <strong>Standards</strong>.<br />
ACCESS DECK means a structure having a surface in the open air suitable for ingress and egress of persons to a<br />
building.<br />
*the ACT means the Building (Scotland) Act 1959.<br />
*AGRICULTURE has the same meaning as in the Agriculture (Scotland) Act 1948 (a), and AGRICULTURAL shall<br />
be construed accordingly.<br />
*AIR SUPPORTED STRUCTURE means a structure which has a space-enclosing single-skin membrane anchored<br />
to the ground and kept in tension by internal air pressure so that it can support applied loading.<br />
ALTERNATIVE EXIT means an exit from a dwelling which is through a door other than its main entrance door and<br />
is available for use at all times.<br />
APARTMENT means a room in a dwelling not used solely as a kitchen, store or utility room.<br />
APPLIANCE COMPARTMENT means a space constructed or adapted specifically for the housing of a combustion<br />
appliance.<br />
BASEMENT STOREY means any storey which is below the level of the ground storey.<br />
*BOUNDARY means a boundary between land on which the building is situated and land in different occupation,<br />
so however that -<br />
a. in relation to any external side of a building it shall exclude any part of the boundary which<br />
makes an angle with that side of more than 80°;<br />
b. in relation to any road, whether public or private, public access way or public right of way, river,<br />
stream, canal, loch, pond, common land or public open space it shall be taken to mean the centre<br />
line thereof; and<br />
c. the sea and its foreshore shall not be regarded as land in different occupation.<br />
*BUILDING means any structure or erection of what kind or nature soever, whether temporary or permanent, and<br />
every part thereof, including any fixture affixed thereto, not being a structure or erection or part thereof consisting<br />
of, or ancillary to -<br />
a. any road, whether public or private, including in the case of a public road (but not in the case of a<br />
private road) any bridge on which the road is carried;<br />
b. any sewer or water main which is, or is to be, vested in a public authority;<br />
c. any aerodrome runway;<br />
d. any railway line;<br />
e. any large raised reservoir within the meaning of the Reservoirs Act 1975(b); or<br />
f. wires and cables, their supports above ground and other apparatus used for telephonic or telegraphic<br />
communication;<br />
and includes any prospective building; and in relation to the extension, alteration or change of use of a building<br />
any reference to the building shall be construed as a reference only to so much of the building as is comprised<br />
in the extension or is subject to alteration or change of use as the case may be.<br />
(a) 1948 c.45<br />
(b) 1975 c.23<br />
Amdt: September 2001<br />
6A
*CARPORT means a roofed building for vehicle storage which is open on at least two sides except for roof<br />
supports.<br />
CAVITY in Part D means a concealed space enclosed by elements of a building (including a suspended ceiling)<br />
or contained within an element, but not a room, cupboard, circulation space, stair enclosure, lift well, flue or a<br />
space within a chute, duct, pipe or conduit.<br />
CAVITY BARRIER means any construction provided to seal a cavity against the penetration of fire and smoke, or<br />
to restrict its movement within the cavity.<br />
*CHIMNEY means a structure enclosing one or more flues, not being a flue-pipe, but including a factory-made<br />
chimney, and including any opening for the accommodation of a combustion appliance, but does not include a<br />
chimney-can.<br />
CHIMNEY-STACK means that part of a chimney which rises above the roof of the building of which it forms part<br />
and includes any cope but not a chimney-can.<br />
CIRCULATION AREA in Parts D and E means an area mainly used as a means of access between an apartment<br />
and an exit; or an area forming an unprotected zone or part of an unprotected zone; or an area in a room or a<br />
space, which provides access to an exit and is permanently demarcated from any space intended for human<br />
occupation.<br />
*COMPARTMENT means a part of a building (which may contain one or more rooms, spaces or storeys and<br />
includes, where relevant, the space above the top storey of the compartment) constructed so as to prevent the<br />
spread of fire to or from another part of the same building; and COMPARTMENTED and COMPARTMENTATION<br />
shall be construed accordingly.<br />
*COMPARTMENT FLOOR and COMPARTMENT WALL mean respectively a floor or a wall with the level of fire<br />
safety performance required to ensure compartmentation.<br />
*CONSERVATORY means a building attached to a dwelling and having a door separating it from that dwelling<br />
and having not less than three-quarters of the area of its roof and not less than one-half of the area of its external<br />
walls made of translucent material.<br />
*CONSTRUCT includes alter, erect, extend and fit, and CONSTRUCTION shall be construed accordingly.<br />
*COVERED AREA means a roofed building which is open on at least two sides except for roof supports.<br />
CURTILAGE means land area within the same occupation.<br />
DEAD LOAD means the load due to the weight of all walls, permanent partitions, floors, roofs and finishes,<br />
including services and other permanent construction.<br />
DECORATIVE FUEL-EFFECT GAS APPLIANCE means an open flued appliance designed to simulate a solid fuel<br />
open fire primarily for decorative purposes and intended to be installed so that the products of combustion pass<br />
unrestricted from the firebed to the flue.<br />
*DIFFERENT OCCUPATION, in relation to two adjoining buildings or parts of one building, means occupation or<br />
intended occupation of those buildings or parts by different persons.<br />
DISABLED PEOPLE means persons with a physical, hearing or sight impairment which affects their mobility or<br />
their use of buildings.<br />
*DRAINAGE SYSTEM means the system of pipes and drains used for the drainage of a building, including all<br />
other fittings, appliances and equipment so used.<br />
DRY FIRE MAIN means a pipe installed in a building for fire-fighting purposes which is normally dry but is<br />
capable of being charged with water by pumping from a fire service appliance.<br />
DUCT means the structure, trunking, or casing, with any apertures, enclosing a passage, other than a flue, used<br />
solely for conveying air, gases, or services including refuse.<br />
*DWELLING means a unit of residential accommodation occupied (whether or not as a sole or main residence)a.<br />
by a single person or by people living together as a family; or<br />
b. by not more than six residents living together as a single household (including a household where<br />
care is provided for residents).<br />
ELECTRO-MAGNETIC OR ELECTRO-MECHANICAL DEVICE SUSCEPTIBLE TO SMOKE means a device which allows<br />
a door held open by it to be operated manually at all times and to close automatically upona.<br />
the operation of an automatic smoke detector; or<br />
7A<br />
Amdt: September 2001<br />
A
A<br />
b. the manual operation of a switch fitted in a suitable position; or<br />
c. the failure of electrical supply to the device, apparatus or switch; or<br />
d. if a fire alarm system is installed in the building, operation of that system.<br />
ELEMENT OF STRUCTURE means a part of a building which is part of the structural frame (beams and columns),<br />
loadbearing (other than a part which is only self-loadbearing), a floor, or supports a floor.<br />
EMERGENCY DOOR means a door which may be a fire door and which is intended to be used only during an<br />
emergency.<br />
EMERGENCY LIGHTING means lighting, designed to come into, or remain in, operation automatically in the event<br />
of either a local or general power failure.<br />
ESCAPE ROUTE means a route by which a person may reach a place of safety, and in relation toa.<br />
a storey, a space or an access deck, means a route from an exit from that storey, space or access<br />
deck;<br />
b. a room, means a route from an exit of that room;<br />
c. an inner room, other than an inner room in a dwelling, means a route from an exit of the room<br />
which provides access to the inner room;<br />
d. a flat or maisonette, means a route from the main entrance door of that flat or maisonette;<br />
e. a gallery, catwalk or openwork floor, means a route from any doorway of, or from the head of<br />
any unenclosed escape stair from, that gallery, catwalk or openwork floor;<br />
f. a place of special fire risk, means a route from an exit of that room or from an exit of the protected<br />
lobby serving that room, or from an exit of the room or lobby separating the place of<br />
special fire risk from any other accommodation, as the case may be.<br />
ESCAPE STAIR means a stair or ramp forming part of an escape route. In shared residential accommodation the<br />
escape stair for the purpose of Part S (maximum permissible pitch) is considered to be a private stair.<br />
EXIT means a point of egress from a room, storey, protected zone, space, gallery, catwalk or openwork floor<br />
which forms part of, or gives access to, an escape route or place of safety.<br />
EXPOSED in Part J in relation to a building element means an element directly exposed to the outside air or<br />
directly in contact with the ground or a ground floor directly in contact with a ventilated underfloor space.<br />
*EXTERNAL WALL includes a part of a roof pitched at an angle of 70° or more to the horizontal.<br />
FIRE DOOR means a door which, together with its frame and furniture as installed in a building, is intended,<br />
when closed, to resist the passage of fire and, where prescribed, smoke and is capable of meeting specified<br />
performance criteria in Part D.<br />
FIRE-FIGHTING LIFT means a lift with additional protection, and with controls to enable it to be used under the<br />
direct control of the fire service when fighting a fire.<br />
FIRE-FIGHTING LOBBY means a lobby within a fire-fighting shaft providing access from the escape stair to the<br />
accommodation and to any associated fire-fighting lift.<br />
FIRE-FIGHTING SHAFT means an enclosure protected from fire in adjoining accommodation and containing, an<br />
escape stair, a fire-fighting lobby at every storey at which the fire-fighting shaft can be entered from the accommodation<br />
and, if provided, a fire-fighting lift together with its machine room.<br />
FIRE-STOP means a seal provided to close an imperfection of fit or design tolerance between elements, components<br />
or construction so as to restrict the passage of fire and smoke through that imperfection. FIRE-STOPPING<br />
and FIRE-STOPPED shall be construed accordingly.<br />
*FLAT means a dwelling on one storey, forming part of a building from some other part of which it is divided<br />
horizontally, and includes a dwelling of which the main entrance door and associated hall are on a different<br />
storey from the remainder of the dwelling.<br />
FLAT ROOF means a roof the slope of which does not exceed 10° from the horizontal.<br />
FLIGHT means part of a stair or ramp uninterrupted by a landing.<br />
Amdt: September 2001<br />
8A
FLOOR in Part G means any construction between the surface of the ground, or the surface of any hardcore laid<br />
upon the ground, and the upper surface of the floor, together with any floor finishes which are laid as part of<br />
the permanent construction.<br />
*FLUE means a passage which conveys the products of combustion to the open air.<br />
*FLUE-PIPE means a pipe forming a flue, but not a pipe fitted as a lining in a chimney.<br />
*FOUNDATION means that part of the structure in direct contact with, and transmitting loads to, the ground.<br />
*GALLERY means a raised floor or platform, including a raised storage floor, which is open to the room or space<br />
into which it projects and whicha.<br />
has every part of its upper surface not less than 1.8 metres above the surface of the main floor of<br />
the said room or space; and<br />
b. occupies (or, in the case of there being more than one gallery, together occupy), not more than<br />
one-half of the floor area of the said room or space.<br />
GLAZING means any permanently secured sheet of glass or plastics, and GLAZED shall be construed accordingly.<br />
*GREENHOUSE, except in the expression agricultural greenhouse, means a building ancillary to a dwelling used<br />
mainly for growing plants which is eithera.<br />
detached from the dwelling; or<br />
b. attached to, but not entered from, the dwelling.<br />
GREYWATER means wastewater not containing faecal matter or urine.<br />
GROUND STOREY means the storey of a building in which there is situated an entrance to the building from the<br />
level of the adjoining ground or, if there is more than one such storey, the lower or lowest of these.<br />
HARMFUL OR DANGEROUS SUBSTANCES includes deposits of faecal or animal matter and any substance or<br />
mixture of substances which is or could become corrosive, explosive, flammable, radioactive or toxic or which<br />
produces or could produce any gas likely to have any such characteristic.<br />
HOSPITAL means a building in purpose sub-group 2A for the treatment of persons suffering from illness or<br />
mental or physical disability or handicap.<br />
HOSPITAL STREET means a protected zone in a hospital provided to assist in facilitating circulation and horizontal<br />
evacuation, and to provide a fire-fighting bridgehead.<br />
*HOUSE means a dwelling on one or more storeys, either detached or forming part of a building from all other<br />
parts of which it is divided only vertically.<br />
IMPOSED LOAD means the load assumed to be produced by the intended occupancy or use, including the weight<br />
of moveable partitions; distributed, concentrated, impact, inertia and snow loads, but excluding wind loads.<br />
INNER ROOM means a room, other than a kitchen in a dwelling, which does not have a direct access to an exit,<br />
or direct access to an enclosed circulation area having an exit.<br />
*KITCHEN means any room or part of a room used primarily for the preparation or cooking of food.<br />
*LAND IN DIFFERENT OCCUPATION, in relation to a building, means land occupied or to be occupied by a person<br />
other than the occupier of the land on which the building is or is to be situated.<br />
*LIMITED LIFE BUILDING means a building intended to have a life of the period specified in Regulation 5. [This<br />
is currently five years].<br />
*MAISONETTE means a dwelling on more than one storey, forming part of a building from some other part of<br />
which it is divided horizontally.<br />
NET INPUT RATING of an appliance means the total energy input rate determined when the water produced by<br />
the combustion of the fuel is assumed to remain as a vapour.<br />
NON-COMBUSTIBLE means that a material is resistant to combustion as determined by an appropriate test procedure<br />
as specified in Part D.<br />
NOTIFIED BODY means an organisation appointed for the purpose of the relevant directive by a member state<br />
and whose name is notified to the European Commission to certify, inspect or test the production of goods.<br />
*OCCUPANCY CAPACITY shall be construed in accordance with Regulation 7.<br />
*OCCUPIER, in relation to a dwelling, means the person inhabiting the dwelling.<br />
9A<br />
Amdt: September 2001<br />
A
A<br />
OPEN-FLUED APPLIANCE means one that draws its air for combustion from the room or internal space within<br />
which it is installed and uses a flue system to discharge its products of combustion to the outside air.<br />
*PASSENGER CONVEYOR means a power-driven installation containing an endless moving walkway for the<br />
conveyance of persons between different levels or between different parts of the same level of a building.<br />
PERMANENT VENTILATOR means a ventilator which provides continuous ventilation.<br />
PLACE OF SAFETY means eithera.<br />
an unenclosed space in the open air at ground level; or<br />
b. an enclosed space in the open air at ground level leading to an unenclosed space, via an access<br />
not narrower than the total width of the exits leading from the building to that enclosed space.<br />
PLACE OF SPECIAL FIRE RISK means any place within, or attached to, or on the roof of, a building in which<br />
there are installed one or morea.<br />
solid fuel appliances, with a total installed output rating more than 50 kW, other than kitchen<br />
appliances; or<br />
b. oil or gas-fired appliances, with a total installed net input rating more than 70 kW, other than<br />
kitchen appliances, forced air convection or radiant heaters in buildings of purpose groups 3 to 7<br />
inclusive; or<br />
c. fixed internal combustion engines, including gas turbine engines, with a total output rating more<br />
than 45 kW; or<br />
d. oil-immersed electricity transformers or switch gear apparatus with an oil capacity more than 250<br />
litres and operating at a supply voltage more than 1000 volts; or<br />
e. fuel oil storage tanks having a capacity of more than 90 litres; or<br />
f. paint spray booths or rooms where a cellulose or other flammable liquid spray is used.<br />
*PORCH means a building attached to and providing a covered entrance to a dwelling.<br />
PRIVATE STAIR OR RAMP means a stair or rampa.<br />
wholly within a dwelling; or<br />
b. wholly within shared residential accommodation.<br />
PROTECTED CIRCUIT means a circuit originating at the main incoming switch or distribution board, the conductors<br />
of which are suitably protected against fire.<br />
PROTECTED DOOR means a fire door giving access toa.<br />
a protected zone, including a protected lobby; or<br />
b. a fire-fighting shaft; or<br />
c. another compartment; or<br />
d. a place of safety; or<br />
e. an unenclosed external escape stair; or<br />
f. an open access balcony; or<br />
g. an escape route across a flat roof or access deck.<br />
PROTECTED ENCLOSURE in a dwelling means a circulation area constructed to resist fire in adjoining accommodation.<br />
It includes a hall, landing or private stair or ramp but not a room.<br />
PROTECTED LOBBY means a lobby within a protected zone but separated from the remainder of the protected<br />
zone so as to resist the movement of smoke from the adjoining accommodation to the remainder of the protected<br />
zone.<br />
Amdt: September 2001<br />
10A
PROTECTED ZONE means that part of an escape route which is within a building, but not within a room, and to<br />
which access is only by way of a protected door and from which there is an exit directly to a place of safety,<br />
and which is constructed as a compartment.<br />
*PUBLIC OPEN SPACE includes land used as a public park or for public recreation or as a burial ground.<br />
*PUBLIC ROAD has the same meaning as in the Roads (Scotland) Act 1984(a)<br />
*PURPOSE GROUP and PURPOSE SUB-GROUP mean respectively a group or sub-group of buildings specified in<br />
Schedule 3. [to the Building <strong>Standards</strong> (Scotland) Regulations 1990 (as amended).]<br />
*REASONABLY PRACTICABLE in relation to the carrying out of any operation, means reasonably practicable<br />
having regard to all the circumstances including the expense involved in carrying out the operation.<br />
*RELEVANT STANDARD means a standard set out in the <strong>Technical</strong> <strong>Standards</strong> which relates to the requirements of<br />
a particular provision of these regulations [i.e. the Building <strong>Standards</strong> (Scotland) Regulations 1990 as<br />
amended].<br />
ROOF in Part G means any roof, including eaves and junctions with other elements penetrating or connected to<br />
the roof.<br />
ROOF SPACE means any space in a building between a part of the roof and the ceiling below.<br />
*ROOM means any enclosed part of a storey intended for human occupation or, where no part of any such storey<br />
is so enclosed, the whole of that storey, but excepting in either case any part used solely as a bathroom, shower<br />
room, washroom, toilet, stair or circulation area.<br />
*ROOM-SEALED APPLIANCE means a combustion appliance which, when in operation, has its combustion<br />
chamber, air inlet and its flue outlet ways isolated from the room or space in which it is installed.<br />
SANDWICH PANEL means a factory made non-loadbearing component of a wall, ceiling or roof consisting of a<br />
panel having an insulated core filling the entire area between sheet metal outer facings, which may or may not<br />
have decorative and/or weatherproof coatings.<br />
SANITARY ACCOMMODATION includes bathrooms, shower rooms, washrooms and toilets.<br />
*SANITARY FACILITIES includes washbasins, baths, showers, sinks, urinals and waterclosets (and waterless<br />
closets in dwellings only).<br />
SELF-CLOSING FIRE DOOR means a fire door, fitted to close automatically from any angle of swing.<br />
SEPARATING FLOOR and SEPARATING WALL mean respectively a floor or wall constructed to prevent the spread<br />
of fire between buildings or parts of a building in accordance with Part D.<br />
SERVICE OPENING means any opening to accommodate a duct, pipe, conduit or cable (including fibre optics or<br />
similar tubing).<br />
SHARED RESIDENTIAL ACCOMMODATION means a unit of accommodation of purpose sub-group 2B having an<br />
occupancy capacity not exceeding 10, entered from the open air at ground level and having no storey at a<br />
height exceeding 7.5 m.<br />
*SITE in relation to a building, means the area of ground covered or to be covered by the building, including its<br />
foundations.<br />
SMOKE ALARM means a device powered by mains electricity, with a secondary power source, containing within<br />
one housing all the components necessary for detecting fire and thereupon giving an audible alarm.<br />
*SOCKET OUTLET means a fixed device containing contacts for the purpose of connecting to a supply of electricity<br />
the corresponding contacts of a plug attached to any current-using appliance.<br />
*STOREY means that part of a building which is situated between the top of any floor being the lowest floor<br />
level within the storey and the top of the floor next above it being the highest floor level within the storey or, if<br />
there is no floor above it, between the top of the floor and the ceiling above it or, if there is no ceiling above it,<br />
the internal surface of the roof; and for this purpose a gallery or catwalk, or an openwork floor or storage<br />
racking, shall be considered to be part of the storey in which it is situated.<br />
SUB-COMPARTMENT means a part of a building (which may contain one or more rooms, and includes, where<br />
relevant, the space above the top storey of the sub-compartment) constructed so as to aid horizontal evacuation.<br />
SUB-COMPARTMENT WALL means a wall with the level of fire safety performance required to create a subcompartment.<br />
(a) 1984 c.54<br />
11A<br />
Amdt: September 2001<br />
A
A<br />
*SURFACE WATER means the run-off of rainwater from roofs and any paved ground surface within the curtilage<br />
of a building.<br />
TAPERED TREAD means a stair tread in which the nosing is not parallel to the nosing of the tread or landing next<br />
above.<br />
*TECHNICAL STANDARDS means the <strong>Technical</strong> <strong>Standards</strong> for compliance with the Building <strong>Standards</strong> (Scotland)<br />
Regulations 1990 issued by the <strong>Scottish</strong> Office in October 1990, as amended by the substitute pages issued by<br />
the <strong>Scottish</strong> Executive in and dated December 1999 and September 2001.<br />
*TOILET means an enclosed part of a storey which contains a watercloset, a waterless closet or a urinal, which<br />
are properly installed for use.<br />
TRAVEL DISTANCE has the meaning assigned to that expression by the <strong>Technical</strong> <strong>Standards</strong> E2.16, E5.2, E5.3,<br />
E5.4 and E5.5.<br />
TRICKLE VENTILATOR means a closeable small ventilator which can provide minimum ventilation.<br />
UNPROTECTED ZONE means that part of an escape route, which is separated by walls, glazed screens or any<br />
other permanent form of demarcation from any space intended for human occupation, including a protected<br />
zone.<br />
UPPER STOREY means any storey which is above the level of the ground storey.<br />
U-VALUE (or thermal transmittance co-efficient) means the rate of heat transfer through one square metre of a<br />
structure when the temperature at each side of the structure differs by 1°C (expressed in W/m 2 K).<br />
VENTILATOR means a window, rooflight, grille or similar building component (and in the case of a dwelling<br />
includes a door) capable of being opened to provide ventilation.<br />
WALL in Part G means any wall including piers, chimneys, columns and parapets which form part of the wall.<br />
*WASTEWATER means water that is contaminated by use and normally discharged from a watercloset, shower,<br />
bath, bidet, washbasin, sink, washing machine, floor gully and similar facility and also includes rainwater when<br />
discharging in a wastewater drainage system.<br />
WET FIRE MAIN means a pipe installed in a building for fire-fighting purposes which is permanently charged<br />
with water from a pressurised supply.<br />
WIND LOAD means the load due to the effects of wind pressure or suction.<br />
Amdt: September 2001<br />
12A
References to published standards<br />
1. The Construction Products Directive (CPD) (89/106/EEC), implemented in the UK through the Construction<br />
Products Regulations 1991, has permitted the introduction of a wide range of standards and specifications<br />
recognised throughout the European Economic Area (EEA) (see Note 1). They provide standards of safety,<br />
suitability and fitness measured against factors common throughout Europe and are intended to avoid unnecessary<br />
barriers to trade. The European Organisation for <strong>Standards</strong> (CEN) is expected to produce approximately<br />
2000 harmonised European <strong>Standards</strong> (EN) over the next 5 or 6 years to replace the variety of standards used<br />
throughout Member States (see Note 2). These EN will be published in the UK by the British <strong>Standards</strong> Institution<br />
(BSI) as a BS EN. Once a BS EN is published, BSI will declare the corresponding BS obsolescent and a<br />
transitional period (normally 1 year) will come into force whereby both BS and BS EN may be referenced. At<br />
the end of the transitional period the BS will be withdrawn and the BS EN should be adopted.<br />
2. The complex processes involved in the production of European <strong>Standards</strong> can create lengthy development<br />
times. European <strong>Standards</strong> in draft form are termed prEN and are released into the public domain when they<br />
are issued for consultation. It has been found necessary, occasionally, to reference prEN in the <strong>Technical</strong><br />
<strong>Standards</strong> where no other suitable document exists.<br />
3. Any reference in the <strong>Technical</strong> <strong>Standards</strong> to a British Standard (BS), British Standard Code of Practice<br />
(CP), European Standard (BS EN or prEN) or International Standard (BS EN ISO) is to a BS or CP published<br />
by the British <strong>Standards</strong> Institution. Any reference in the <strong>Technical</strong> <strong>Standards</strong> to a particular requirement of<br />
recommendation of a BS or CP shall be taken, unless the context otherwise requires, as including reference to<br />
any relevant commentary and defined terminology contained in that BS or CP. Attention is also drawn to the<br />
status accorded to standards and specifications recognised elsewhere in the EEA which provide an equivalent<br />
standard – see Part B: Fitness of Materials and Workmanship: deemed to satisfy provisions. Compliance with<br />
the standards contained in publications in these categories represents compliance with the appropriate standards<br />
referred to elsewhere in the <strong>Technical</strong> <strong>Standards</strong> and is acceptable until a harmonised standard is introduced for<br />
any particular product.<br />
4. Harmonised test methods have been agreed collectively by Member States and CEN on the basis of the<br />
implications of health and safety of the product and on the particular nature and production process for the<br />
product itself. Certification, inspection and testing of construction products will be carried out by notified<br />
bodies who have been appointed for the purpose by a Member State and whose name has been notified to the<br />
European Commission. The British Board of Agrément (BBA) is a notified body for certain products. Any<br />
reference in the <strong>Technical</strong> <strong>Standards</strong> to a certificate issued by a notified body or to a BBA Certificate shall be<br />
construed as reference to a Certificate current as at 1 June 2001.<br />
5. Any reference in the <strong>Technical</strong> <strong>Standards</strong> to a publication shall be construed as a reference to that publication<br />
as detailed in Column 1 of the list of publications given in the Appendix, subject to such amendments,<br />
supplements or addenda as are detailed in column 3 of the Appendix.<br />
6. Where a publication referred to in the <strong>Technical</strong> <strong>Standards</strong> itself refers to another publication, the reference<br />
to such other publication shall be a reference to the latest edition thereof as at 1 June 2001 including any<br />
amendments, supplements or addenda thereto current at that date.<br />
Notes:<br />
1. The European Economic Area Agreement is given affect in the UK by the European Economic Area Act<br />
1993 and entered into force on 1 January 1994.<br />
2. A Member State is a state which is a member of the European Union or the European Free Trade Association<br />
and is a contracting party to the European Economic Area Agreement.<br />
13A<br />
Amdt: September 2001<br />
A
14A
Regulations 3 to 9<br />
The following is a complete extract of Regulations<br />
3 to 9 of the Building <strong>Standards</strong> (Scotland)<br />
Regulations 1990 as amended. The Regulations<br />
are reproduced for the convenience of readers to<br />
assist in considering the application and interpretation<br />
of the relevant standards as set out in the<br />
succeeding Parts of the <strong>Technical</strong> <strong>Standards</strong>.<br />
EXEMPTED CLASSES OF BUILDINGS<br />
3. Subject to the exceptions in column (3) of<br />
Schedule 1, these Regulations shall not<br />
apply to any building the whole of which<br />
falls into any one or more of the exempted<br />
classes specified in Part I of that Schedule<br />
or to any extension to a building the<br />
whole of which extension falls into any<br />
one or more of the exempted classes<br />
specified in Part II thereof.<br />
FIXTURES NOT REQUIRING A WARRANT<br />
4. For the purposes of the proviso to section<br />
6(1) of the Act, any operation for the<br />
alteration of a building which consists<br />
solely of the fitting of a fixture of a kind<br />
specified in Schedule 2 shall not, subject<br />
to the exceptions in column (3) of that<br />
Schedule, require a warrant.<br />
LIMITED LIFE BUILDINGS<br />
5. For the purposes of section 3(3)(b) of the<br />
Act which enables special provision to be<br />
made for buildings intended to have a<br />
limited life) a period of five years is<br />
specified.<br />
CLASSIFICATION OF BUILDINGS BY PURPOSE<br />
6. (1) For the purposes of these Regulations,<br />
buildings or parts thereof<br />
shall be classified according to the<br />
numbered purpose group or groups<br />
and, where applicable, lettered<br />
purpose sub-group or sub-groups<br />
set out in Schedule 3.<br />
15A<br />
(2) In the determination of such classification,<br />
any use which is ancillary<br />
to another use or which is of a<br />
minor nature shall be disregarded<br />
and the classification shall be that<br />
of the principal use or uses.<br />
(3) Where a building is divided into<br />
compartments, nothing in this<br />
regulation shall prevent these<br />
compartments being independently<br />
classified, whether or not the<br />
division is required by any provision<br />
of these Regulations.<br />
(4) Where a building or part of a<br />
building does not fall into any<br />
purpose group or sub-group these<br />
Regulations shall have effect as if<br />
the more or most onerous standard<br />
applicable to any classification<br />
applied.<br />
OCCUPANCY CAPACITY<br />
7. (1) For the purposes of these Regulations,<br />
the occupancy capacity of a<br />
room or space shall be-<br />
(a) in the case of a room or space<br />
described in column (1) of<br />
Schedule 4 the number (or in<br />
the case of a fractional number<br />
the next lowest whole number)<br />
obtained by dividing the area of<br />
the room or space in square<br />
metres by the relevant occupancy<br />
load factor specified in<br />
column (2) of that Schedule; or<br />
(b) in any other case the number of<br />
persons the room or space is<br />
likely to accommodate in use.<br />
(2) The occupancy capacity of a<br />
building or storey which is divided<br />
into rooms or spaces shall be-<br />
Amdt: September 2001<br />
A
A<br />
(a) in the case of a storey of a<br />
building of purpose group 2<br />
which is not open to the public<br />
and which contains both day<br />
rooms and sleeping rooms, the<br />
sum of the occupancy capacities<br />
of either the day rooms or<br />
the sleeping rooms, which ever<br />
is the greater; or<br />
(b) in any other case the sum of the<br />
occupancy capacities of the<br />
rooms or spaces.<br />
(3) Where a room or space is likely to<br />
be put to more than one use, the<br />
greater or greatest relevant occupancy<br />
capacity shall apply.<br />
(4) In this Regulation “space” includes<br />
a roof or other area open to the<br />
external air to which there is access<br />
for a purpose other than the maintenance<br />
of the building.<br />
MEASUREMENTS<br />
8. For the purposes of these Regulations,<br />
measurements shall be made or calculated<br />
in accordance with Schedule 5.<br />
COMPLIANCE WITH BUILDING STANDARDS<br />
9. (1) The requirements of Regulations<br />
10 to 32 shall be satisfied only by<br />
compliance with the relevant<br />
standards.<br />
(2) Without prejudice to any other<br />
method of complying with a relevant<br />
standard, conformity with<br />
provisions which are stated in the<br />
<strong>Technical</strong> <strong>Standards</strong> to be deemed<br />
to satisfy that standard shall constitute<br />
such compliance.<br />
Amdt: September 2001<br />
16A
Part A - Schedules 1 to 5<br />
The following extract from the Building <strong>Standards</strong> (Scotland) Regulations 1990 as amended sets out Schedules 1<br />
to 5 for ease of reference when deciding the application of the relevant standards.<br />
SCHEDULE 1 REGULATION 3<br />
EXEMPTED CLASSES OF BUILDINGS<br />
(1) (2) (3)<br />
Class Description Exceptions<br />
PART 1 - DETACHED BUILDINGS<br />
Buildings controlled by other legislation<br />
1 A building the construction of which is subject<br />
to the Explosives Acts 1875 and 1923(a)<br />
2 A building erected on a site which is subject to A dwelling, office or canteen<br />
licensing under the Nuclear Installations Act 1965(b)<br />
3 A building included in the Schedule of monuments A building of purpose group 1 or 2<br />
maintained under section 1 of the Ancient Monuments<br />
and Archaeological Areas Act 1979(c)<br />
Buildings not frequented by people<br />
4 A building into which people cannot or do a. A building (other than a wall or fence) within<br />
not normally go 10 metres or the equivalent of its height<br />
(whichever is the less) of the boundary, and for<br />
the purpose of this exception, the boundary, in<br />
relation to any road, public access way or public<br />
right of way, river, stream, canal, loch, pond,<br />
common land or public open space, shall be<br />
taken to be the nearest edge thereof to the relevant<br />
land<br />
b. A wall or fence within the exceptions in Class 13<br />
of this Schedule<br />
c. A tank, cable, sewer, drain or other pipe above or<br />
below ground which falls within any of the<br />
exceptions in Class 16 of this Schedule<br />
5 Fixed plant or machinery or a building housing only A building within 1 metre of a boundary<br />
fixed plant or machinery, the only normal visits to<br />
which are intermittent visits to inspect or maintain the<br />
fixed plant or machinery<br />
(a) 1875 c.17 and 1923 c.17.<br />
(b) 1965 c.57.<br />
(c) 1979 c.46; section 1 was amended by the National Heritage Act 1983 (c.47), Schedule 4, paragraph 25<br />
17A<br />
Amdt: September 2001<br />
A
A<br />
(1) (2) (3)<br />
Class Description Exceptions<br />
Agricultural greenhouses and other agricultural buildings<br />
6 An agricultural greenhouse or other building A buildingof<br />
mainly translucent material used mainly<br />
for commercial growing of plants i. used to any extent for retailing (including storage<br />
of goods for retailing) or exhibiting; or<br />
7 A building used for any other form of agriculture a. A building-<br />
Works of civil engineering<br />
ii. situated on land within the boundaries of which<br />
there are harmful or dangerous substances<br />
i. used to any extent for retailing (including<br />
storage of goods for retailing) or exhibiting;<br />
ii. exceeding 2000 cubic metres in capacity;<br />
iii within 10 metres or the equivalent of its height<br />
(whichever is the less) of a boundary of a building<br />
of purpose group 1 or 2; or<br />
iv A building situated on land within the boundaries<br />
of which there are harmful or dangerous<br />
substances<br />
b. A tank, cable, sewer, drain or other pipe above or<br />
below ground which falls within Class 16 of this<br />
Schedule<br />
c. A dungstead<br />
8 A work of civil engineering construction including A septic tank, or private sewage treatment plant,<br />
a dock, wharf, harbour, pier, quay, sea defence work, which is serving a building subject to regulation 24<br />
lighthouse, embankment, riverwork, dam, bridge,<br />
tunnel, filter station or bed, inland navigation, reservoir,<br />
water works, pipe line, sewage treatment works, gas<br />
holder or main, electricity supply line and supports.<br />
Buildings of a specialised nature<br />
9 A building essential for the operation of a railway a. A signalling and control centre for a railway<br />
including a locomotive or carriage shed, or for the or dock<br />
operation of a work of civil engineering contained in<br />
Class 8, and erected within the curtilage of such a b. A building, not being a building falling within Class<br />
railway or work 10 of this Schedule, of purpose group 4 or 5 erected<br />
within the curtilage of such a railway or work<br />
10 A road or rail passenger shelter or a telephone kiosk A building containing a combustion appliance<br />
having a floor area not exceeding 30 square metres, which is subject to regulation 14<br />
and which, insofar as it is glazed, complies with the<br />
requirements of regulation 27(1)(b)<br />
Amdt: September 2001<br />
18A
(1) (2) (3)<br />
Class Description Exceptions<br />
11 A caravan or mobile home within the meaning of the A septic tank, or private sewage treatment plant<br />
Caravan Sites and Control of Development Act serving a building of this class<br />
1960(a), or a tent, van or shed within the meaning of<br />
section 73 of the Public Health (Scotland) Act 1897(b)<br />
Small buildings<br />
12 A single-storey building having an area not exceeding A building-<br />
30 square metres, and which, insofar as it is glazed,<br />
complies with the requirements of regulation 27(1)(b), i. of purpose group 1;<br />
other than a building falling within exempted classes<br />
10, 13, 18, 19 or 20 of this Schedule ii. ancillary to or within the curtilage of a building<br />
of purpose group 1;<br />
iii within 1 metre of a boundary;<br />
iv containing sleeping accommodation or a combustion<br />
appliance which is subject to<br />
regulation 14;<br />
v. containing sanitary accommodation; or<br />
vi situated on land within the boundaries of which<br />
there are harmful or dangerous substances<br />
13 A wall or fence A wall exceeding 1.2 metres or<br />
a fence exceeding 2 metres in height<br />
Construction and development buildings<br />
14 A building used only by people engaged in the A building containing sleeping accommodation<br />
construction, demolition or repair of any building or<br />
structure during the course of that work<br />
15 A building used in connection with the letting or sale A building containing sleeping accommodation<br />
of any building under construction until such time as<br />
the letting or sale of all related buildings is completed<br />
Tanks, cables, sewers, drains etc<br />
16 Any tank, cable, sewer, drain or other pipe above or a. A drainage system, septic tank or private<br />
below ground sewage treatment plant, which is serving a<br />
building subject to regulation 24<br />
b. A tank which is subject to regulations 15 or 31<br />
c. A cable, conductor or apparatus which is subject<br />
to regulation 26<br />
(a) 1960 c.62.<br />
(b) 1897 c.38; section 73 was amended by the National Health Service (Scotland) Act 1972 (c.58),<br />
Schedule 6, paragraph 56.<br />
19A<br />
Amdt: September 2001<br />
A
A<br />
(1) (2) (3)<br />
Class Description Exceptions<br />
Temporary buildings<br />
17 A building erected on a site for a period not exceeding<br />
28 consecutive days or 60 days in any period of 12 months<br />
Buildings ancillary to dwellings<br />
18 A single-storey building ancillary to and within the A building -<br />
curtilage of a dwelling of purpose sub-group 1B or<br />
1C, comprising a garage, garden hut or store or i. exceeding 30 square metres in area;<br />
building for keeping animals, birds or other livestock<br />
for domestic purposes. ii. within 1 metre of the dwelling, unless it is at<br />
least 500 millimetres from any boundary;<br />
iii. containing a combustion appliance which is<br />
subject to regulation 14; or<br />
iv. situated on land within the boundaries of which<br />
there are harmful or dangerous substances<br />
19 Any other single-storey building ancillary to and A building -<br />
within the curtilage of a dwelling of purpose<br />
sub-group 1B or 1C, including a carport, covered area, i. exceeding 30 square metres in area;<br />
greenhouse, summer house or swimming pool enclosure<br />
ii. containing a combustion appliance which is<br />
subject to regulation 14; or<br />
iii. situated on land within the boundaries of which<br />
there are harmful or dangerous substances<br />
iv. containing sleeping or sanitary accommodation<br />
20 An underground or substantially underground A building -<br />
building within the curtilage of a dwelling of purpose<br />
sub-group 1B or 1C, the purpose of which is solely i. exceeding 30 square metres in area;<br />
to afford shelter or protection from the effects of<br />
weapons of war (whether nuclear, chemical or ii. the excavation for which is nearer to any exposed<br />
conventional) part of another building than a distance equal to<br />
the depth of the excavation plus 1 metre; or<br />
Amdt: September 2001<br />
20A<br />
iii. situated on land within the boundaries of which<br />
there are harmful or dangerous substances
(1) (2) (3)<br />
Class Description Exceptions<br />
PART II - BUILDINGS ATTACHED TO DWELLINGS OF PURPOSE SUB-GROUP 1B OR 1C<br />
21 A single-storey extension to an existing dwelling of A building -<br />
purpose sub-group 1B or 1C which is ancillary to the<br />
dwelling and consists of a conservatory or porch i. exceeding 30 square metres in area or, in the case<br />
which, insofar as it is glazed, complies with the of a conservatory or porch, 8 square metres;<br />
requirements of regulation 27(1)(b) or a greenhouse,<br />
carport or covered area ii. containing a flue or a combustion appliance which<br />
is subject to regulation 14;<br />
NOTES:<br />
iii. containing sanitary accommodation;<br />
iv (except in the case of a greenhouse, carport or<br />
covered area) within 1 metre of a boundary; or<br />
v. situated on land within the boundaries of which<br />
there are harmful or dangerous substances<br />
1. In the application of Part 1 of this Schedule no account shall be taken of an office use which is ancillary<br />
to the main purpose of the building.<br />
2. For the purpose of Class 17, an air-supported or otherwise collapsible building shall not be exempt solely<br />
on account of deflation or other form of intermittent collapse.<br />
21A<br />
Amdt: September 2001<br />
A
A<br />
REGULATION 4 SCHEDULE 2<br />
FIXTURES NOT REQUIRING A WARRANT<br />
(1) (2) (3)<br />
Class Description Exceptions<br />
1 A fixture or notice for which there is no requirement<br />
provided in these regulations<br />
2 An outdoor sign which is subject to the Town and<br />
Country Planning (Control of Advertisements)<br />
(Scotland) Regulations 1984 (a)<br />
3 A combustion appliance which is subject i. A solid fuel appliance with an output rating<br />
to regulation 14 more than 50 kW, or an oil or gas-fired appliance<br />
with a net input rating more than 70 kW<br />
ii. A chimney, flue-pipe or hearth, except a balanced<br />
flue as referred to in Category 4 below<br />
4 A balanced flue serving a room-sealed appliance A balanced flue which passes through a<br />
combustible wall<br />
5 A flue liner<br />
6 Provision of thermal insulating material to or within Application of thermal insulating material to the<br />
a wall, ceiling, roof or floor outer surface of an external wall<br />
7 Replacement of a fixture or appliance, in whole or in<br />
part, by another of the same general type as it is<br />
replacing, including a sanitary appliance or sink<br />
(together with any relevant branch soil or waste pipe),<br />
rainwater gutter or downpipe, combustion appliance,<br />
electrical fixture, ventilation fan, chimney or flue outlet<br />
fitting or terminal, fire hydrant or main, lift, escalator,<br />
solid waste chute or container, door or window<br />
7A Replacement, in whole or part, by material of the same<br />
general type as that which it is replacing, of lining,<br />
cladding, covering or rendering of an internal or<br />
external wall, ceiling or roof<br />
8 Replacement of a window by another which is not of the<br />
same general type as that which it is replacing<br />
(a) S.I . 1984/467<br />
Amdt: September 2001<br />
22A
REGULATION 4 SCHEDULE 2<br />
FIXTURES NOT REQUIRING A WARRANT<br />
(1) (2) (3)<br />
Class Description Exceptions<br />
9 Provision of a single sanitary facility, other than a<br />
watercloset or shower, or relocation within the same<br />
room or space of sanitary facilities (together with any<br />
relevant branch soil or waste pipe)<br />
10 Provision of a stairlift within a dwelling<br />
11 Refillable liquefied petroleum gas storage cylinders<br />
supplying, via a fixed pipework installation, combustion<br />
appliances used principally for providing space or water<br />
heating, or cooking facilities.<br />
NOTE:<br />
Notwithstanding the fact that the fixtures listed in this Schedule do not require a warrant, they shall, except<br />
where replacing with the same general type, in all respects and in the manner of their fitting meet any relevant<br />
requirements of these Regulations (see section 6(1) of the Act).<br />
23A<br />
Amdt: September 2001<br />
A
A<br />
SCHEDULE 3 REGULATION 6<br />
CLASSIFICATION OF BUILDINGS BY PURPOSE<br />
(1) (2) (3)<br />
Purpose Purpose Description of purpose or form of building<br />
group and sub-group,<br />
descriptive where<br />
title applicable<br />
1 Dwellings* 1A Flats and maisonettes<br />
1B Houses containing a habitable storey at a height exceeding 4.5 metres<br />
1C Houses not containing a habitable storey at a height exceeding 4.5 metres<br />
2 Institutional 2A Residential accommodation, other than dwellings, for old people or children<br />
and other or for the treatment, care or maintenance of persons suffering from illness or<br />
residential mental or physical disability or handicap<br />
2B Any other building, other than a dwelling, containing sleeping accommodation<br />
3 Offices Offices or premises used for office, administrative or clerical purposes<br />
(including writing, book-keeping, sorting papers, filing, typing, duplicating,<br />
machine calculating, police and fire service work, drawing and the editorial<br />
preparation of work for publication), financial transactions (including<br />
banking and building society work) and communications (including postal,<br />
telegraph and radio, television, film, audio or video recording or performance<br />
(not open to the public), communication or control)<br />
4 Shops and Shops or premises used for retail or wholesale trade or business, including<br />
Commercial sales by auction, self-selection and over-the-counter wholesale trading,<br />
hairdressing and beauty or body care and premises to which members of the<br />
public are invited to resort for the purpose of delivering or uplifting goods in<br />
connection with their cleaning, repair, hire or other treatment or (except in the<br />
case of the repair of motor vehicles) of themselves carrying out such cleaning,<br />
repair or other treatment.<br />
5 Assembly 5A Places of entertainment and recreation other than sports stadia, including bingo<br />
and halls, broadcasting, recording and film studios open to the public, casinos,<br />
recreational dance halls, entertainment, conference, exhibition and leisure centres (except<br />
where consisting predominantly of a swimming pool), funfairs and amusement<br />
arcades, licensed betting offices, non-residential clubs, public houses,<br />
restaurants, cafes, snack bars, theatres, cinemas and concert halls<br />
5B Any other places of assembly, including swimming pool buildings, churches<br />
and other places of worship, crematoria, dancing schools, educational<br />
establishments, gymnasia, law courts, libraries open to the public,<br />
non-residential day centres, clinics, health centres and surgeries, passenger<br />
stations and termini for air, rail, road or sea travel, public toilets, riding<br />
schools, ice rinks, sports pavilions, sports stadia, zoos and menageries,<br />
museums and art galleries<br />
* Includes any surgeries, consulting rooms, offices or other accommodation not exceeding in the aggregate<br />
50 square metres forming part of a dwelling and used by an occupant of the dwelling in a professional or<br />
business capacity.<br />
Amdt: September 2001<br />
24A
(1) (2) (3)<br />
Purpose Purpose Description of purpose or form of building<br />
group and sub-group,<br />
descriptive where<br />
title applicable<br />
6 Industrial 6A Manufacturing, processing, repairing, cleaning, washing, breaking up or<br />
otherwise treating any substance comprising or used in association with -<br />
adhesives<br />
asphalt and bituminous products<br />
chemical and allied industries<br />
cleaners and solvents<br />
clothing and footwear (excluding laundering)<br />
coal and petroleum products<br />
cork products<br />
dry cleaning<br />
dye-stuffs and pigments<br />
fertilisers<br />
grains and cereals<br />
inks<br />
insulated wires and cables<br />
leather, sheepskin and fur<br />
linoleum<br />
magnetic tape<br />
oils and greases<br />
paints<br />
paper, printing and publishing (excluding paper manufacturing)<br />
pharmaceutical products<br />
photographic materials and products<br />
plastics<br />
polishes<br />
rubber and synthetic rubber<br />
soaps and detergents<br />
spirit distilling<br />
surgical bandages and plasters<br />
synthetic resins<br />
textiles<br />
timber, joinery, furniture, brushes and brooms<br />
toilet preparations<br />
upholstery<br />
weedkillers and pesticides<br />
6B Any other industrial building including buildings used for generating or supplying<br />
power or slaughtering livestock<br />
25A<br />
Amdt: September 2001<br />
A
A<br />
(1) (2) (3)<br />
Purpose Purpose Description of purpose or form of building<br />
group and sub-group,<br />
descriptive where<br />
title applicable<br />
7 Storage and 7A Storage of hazardous goods or materials, and storage of vehicles containing<br />
warehousing** hazardous goods or materials, including –<br />
i. any compressed, liquefied or dissolved gas;<br />
ii. any substance which becomes dangerous by interaction with either<br />
water or air;<br />
iii. any liquid substance with a flash point below 65° Celsius including<br />
whisky or other spirituous liquor;<br />
iv. any corrosive substance<br />
v. any substance capable of emitting poisonous fumes;<br />
vi. any oxidising agent;<br />
vii. any substance liable to spontaneous combustion;<br />
viii. any substance that changes or decomposes readily giving out heat when<br />
doing so;<br />
ix. any combustible solid substance with a flash point less than 120° Celsius;<br />
x. any substance likely to spread fire by flowing from one part of a building<br />
to another<br />
7B Storage of any other goods or materials, and car parks and parking garages not<br />
coming within purpose sub-group 7A or 7C<br />
7C Open-sided*** car parks and parking garages, designed to admit or accommodate<br />
only passenger or light goods vehicles not exceeding 2500 kilograms<br />
gross mass<br />
** Warehousing excludes self-selection wholesale trading included in purpose group 4<br />
*** For the purpose of this description “open-sided” means naturally ventilated to provide an adequate supply<br />
of air in accordance with regulation 23.<br />
Amdt: September 2001<br />
26A
SCHEDULE 4 REGULATION 7<br />
OCCUPANCY LOAD FACTORS TO BE APPLIED TO ROOMS AND SPACES WITHOUT FIXED SEATING,<br />
OTHER THAN IN BUILDINGS OF PURPOSE GROUP 1<br />
(1) (2)<br />
Description of room or space Occupancy load factor<br />
Standing spectators’ area 0.3<br />
Amusement arcade, assembly hall (including a general-purpose place of assembly), 0.5<br />
bar (public area), bingo hall<br />
Concourse, dance hall or floor, queuing area, mall areas in enclosed shopping centres (Class A) 0.7<br />
Committee room, common room, conference room, dining room, licensed betting office 1.0<br />
(public area), lounge (other than a lounge bar), meeting room, reading room, restaurant,<br />
staff room, waiting room, food courts in enclosed shopping centres<br />
Exhibition hall 1.5<br />
Shop sales area (Class 1), mall areas in enclosed shopping centres (Class B) 2.0<br />
Shop sales area (Class 3) 4.0<br />
Art gallery, dormitory, factory production area, museum, workshop 5.0<br />
Office 6.0<br />
Kitchen, library, shop sales area (Class 2) 7.0<br />
Bedroom or study bedroom 8.0<br />
Bed-sitting room, billiards room 10.0<br />
Car park, storage and warehouse accommodation 30.0<br />
NOTES:<br />
1. For the purposes of this Schedule shop sales areas are classified thus –<br />
Class 1 – shop sales areas other than those listed below as Class 2, including supermarkets and department<br />
stores (all sales areas), shops for personal services such as hairdressing and shops for the delivery or<br />
uplift of goods for cleaning, repair or other treatment or for members of the public themselves carrying<br />
out such cleaning, repair or other treatment.<br />
Class 2 – shop sales areas in shops trading predominantly in furniture, floor coverings, cycles, perambulators,<br />
large domestic appliances or other bulky goods or trading on a wholesale self-selection basis.<br />
Class 3 – shop sales areas in shops within an enclosed shopping centre when calculating an aggregate<br />
occupancy for all shops in a centre - not to be used for individual shops.<br />
2. The descriptions arcade, hall, gallery and room used in the Schedule do not indicate a particular design or<br />
configuration of building.<br />
3. For the purposes of this Schedule mall areas in enclosed shopping areas are classified thus –<br />
Class A – up to 6 metres wide<br />
Class B – all areas beyond the 6 metres width in Class A.<br />
27A<br />
Amdt: September 2001<br />
A
A<br />
REGULATION 8 SCHEDULE 5<br />
RULES OF MEASUREMENT<br />
Area<br />
1 The area of -<br />
(a) a single-storey building for the purpose of regulation 3 shall be taken to be the total area, excluding<br />
any gallery or openwork floor;<br />
Cubic capacity<br />
(b) a storey shall be taken to be the total floor area of all floors within that storey, including the floor<br />
area of any gallery or openwork floor;<br />
(c) a room excludes any built-in fixture extending from the floor to the ceiling and in the case of a<br />
dwelling any part of the room where the height is less than 1.5 metres;<br />
(d) a compartment shall be taken to be the total floor area of all storeys within that compartment;<br />
(e) an enclosed shopping centre shall be taken to be the total floor area of all storeys.<br />
2 The cubic capacity of a building or compartment shall be taken to be the volume of the space contained<br />
by its enclosing walls, the upper surface of the floor of the lowest storey in the building or compartment,<br />
and the topmost ceiling in the building or compartment or, if the topmost storey has no ceiling, the internal<br />
surface of the roof.<br />
Height and depth<br />
3 The height of -<br />
(a) a building shall be taken to be the height from the surface of the ground to the underside of the<br />
ceiling of the topmost storey or, if the topmost storey has no ceiling, one half of the height of the<br />
roof above its lowest part;<br />
(b) a compartment shall be taken to be the height within the compartment from the upper surface of<br />
the floor of the lowest storey to the topmost ceiling or, if the topmost storey has no ceiling, the<br />
internal surface of the roof;<br />
3A The height of a storey above the ground or depth of a storey below the ground shall be taken to be the<br />
vertical height or depth as the case may be from the ground to the upper surface of the floor of the storey,<br />
and the expressions “a storey at a height” and “ a storey at a depth” shall be construed accordingly.<br />
4 In the measurement of height or depth from ground which is not level the height or depth shall be taken<br />
to be the mean height or depth, except that<br />
(a) for the purpose of Class 13 of Schedule 1; and<br />
General<br />
(b) for any other purpose where the difference in level is more than 2.5 metres,<br />
the height or depth shall be taken to be the greatest height or depth.<br />
5 Except where the context otherwise requires, measurements shall be horizontal or vertical.<br />
6 Measurements of area and cubic capacity shall be taken to the inner surfaces of enclosing walls or, on any<br />
side where there is no enclosing wall, to the outermost edge of the floor on that side.<br />
7 Any expression of gradient, slope or fall shall be taken to mean one unit of vertical measurement in a<br />
given number of such units of horizontal measurement.<br />
8 Except for the purpose of regulation 3, any measurements of parts of a building in different occupation<br />
shall be taken separately.<br />
28A
FITNESS OF MATERIALS<br />
AND WORKMANSHIPB
Contents<br />
INTRODUCTION<br />
REGULATION 10<br />
Fitness of materials and workmanship<br />
THE STANDARDS<br />
B1 Application of Part B B1.1 - B1.2<br />
B2 Selection and use of materials,<br />
fittings, and components,<br />
and workmanship B2.1 - B2.2<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(B2.1), (B2.2) Selection and use of materials, fittings<br />
and components, and workmanship<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A, General.<br />
3B<br />
Amdt: September 2001<br />
B
Amdt: September 2001 4B
Introduction<br />
1. The intention of this Part is to ensure that materials, fittings, and components<br />
used in the construction of buildings, to the extent that they are<br />
subject to the Regulations or where they are used to meet a requirement<br />
of the regulations, are suitable for their purpose, are correctly used<br />
or applied and are sufficiently durable, taking account of normal maintenance<br />
practices, to ensure the health and safety of people.<br />
2. The requirements of this Part are deemed to be satisfied by reference<br />
to the named standards specified in the <strong>Technical</strong> <strong>Standards</strong> or by reference,<br />
among other things, to any national or international standards, or to<br />
any specification, recognised by Member States within the European Economic<br />
Area (see Note below), which provides an equivalent standard of<br />
safety, suitability and fitness, or by reference to traditional procedures of<br />
manufacture of any such Member State which are supported by an adequate<br />
technical description.<br />
3. The intention is to provide for adequate flexibility to accommodate<br />
new techniques as well as proven traditional practices and to ensure the<br />
proper acceptance of products which satisfy the essential requirements of<br />
the Construction Products Directive (CPD) (89/106/EEC), as amended by<br />
the CE Marking Directive (93/68/EEC), and the Fixing and Use of CE<br />
Marks Directive (93/465/EEC); and to avoid barriers to trade. This means,<br />
for instance, that products bearing a CE (European Community mark of<br />
conformity) mark must be accepted as complying where they are correctly<br />
used. A building control officer may only reject products bearing a CE<br />
mark if he/she suspects non-compliance with a technical standard, or if the<br />
accompanying documentation is incomplete. If the building control officer<br />
does not accept the product he/she must notify the trading standards<br />
officer. This will enable the UK <strong>Government</strong>, where necessary, to notify<br />
the Commission that they are prohibiting the placing on the market of the<br />
product in question or making it subject to special conditions.<br />
The correct use of materials, deemed to satisfy the Part B standards,<br />
demonstrates compliance with appropriate standards throughout the <strong>Technical</strong><br />
<strong>Standards</strong>.<br />
4. In relation to a specific purpose of a material, fitting, or component,<br />
compliance with the requirements of an EC Directive is recognised as<br />
compliance with the requirements of the regulation that relates to that<br />
purpose. This means for example that a self-contained smoke alarm, manufactured<br />
in accordance with Council Directive 89/336/EEC (Electro magnetic<br />
compatibility), shall be deemed to satisfy the requirements of the<br />
appropriate regulation insofar as it relates to the prevention of electromagnetic<br />
disturbances by and protection against disturbances to such smoke<br />
alarms. Similarly a self-contained smoke alarm manufactured in accordance<br />
with Council Directive 73/23/EEC (Electric equipment designed for<br />
use with in certain voltage limits) (where it applies) shall be deemed to<br />
satisfy the requirements of the regulations insofar as it relates to the safety<br />
of persons on the use of such a smoke alarm. Furthermore, self-contained<br />
smoke alarms must in all cases be manufactured and placed on the market<br />
in accordance with Council Directive 73/23/EEC relating to the safety of<br />
electrical appliances, and according to which the conformity with standards-national,<br />
international or others is not mandatory unless the smoke<br />
alarm is being considered for use in a building where it is necessary to<br />
comply with the Building <strong>Standards</strong> (Scotland) Regulations 1990, as<br />
amended.<br />
5B<br />
Amdt: September 2001<br />
B
B<br />
5. The EC is introducing durability requirements into<br />
EN’s. Durability is not a term defined in the <strong>Technical</strong><br />
<strong>Standards</strong> however it has been defined by the European<br />
Commission as: the ability of a building material, fitting,<br />
component, or part thereof to perform its required function<br />
over a period of time and under the influence of agents.<br />
Agents/factors that may affect the durability of a product<br />
include: exposure conditions, temperature, humidity,<br />
water, UV radiation, abrasion, chemical attack, biological<br />
attack, corrosion, weathering, frost, freeze-thaw, and<br />
fatigue.<br />
Subject to normal maintenance, a product should enable a<br />
properly designed and executed works to fulfil the Essential<br />
Requirements for an economically reasonable period<br />
of time (i.e. the working life of the product).<br />
Durability is thus dependent on the intended use of the<br />
product and its service conditions. The assessment of<br />
durability can relate to the product as a whole or to its performance<br />
characteristics, insofar as these play a significant<br />
part with respect to the fulfilment of the Essential<br />
Requirements. In either case, the underlying assumption is<br />
that the performance will meet or exceed minimum<br />
acceptable values (thresholds) throughout its working life.<br />
The assessment of durability of construction products may<br />
be assessed using performance-based methods, descriptive<br />
solutions or a combination of both.<br />
Levels of durability can in theory be set only by reference<br />
to criteria laid down in the harmonised test procedures. At<br />
present most harmonised standards are prescriptive, giving<br />
for example a minimum thickness of material rather than<br />
a level of performance, e.g. that the product must last say<br />
at least X number of years. The EC still have the issue<br />
under consideration and it is likely that in future there will<br />
be a move towards performance standards.<br />
In the mean time until the EU Commission have prepared<br />
and issued guidance on this subject, for building reference<br />
can be made to BS 7543: 1998, which covers the durability<br />
of building elements, products and components.<br />
6. The term ‘workmanship’ has been included so that<br />
references to methods of establishing workmanship (BS<br />
8000) can be included in the Deemed to Satisfy (DTS) to<br />
assist building control officers, designers, and contractors.<br />
For example where suitability depends on the construction<br />
being carried out with adequate workmanship, say in the<br />
sound proofing of separating walls, it will prove useful to<br />
consider the aids to establishing workmanship listed in the<br />
DTS. It is not the intention that building control officers<br />
should take on the responsibility for aesthetic issues in<br />
buildings (such as rough plasterwork), but to provide<br />
assistance with issues of workmanship related solely to the<br />
matters covered by the <strong>Technical</strong> <strong>Standards</strong> which are<br />
already enforced by building control.<br />
Note:<br />
The European Economic Area Agreement is given effect<br />
in this country by the European Economic Area Act 1993<br />
and entered into force on 1 January 1994.<br />
Amdt: September 2001<br />
6B<br />
Regulation 10<br />
FITNESS OF MATERIALS AND WORKMANSHIP<br />
10. Construction to meet a requirement of these<br />
regulations must be carried out in a technically<br />
proper and workmanlike manner, and the<br />
materials used must be durable, and fit for their<br />
intended purpose.
The standards<br />
B1 Application of Part B<br />
B1.1 This Part sets out the required standards for Regulation 10.<br />
B1.2 The standards apply to all buildings, but only to those materials, fittings, and components, which are<br />
subject to a particular requirement of these Regulations.<br />
B2 Selection and use of materials, fittings, and components, and<br />
workmanship<br />
B2.1 * In a building, the materials, fittings, and components must be constructed in a technically proper and<br />
workmanlike manner.<br />
B2.2 * In a building, the materials, fittings and components used must be suitably durable and fit for their<br />
intended use and, where suitability depends on proper maintenance or periodic renewal, must be readily<br />
accessible so that replacement is reasonably practicable.<br />
7B<br />
B1.1 – B2.2<br />
Amdt: September 2001<br />
B
Amdt: September 2001 8B
Provisions deemed to satisfy the standards<br />
SELECTION AND USE OF MATERIALS, FITTINGS, AND COMPONENTS, AND WORKMANSHIP<br />
(B2.1)<br />
Some methods of establishing workmanship are:<br />
(B2.2)<br />
a. Compliance with BS 8000: Workmanship on building sites, or<br />
b. Compliance with a equivalent technical specification which may include a national technical<br />
specification of other Member States, which are contracting parties to the European Economic<br />
Area, or<br />
c. The workmanship is specified for a material, fitting, or component, covered by a national or<br />
European certificate issued by a European <strong>Technical</strong> Approvals issuing body, and the conditions<br />
of use are in accordance with the terms of the certificate, or<br />
d. The workmanship may be covered by an equivalent technical approval (including a technical<br />
approval of another Member State of the European Organisation for <strong>Technical</strong> Approvals,<br />
EOTA), that provides an equivalent level of performance and the conditions of use are in accordance<br />
with the terms of the technical approval, or<br />
e. The workmanship is covered by a scheme, which complies with the relevant recommendations of<br />
BS EN ISO 9000: Quality management and quality assurance standards. There are also independent<br />
schemes for accreditation and registration of installers of materials and products that provide<br />
a means of ensuring that the work has been carried out by knowledgeable contractors to an<br />
appropriate standard e.g. Council of Registered Gas Installers (CORGI), or<br />
f. By use of past experience. Where it can be shown by experience, such as a building in use, that<br />
the method of workmanship is capable of performing the function for which it is intended, or<br />
g. By use of recognised test methods.<br />
1 Subject to paragraph 2 below the requirements of B2.2 will be met where materials, fittings, and components,<br />
or parts thereof comply with any of the following standards:<br />
a. the standard (whether British Standard or otherwise) specified in the <strong>Technical</strong> <strong>Standards</strong>, either<br />
in a relevant standard or a deemed to satisfy provision;<br />
b. a relevant standard or code of practice of a national standards institution or equivalent body of<br />
any Member State within the European Economic Area;<br />
c. a relevant international standard recognised in any Member State within the European Economic<br />
Area;<br />
d. a relevant specification acknowledged for use as a standard by a public authority of any Member<br />
State within the European Economic Area;<br />
e. traditional procedures of manufacture of a Member State within the European Economic Area<br />
where these are the subject of a written technical description sufficiently detailed to permit<br />
assessment of the materials, fittings, and components, or parts thereof for the use specified; or<br />
9B<br />
(B2.1) – (B2.2)<br />
Amdt: September 2001<br />
B
B<br />
(B2.2)<br />
Amdt: September 2001<br />
f. for materials, fittings, and components, or parts thereof, of an innovative nature or subject<br />
to an innovative process of manufacture and which fulfil the purpose provided for by the<br />
specified standard -<br />
i. a European <strong>Technical</strong> Approval issued in accordance with the Construction Products<br />
Directive (CPD) (89/106/EEC) as amended by (93/68/EEC) and (93/465/EEC); or<br />
ii. a specification sufficiently detailed to permit assessment.<br />
2 The standard, code of practice, specification, technical description or European <strong>Technical</strong><br />
Approval referred to in paragraph 1b to f must provide in use levels of safety, suitability and<br />
fitness for purposes equivalent to those required by the specified standard referred to in paragraph<br />
1a insofar as such levels are not inconsistent with the Essential Requirements set out in terms of<br />
objectives in Annex 1 to the Construction Products Directive (89/106/EEC), as amended by the<br />
CE Marking Directive (93/68/EEC), and the Fitting and Use of CE Marks Directive<br />
(93/465/EEC).<br />
3 Where materials, fittings, and components, are used on the basis of a standard, code of practice,<br />
specification, technical description or European <strong>Technical</strong> Approval referred to in paragraph 1,<br />
testing and sampling may be carried out as specified in or applicable to such standard, code of<br />
practice, specification, technical description or European <strong>Technical</strong> Approval.<br />
4 Where testing is carried out in a Member State within the European Economic Area, such tests<br />
shall be carried out by an appropriate organisation offering suitable and satisfactory evidence of<br />
technical and professional competence and independence. The requirements shall be satisfied if<br />
the organisation is accredited in a State within the European Economic Area in accordance with<br />
BS 7501 and BS 7502: 1989, and/or BS EN’S: 17025, 45002, 45003, 45004, 45011, 45012,<br />
45013, and 45014.<br />
10B
STRUCTUREC
Contents<br />
INTRODUCTION<br />
REGULATION 11<br />
Structure<br />
THE STANDARDS<br />
C1 Application of Part C C1.1-C1.3<br />
C2 Structure<br />
Stability C2.1<br />
C3 Disproportionate collapse C3.1<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(C2.1) Loadings, construction, and small buildings<br />
(C3.1) Disproportionate collapse<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A General.<br />
3C<br />
Amdt: December 1999<br />
C
5C<br />
Introduction<br />
1. The intention of this Part is to ensure that the structure of<br />
a building is safe. The safety of a structure depends on<br />
several factors and the following criteria are relevant in all<br />
cases -<br />
a. loading;<br />
b. properties of materials;<br />
c. structural analysis;<br />
d. details of construction;<br />
e. safety factors;<br />
f. workmanship; and<br />
g. the nature of the ground.<br />
2. Where approaches to construction other than those given<br />
in the deemed-to-satisfy provisions are adopted then the criteria<br />
given above in paragraph 1 are particularly relevant,<br />
especially in relation to any numerical values of safety<br />
factors. A change in any one of these criteria may disturb the<br />
stability of the structure.<br />
3. Loads used in calculations must allow for possible<br />
dynamic, concentrated and peak load effects that may occur.<br />
EUROPEAN PRE-STANDARDS (ENV)<br />
4. The British <strong>Standards</strong> Institution has published, for trial<br />
use by designers, most of the ENV Structural Eurocodes prepared<br />
by the European <strong>Standards</strong> Organisation (CEN). Each<br />
of these pre-standards are prefaced with a National Application<br />
Document (NAD) which renders the standards suitable<br />
for use in the UK. The practical experience gained in these<br />
trials is providing valuable feed back to the CEN project<br />
teams responsible for the conversion of the ENV pre-standards<br />
into full EN standards.<br />
5. When the ENV Eurocodes are eventually published as<br />
EN’s they will be referenced in the deemed-to-satisfy provisions<br />
in Part C. In the mean time, the BSI pre-standards may<br />
be used as an alternative approach for satisfying the relevant<br />
standards in Part C. There will be a period of transition<br />
during which time Eurocodes and national standards will be<br />
allowed to co-exist. This period of co-existence has yet to be<br />
determined, but upon its expiry the corresponding national<br />
standards will be withdrawn by BSI.<br />
Amdt: December 1999<br />
C
C<br />
Regulation 11<br />
STRUCTURE<br />
11 (1) Every building shall be so designed and constructed<br />
that the combined loads to which the<br />
building may be subject are sustained and<br />
transmitted to the ground without impairing<br />
the stability of the building.<br />
(2) Subject to paragraph (3), every building of<br />
five or more storeys shall be so designed and<br />
constructed that in the event of damage occurring<br />
to any part of the structure of the building<br />
the extent of any resultant collapse will not be<br />
disproportionate to the cause of the damage.<br />
(3) In calculating the number of storeys for the<br />
purpose of paragraph (2), no account shall<br />
be taken of any storey within a roof space<br />
where the slope of the roof does not exceed<br />
70 degrees to the horizontal.<br />
Amdt: December 1999<br />
6C
The standards<br />
C1 Application of Part C<br />
C1.1 This Part sets out the required standards for Regulation 11.<br />
C1.2 Standard C2.1 applies to all buildings.<br />
C1.3 Standard C3.1 applies to buildings of any purpose group, having five or more storeys, counting each<br />
basement storey as one storey but discounting a storey within a roof space where the slope of the roof<br />
is not more than 70 degrees to the horizontal.<br />
C2 Structure<br />
STABILITY<br />
C2.1* A building must be designed and constructed so that, taking into account the nature of the ground the<br />
combined dead loads, imposed loads, and wind loads are sustained, and transmitted to the ground,<br />
without impairing the safety of any part of the building or causing such movement of the ground as will<br />
impair the stability of any part of the building.<br />
C3 Disproportionate collapse<br />
DISPROPORTIONATE COLLAPSE<br />
C3.1* A building to which this standard applies must be designed and constructed so that in the event of<br />
damage occurring to any part of the building, the extent of any resulting collapse will not be disproportionate<br />
to the cause of the damage.<br />
7C<br />
C1.1 – C3.1<br />
Amdt: December 1999<br />
C
Provisions deemed to satisfy the standards<br />
STABILITY<br />
(C2.1)<br />
a. loadings:<br />
b. construction:<br />
The requirements of C2.1 as regards loading will be met where the loads to which the building<br />
will be subjected are calculated in accordance with -<br />
i. for dead loads and imposed loads (excluding roof loads), BS6399: Part 1: 1996;<br />
ii. for imposed roof loads, BS6399: Part 3: 1988;<br />
iii. for wind loads -<br />
A. BS6399: Part 2: 1997, or<br />
B CP 3: Chapter V :Part 2: 1972 (in no case shall S3 be taken as less than 1);<br />
iv. for loading of any building for agriculture, BS5502: Part 22: 1993;<br />
v. any greater load to which the building is likely to be subjected.<br />
The requirements of C2.1 as regards design and construction will be met where the work is<br />
carried out in accordance with -<br />
i. for foundations, BS 8004: 1986;<br />
ii. for structural work of reinforced, prestressed or plain concrete, BS 8110: Part 1: 1997,<br />
BS8110: Part 2 and Part 3: 1985;<br />
iii. for structural work of steel -<br />
A. BS449: Part 2: 1969, or<br />
B. BS 5950: Part 1: 1990, BS5950: Part 2: 1992, BS5950: Part 5: 1987, BS5950:<br />
Part 6: 1995, BS5950: Part 7: 1992, BS5950: Part 8: 1990;<br />
iv. for structural work of composite steel and concrete construction, Section 3.1 of<br />
BS5950: Part 3:1990, and BS 5950: Part 4: 1994;<br />
v. for structural work of aluminium, BS8118: Parts 1 and 2: 1991; for the purpose of<br />
section 7.2 of Part 1 of that code, the structure must be classified as a safe-life structure;<br />
vi. for structural work of masonry, BS5628: Part 1: 1992, BS 5628: Part 2: 1995, and<br />
BS5628: Part 3: 1985;<br />
vii. for structural work of timber, BS5268: Part 2: 1996, BS5268: Part 3: 1998, and section<br />
6:1 of BS5268: Part 6: 1996;<br />
viii. for structural design of low rise buildings, BS8103: Part 1: 1995, BS8103: Part 2: 1996,<br />
BS8103: Part 3: 1996, and BS8103: Part 4: 1995; or<br />
9C<br />
(C2.1)<br />
Amdt: December 1999<br />
C
C<br />
(C2.1 – C3.1)<br />
c. small buildings:<br />
Where a building is -<br />
i. of purpose group 1 and not more than 3 storeys; or<br />
ii. an annex, of not more than 3 metres high, to a building of purpose group 1, including a garage or<br />
outbuilding; or<br />
iii. a single storey, non- residential building of any other purpose group,<br />
the requirements of C2.1 will be met by a structure constructed in accordance with the ‘Small Buildings<br />
Guide’ (1994 Edition) published by The Stationery Office.<br />
DISPROPORTIONATE COLLAPSE<br />
(C3.1) The requirements of C3.1 will be met where the structure of the building, having five or more<br />
storeys, is constructed, taking into account the recommendations on ties and on the effect of<br />
misuse or accident, in accordance with -<br />
Note:<br />
a. for structural work of reinforced, prestressed or plain concrete, BS8110: Part 1: 1997<br />
and BS8110: Part 2: 1985; or<br />
b. for structural work of steel, BS5950: Part 1: 1990 (the accidental loading referred to in<br />
clause 2.4.5.5 shall be chosen having particular regard to the importance of the key<br />
elements and the consequences of failure, and the key element shall always be capable<br />
of withstanding a load of at least 34 kn/m 2 applied from any direction); or<br />
c. for structural work of masonry, BS5628: Part 1: 1992, and BS5628 Part 2: 1995.<br />
When applying the recommendations given in the British <strong>Standards</strong> mentioned in C3.1 a, b, and c above the<br />
area of the structure at risk of collapse within the storey and within the immediate adjacent storeys must be<br />
restricted to the lesser of -<br />
i. 70 square metres of each of, the storey, the adjoining storey above and adjoining storey below, or<br />
ii. 15% of the area of each of, the storey, the adjoining storey above and adjoining storey below.<br />
Amdt: December 1999<br />
10C
STRUCTURAL FIRE<br />
PRECAUTIONSD
Contents<br />
INTRODUCTION<br />
REGULATION 12<br />
Structural fire precautions<br />
The <strong>Standards</strong> 1997+<br />
Equivalent<br />
D1 Application of Part D D1.1-D1.3 D1.1, D1.2<br />
D2 Structural protection<br />
Principles D2.1-D2.2 D2.1<br />
Non-combustible materials D2.3 D2.2<br />
D3 Compartmentation<br />
Principles D3.1-D3.2 D3.2<br />
Basements D3.3-D3.4 D3.2<br />
Buildings of purpose group 2 D3.5 No equivalent<br />
Buildings of purpose group 4 D3.6-D3.7 D3.2, D7.5<br />
Places of special fire risk D3.8-D3.9 D3.10, D3.11<br />
Fire-fighting shafts D3.10 D2.1<br />
Smoke venting shafts D3.11 D2.1<br />
Lifts D3.12-D3.13 D3.9<br />
Openings D3.14 D3.6<br />
Junctions D3.15-D3.17 D3.5<br />
D4 Sub-compartmentation<br />
Buildings of purpose sub-group 2A D4.1-D4.3 No equivalent<br />
Hospitals D4.4-D4.5 No equivalent<br />
Buildings of purpose sub-group 2B D4.6 No equivalent<br />
Openings D4.7 No equivalent<br />
Junctions D4.8 No equivalent<br />
D5 Separating walls and separating floors<br />
Principles D5.1 D3.1<br />
Buildings of purpose group 1 D5.2 D3.8<br />
Hospitals D5.3-D5.4 No equivalent<br />
Enclosed shopping centres with malls D5.5 D7.3, D7.4<br />
Non-combustible materials D5.6-D5.7 D2.2<br />
Openings D5.8 D3.6<br />
Junctions D5.9-D5.11 D3.5, D5.3<br />
D6 Concealed Spaces<br />
Principles D6.1-D6.4 D4.1<br />
Rainscreen cladding D6.5 D4.2<br />
Ceilings instead of cavity barriers D6.6 D4.1<br />
Openings D6.7 D4.1<br />
Junctions D6.8-D6.10 D4.1<br />
D7 Fire spread on internal linings<br />
Principles D7.1-D7.2 E6.1<br />
Sandwich panels D7.3-D7.4 No equivalent<br />
3D<br />
Amdt: September 2001<br />
D
D<br />
Amdt: September 2001<br />
D8 Fire spread to adjoining buildings<br />
Principles D8.1 D6.3<br />
Non-combustible materials D8.2 D2.2<br />
Two or more buildings on land in<br />
the same occupation D8.3 D8.3<br />
D9 Fire spread from adjoining buildings D9.1 D6.7<br />
D10 Fire spread on the external wall<br />
Principles D10.1-D10.2 D4.2, D6.8<br />
Buildings of sub-purpose group 2A D10.3 No equivalent<br />
D11 Escape route protection<br />
Protected zones D11.1 No equivalent<br />
Protected lobbies D11.2 No equivalent<br />
Protected enclosures D11.3 D3.4<br />
Corridor divisions D11.4 D2.1<br />
Enclosing rooms in escape stairs D11.5 E4.7<br />
Galleries D11.6 E7.1<br />
External walls D11.7-D11.10 E4.6, E4.12<br />
Escape over flat roofs D11.11 E3.2<br />
Non-combustible materials D11.12 D2.2<br />
Auditoria D11.13-D11.15 E8.20, E8.21<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(D1.3) Level of fire safety performance<br />
Resistance to fire<br />
Reaction to fire<br />
(D2.1)(D5.1)(D5.3)(D8.1) Fire control system<br />
(D3.6)(D3.7) Smoke and heat exhaust ventilation systems<br />
(D3.8) Paint spray booths<br />
(D3.14)<br />
(D3.14)(D4.7)(D5.8)(D6.7)(D11.1)<br />
Activation of shutters sealing compartment floors<br />
(D11.2)(D11.3)(D11.4)(D11.5) Self-closing fire doors<br />
(D3.14)(D4.7)(D5.8)(D6.7) Service openings<br />
(D3.14)(D4.7)(D5.8)(D6.7)(D6.9) Fire-stopping<br />
(D3.16)(D5.10) Junctions between compartment walls or separating<br />
walls and roofs<br />
(D7.1) and (D7.2) Fire spread on internal linings<br />
(D7.4) Sandwich panels<br />
(D8.1) Calculation of unprotected area<br />
(D9.1) Fire safety of roofs and rooflights<br />
(D10.1) Test for the fire safety performance of external<br />
cladding systems<br />
(D11.13) Safety curtains<br />
(D11.14) Ventilation system<br />
(D11.15) Smoke outlet<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A, General.<br />
+ As amended December 1999.<br />
4D
Introduction<br />
1. The intention of this Part is to ensure that the structure of a building,<br />
and the parts of a building, will remain stable in the event of fire, will<br />
restrict the spread of fire and smoke within the building and the spread of<br />
fire to other buildings.<br />
2. During a fire the elements of structure must continue to function, and<br />
remain capable of supporting and retaining any necessary protection of<br />
escape routes and fire access routes for an adequate period of time.<br />
3. To restrict the internal spread of fire, a building may have to be divided<br />
into compartments separated from each other by compartment walls or<br />
compartment floors intended to provide a complete barrier to fire between<br />
the compartments. In practice, the continuity of such walls and floors will<br />
have to be breached by openings for circulation or services and where this<br />
occurs special precautions are necessary to maintain the effectiveness of<br />
the barrier. The acceptable size of a compartment for this purpose is determined<br />
by its likely fire load which is, in turn, influenced by the purpose<br />
group of the building, or part of the building, in which it is situated and the<br />
provision, or otherwise, of active fire protection measures.<br />
4. To assist in the safe horizontal evacuation of residents in hospitals, residential<br />
care homes, and similar buildings there is a requirement for buildings<br />
in purpose sub-group 2A to be additionally divided into<br />
sub-compartments. By providing such a series of barriers it is intended<br />
that patients or residents will be able to remain longer in the building and<br />
avoid evacuation down stairs or to the outside.<br />
5. In order to limit the rapid spread of fire, standards are imposed on<br />
certain materials in terms of their reaction to fire.<br />
6. In order to reduce the danger to the occupants of other buildings, suitable<br />
separation must be provided between one building and another by<br />
either structure or distance. The acceptable distance between a building<br />
and its relevant boundary is dictated by the amount of heat that is likely to<br />
be radiated in the event of fire. This will be influenced by the extent of<br />
openings, or other unprotected areas, in the wall and the likely fire load of<br />
the building. Provision is also made to reduce the likelihood of fire spreading<br />
to roofs from an external source, and fire spreading up the elevations<br />
of a building.<br />
7. <strong>Standards</strong> are included which make specific provision for the fire<br />
safety of hospitals. However within the <strong>Technical</strong> <strong>Standards</strong> it is not possible<br />
to cover all aspects of fire safety relevant to hospitals. Fire safety is<br />
also dependent upon the way a building is furnished, staffed and managed.<br />
Designers of hospitals and other healthcare buildings will need to make<br />
reference to the full suite of documents that comprise “NHS in Scotland<br />
Firecode”.<br />
8. In order to permit the use of building materials tested either to British<br />
<strong>Standards</strong> or to European harmonised fire tests the “Deemed to Satisfy<br />
Provisions” provide alternative specifications which are equally acceptable.<br />
5D<br />
Amdt: September 2001<br />
D
D<br />
Regulation 12<br />
STRUCTURAL FIRE PRECAUTIONS<br />
12.(1) Every building shall be so constructed that, for<br />
a reasonable period, in the event of fire -<br />
(a) its stability is maintained;<br />
(b) the spread of fire and smoke within the<br />
building is inhibited; and<br />
(c) the spread of fire to and from other<br />
buildings is inhibited.<br />
(2) This regulation shall not be subject to specification<br />
in a notice served under section 11 of<br />
the Act.<br />
Amdt: September 2001<br />
6D
The <strong>Standards</strong><br />
D1 Application of Part D<br />
D1.1 This Part sets out the required standards for Regulation 12.<br />
D1.2 The <strong>Standards</strong> apply to all buildings, unless specified otherwise.<br />
7D<br />
D1.1 – D2.2<br />
D1.3* The level of fire safety performance of a building element or component is specified in terms of its -<br />
a. resistance to fire; and<br />
b. reaction to fire.<br />
Note: Alternative “Deemed to Satisfy Provisions” are provided for D1.3 setting out methods of<br />
establishing levels of fire safety performance in terms of either fire tests specified in British<br />
<strong>Standards</strong> or European harmonised fire tests.<br />
D2 Structural protection<br />
PRINCIPLES<br />
D2.1* In order to enable the occupants of a building to reach a place of safety and to ensure that fire-fighters<br />
engaged in rescue or fire-fighting operations are not placed at undue risk, the elements of structure in a<br />
building must have a level of fire safety performance (see D1.3) which meets the requirements of Table<br />
1 or Table 2 to this standard,<br />
except -<br />
a. an element of structure in a single storey building which does not form part of, or support, a separating<br />
wall, compartment wall, or the enclosing structure of a protected zone;<br />
b. a floor consisting of removable panels situated directly above a floor which is an element of structure;<br />
c. a gallery floor;<br />
d. an openwork floor;<br />
e. a catwalk;<br />
f. the lowest floor of a building.<br />
Note: Table 1 to D2.1 must be used for a single storey building, or the single storey part of a multistorey<br />
building where the single storey part is a separate compartment or compartments.<br />
Table 2 to D2.1 must be used for all other buildings.<br />
D2.2 Where an element of structure provides support to another element of structure, a compartment wall, a<br />
compartment floor, a separating wall, a separating floor, the enclosing structure of a protected zone, a<br />
flat roof, an access deck or an external wall, to which a higher standard applies, the element of structure<br />
must meet that higher standard.<br />
Amdt: September 2001<br />
D
D<br />
D2.3<br />
NON-COMBUSTIBLE MATERIALS<br />
D2.3 Where an element of structure provides support to a separating floor (see D5.6), a separating wall (see<br />
D5.7), an external wall (see D8.2), or an escape stair (including the floor of a protected lobby) (see<br />
D11.12) which is required to be of materials which are non-combustible, the element of structure must<br />
also be of materials which are non-combustible (see D1.3).<br />
Table 1 to D2.1: Minimum duration and maximum compartment area in a single storey building<br />
Purpose groups and purpose sub-groups Maximum area of a Minimum duration of Minimum<br />
compartment (m2 ) compartmentation, duration of<br />
[1] where required external walls<br />
(see D3.1) (see D8.1)<br />
1 Dwellings Unlimited Not required Medium [2, 3]<br />
2A Institutional 1,500 Medium Medium [3]<br />
2B Other residential 2,000 Medium Medium [3]<br />
3 Offices 4,000 Medium Medium [3]<br />
4 Shops and commercial 2,000 [4] Long Medium [5]<br />
5A Assembly and recreational (high risk) 2,000 Medium Medium [5]<br />
5B Assembly and recreational (low risk) 6,000 Long Medium [3]<br />
6A Industrial (high risk) 33,000 Long Medium [5]<br />
6B Industrial (low risk) 93,000 Long Medium [3]<br />
7A Storage (high risk) 1,000 Long [6] Medium [5]<br />
7B Storage (low risk) 14,000 Long Medium [5]<br />
7C Open-sided car park Unlimited Not required Not required<br />
Notes:<br />
1. In a building of purpose groups 3 and 5-7 areas can be doubled where there is an appropriate fire<br />
control system.<br />
2. Short duration for -<br />
a. a dwelling with an appropriate fire control system;<br />
b. a detached building ancillary to a dwelling comprising a garden hut or store, or a building for<br />
keeping animals, birds or other livestock for domestic purposes;<br />
c. a conservatory or porch attached to a dwelling;<br />
d. a garage wall.<br />
3. Short duration for a building more than 1 m from the boundary.<br />
4. Unlimited provided there is an appropriate fire control system.<br />
5. Short duration for a building more than 1 m from the boundary which has an appropriate fire<br />
control system.<br />
6. A building comprising a single compartment of not more than 1000 m 2 is permitted. Where a<br />
building has a floor area more than this, it must be divided into a series of compartments so that no<br />
compartment is more than 200 m 2 if the compartment walls have a medium duration, or 500m 2 if<br />
the compartment walls have a long duration.<br />
Amdt: September 2001<br />
8D
Table 2 to D2.1: Minimum duration and maximum compartment area in a building other than a single<br />
storey<br />
Purpose Maximum Maximum Duration of Duration of Duration of elements of structure,<br />
groups and area of a area of an external elements of and where appropriate<br />
purpose compart- individual walls structure, compartmentation (see D3.1)<br />
sub-groups ment storey (see D8.1) and where The The The<br />
(m2 ) [1] Within a appropriate topmost topmost topmost<br />
compart- compart- storey of a storey of a storey of<br />
ment (m2 ) mentation building is building is a building<br />
[1] (see D3.1) at a height at a height is at a<br />
in a of not more of not more height of<br />
basement than 7.5 m than 18 m more than<br />
above above 18m above<br />
ground ground ground<br />
1 Dwellings Unlimited Unlimited Medium [2] Medium Short Medium Long<br />
2A Institutional 1,500 1,500 Medium Medium Medium Medium Long [3]<br />
2B Other 1,000 1,000 Medium [2] Medium Short Medium Long [3]<br />
residential 2,000 2,000 Medium Medium Medium Medium Long [3]<br />
4,000 2,000 Medium Medium Long Long Long<br />
3 Offices 2,000 2,000 Medium [2] Medium Short Medium Long [3]<br />
4,000 4,000 Medium Medium Medium Medium Long [3]<br />
8,000 4,000 Medium Medium Long Long Long<br />
4 Shops and 500 [4] 500 [4] Medium [3] Medium Short Medium Long [3]<br />
commercial 1,000 [5] 1,000 [5] Medium Medium Medium Medium Long [3]<br />
2,000 [6] 1,000 [6] Medium Medium Long Long Long<br />
5A Assembly & 1,000 1,000 Medium [2] Medium Short Medium Long [3]<br />
recreational 2,000 2,000 Medium Medium Medium Medium Long [3]<br />
(high risk) 4,000 2,000 Medium Medium Long Long Long<br />
5B Assembly & 1,500 1,500 Medium [2] Medium Short Medium Long [3]<br />
recreational 3,000 3,000 Medium Medium Medium Medium Long [3]<br />
(low risk) 6,000 3,000 Medium Medium Long Long Long<br />
6A Industrial 500 500 Medium Medium Medium Medium Long [3]<br />
(high risk) 6,000 3,000 Medium Medium Long Long Long<br />
6B Industrial 2,000 2,000 Medium Medium Medium Medium Medium<br />
(low risk) 15,000 7,500 Medium Medium Long Long Long<br />
7A Storage 200 200 Medium Medium Medium Medium Long [3]<br />
(high risk) 1,000 500 Medium Medium Long Long Long<br />
7B Storage 500 500 Medium Medium Medium Medium Medium<br />
(low risk) 5,000 2,500 Medium Medium Long Long Long<br />
7C Open-sided<br />
car park<br />
Unlimited Unlimited Short Medium Short Short Short<br />
Notes:<br />
1. In a building of purpose groups 3 and 5-7, areas may be doubled where there is an appropriate fire<br />
control system.<br />
2. Short duration for –<br />
a. external walls more than 1 m of the boundary; and<br />
b. external walls not more than 1 m from the boundary in the case of a building with an appropriate<br />
fire control system.<br />
3. Medium duration for compartmentation.<br />
4. 1,000 m 2 , provided there is an appropriate fire control system.<br />
5. 2,000 m 2 , provided there is an appropriate fire control system.<br />
6. Unlimited, provided there is an appropriate fire control system.<br />
9D<br />
D2.1<br />
Amdt: September 2001<br />
D
D<br />
D3.1 – D3.9<br />
D3 Compartmentation<br />
PRINCIPLES<br />
D3.1 In order to reduce the spread of fire and smoke, a building, or part of a building, with a total storey area<br />
more than the limits given in Tables 1 and 2 to D2.1 must be sub-divided by compartment walls and<br />
compartment floors with the level of fire safety performance in accordance with Tables 1 and 2 to D2.1.<br />
D3.2 Every storey at a height of more than 18 m above ground must form a separate compartment, or compartments<br />
where required by D3.1.<br />
BASEMENTS<br />
D3.3 Where a building has a basement storey, the floor of the ground storey must be a compartment floor,<br />
except -<br />
in a building, other than a building of purpose sub-group 2A, where the building comprises 1 basement<br />
storey and not more than 2 other storeys, and no storey has an area more than 280 m 2 .<br />
D3.4 Where a building has a basement storey at a depth of more than 10 m, every basement storey must form<br />
a separate compartment.<br />
BUILDINGS OF PURPOSE GROUP 2<br />
D3.5 In a building of purpose group 2, every upper storey and every basement storey must form a separate<br />
compartment, or compartments where required by D3.1.<br />
BUILDINGS OF PURPOSE GROUP 4<br />
D3.6* In a building of purpose group 4, each compartment with an area more than 5,600 m 2 must be provided<br />
with an appropriate smoke and heat exhaust ventilation system.<br />
D3.7* In an enclosed shopping centre with a mall on 2 or more storeys or having a total floor area more than<br />
5,600 m 2 , the mall and every shop with a floor area more than 1,300 m 2 must be provided with an appropriate<br />
smoke and heat exhaust ventilation system.<br />
PLACES OF SPECIAL FIRE RISK<br />
D3.8* A place of special fire risk must be enclosed with the same level of fire safety performance as that<br />
required for a compartment with a medium duration,<br />
except -<br />
a suitably protected paint spray booth or room where a cellulose or other flammable liquid spray is used,<br />
having a floor area not more than 100 m 2 , and constructed of prefabricated factory made panels.<br />
D3.9 Where a place of special fire risk contains any appliance or equipment using hazardous liquid, any<br />
opening in a wall or floor separating it from the remainder of the building must be constructed in such a<br />
manner that, in the event of any liquid spillage, the room will contain all the liquid in the appliance or<br />
equipment, plus 10%.<br />
Amdt: September 2001<br />
10D
FIRE-FIGHTING SHAFTS<br />
11D<br />
D3.10 – 3.14<br />
D3.10 A fire-fighting shaft must be enclosed with the same level of fire safety performance as that required for<br />
a compartment with a long duration,<br />
except -<br />
where the elements of structure of the building are only required to have a medium duration the firefighting<br />
shaft need only have a medium duration.<br />
SMOKE VENTING SHAFTS<br />
D3.11 A smoke venting shaft must be enclosed with the same level of fire safety performance as that required<br />
for a compartment with a medium duration,<br />
except -<br />
LIFTS<br />
at the smoke inlets and smoke outlets to the shaft.<br />
D3.12 Every lift well must be enclosed by compartment walls with a medium duration and, where the lift well<br />
is not the full height of the building, a compartment floor with a medium duration,<br />
except -<br />
a. a compartment wall is not required between a lift well and a protected zone; and<br />
b. the requirement for a lift well to be enclosed by compartment walls does not apply to -<br />
i. a lift well in a building of purpose sub-group 1C, or<br />
ii. a lift well within a protected enclosure of a building of purpose sub-group 1B.<br />
D3.13 Where a lift is installed, the landing controls and lift car controls must be of a type that do not operate<br />
because of conditions resulting from the effects of fire.<br />
OPENINGS<br />
D3.14*A compartment wall and a compartment floor must have no openings and must provide a barrier to fire<br />
between the parts of a building to be divided, including any roof space,<br />
except -<br />
a. for a chimney or flue-pipe which is of suitable construction, so that in the event of fire the level of<br />
fire safety performance required of the compartment wall or compartment floor is maintained; or<br />
b. where there is an opening in the compartment wall with a suitable self-closing fire door with the<br />
same duration as the compartment wall,<br />
except -<br />
a lockable door to a cupboard or service duct with a floor area not more than 3 m 2 need not be selfclosing,<br />
or<br />
c. where there is an opening in the compartment wall with a shutter with the same duration as that<br />
required of the compartment wall actuated by a fusible link or other heat sensitive device with a<br />
controlled movement mechanism and audible warning when operated; or<br />
Amdt: September 2001<br />
D
D<br />
D3.14 – D4.2<br />
JUNCTIONS<br />
d. where there is a service opening -<br />
Amdt: September 2001<br />
i. which is of suitable construction, or where the services are suitably protected, so that in the<br />
event of fire the level of fire safety performance required of the compartment wall or compartment<br />
floor is maintained, and<br />
ii. which is suitably fire-stopped; or<br />
e. where there is an opening in the compartment floor, which contains a stair only, other than an<br />
escape stair, and/or not more than 2 escalators, and is provided either -<br />
i. at compartment floor level with a suitably activated shutter in the plane of the floor which<br />
when closed maintains the level of fire safety performance of the compartment floor, or<br />
ii. at each floor level, other than the top floor level, with a suitably activated shutter in the vertical<br />
plane which moves to enclose the opening and provide a barrier with the fire safety performance<br />
equivalent to a compartment wall with the same duration as the compartment floor.<br />
D3.15 Where a compartment wall or compartment floor meets an external wall, a separating wall or a compartment<br />
wall, the junction must maintain the required level of fire safety performance of the compartment<br />
wall or compartment floor.<br />
D3.16*Where a compartment wall forms a junction with a roof, a suitable form of roof construction must be<br />
adopted.<br />
D3.17 In a hospital where a compartment wall meets an external wall there must be a 1 m wide strip of the<br />
external wall which has the same level of fire safety performance as the compartment wall to prevent<br />
lateral fire spread.<br />
D4 Sub-compartmentation<br />
BUILDINGS OF PURPOSE SUB-GROUP 2A<br />
D4.1 In order to aid progressive horizontal evacuation and to limit fire spread in a building of purpose subgroup<br />
2A, every compartment must be divided into sub-compartments by sub-compartment walls with a<br />
level of fire safety performance (see D1.3) with a short duration so that no sub-compartment is greater<br />
than 750 m 2 .<br />
D4.2 In a building of purpose sub-group 2A the following rooms must be enclosed with the same level of fire<br />
safety performance as that required for a sub-compartment -<br />
a. chemical stores;<br />
b. cleaners’ rooms;<br />
c. clothes storage;<br />
d. dayrooms with a floor area greater than 20 m 2 ;<br />
e. smoking rooms;<br />
f. disposal rooms;<br />
12D
g. laboratories;<br />
h. lift motor rooms;<br />
i. linen stores;<br />
j. bedrooms in a building other than a hospital;<br />
k. bedrooms in a hospital where they are used by -<br />
i. elderly people, or<br />
ii. those suffering with mental illness, or<br />
iii. people with learning difficulties;<br />
l. kitchens (other than separate hospital departments);<br />
m. laundry rooms;<br />
n. staff changing and locker rooms;<br />
o. store rooms;<br />
p. X-ray film and record stores; and<br />
13D<br />
D4.2 – D4.6<br />
q. all rooms within a main laundry in which delivery, sorting, processing packing and storing are<br />
carried out.<br />
D4.3 In a building of purpose sub-group 2A no room containing sleeping accommodation shall be intended<br />
for use by more than 4 people,<br />
except -<br />
HOSPITALS<br />
in a hospital.<br />
D4.4 In a hospital every intensive therapy unit must be divided into at least 2 sub-compartments by subcompartment<br />
walls with a level of fire safety performance (see D1.3) with a short duration.<br />
D4.5 In a hospital every entrance to an intensive therapy unit must be either -<br />
a. from a hospital street (see E8.9); or<br />
b. through a lobby, enclosed with the same level of fire safety performance as that required for a subcompartment.<br />
BUILDINGS OF PURPOSE SUB-GROUP 2B<br />
D4.6 In order to aid evacuation and to limit fire spread, in a building of purpose sub-group 2B, each room<br />
containing sleeping accommodation (including any en-suite sanitary accommodation where provided)<br />
must be enclosed with the same level of fire safety performance as that required for a sub-compartment,<br />
except -<br />
a. for a wall between such rooms. and<br />
b. in the case of a place of lawful detention.<br />
Amdt: September 2001<br />
D
D<br />
D4.7 – 5.1<br />
OPENINGS<br />
D4.7* A sub-compartment wall must have no openings and must provide a barrier to fire between the parts of a<br />
building to be divided, including any roof space,<br />
except -<br />
JUNCTIONS<br />
a. for a chimney or flue-pipe which is of suitable construction, so that in the event of fire the level of<br />
fire safety performance required of the sub-compartment wall is maintained; or<br />
b. where there is an opening with a suitable self-closing fire door with the same duration as the subcompartment<br />
wall,<br />
except -<br />
Amdt: September 2001<br />
a lockable door to a cupboard or service duct with a floor area not more than 3 m 2 need not be selfclosing,<br />
or<br />
c. where there is a service opening -<br />
i. which is of suitable construction, or where the services are suitably protected, so that in the<br />
event of fire the level of fire safety performance required of the sub-compartment wall is<br />
maintained, and<br />
ii. which is suitably fire-stopped.<br />
D4.8 In a hospital where a sub-compartment wall meets an external wall there must be a 1 m wide strip of the<br />
external wall which has the same level of fire safety performance as the sub-compartment wall to<br />
prevent lateral fire spread.<br />
D5 Separating walls and separating floors<br />
PRINCIPLES<br />
D5.1* In order to limit the spread of fire and smoke, a separating wall or separating floor with a level of fire<br />
safety performance (see D1.3) with a medium duration must be provided between adjoining buildings or<br />
parts of a building where -<br />
a. they are in different occupation,<br />
except -<br />
between garages in a block of garages where each garage is not more than 40 m 2 and the block is considered<br />
to be a single building for the purposes of this Part; or<br />
b. one part of the building is in single occupation and the other is in communal occupation,<br />
except -<br />
i. between a part in single occupation and an external access balcony or access deck,<br />
ii. in the case of an enclosed shopping centre with a mall on not more than 2 storeys, between a<br />
shop and the mall (see D5.5); or<br />
14D
c. they are in the same occupation, but of different purpose groups,<br />
except -<br />
15D<br />
D5.1 – D5.3<br />
i. where the affected parts of the building comply throughout with whatever is the most onerous<br />
of any required standard contained in this Part,<br />
ii. short duration is sufficient where both the purpose groups concerned are of purpose groups or<br />
sub-purpose group 3, 4, 6b or 7b, and an appropriate fire control system is installed on both<br />
sides of the separating wall, or on the storeys above and below the separating floor; or<br />
d. in the case of a hospital -<br />
i. between different hospital departments, and<br />
ii. between a hospital department and a protected zone, and<br />
iii. between different storeys,<br />
except -<br />
short duration is sufficient in a single storey hospital.<br />
BUILDINGS OF PURPOSE GROUP 1<br />
D5.2 In the case of a building of purpose group 1, a separating wall or separating floor with a level of fire<br />
safety performance (see D1.3) with a short duration must be provided -<br />
HOSPITALS<br />
a. between solid waste storage accommodation and the rest of the building; and<br />
b. between a dwelling and any integral or attached garage,<br />
except -<br />
where the garage ceiling has a short duration, any roof space directly above the garage need not be<br />
separated from the dwelling, or any roof space above the dwelling, by a separating wall.<br />
D5.3* In a hospital the following hospital departments must -<br />
a. never be directly below, nor directly adjoin, the operating theatres, intensive therapy units or special<br />
care baby units; and<br />
b. be provided with an appropriate fire control system where they are directly below, or directly<br />
adjoin, any other hospital department to which patients have access -<br />
i. boiler house,<br />
ii. central stores,<br />
iii. commercial enterprises,<br />
iv. flammable stores,<br />
v. laundry,<br />
vi. main electrical switchgear,<br />
vii. main kitchens,<br />
Amdt: September 2001<br />
D
D<br />
D5.3 – 5.6<br />
Amdt: September 2001<br />
viii. refuse collection and incineration,<br />
ix. works department.<br />
D5.4* In a hospital the following hospital departments must be provided with an appropriate fire control<br />
system where they are directly below, or directly adjoin operating theatres, intensive therapy units, or<br />
special care baby units -<br />
a. central staff change;<br />
b. central sterile supplies;<br />
c. hospital sterilising and disinfecting unit;<br />
d. health records;<br />
e. pathology;<br />
f. manufacturing pharmacy.<br />
ENCLOSED SHOPPING CENTRES WITH MALLS<br />
D5.5 An enclosed shopping centre with a mall must be designed so that -<br />
a. the mall width must at no part be less than 6 m; and<br />
b. where 2 or more shops having mall-level storey areas more than 2000 m 2 are located opposite each<br />
other, then at least 1 must be separated from the mall by a separating wall.<br />
Note:<br />
In this standard opposing shop frontages are those which make an angle of less than 80 degrees with<br />
each other.<br />
NON-COMBUSTIBLE MATERIALS<br />
D5.6 Every part of a separating floor must be of materials which are non-combustible (see D1.3),<br />
except -<br />
a. in a building of purpose sub-group 1A with no storey at a height of more than 18 m, other than<br />
over solid waste storage accommodation;<br />
b. between a shop or office and a dwelling above the shop or office in the same occupation and<br />
where -<br />
i. there is no other dwelling above the shop or office,<br />
ii. the building has no storey at a height of more than 18 m, and<br />
iii. the area of the shop or office is not more than 1 1 /2 times the area of the separating floor;<br />
c. above a pend in a building of purpose group 1, where the ceiling of the pend is constructed of noncombustible<br />
materials (see D1.3) and the floor immediately above has a level of fire safety performance<br />
with medium duration;<br />
d. between dwellings and shared residential accommodation.<br />
16D
D5.7 Every part of a separating wall must be of materials which are non-combustible (see D1.3),<br />
except -<br />
OPENINGS<br />
17D<br />
D5.7 – D5.9<br />
a wall may contain a structural frame of material which is low, medium, high or very high risk, provided<br />
any insulants exposed to a cavity are low risk materials or non-combustible, the internal linings are low<br />
risk materials or non-combustible, and the wall contains no pipes, wires or other services, and is<br />
between -<br />
a. houses; or<br />
b. a dwelling and any integral or attached garage; or<br />
c. garages; or<br />
d. flats or maisonettes, with no storey at a height of more than 18 m, where the wall does not form<br />
part of the enclosure of solid waste storage accommodation; or<br />
e. in a building with no storey at a height of more than 18 m, between flats or maisonettes and an<br />
escape stair enclosure; or<br />
f. between dwellings and shared residential accommodation.<br />
D5.8* A separating wall and a separating floor must have no openings and must provide a barrier to fire<br />
between the parts of a building to be separated, including any roof space,<br />
except -<br />
JUNCTIONS<br />
a. for a chimney or flue-pipe which is of suitable construction so that in the event of fire the level of<br />
fire safety performance required of the separating wall or separating floor is maintained; or<br />
b. where the separating wall is required by D5.1b and it is an opening with a suitable self-closing fire<br />
door with the same duration as the separating wall,<br />
except -<br />
a fire door in a separating wall between a flat or maisonette and a protected lobby or protected zone<br />
may be short duration; or<br />
c. where the separating wall is required by -<br />
i. D5.1c, D5.1d or D5.2b, and<br />
ii. it is an opening with a suitable self-closing fire door with the same duration as the separating<br />
wall; or<br />
d. where there is a service opening -<br />
i. which is of suitable construction, or where the services are suitably protected, so that in the<br />
event of fire the level of fire safety performance required of the separating wall or separating<br />
floor is maintained, and<br />
ii. which is suitably fire-stopped.<br />
D5.9 Where a separating wall or separating floor meets an external wall or a separating wall, the junction<br />
must maintain the required level of fire safety performance of the separating wall or separating floor.<br />
Amdt: September 2001<br />
D
D<br />
D5.10 – D6.2<br />
D5.10* Where a separating wall forms a junction with a roof -<br />
a. low, medium, high and very high risk material (see D1.3) must not be built into, or carried through<br />
or across the ends of, or over the top of, the wall in such a way as to impair resistance to spread of<br />
fire between the relevant parts of the building; and<br />
b. a suitable form of roof construction must be adopted.<br />
D5.11 In a hospital where a separating wall meets an external wall there must be a 1 m wide strip of the<br />
external wall which has the same level of fire safety performance as the separating wall to prevent<br />
lateral fire spread.<br />
D6 Concealed spaces<br />
PRINCIPLES<br />
D6.1 In order to prevent the unseen spread of fire and smoke, every cavity and roof space within a building<br />
must be divided by cavity barriers with a level of fire safety performance (see D1.3) with a short duration<br />
installed -<br />
a. around the edges of the cavity; and<br />
b. between the cavity and any other cavity,<br />
except -<br />
Amdt: September 2001<br />
at a junction between 2 walls each comprising two leaves of masonry or concrete at least 75 mm<br />
thick; and<br />
c. between a roof space and any other roof space.<br />
D6.2 Every cavity must be divided up by cavity barriers with a level of fire safety performance (see D1.3)<br />
with a short duration so that the maximum distance between cavity barriers is not more than 20 metres<br />
where the cavity has surfaces which are non-combustible or low risk materials, or 10 m where the cavity<br />
has surfaces which are medium, high or very high risk materials,<br />
except -<br />
a. a cavity between a roof and a ceiling (see D6.3); or<br />
b. a cavity formed by 2 leaves of masonry or concrete at least 75 mm thick; or<br />
c. a cavity between a floor and a ceiling with a suitable fire safety performance (see D1.3) with a<br />
short duration; or<br />
d. a cavity below an imperforate floor next to the ground and the cavity is either inaccessible or is not<br />
more than 1 m high; or<br />
e. a cavity formed by overcladding, where both surfaces of the overcladding are low risk materials or<br />
non-combustible (see D1.3) attached to a masonry or concrete external wall or a concrete roof, and<br />
where the cavity contains only non-combustible material; or<br />
f. a cavity between a floor which is an element of structure, and a raised floor consisting of removable<br />
panels; or<br />
g. a cavity above an operating theatre and its ancillary rooms within a hospital.<br />
18D
19D<br />
D6.3 – D6.7<br />
D6.3 A cavity barrier with a level of fire safety performance (see D1.3) with a short duration must be<br />
installed between a roof and a ceiling in a building of purpose groups 2-7 above an undivided space, as<br />
set out in the table to this standard,<br />
except -<br />
a. where the ceiling has a suitable level of fire safety performance with a short duration (see D1.3); or<br />
b. a cavity above an operating theatre and its ancillary rooms within a hospital.<br />
Table to D6.3: Maximum distance between cavity barriers (m)<br />
Above an undivided space : Where surfaces are non- Where surfaces are medium, high<br />
combustible or low risk materials or very high risk materials<br />
Intended for sleeping 20 15<br />
Not intended for sleeping<br />
Note:<br />
20 [1] 20<br />
1. No limit in purpose sub-group 2B and purpose groups 3-7.<br />
D6.4 Where a cavity is above a ceiling in a building of purpose sub-group 2B and continues over a wall<br />
between bedrooms or between a bedroom and any other part of the building, a cavity barrier with a<br />
level of fire safety performance (see D1.3) with a short duration must be installed in the same plane as<br />
the wall,<br />
except -<br />
where the ceiling has a level of fire safety performance (see D1.3) with a short duration.<br />
RAINSCREEN CLADDING<br />
D6.5 In a building with a storey at a height of more than 18 m above the ground with ventilated rainscreen<br />
panels cavity barriers with a level of fire safety performance (see D1.3) with a short duration must be<br />
installed within the ventilated void horizontally at every floor level and vertically on the line of every<br />
compartment wall, sub-compartment wall or separating wall abutting the external wall.<br />
CEILINGS INSTEAD OF CAVITY BARRIERS<br />
D6.6 Where a ceiling is provided, instead of a cavity barrier as required by D6.2, D6.3 or D6.4, it must be -<br />
OPENINGS<br />
a. not easily demountable; and<br />
b. non-combustible (see D1.3), or where there is any thermal insulation which is supported by the<br />
ceiling, that insulation must be non-combustible.<br />
D6.7* A cavity barrier, and a ceiling provided instead of a cavity barrier, must be imperforate,<br />
except -<br />
a. a cavity barrier may contain a suitable self-closing fire door;<br />
b. a ceiling may contain a hatch which, when closed, will maintain the level of fire safety performance<br />
of the ceiling;<br />
Amdt: September 2001<br />
D
D<br />
D6.7 – 7.1<br />
JUNCTIONS<br />
c. for a service opening -<br />
Amdt: September 2001<br />
i. which is of suitable construction, or where the services are suitably protected, so that in the<br />
event of fire, the level of fire safety performance required is maintained, and<br />
ii. where it is suitably fire-stopped.<br />
D6.8 Where a wall, floor or other part of a building which is required to have a level of fire safety performance,<br />
abuts a structure containing a cavity, a cavity barrier with a level of fire safety performance (see<br />
D1.3) with a short duration must be installed so as to extend the line of the structure with the level of<br />
fire safety performance,<br />
except -<br />
a. a cavity formed by two leaves of masonry or concrete at least 75 mm thick; or<br />
b. a cavity formed by overcladding, both surfaces of which are non-combustible or low risk materials,<br />
attached to a masonry or concrete external wall or a concrete roof and the cavity contains only noncombustible<br />
materials; or<br />
c. in the case of a wall which is required to have a level of fire safety performance only because it is<br />
loadbearing.<br />
D6.9* A cavity barrier must be tightly fitted to rigid construction, or where this is not possible (for example, in<br />
the case of a junction with slates, tiles, corrugated sheeting or similar materials) the junction must be<br />
suitably fire-stopped.<br />
D6.10 A cavity barrier must be fixed so that its performance is not affected by -<br />
a. movement of the building due to subsidence, shrinkage or thermal change;<br />
b. collapse in a fire of any services penetrating it;<br />
c. failure in a fire of its fixings;<br />
d. failure in a fire of any material or element of structure which it abuts,<br />
except -<br />
where a cavity barrier is installed between a roof and a ceiling, there is no requirement to protect<br />
roof members supporting the cavity barrier.<br />
D7 Fire spread on internal linings<br />
PRINCIPLES<br />
D7.1* In order to resist the spread of fire and smoke, every room, fire-fighting shaft, protected zone or unprotected<br />
zone, must have wall and ceiling surfaces with a level of fire safety performance (see D1.3) which<br />
meet the requirements of the table to this standard,<br />
except-<br />
a. in a room any part of the wall may be of one risk category higher than that required (but not very<br />
high risk) where the total area of those parts in any 1 room is not more than either half the floor<br />
20D
area of the room; or in the case of a building of -<br />
i. purpose group 1 or 2, 20 m 2 , or<br />
ii. any other purpose group, 60 m 2 ,<br />
whichever is the lesser; and<br />
21D<br />
D7.1 – D7.3<br />
b. in a building solely housing livestock, the surfaces of unprotected zones may have any level of fire<br />
safety performance, other than very high risk; and<br />
c. thermoplastic materials in ceilings, rooflights and light fittings with diffusers (see D7.2); and<br />
d. external windows and internal glazing to rooms (but not protected zones or unprotected zones) may<br />
be fitted with suitable plastics glazing materials.<br />
Notes:<br />
1. A wall includes the surface of glazing and any ceiling or soffit at an angle to the horizontal of more<br />
than 70 degrees but excludes doors, skirtings and other facings.<br />
2. A ceiling includes the underside of rooflights, but excludes ceiling hatches and facings.<br />
3. Wall and ceiling surfaces means the substrate or lining material including any treatment thereof to<br />
restrict flame spread, but excludes any wallpaper or paints applied on site for decorative purposes only.<br />
Table to D7.1: Fire spread on wall and ceiling surfaces<br />
Purpose group or Highest permitted level of risk<br />
purpose sub-group Room not Room more Room more UnprotectedProtected<br />
more than than 4 m2 than 30 m2 zone and zone and<br />
4 m2 and not more protected fire-fighting<br />
than 30 m2 enclosure shaft [1]<br />
1 Dwellings Medium [2] Medium Medium Medium Low<br />
2A Institutional High Medium Low [3] Low Low<br />
2B Other residential High Medium Medium Medium Low<br />
3 Offices High High Medium Medium Low<br />
4 Shops and commercial High High Medium Low [4] Low<br />
5 Assembly & recreational High High Medium Medium Low<br />
6 Industrial High High Medium Medium Low<br />
7A Storage (high risk) High High Low Medium Low<br />
7B & C<br />
Notes:<br />
Storage (low risk) and<br />
open-sided car parks<br />
High High Medium Medium Low<br />
1. Including any sanitary accommodation within the enclosures of a protected zone<br />
2. A room other than a kitchen may be high risk.<br />
3. A ceilings may be medium risk.<br />
4. In an enclosed shopping centre with a mall, structural timbers supporting glazing that forms part of<br />
a shop front unit signs (except very high risk), and stallboard risers, are permitted provided they are<br />
not in total more than 20% of the area of the shop front.<br />
D7.2* Thermoplastic materials in ceilings, rooflights and light fittings with diffusers must be suitably designed<br />
and installed.<br />
SANDWICH PANELS<br />
D7.3 A sandwich panel used for internal walls or linings in a building of purpose groups 1 or 2 must be fully<br />
filled with a core which consist of non-combustible material (see D1.3).<br />
Amdt: September 2001<br />
D
D<br />
D7.4 – D8.2<br />
D7.4* A sandwich panel used for internal walls or linings in a building of purpose groups 3 to 7 must be<br />
suitably designed and installed.<br />
D8 Fire spread to adjoining buildings<br />
PRINCIPLES<br />
D8.1* In order to minimises the risk of spread of fire between buildings, an external wall of a building must<br />
meet the requirements of Tables 1 and 2 to D2.1,<br />
except -<br />
a. for a level of unprotected area as indicated in the table to this standard; or<br />
b. in the case of a building ancillary to a dwelling and comprising a carport, covered area,<br />
greenhouse, summerhouse, or swimming pool enclosure.<br />
Table to D8.1: Permitted level of unprotected area<br />
Purpose group or purpose sub-group permitted level of unprotected area<br />
not more than 1 m more than 1 m from the boundary<br />
from the boundary no appropriate fire appropriate fire<br />
control system control system<br />
1 Dwellings Level C Level A Unlimited<br />
2 Institutional and other residential Level C Level A Unlimited<br />
3 Offices Level C Level A Unlimited<br />
4 Shops and commercial Level C Level B Level A<br />
5A Assembly & recreational (high risk) Level C Level B Level A<br />
5B Assembly & recreational (low risk) Level C Level A Unlimited<br />
6A Industrial (high risk) Level C Level B Level A<br />
6B Industrial (low risk) Level C Level A Unlimited<br />
7A, 7B Storage Level C Level B Level A<br />
7C<br />
Note:<br />
Open-sided car parks Level C Unlimited Unlimited<br />
UNPROTECTED AREAS are:<br />
a. any part of an external wall which has a level of fire safety performance less than that required by<br />
the Tables to D2.1; and<br />
b. any opening, including a door or window, but not an unopenable window containing only glazing<br />
which reacts to heat to provide the required level of fire safety performance for an external wall;<br />
and<br />
c. any part of an external wall which has a material, more than 1 mm thick attached or applied to its<br />
external face, whether for cladding or any other purpose, which is low, medium, high or very high<br />
risk (see D1.3).<br />
NON-COMBUSTIBLE MATERIALS<br />
D8.2 Every part of an external wall not more than 1 m from a boundary must be of non-combustible materials<br />
(see D1.3),<br />
except -<br />
a. a wall in a building of purpose group 1, or in shared residential accommodation, with no storey at a<br />
height of more than 18 m above ground containing a structural frame of a material other than one<br />
which is non-combustible and with an external cladding of a material which is non-combustible;<br />
Amdt: September 2001<br />
22D
23D<br />
D8.2 – D9.1<br />
b. any thermal insulation in a wall in a building with no storey at a height of more than 18 m above<br />
ground.<br />
Note: See also D10.1.<br />
TWO OR MORE BUILDINGS ON LAND IN THE SAME OCCUPATION<br />
D8.3 Where the combined areas of any storey of each of 2 or more buildings is more than that allowed by<br />
D3.1, and the buildings are to be on land in the same occupation, or in the case of a single building<br />
having opposing compartments externally, then -<br />
a. the buildings must be separated by a distance not less than the sum of the distances calculated in<br />
respect of each building relative to a notional boundary between them in accordance with this<br />
standard, as if the notional boundary were a boundary (see diagram to D8.3); and<br />
b. the roofs of the buildings must be separated by a distance not less than the sum of the distances<br />
provided in relation to the notional boundary in accordance with the requirements of D9 in respect<br />
of each roof.<br />
Note:<br />
Where a notional boundary described above is to be established between 2 buildings, one of which is an<br />
existing building, for the purposes of this standard the existing building must be regarded as if it were a<br />
new building.<br />
Diagram to D8.3: Notional boundaries<br />
Boundary<br />
Compliance with the provisions<br />
for separation in respect of Building A<br />
D9 Fire spread from an adjoining building<br />
Notional boundary<br />
Building A Building B<br />
Compliance with the provisions<br />
for separation in respect of Building B<br />
D9.1* In order to resist penetration or ignition by fire from an external source and limit the spread of flame on<br />
its external surface, the roof of a building, including any rooflights, but excluding any wallhead fascia,<br />
soffit or barge board, must meet the requirements of the table to this standard,<br />
except -<br />
the roof of a detached garage, greenhouse, garden hut or store, summerhouse or building for keeping<br />
animals, birds or other livestock for domestic purposes ancillary to a dwelling, that are located at least<br />
1 m from the dwelling and 1 m from the boundary.<br />
Amdt: September 2001<br />
D
D<br />
D9.1 – D10.2<br />
Table to D9.1: Acceptable roof coverings<br />
Maximum distance to the Highest permitted vulnerability of roof covering<br />
boundary Building of purpose sub-group 2A All other buildings<br />
not more than 6m low low<br />
more than 6 m low medium [1]<br />
more than 12 m low medium [2]<br />
more than 24 m<br />
Notes:<br />
high high<br />
1. High vulnerability is permitted in a detached house, in a part of the roof not more than 3 m2 in area<br />
and at least 1.5 m from any similar part, the remainder of the roof being of a medium vulnerability.<br />
2. High vulnerability is acceptable in a detached house.<br />
Note:<br />
A roof covering or rooflight which is exposed within the building will be subject also to the requirements<br />
of D7.2.<br />
D10 Fire spread on an external wall<br />
D10.1* In order to limit the fire spread on an external wall, any cladding to the external wall must either -<br />
a. be of materials with a level of fire safety performance (see D1.3) to meet the requirements of the<br />
table to this standard; or<br />
b. meet the requirements of a suitable test for the fire safety performance of external cladding<br />
systems.<br />
Note: See also D8.2.<br />
Table to D10.1: Required level of fire safety performance of the cladding to an external wall<br />
A building at a Purpose group or Location Highest permitted<br />
height of sub-purpose group level of risk<br />
Not more than 5 Not more than 10 m above the Low<br />
18 m above the ground (or above a roof or any<br />
ground part of the building to which<br />
the public have access)<br />
Amdt: September 2001<br />
5 More than 10 m above the ground Very high<br />
2A Any Low<br />
All others Any Very high<br />
More than 18 m<br />
above the ground Any Any Low<br />
D10.2 In a building with a storey at a height of more than 18 m above the ground, insulation material situated<br />
or exposed within a cavity in the external wall construction must be non-combustible (see D1.3),<br />
except -<br />
for a cavity which is between 2 leaves of masonry or concrete at least 75 mm thick, and which has a<br />
cavity barrier around all openings in the wall and at the top of the wall.<br />
24D
BUILDINGS OF SUB-PURPOSE GROUP 2A<br />
25D<br />
D10.3 – D11.5<br />
D10.3 In a building of sub-purpose group 2A where a lower roof abuts an external wall the roof must provide a<br />
level of fire safety performance (see D1.3) with a medium duration for a distance of at least 3 m from<br />
the wall.<br />
D11 Escape route protection<br />
PROTECTED ZONES<br />
D11.1*The enclosing structure of a protected zone, not being a roof or an external wall but including the floor<br />
other than that of the lowest storey, must have a level of fire safety performance (see D1.3) with a<br />
medium duration, unless a more onerous standard is required (see D2 and D3), and any door in the<br />
enclosing structure of a protected zone must be a suitable self-closing fire door,<br />
except-<br />
in the case of a protected zone in shared residential accommodation, short duration.<br />
PROTECTED LOBBIES<br />
D11.2*Where a protected lobby is required within a protected zone, the wall dividing the protected lobby from<br />
the rest of the protected zone must have a level of fire safety performance (see D1.3) with a short duration<br />
and any door in the wall must be a suitable self-closing fire door.<br />
PROTECTED ENCLOSURE<br />
D11.3*Where a protected enclosure is required within a dwelling, the walls must have a level of fire safety<br />
performance (see D1.3) with a short duration, and any door in the wall must be a suitable self-closing<br />
fire door,<br />
except -<br />
where a wall between sanitary accommodation and an adjacent room has a level of fire safety performance<br />
with a short duration, a wall or door between the sanitary accommodation and the protected<br />
enclosure need not have a level of fire safety performance.<br />
CORRIDOR DIVISIONS<br />
D11.4*Where a wall is required to divide a corridor for smoke control (see E5.23) it must have a level of fire<br />
safety performance (see D1.3) with a short duration and any door in the wall must be a suitable selfclosing<br />
fire door.<br />
Note:<br />
A cavity barrier may also be required see D6.7.<br />
ENCLOSING ROOMS IN ESCAPE STAIRS<br />
D11.5*Every wall or screen separating a reception room, an office, a cleaner’s room, or a store from an escape<br />
stair (see E6.8c) must have a level of fire safety performance (see D1.3) with a short duration and every<br />
door in the wall or screen structure must be a suitable self-closing fire door,<br />
except -<br />
a lockable door to a cleaner’s room or a store with a floor area not more than 3 m 2 need not be selfclosing.<br />
Amdt: September 2001<br />
D
D<br />
D11.6 – D11.12<br />
GALLERIES<br />
D11.6 Where it is permitted to enclose below a gallery (see E5.24), the floor of the gallery must have a level of<br />
fire safety performance (see D1.3) with a short duration.<br />
EXTERNAL WALLS<br />
D11.7 Every part of an external wall, including a door, below an external escape stair, or not more than 2 m<br />
from the stair, must have a level of fire safety performance (see D1.3) with a short duration.<br />
D11.8 Every door from a building to an external escape stair, including a landing, access gallery or access<br />
deck served by the escape stair, past which door there is an escape route must have a level of fire safety<br />
performance (see D1.3) with a short duration,<br />
except -<br />
the door at the top of the external escape stair.<br />
D11.9 In a building of purpose sub-group 1A, every part of an external wall, including a door, past which there<br />
is an escape route, including a landing, access gallery or access deck served by an escape stair, must<br />
have a level of fire safety performance (see D1.3) with a short duration up to a height of at least 1.1 m<br />
measured from the level of the escape route.<br />
D11.10Where any part of an external wall of an escape stair enclosure is not more than 2 m from, and makes<br />
an angle of not more than 135 degrees with, any part of an external wall of another part of the building,<br />
it must have a level of fire safety performance (see D1.3) with a medium duration.<br />
ESCAPE OVER FLAT ROOFS<br />
D11.11Where a flat roof or access deck forms part of an escape route -<br />
a. it must have a level of fire safety performance (see D1.3) with medium duration for the width of the<br />
escape route and for a further 3 m on either side of the escape route; and<br />
b. every wall not more than 2 m from either side of the escape route must comply with D11.9.<br />
NON-COMBUSTIBLE MATERIALS<br />
D11.12 Every part of an escape stair including the floor of a protected lobby must be non-combustible (see<br />
D1.3),<br />
except -<br />
a. in shared residential accommodation; or<br />
b. any handrail on an escape stair; or<br />
c. an escape stair which complies with E6.6a or E6.6b; or<br />
d. a floor finish, wall or ceiling lining, or an external cladding, which does not contribute to the level<br />
of fire safety performance required for the part it covers.<br />
Amdt: September 2001<br />
26D
AUDITORIA<br />
27D<br />
D11.13 – D11.15<br />
D11.13*In a building containing an auditorium having an occupancy capacity of more than 500, any separated<br />
stage and stage area must be separated from the remainder of the building by a wall with the same level<br />
of fire safety performance as a compartment wall with a medium duration,<br />
except -<br />
at the proscenium opening, provided there is a suitable safety curtain.<br />
D11.14*In a building containing an auditorium, the ventilation system must be suitably designed to ensure that<br />
the direction of air movement in the event of fire is from the auditorium towards the stage.<br />
D11.15*In a building containing an auditorium having an occupancy capacity of more than 500, any separated<br />
stage and stage area must have a suitable high level outlet over the stage of sufficient area to allow the<br />
escape of smoke and hot gases in the event of fire on the stage.<br />
Note:<br />
A separated stage means a stage which is separated from the auditorium except at the proscenium<br />
opening. For this purpose the stage area includes any scenery dock, workshop, under-stage area and<br />
staff or orchestra room, and any other part ancillary to the stage.<br />
Amdt: September 2001<br />
D
D<br />
Amdt: September 2001<br />
28D
Provisions deemed to satisfy the standards<br />
LEVEL OF FIRE SAFETY PERFORMANCE<br />
RESISTANCE TO FIRE<br />
29D<br />
(D1.3)<br />
(D1.3) The requirements of D1.3a in terms of resistance to fire are satisfied by the alternative “Deemed to<br />
Satisfy Provisions” which set out methods of establishing levels of fire safety performance in terms of<br />
either fire tests specified in British <strong>Standards</strong> or European harmonised fire tests. There are also additional<br />
notes on single storey steel portal frame buildings, suspended ceilings, and steel framed opensided<br />
carparks after the section on Harmonised European <strong>Standards</strong>.<br />
a. British <strong>Standards</strong> and Associated Specifications<br />
The duration required will be satisfied where the construction is capable of meeting the time criteria<br />
set out in the Columns 3, 4 and 5 of Table 1 to (D1.3). The tests and specifications being in either -<br />
i. Clause 10 of BS 476: Part 20: 1987, when read in conjunction with -<br />
for loadbearing elements - BS 476: Part 21: 1987,<br />
for non-loadbearing elements - BS 476: Part 22: 1987,<br />
for components - BS 476: Part 23: 1987,<br />
for ventilation ducts - BS 476: Part 24: 1987,<br />
for fire door assemblies with non-metallic leaves - BS 8214: 1990: Sections 1 and 2, or<br />
ii. in the case of structural steelwork, BS 5950: Part 8: 1990; or<br />
iii. in the case of structural use of timber, BS 5268: Part 4: Sections 4.1 and 4.2: 1990, or<br />
iv. in the case of structural use of concrete, BS 8110: Part 2: 1985: Section 4.3 “Tabulated data<br />
(method 1)”; or<br />
v. an appropriate specification given in the Building Research Establishment Report BR 128<br />
“Guidelines for the Construction of Fire Resisting Structural Elements” (BRE 1988);<br />
b. Harmonised European <strong>Standards</strong><br />
The duration required will be satisfied where the construction is capable of meeting the time criteria<br />
set out in the Column 6 of Table 1 to (D1.3) and specified in Commission Decision<br />
2000/367/EC of 3/5/2000 implementing Council Directive 89/106/EEC as regards the classification<br />
of the resistance to fire safety performance of construction products, construction works and parts<br />
thereof. The tests being specified as follows -<br />
prEN 13501-2: 1999, Fire classification of construction products and building elements-Part 2:<br />
Classification using data from fire resistance tests (excluding products for use in ventilation<br />
systems).<br />
BS EN 1363-1: 1999, Fire resistance tests, Part 1-General requirements<br />
BS EN 1363-2: 1999, Fire resistance tests, Part 2-Alternative and additional procedures<br />
DD EN 1363-3: 1999, Fire resistance tests, Part 3-Verification of furnace performance<br />
BS EN 1364-1: 1999, Fire resistance tests for non-loadbearing elements-Part 1: Walls<br />
BS EN 1364-2: 1999, Fire resistance tests for non-loadbearing elements-Part 2: Ceilings<br />
Amdt: September 2001<br />
D
D<br />
(D1.3)<br />
Table 1 to (D1.3): Minimum periods of resistance to fire<br />
Column 1 Column 2 Column 3 Column 4 Column 5 Column 6 Column 7<br />
Construction Duration British <strong>Standards</strong> European Test<br />
<strong>Standards</strong> exposure<br />
Loadbear- Integrity Insulation<br />
ing capacity (mins)<br />
(mins)<br />
(mins)<br />
1. Structural frame, column Short 30 None None R 30 Faces<br />
or beam Medium 60 None None R 60 exposed on<br />
Long 120 None None R 120 the inside<br />
2. Compartment floor, Short 30 30 30 REI 30 From the<br />
separating floor, floor of a Medium 60 60 60 REI 60 underside<br />
gallery (where enclosure<br />
below is permitted), floor<br />
of a protected zone, and<br />
flat roof or access deck<br />
used as an escape route<br />
Long 120 120 120 REI 120<br />
3. Floor, other than a Short 30 None None R 30 From the<br />
floor in 2. Medium 60 None None R 60 underside<br />
Long 120 None None R 120<br />
4. Shutter in a compart- Short None 30 None E 30 From the<br />
ment floor (see D3.14) Medium None 60 None E 60 underside<br />
Long None 120 None E 120 when fitted<br />
in frame<br />
5. Compartment wall, sub- Short 30 [4] 30 30 [5] REI 30 [4,5] Each side<br />
compartment wall, Medium 60 [4] 60 60 REI 60 [4] separately<br />
separating wall, or a<br />
wall or screen required<br />
for escape route protection<br />
Long 120 [4] 120 120 REI 120 [4]<br />
6. Loadbearing wall, other Short 30 None None R 30 Each side<br />
than a wall in 5 Medium 60 None None R 60 separately<br />
Long 120 None None R 120<br />
7. Fire door in a wall in 5 Short None 30 [6] None E 30 Sa [6] Each side<br />
Medium None 60 [6] None E 60 Sa [6] separately,<br />
Long None 120 [6] None E 120 Sa [6] when fitted<br />
in frame [7]<br />
8. Shutter in a compartment Short None 30 30 [8] EI 30 [8] Each side<br />
wall (see D3.14), or in a Medium None 60 60 [8] EI 60 [8] separately,<br />
wall or screen required Long None 120 120 [8] EI 120 [8] when fitted<br />
for escape route protection. in frame [7]<br />
9. External wall [1] more than Short 30 [4] 30 None RE 30 [4] From the<br />
1 m from a boundary [2] Medium 60 [4] 60 30 RE 60 & I 30 [4] inside only<br />
10. External wall [1] not more Short 30 [4] 30 30 REI 30 [4] Each side<br />
than 1 m from a boundary [2] Medium 60 [4] 60 60 REI 60 [4] separately<br />
11. Horizontal cavity barrier [3] Short None 30 None E 30 From the<br />
underside<br />
12. Vertical cavity barrier [3] Short None 30 None E 30 Each side<br />
separately<br />
13. Ceiling dispensing with a Short None 30 30 EI 30 From the<br />
cavity barrier (D6.2,6.3,6.4) underside<br />
14. Roof against an external Medium None 60 60 EI 60 From the<br />
wall (see D10.3) inside<br />
Amdt: September 2001<br />
30D
31D<br />
(D1.3)<br />
Notes:<br />
1. Except for an unprotected area, unless required fire resistance is needed for escape route protection.<br />
2. Any shutter or door in an external wall, which is not included in the calculation of unprotected area,<br />
should have the same period of fire resistance and the same test exposure as the external wall.<br />
3. In a timber stud wall or partition the following will also be deemed to have a short duration -<br />
a. polythene sleeved mineral wool, or mineral wool slab, in either case under compression when<br />
installed; or<br />
b. calcium silicate, cement based or gypsum based board at least 12 mm thick; or<br />
c. steel at least 0.5 mm thick; or<br />
d. timber at least 38 mm thick.<br />
4. None in the case of column 4, and no loadbearing (R) in the case of column 6, if it is not a loadbearing<br />
construction.<br />
5. None in the case of column 5, and E 30 in the case of column 6, for a single window not more than 1 m 2<br />
in a room required to be enclosed by D4.2 or D11.5.<br />
6. Unless pressurisation techniques complying with BS 5588: Part 4: 1998 are used, the fire door should<br />
also either -<br />
a. in the case of column 4, have a leakage rate not exceeding 3m 3 /m/hour, head and jambs only, when<br />
tested at 25Pa according to Section 31.1 of BS 476: 1983 with AMD 8366/ November 1994, or<br />
b. in the case of column 6, meet the additional classification requirement of Sa when tested to<br />
BS EN 1634-3 2001, except, where the fire door is in an external wall.<br />
7. Other than a lift door which is tested from the outside only, and<br />
other than a fire door in an external wall which is tested from the inside only.<br />
8. None in the case of column 5, and no insulation (I) requirement in the case of column 6, where -<br />
a. the width of the shutter or the aggregate width of any shutters in the wall or part of the wall is not<br />
more than one-quarter of the length of the relevant part of the wall; or<br />
b. people or vehicle circulation routes are clearly marked and will prevent any fire load adjacent to the<br />
shutter (e.g. position of stairs, escalators, lifts and corridors).<br />
Amdt: September 2001<br />
D
D<br />
(D1.3)<br />
Amdt: September 2001<br />
BS EN 1365-1: 1999, Fire resistance tests for loadbearing elements-Part 1: Walls<br />
BS EN 1365-2: 1999, Fire resistance tests for loadbearing elements-Part 2: Floors and roofs<br />
BS EN 1365-3: 1999, Fire resistance tests for loadbearing elements-Part 3: Beams<br />
BS EN 1365-4: 1999, Fire resistance tests for loadbearing elements-Part 4: Columns<br />
BSEN 1366-1: 1999, Fire resistance tests for service installations-Part 1: Ducts<br />
BSEN 1366-2: 1999, Fire resistance tests for service installations-Part 2: Fire dampers<br />
BS EN 1634-1: 2000, Fire resistance tests for door and shutter assemblies-Part 1: Fire doors and<br />
shutters<br />
BS EN 1634-3: 2001, Fire resistance tests for door and shutter assemblies-Part 3: Smoke control doors<br />
c. Single storey steel portal frame buildings<br />
In the case of a single storey steel portal frame building the requirements of D2.1 for protection to<br />
the elements of structure may be met by a steel portal frame having fixed column base connections<br />
or designed in accordance with the guide ‘The Behaviour of Steel Portal Frames in Boundary<br />
Conditions’ second edition published in 1990 by The Steel Construction Institute (SCI), instead of<br />
the level of fire safety performance set out in Table 1 to (D1.3).<br />
Where level of fire safety performance is required for a steel portal frame member because it supports<br />
a compartment wall or a separating wall or an external wall related to its distance from a<br />
boundary (D2.2) such a level of fire safety performance shall apply only to that part of the member<br />
built into or directly supporting the wall up to the underside of the haunch or the underside of the<br />
rafter where there is no haunch, and shall not apply to any other part notwithstanding that it is part<br />
of the same portal frame.<br />
In the case of a gable steel portal frame member which is required to have a level of fire safety<br />
performance because of the distance of the gable wall from a boundary (D2.2), the entire portal<br />
frame shall have the level of fire safety performance.<br />
d. Suspended ceilings<br />
The level of fire safety performance of a floor may include that of an associated suspended ceiling<br />
with a level of fire safety performance where the ceiling -<br />
i. complies with Table 2 to (D1.3) with no openings other than those permitted in the<br />
standard concerned, and<br />
ii. any access hatch, door or panel to the cavity formed by the ceiling maintains the level<br />
of fire safety performance of the ceiling when closed.<br />
The level of fire safety performance of the floor shall be the level of fire safety performance of the<br />
floor/ceiling assembly.<br />
Table 2 to (D1.3): Suspended ceilings<br />
Where the desired level of Height of topmost Then the construction and level of fire safety<br />
fire safety performance of storey of building performance of the ceiling should be -<br />
the floor/ceiling assembly is - (m)<br />
Short or Medium Not more than 7.5 Ceiling of low risk material or non-combustible<br />
More than 7.5 Ceiling of low risk material or non-combustible; and<br />
Ceiling imperforate; and<br />
Supports and fixings for the ceiling non-combustible.<br />
Long Any Ceiling non-combustible; and<br />
Ceiling imperforate; and<br />
Supports and fixings for the ceiling of<br />
non-combustible; and<br />
No access hatch, door or panel is permitted.<br />
32D
e. steel framed open-sided car parks (purpose sub-group 7c)<br />
33D<br />
(D1.3)<br />
In the case of steel framed open sided car parks (purpose sub-group 7c), where the topmost storey<br />
of the building is at a height of not more than 18m above ground, the requirements of D2.1 for the<br />
structural frame, columns and beams may be met by -<br />
REACTION TO FIRE<br />
i. beams supporting concrete floors, each beam having a maximum<br />
Hp/A = 230 -1 m, and<br />
ii. free standing columns, each having a maximum Hp/A = 180 -1 m, and<br />
iii. wind bracing and struts, each having a maximum Hp/A = 210 -1 m.<br />
Where Hp = heated perimeter of the section in m<br />
and A = gross cross-sectional area of the section in m 2 .<br />
(D1.3) The requirements of D1.3b. in terms of reaction to fire are satisfied by the alternative “Deemed to<br />
Satisfy Provisions” which are provided setting out methods of establishing levels of fire safety performance<br />
in terms of either fire tests specified in British <strong>Standards</strong> or European harmonised fire tests for<br />
the reaction to fire of elements of structure, separating walls, separating floors, cavity barriers, linings,<br />
external walls, ceilings, external claddings and escape stairs. In addition, some materials are deemed<br />
intrinsically to be non-combustible and therefore do not require testing.<br />
a. British <strong>Standards</strong><br />
Column 2 of Table 3 to (D1.3) sets out the reaction to fire standards to BS 476 which are deemed<br />
to satisfy.<br />
b. Harmonised European <strong>Standards</strong><br />
Column 3 of Table 3 to (D1.3) sets out the reaction to fire test standards which are deemed to<br />
satisfy in accordance with Commission Decision 2000/147/EC of 8/2/2000 implementing Council<br />
Directive 89/106/EEC as regards the classification of the reaction to fire safety performance of<br />
construction products defines the classes of the essential requirement “Safety in case of fire”.<br />
prEN 13501-1 2000 provides the reaction to fire classification procedure for all construction products<br />
within the scope of the Construction Products Directive.<br />
Amdt: September 2001<br />
D
D<br />
(D1.3)<br />
Table 3 to (D1.3): Reaction to Fire<br />
Column 1 Column 2 Column 3<br />
Risk British <strong>Standards</strong> European <strong>Standards</strong><br />
Non-combustible The material is certified non- The material has achieved a classification of A1<br />
combustible according to the test when tested in accordance with BS EN ISO 1182<br />
specified in BS 476: Part 4: 1970<br />
(1984) throughout; or<br />
and BS EN ISO 1716; or<br />
The material has achieved a classification<br />
The material does not flame or cause of A2 when tested in accordance with<br />
any rise in temperature on either the BS EN 13823 and BS EN ISO 1182<br />
centre (specimen) or furnace<br />
thermocouples according to the test<br />
or BS EN ISO 1716; or<br />
specified in BS 476 Part 11: 1982 Products made from only 1 or more of the<br />
(1988). materials considered as Class A1 without the<br />
need for testing, as defined in Commission<br />
Decision 96/603/EC of 4/10/1996 (amended<br />
26/9/2000) establishing the list of products<br />
belonging to Class A1 “No contribution to fire”<br />
provided for in the Decision 94/611/EC<br />
implementing Article 20 of the Council<br />
Directive 89/106/EEC on the construction<br />
products. None of the materials contain<br />
more than 1.0% by weight or volume<br />
(whichever is the lower) of homogeneously<br />
distributed organic material.<br />
Low risk The surface material (or where it is The material has achieved a classification of B or<br />
bonded throughout to a substrate, the better when tested in accordance with<br />
surface material combined with the BS EN 13823 and BS EN ISO 11925-2<br />
substrate) has a surface of Class 1<br />
and, when tested in accordance with<br />
BS 476: Part 6: 1981 or BS 476:<br />
Part 6: 1989 has an index of<br />
performance (I) not more than 12<br />
and a sub-index (i 1) not more than 6.<br />
Medium risk The material of the wall or ceiling The material has achieved a classification of C or<br />
complies with the tests for surface better when tested in accordance with<br />
spread of flame in relation to Class 1 BS EN 13823 and BS EN ISO 11925-2<br />
in BS 476: Part 7: 1987 (1993).<br />
High risk The material of the wall or ceiling The material has achieved a classification of D<br />
complies with the tests for surface or better when tested in accordance with<br />
spread of flame in relation to Class 2 BS EN 13823 and BS EN ISO 11925-2<br />
or Class 3 in BS 476: Part 7: 1987<br />
(1993).<br />
Very high risk A material which does not meet the criteria for high risk<br />
Amdt: September 2001<br />
34D
FIRE CONTROL SYSTEM<br />
(D2.1)(D5.1)(D5.3)(D5.4)(D8.1)<br />
35D<br />
(D2.1, D5.1, D5.4, D8.1, D3.6 – D3.7)<br />
The requirements of D2.1, D5.1, D5.3, D5.4 and D8.1 for an appropriate fire control system will be met<br />
by adopting, in the case of -<br />
a. a sprinkler system, BS5306: Part 2: 1990;<br />
b. a carbon dioxide system, BS 5306: Part 4: 1986;<br />
c. a low expansion foam system, BS 5306: Part 6: Section 6.1: 1988;<br />
d. a medium and high expansion foam system, BS 5306: Part 6: Section 6.2: 1989;<br />
e. a powder system, BS 5306: Part 7: 1988.<br />
Note:<br />
Selection of system is discussed in BS 5306: Part 0: 1986.<br />
In an enclosed shopping centre, the fire control system should cover the entire shopping centre,<br />
except -<br />
i. a mall or part of a mall with a ceiling height more than 10 m,<br />
ii. a stairway enclosure,<br />
iii. a car park, and<br />
iv. every area where sprinklers would prove a hazard (e.g. main electrical switchgear).<br />
In an enclosed shopping centre the level of fire control protection should be appropriate to the occupancies<br />
within the shopping centre and should be determined on the basis of risk assessment, with Quick<br />
Response Sprinklers (with a response time index of less than 50m 1 /2 s 1 /2); and comply with the Loss Prevention<br />
Council Rules for Automatic Sprinkler Installations (LPC, 1994) (including all additional life<br />
safety recommendations).<br />
SMOKE AND HEAT EXHAUST VENTILATION SYSTEMS<br />
(D3.6) The requirement of D3.6 and D3.7 for an appropriate Smoke and Heat Exhaust Ventilation<br />
(D3.7) System will be one which -<br />
a. is designed in accordance with the principles set out in -<br />
i. the Building Research Establishment Report, BR 368, “Design methodologies for smoke and<br />
heat exhaust ventilation, (1999), and<br />
ii the CIBSE <strong>Technical</strong> Memorandum 19 (1995); and<br />
b. is designed as follows -<br />
i. by dividing the underside of the roof into smoke reservoirs each of which should be not more<br />
than 2000 m 2 in area and at least 1.5 m deep measured to the underside of the roof or any<br />
high level plant or ducts within the smoke reservoir or the underside of an imperforate suspended<br />
ceiling,<br />
Amdt: September 2001<br />
D
D<br />
(D3.6, 3.7)<br />
Amdt: September 2001<br />
ii. by separating the smoke reservoirs by fixed or automatically descending smoke curtains<br />
which are no greater than 60 m apart, measured at right angles to the curtains, and comply<br />
with BS 7346: Part 1:1990,<br />
iii. smoke should not be allowed to descend to a height of less than 3 m above any floor level,<br />
iv. each smoke reservoir should be provided with the necessary number of smoke ventilators or<br />
extract fans to extract the calculated volume of smoke produced, spaced evenly throughout<br />
the reservoir,<br />
v. where mechanical extraction is used, there should be spare fan capacity equivalent to the<br />
largest single fan in the reservoir which will operate automatically on the failure of any one<br />
of the fans, or which runs concurrently with the fans,<br />
vi. any fans, ducts and reservoir screens provided should be designed to operate at the calculated<br />
maximum temperature of the smoke within the reservoir in which they are located but rated<br />
to a minimum of 300º C for 30 minutes, in accordance with BS 7346: 1990,<br />
vii. structures supporting any fans, ducts or reservoir screens should have the same level of fire<br />
safety performance as the element it supports,<br />
viii. the fans or ventilators within a smoke reservoir should operate on the actuation of the fire<br />
control system or smoke detection system within the reservoir or on the operation of the fire<br />
control system or more than one smoke detector or, following a delay not exceeding 4<br />
minutes, one smoke detector, in any adjoining area not being another smoke reservoir,<br />
ix. replacement air should be provided automatically on the operation of the ventilation or exhaust<br />
system at a level at least 0.5 m below the calculated level of the base of the smoke layer,<br />
x. any power source provided to any elements of the smoke and heat ventilation system should be<br />
connected by mineral insulated cables or by cables which meet the requirements of code A<br />
category specified in BS 6387: 1994 or by cables protected from damage to an equal standard,<br />
xi. an automatically switched standby power supply provided by a generator should be connected<br />
to any fans provided as part of the smoke and heat ventilation system capable of simultaneously<br />
operating the fans in the reservoir affected and the two adjacent reservoirs,<br />
xii. simple manual overriding controls for all smoke exhaust, ventilation and air input systems<br />
should be provided at all fire brigade access points and any fire control room provided,<br />
xiii. where outlets are provided with weather protection they should open on the activation of the<br />
fan(s) or ventilators,<br />
xiv. smoke from areas adjoining the smoke reservoirs should only be able to enter one reservoir,<br />
xv. where there is an openwork ceiling the free area of the ceiling should not be less than 25% of<br />
the area of the smoke reservoir, or, for natural ventilation, 1.4 times the free area of the roof<br />
mounted fire ventilator above (3 times where the height from floor to roof ventilator is more<br />
than 12 m), whichever free area is the greater, and be evenly distributed to prevent an unbalanced<br />
air flow into the reservoir, and<br />
xvi. when a natural ventilation system is used and the smoke reservoir includes a suspended<br />
ceiling, other than an openwork ceiling, the free area of the ventilator opening in the suspended<br />
ceiling, or any ventilator grille in the ceiling, should not be less than 1.4 times (3<br />
times where the height from floor to roof ventilator is more than 12 m) that of the roof<br />
mounted fire ventilator above in the case of a ventilator opening, or 2 times (3.5 times where<br />
the height from floor to roof ventilator is more than 12 m) for any ventilator grille.<br />
36D
PAINT SPRAY BOOTHS<br />
(D3.8), (D3.14, D4.7, D5.8, D6.7, D11.1, D11.2, D11.3, D11.4, D11.5)<br />
(D3.8) The requirements of D3.8 for a suitably protected paint spray booth or room where a cellulose or other<br />
flammable liquid spray is used, will be met where it is formed in accordance with the Health and Safety<br />
Executive Guidance Note PM25 “Vehicle finishing units fire and explosion hazards”.<br />
ACTIVATION OF SHUTTERS SEALING COMPARTMENT FLOORS<br />
(D3.14)The requirements of D3.14e.i. for suitable activation of a shutter in the plane of the floor will be met by<br />
a fusible link or other heat-sensitive device positioned to detect fire in the lower compartment which,<br />
when activated -<br />
a. will cause any escalator within the opening to come to a halt and then cause the shutter to close or;<br />
b. where there is no escalator, cause the shutter to close immediately.<br />
There should also be appropriate audible and visual warning devices which operate on detection.<br />
The requirements of D3.14e.ii. for suitable activation of a shutter in the vertical plane will be met by a<br />
smoke detection in every floor served by the escalator or staircase which, when activated, will cause -<br />
a. any escalator within the opening to come to a halt and then cause the shutter to close on the floor<br />
where detection has occurred or;<br />
b. where there is no escalator, cause the shutter to close immediately on the floor where detection has<br />
occurred.<br />
There should also be appropriate signage on the side of the shutter facing the stairway or escalator to<br />
indicate the appropriate direction of escape from each floor. There should also be appropriate audible<br />
and visual warning devices which operate on detection.<br />
SELF-CLOSING FIRE DOORS<br />
(D3.14)(D4.7)(D5.8)(D6.7)(D11.1)(D11.2)(D11.3)(D11.4)(D11.5)<br />
The requirements of D3.14, D4.7, D5.8, D6.7, D11.1, D11.2, D11.3, D11.4 and D11.5 for a suitable<br />
self-closing fire door will be met by one which -<br />
a. is installed accord with the guidance in the Builders Hardware Industry Federation, Code of Practice,<br />
“Hardware for Timber Fire and Escape Doors”, and<br />
b. is only held in the open position by an automatic door release mechanism, if it complies with<br />
BS 5839: Part 3: 1988 and is not -<br />
i. an emergency door, or<br />
ii. a protected door serving the only escape stair in the building or the only escape stair serving<br />
a part of the building, or<br />
iii. a door to a fire-fighting shaft.<br />
Note: An automatic door release mechanism should be -<br />
A. activated by smoke detectors provided to the L2 standard complying with BS 5839: Part 1:<br />
1988, or located on each side of the door and positioned not less than 500 mm and not more<br />
than 3 m from the door; and<br />
B. provided with a ready means of manual operation from a position at the door; and<br />
37D<br />
Amdt: September 2001<br />
D
D<br />
(D3.14, D4.7, D5.8, D6.7)<br />
SERVICE OPENINGS<br />
Amdt: September 2001<br />
C. activated by any loss of power in the device, apparatus or switch; and<br />
D. activated on the operation of any fire alarm system and any loss of power or occurrence of a<br />
fault in that system.<br />
(D3.14)(D4.7)(D5.8)(D6.7)<br />
The requirements of D3.14, D4.7, D5.8 and D6.7 for a service opening other than for a ventilating duct<br />
will be met where the building service -<br />
a. has at least the level of fire safety performance required for the wall or floor; or<br />
b. is protected by a construction which has at least the level of fire safety performance required for the<br />
wall or floor provided by -<br />
i. a casing which has the required level of fire safety performance from the outside, or<br />
ii. where the level of fire safety performance required is medium duration, a casing which has<br />
short duration from each side, or<br />
iii. where the level of fire safety performance required is long duration, a casing which has<br />
medium duration from each side; or<br />
c. is provided with an automatic heat activated sealing device which, in the event of fire, will maintain<br />
the level of fire safety performance in respect of integrity required for the wall or floor regardless of<br />
the diameter; or<br />
d. is a pipe, or in the case of i. below is a cable, which -<br />
i. has a bore, or diameter, of not more than 40 mm and, where there are not more than 4 such<br />
pipes or cables, they are at least 40 mm apart and at least 100 mm from any other pipe or<br />
cable, or, where there are more than 4 such pipes or cables they are at least 100 mm apart, or<br />
ii. has a bore of not more than 160 mm and is of iron, steel or copper, or of a material capable of<br />
with-standing 800º C without allowing flames or hot material to pass through the wall of the<br />
pipe, or<br />
iii. is a branch pipe of a bore of not more than 110 mm to a vertical drainage or water service<br />
pipe, is of aluminium or aluminium alloy, or of uPVC to BS 4514: 1983 (1998), passes<br />
through a wall and the vertical pipe is enclosed throughout in a construction which has a level<br />
of fire safety performance as specified in sub-paragraph b. above or is protected in accordance<br />
with sub-paragraph c. above.<br />
Note:<br />
Where a pipe passing through a service opening is connected not more than 1 m from a wall or floor<br />
required to have a level of fire safety performance to another pipe to which a more onerous provision<br />
applies the pipe has to meet that more onerous provision.<br />
The requirements of D3.14, D4.7, D5.8 and D6.7 for a service opening which is a ventilating duct will<br />
be met where it complies with the provisions of BS 5588: Part 9: 1999.<br />
Note:<br />
A duct passing through sub-compartment walls need not be provided with automatic shutters provided<br />
that the duct serves only 1 sub-compartment and the duct and its supports have a level of fire safety<br />
performance equivalent to that of the sub-compartmentation.<br />
38D
FIRE-STOPPING<br />
(D3.14)(D4.7)(D5.8)(D6.7)(D6.9)<br />
(D3.14, D4.7, D5.8, D6.7, D6.9), (D3.16, D5.10)<br />
The requirements of D3.14, D4.7, D5.8 and D6.7 for fire-stopping of service openings and D6.9 for firestopping<br />
will be met in the case when -<br />
a. a minimal differential movement is anticipated by the use of -<br />
i. cement mortar;<br />
ii. gypsum based plaster;<br />
iii. cement or gypsum based vermiculite/perlite mixes;<br />
iv. glass fibre, crushed rock, blast furnace slag or ceramic based products (with or without resin<br />
binders); or<br />
b. when differential movement is anticipated, either in normal use or during fire exposure, by the use<br />
of a proprietary sealant or sealing system which has shown by test its ability to maintain the<br />
required level of fire safety performance under the conditions appropriate to its end use.<br />
Note:<br />
To prevent displacement, materials used for fire-stopping should be reinforced with, or supported by,<br />
non-combustible materials -<br />
i. where the unsupported span is more than 100 mm, and<br />
ii. where non-rigid materials are used, unless they have been shown by test within their field of application<br />
to be satisfactory.<br />
JUNCTION BETWEEN A COMPARTMENT WALL OR A SEPARATING WALL AND A ROOF<br />
(D3.16)The requirements of D3.16 and D5.10 for a suitable form of roof construction will be met where a<br />
(D5.10)compartment wall or separating wall projects through the roof to a distance of at least 375 mm above<br />
the top surface of the roof,<br />
except -<br />
a compartment wall or separating wall may be taken to the underside of the roof substrate -<br />
a. in the case of a non-combustible substrate, where the junction is fire-stopped and the roof covering<br />
is low vulnerability (see D9) for a distance of at least 1.7 m to each side of the centreline of the<br />
wall; or<br />
b. in the case of a pitched roof covered by slates nailed directly to sarking and underlay, where the<br />
junction between sarking and wall-head is fire-stopped; or<br />
c. in the case of a pitched roof covered by slates or tiles fixed to tiling battens and any counterbattens,<br />
where only the tiling battens and underlay are carried over the wall and are fully bedded in<br />
mortar (or no less suitable material) at the wall-head.<br />
Note:<br />
BRE Housing Defects Prevention Unit “Defect Action Sheet (Design)” February 1985 (DAS 8) should<br />
be referred to in the case of c. above.<br />
39D<br />
Amdt: September 2001<br />
D
D<br />
(D7.1), (D7.2)<br />
FIRE SPREAD ON INTERNAL LININGS<br />
(D7.1) The requirements of D7.1 for suitable plastics glazing materials will be met by -<br />
a. rigid solid PVC (uPVC); or<br />
b. polycarbonate rigid solid sheet at least 3 mm thick; or<br />
c. multiskin polycarbonate sheet at least 10 mm thick overall which has a level of fire safety performance<br />
(see D1.3) of low risk or medium risk.<br />
(D7.2) The requirements of D7.2 will be met by -<br />
a. a ceiling constructed from panels of thermoplastic materials, either as a suspended or stretched skin<br />
membrane, -<br />
Amdt: September 2001<br />
i. with a TP(a) flexible classification, and<br />
ii with an area not more than 5 m 2 , and<br />
iii which is supported on all its sides, and<br />
iv. which is not in a protected zone or fire-fighting shaft;<br />
b. a rooflight constructed of thermoplastic materials with a size and disposition as indicated in the<br />
table and diagram to this standard;<br />
c. a light fitting with a diffuser constructed of thermoplastic materials which, -<br />
i. does not form part of the ceiling and is so designed that the diffuser will fall out of its mounting<br />
when softened by heat, or<br />
ii is a pendant fitting suspended beneath the ceiling, or<br />
iii has a size and disposition as indicated in the table and diagram to this standard, or<br />
iv. is part of a fire-resisting ceiling which has been satisfactorily tested as part of a ceiling<br />
system to provide appropriate fire protection.<br />
40D
Diagram to (D7.2)b and c: Layout restrictions on thermoplastic rooflights and light fittings with<br />
diffusers<br />
not more<br />
than 5m<br />
at least 3m between<br />
groups of panels<br />
not more than 5m for<br />
group of panels at least 3m<br />
not more than 5m<br />
Note:<br />
1. Upper and lower surface of suspended ceiling, between plastic panels, to comply with D7.1.<br />
41D<br />
Key<br />
5m 2 is max. area of diffuser<br />
or rooflight in any one 5m x 5m<br />
group<br />
panels of diffusers<br />
or rooflights<br />
separate groups of<br />
panels or rooflights<br />
(D7.2)<br />
Amdt: September 2001<br />
D
D<br />
(D7.2)<br />
Table to (D7.2)b and c: Limitations applied to thermoplastic rooflights and light fittings with diffusers<br />
Use of Minimum Maximum area Maximum total area of Minimum separation<br />
space classification of each diffuser diffuser panels and distance between<br />
below the of lower panel or rooflights as percentage diffuser panels or<br />
diffusers or surface rooflight (m2 ) of floor area of the space rooflights (m) [1]<br />
rooflights [1] in which the ceiling is<br />
located (%)<br />
Protected<br />
zone or firefighting<br />
shaft<br />
Any Not permitted Not permitted Not permitted<br />
Unprotected TP(a)rigid No limit No limit No limit<br />
zone or<br />
protected TP(a)flexible [3] 5 15 [2] 3<br />
enclosure and TP(b)<br />
Room TP(a)rigid No limit No limit No limit<br />
TP(a)flexible [3]<br />
and TP(b)<br />
5 50 [2] 3<br />
Notes:<br />
1. Smaller panels can be grouped together provided that the overall size of the group and the space<br />
between any others satisfies the dimensions shown in the diagram to (D7.2).<br />
2. The minimum 3 m separation in the diagram to (D7.2) between each 5 m2 should be maintained,<br />
therefore, in some cases it may not also be possible to use the maximum percentage quoted.<br />
3. TP(a) flexible is not permitted in rooflights..<br />
Notes:<br />
1. A thermoplastic material means any synthetic material that has a softening point below 200º C if<br />
tested in accordance with Method 120A in BS 2782: Part 1: 1990. They may be classified TP(a)<br />
rigid, TP(a) flexible or TP(b) as follows -<br />
Amdt: September 2001<br />
a. TP(a) rigid -<br />
i. rigid solid,<br />
ii. solid (as distinct from double- or multiple-skin) polycarbonate sheet at least 3 mm<br />
thick,<br />
iii. multi-skinned rigid sheet made from unplasticised pvc or polycarbonate which has a<br />
level of fire safety performance (see D1.3) of low risk or medium risk.<br />
iv. any other rigid thermoplastic product, a specimen of which (at the thickness of the<br />
product as put on the market), when tested in accordance with Method 508A in<br />
BS 2782: 1970 (1974) performs so that the test flame extinguishes before the first mark,<br />
and the duration of flaming or afterglow does not exceed 5 seconds following removal<br />
of the burner.<br />
b. TP(a) flexible -<br />
flexible products not more than 1mm thick which comply with the Type C requirements<br />
of BS 5867: Part 2: 1980 (1993) when tested in accordance with Test 2 in BS 5438:<br />
1989 (1995) with the flame applied to the surface of the specimens for 5, 15, 20 and 30<br />
seconds respectively, but excluding cleansing procedure.<br />
42D
c. TP(b) -<br />
43D<br />
(D7.4, D8.1)<br />
i. rigid solid polycarbonate sheet products not more than 3mm thick, or multiple-skin<br />
polycarbonate sheet products which do not qualify as TP(a) by test,<br />
ii. other products which, when a specimen of the material more than 1.5 mm and not more<br />
than 3 mm thick is tested in accordance with Method 508A in BS 2782: 1970 (1974),<br />
has a rate of burning which is not more than 50 mm/minute.<br />
2. Thermoplastic rooflights may be subject also to D8.1, depending on their boundary distance, which<br />
may affect in particular the minimum separation between rooflights.<br />
SANDWICH PANELS<br />
(D7.4) The requirements of D7.4 for a suitably designed and installed sandwich panel will be met when it is in<br />
accord with chapter 8 of “Design, Construction, Specification and Fire Management of Insulated<br />
Envelopes for Temperature Controlled Environments”, International Association of Cold Storage Contractors<br />
(European Division), 1999.<br />
CALCULATION OF UNPROTECTED AREA<br />
(D8.1) Level A unprotected area is calculated in relation to the distance between the external wall or side of the<br />
building and the boundary in accordance with either -<br />
a. Method 1 or Method 2 below; or<br />
b. the Building Research Establishment Report “External fire spread: building separation and boundary<br />
distances: 1991: BR 187”.<br />
Level B unprotected area is calculated in relation to the distance between the external wall or side of the<br />
building and the boundary in accordance with either -<br />
a. Method 2 below; or<br />
b. the Building Research Establishment Report “External fire spread: building separation and boundary<br />
distances: 1991: BR 187”.<br />
Level C unprotected area is limited to -<br />
a. ventilators serving the wall, only because the wall is built as an external wall, which do not project<br />
beyond the boundary, and<br />
b. in a wall more than 500 mm from the boundary -<br />
i. the external wall of a protected zone, and<br />
ii. any area which is not more than 0.1 m 2 , and is at least 1.5 m from any other unprotected area<br />
in the same wall and in the same compartment, and<br />
iii. any area, or areas, which add up to not more than 1 m 2 , and are at least 4 m from any other<br />
unprotected area or areas in the same wall and in the same compartment.<br />
Amdt: September 2001<br />
D
D<br />
(D8.1)<br />
METHOD 1 - SIMPLE GEOMETRY<br />
This method applies only where the building is not more than 9 m in height and the maximum length of<br />
any side of the building facing the boundary is 24 m. The method is simple but restrictive and where<br />
failure is indicated Method 2 or the BRE Report methods should be applied. The boundary distance<br />
will be acceptable where the extent of the unprotected area and the minimum distance of any unprotected<br />
area from the boundary are within the limits shown in the Table to Method 1 -<br />
Table to Method 1: Permitted unprotected area in relationship to boundary distance<br />
Maximum total unprotected area of Minimum distance between side of building and<br />
compartment (m2 ) boundary (m)<br />
5.6 1.0<br />
12.0 2.0<br />
18.0 3.0<br />
24.0 4.0<br />
30.0 5.0<br />
No limit 6.0<br />
METHOD 2 - ENCLOSING RECTANGLES (GEOMETRIC METHOD)<br />
This method applies to a building or compartment more than 1 m from any point on the relevant boundary.<br />
The method is based on the concept of enclosing rectangles (see below) and the use of Tables A and B<br />
to this method, in which the distances given relate to different levels of unprotected area permitted.<br />
Diagram 1 to Method 2: Establishing length of baseline of enclosing rectangle<br />
Amdt: September 2001<br />
allowable distance<br />
(step 10)<br />
Notes:<br />
1. Project on to the plane of reference the unprotected areas on all floors to find the dimension of the<br />
base side of the rectangle.<br />
2. The relevant boundary could be a notional boundary depending on the use of the building and the<br />
circumstances.<br />
Step 1 Establish a plane of reference which is the most favourable for the side of the building under<br />
consideration and which -<br />
a. touches all or part of the side;<br />
dimension of base side of<br />
enclosing rectangle (step 4)<br />
dimension of base side<br />
of rectangle (step 3)<br />
44D<br />
90 0<br />
relevant boundary<br />
plane of reference<br />
touching some part of<br />
building (step 1)<br />
more than 80 0<br />
this window and<br />
those parallel to<br />
it are not<br />
included as they<br />
are more than<br />
80 0 to the plane<br />
of reference<br />
(step 2)
45D<br />
(D8.1)<br />
b. however far extended, does not pass within the building (but may pass through projections<br />
such as a balcony or coping); and<br />
c. does not cross the relevant boundary.<br />
Normally it will be best for the plane of reference to be roughly parallel to the relevant boundary.<br />
(Where the boundary distance has not been set, an assumed relationship with the relevant boundary<br />
should be made.)<br />
Step 2 On the plane of reference, and at right angles to it, project lines marking those proposed<br />
unprotected areas which are 80º or less to the plane of reference.<br />
Step 3 Construct a rectangle which encloses all the unprotected areas projected on to the plane of<br />
reference and which complies with Diagrams 2 and 3 to Method 2:<br />
Diagram 2 to Method 2: Establishing enclosing rectangle<br />
Diagram 2A shows the essentials in constructing the<br />
rectangle (shown by diagonal lines) enclosing the<br />
unprotected areas.<br />
verticle<br />
side<br />
90 0<br />
90 0<br />
top side<br />
base side<br />
width<br />
horizontal distance<br />
between outermost lines<br />
of unprotected areas as<br />
projected on to the plane<br />
of reference on plan<br />
2A Setting rectangle<br />
verticle<br />
side<br />
highest point of the<br />
highest unprotected area<br />
90 0<br />
90 0<br />
height<br />
lowest point of the<br />
lowest unprotected area<br />
Diagrams 2B-2D show how the wall construction<br />
determines the size of the rectangle.<br />
In the diagrams the relevant boundary is assumed<br />
as parallel with the wall face and the plane of<br />
reference to coincide with the wall face. But this<br />
will not always be so.<br />
2B<br />
2C<br />
2D<br />
The whole of the<br />
solid wall area<br />
has the required<br />
duration.<br />
Combustible cladding<br />
on wall which<br />
does not have the<br />
required duration.<br />
Unclad wall area<br />
has required<br />
duartion.<br />
Whole of the<br />
wall area behind<br />
and below the<br />
combustible<br />
cladding does<br />
not have the<br />
required<br />
duration.<br />
Note:<br />
1. In diagrams 2C and 2D “combustible cladding” refers to a material, more than 1 mm<br />
thick attached or applied to the wall, whether for cladding or any other purpose, which<br />
is low, medium, high or very high risk (see D1.3).<br />
Step 4 From Tables A or B to Method B, according to the use of the building or compartment, select<br />
an enclosing rectangle which is equal to, or next greater in both height and width to, the<br />
rectangle constructed under step 3. (The tables provide for enclosing rectangles of 3, 6, 9, 12,<br />
or 15 m high, with widths in steps from 3 m to no limit.)<br />
Amdt: September 2001<br />
D
D<br />
(D8.1)<br />
Diagram 3 to Method 2: Effects of compartmentation<br />
Compartmentation of a building has a considerable effect on the distance which its sides (or external<br />
walls) may be from the relevant boundary. This is shown and explained in the following diagrams<br />
which assume a level A unprotected area.<br />
12m 11.5m<br />
6m<br />
5.5m<br />
compartment<br />
floor<br />
6m<br />
Amdt: September 2001<br />
3A Uncompartmented<br />
5.5m<br />
compartment<br />
floor<br />
18m<br />
enclosing rectangle<br />
16m<br />
3B Compartmented<br />
(assume compartmentation as shown)<br />
A<br />
6m<br />
5.5m<br />
12m<br />
11m<br />
C D<br />
compartment wall<br />
B<br />
3C Compartmented<br />
(assume compartmentation as shown)<br />
protecting<br />
structure<br />
protected<br />
zone<br />
protecting<br />
structure<br />
protected<br />
zone<br />
46D<br />
1. Assume rectangle (enclosing unprotected areas) =<br />
11.5m x 16m<br />
2. From Table A enclosing rectangle = 12m x 18m =<br />
216m 2 .<br />
3. Assume unprotected areas (shaded) = 105m 2 .<br />
4. Unprotected percentage (unprotected areas as<br />
percentage of enclosing rectangle) = 105m 2 as<br />
percentage of 216m 2 = 48.6%; use 50% column in<br />
Table A.<br />
5. From Table A distance from boundary = 6m<br />
(minimum).<br />
(a) As the entrance and the stairways are now isolated<br />
the area becomes a protected zone and the glazed<br />
area does not count as part of the unprotected<br />
area.<br />
(b) The remainder of the building is divided by the<br />
compartment floor into compartments A and B. In<br />
this example the compartments have the same<br />
unprotected area. But where there are 2 (or more)<br />
compartments with different unprotected areas take<br />
the compartment with the greatest unprotected<br />
area.<br />
1. Assume rectangle = 5.5m x 11m.<br />
2. From Table A enclosing rectangle = 6m x 12m =<br />
72m 2 .<br />
3. Assume unprotected areas = 26m 2 .<br />
4. Unprotected percentage = 26m 2 as percentage of<br />
72m 2 = 36%; use 40% column in Table A.<br />
5. From Table A distance from boundary = 3m<br />
(minimum).<br />
With the inclusion of a compartment wall the building is<br />
now divided into compartments A, B, C and D each<br />
having the same unprotected area for the purpose of<br />
this example.<br />
1. Assume rectangle = 5.5m x 5.5m.<br />
2. From Table A enclosing rectangle = 6m x 6m =<br />
36m 2 .<br />
3. Assume unprotected areas = 13m 2 .<br />
4. Percentage of unprotected area = 36%; use 40%<br />
column in Table A.<br />
5. From Table A distance from boundary = 2m<br />
(minimum).<br />
Note:<br />
1. In the above diagrams the relevant boundary is assumed as parallel with the wall face and the plane<br />
of reference to coincide with the wall face, but this will not always be so.
Step 5 From the unprotected areas projected under step 2 -<br />
47D<br />
(D8.1)<br />
a. calculate their total area (excluding any areas permitted under the allowance for Level<br />
C); and<br />
b. express this total area as a percentage of the enclosing rectangle. This gives the unprotected<br />
percentage.<br />
Step 6 Proceed to steps 7 to 9 where the boundary distance has been set, or steps 10 to 12 where it<br />
has not.<br />
To find the maximum unprotected area for a given boundary position -<br />
Step 7 From Table A or B find the unprotected percentage allowed for the distance from the relevant<br />
boundary. (This distance relates to the plane of reference and not the side of the building,<br />
unless they coincide.)<br />
Step 8 Where the proposed total unprotected area relative to the size of the enclosing rectangle<br />
exceeds the allowable unprotected percentage for that distance the design should be modified<br />
until an allowable unprotected percentage is established.<br />
Step 9 Repeat the process for all sides of the building situated more than 1 m from any point on the<br />
relevant boundary.<br />
To find the nearest position of the boundary for a given building -<br />
Step 10 From Table A or B, find the minimum allowable distance for the unprotected percentage.<br />
(This distance relates to the plane of reference and not the side of the building, unless they<br />
coincide)<br />
Step 11 Repeat the process for all sides of the building.<br />
Step 12 Where these minimum distances are superimposed upon a plan of the building, a zone around<br />
the building is established upon which a boundary should not encroach.<br />
Amdt: September 2001<br />
D
D<br />
(D8.1)<br />
Table A to Method 2: Permitted unprotected percentages in relation to enclosing rectangles<br />
where a Level A amount of unprotected area is permitted.<br />
Height of Width of Minimum distance from relevant boundary (m) for unprotected<br />
enclosing enclosing percentage not more than -<br />
rectangle rectangle<br />
(m) (m) 20% 30% 40% 50% 60% 70% 80% 90% 100%<br />
3 3 1.0 1.0 1.0 1.5 1.5 1.5 2.0 2.0 2.0<br />
6 1.0 1.0 1.5 2.0 2.0 2.0 2.5 2.5 3.0<br />
9 1.0 1.0 1.5 2.0 2.5 2.5 3.0 3.0 3.5<br />
Amdt: September 2001<br />
12 1.0 1.5 2.0 2.0 2.5 3.0 3.0 3.5 3.5<br />
15 1.0 1.5 2.0 2.5 2.5 3.0 3.5 3.5 4.0<br />
18 1.0 1.5 2.0 2.5 2.5 3.0 3.5 4.0 4.0<br />
21 1.0 1.5 2.0 2.5 3.0 3.0 3.5 4.0 4.5<br />
24 1.0 1.5 2.0 2.5 3.0 3.5 3.5 4.0 4.5<br />
27 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.0 4.5<br />
30 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.0 4.5<br />
no limit 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.0 5.0<br />
6 3 1.0 1.0 1.5 2.0 2.0 2.0 2.5 2.5 3.0<br />
6 1.0 1.5 2.0 2.5 3.0 3.0 3.5 4.0 4.0<br />
9 1.0 2.0 2.5 3.0 3.5 4.0 4.5 4.5 5.0<br />
12 1.5 2.5 3.0 3.5 4.0 4.5 5.0 5.0 5.5<br />
15 1.5 2.5 3.0 4.0 4.5 5.0 5.5 5.5 6.0<br />
18 1.5 2.5 3.5 4.0 4.5 5.0 5.5 6.0 6.5<br />
21 1.5 2.5 3.5 4.0 5.0 5.5 6.0 6.5 7.0<br />
24 1.5 2.5 3.5 4.5 5.0 5.5 6.0 7.0 7.0<br />
27 1.5 2.5 3.5 4.5 5.0 6.0 6.5 7.0 7.5<br />
30 1.5 2.5 3.5 4.5 5.0 6.0 6.5 7.0 8.0<br />
40 1.5 2.5 3.5 4.5 5.5 6.5 7.0 8.0 8.5<br />
50 1.5 2.5 3.5 4.5 5.5 6.5 7.5 8.0 9.0<br />
60 1.5 2.5 3.5 5.0 5.5 6.5 7.5 8.5 9.5<br />
80 1.5 2.5 3.5 5.0 6.0 7.0 7.5 8.5 9.5<br />
no limit 1.5 2.5 3.5 5.0 6.0 7.0 8.0 8.5 10.0<br />
9 3 1.0 1.0 1.5 2.0 2.5 2.5 3.0 3.0 3.5<br />
6 1.0 2.0 2.5 3.0 3.5 4.0 4.5 4.5 5.0<br />
9 1.5 2.5 3.5 4.0 4.5 5.0 5.5 5.5 6.0<br />
12 1.5 3.0 3.5 4.5 5.0 5.5 6.0 6.5 7.0<br />
15 2.0 3.0 4.0 5.0 5.5 6.0 6.5 7.0 7.5<br />
18 2.0 3.5 4.5 5.0 6.0 6.5 7.0 8.0 8.5<br />
21 2.0 3.5 4.5 5.5 6.5 7.0 7.5 8.5 9.0<br />
24 2.0 3.5 5.0 5.5 6.5 7.5 8.0 9.0 9.5<br />
27 2.0 3.5 5.0 6.0 7.0 7.5 8.5 9.5 10.0<br />
30 2.0 3.5 5.0 6.0 7.0 8.0 9.0 9.5 10.5<br />
40 2.0 3.5 5.5 6.5 7.5 8.5 9.5 10.5 11.5<br />
50 2.0 4.0 5.5 6.5 8.0 9.0 10.0 11.5 12.5<br />
60 2.0 4.0 5.5 7.0 8.0 9.5 11.0 11.5 13.0<br />
80 2.0 4.0 5.5 7.0 8.5 10.0 11.5 12.5 13.5<br />
100 2.0 4.0 5.5 7.0 8.5 10.0 11.5 12.5 14.5<br />
120 2.0 4.0 5.5 7.0 8.5 10.0 11.5 12.5 14.5<br />
no limit 2.0 4.0 5.5 7.0 8.5 10.5 12.0 12.5 15.0<br />
Note: The minimum distance from the boundary may be arrived at by interpolation between the percentages<br />
shown.<br />
48D
Table A to Method 2: Continued<br />
49D<br />
(D8.1)<br />
Height of Width of Minimum distance from relevant boundary (m) for unprotected<br />
enclosing enclosing percentage not more than -<br />
rectangle rectangle<br />
(m) (m) 20% 30% 40% 50% 60% 70% 80% 90% 100%<br />
12 3 1.0 1.5 2.0 2.0 2.5 3.0 3.0 3.5 3.5<br />
6 1.5 2.5 3.0 3.5 4.0 4.5 5.0 5.0 5.5<br />
9 1.5 3.0 3.5 4.5 5.0 5.5 6.0 6.5 7.0<br />
12 1.5 3.5 4.5 5.0 6.0 6.5 7.0 7.5 8.0<br />
15 2.0 3.5 5.0 5.5 6.5 7.0 8.0 8.5 9.0<br />
18 2.5 4.0 5.0 6.0 7.0 7.5 8.5 9.0 10.0<br />
21 2.5 4.0 5.5 6.5 7.5 8.5 9.0 10.0 10.5<br />
24 2.5 4.5 6.0 7.0 8.0 8.5 9.5 10.5 11.5<br />
27 2.5 4.5 6.0 7.0 8.0 9.0 10.5 11.0 12.0<br />
30 2.5 4.5 6.5 7.5 8.5 9.5 10.5 11.5 12.5<br />
40 2.5 5.0 6.5 8.0 9.5 10.5 12.0 13.0 14.0<br />
50 2.5 5.0 7.0 8.5 10.0 11.0 13.0 14.0 15.0<br />
60 2.5 5.0 7.0 9.0 10.5 12.0 13.5 14.5 16.0<br />
80 2.5 5.0 7.0 9.0 11.0 13.0 14.5 16.0 17.0<br />
100 2.5 5.0 7.5 9.5 11.5 13.5 15.0 16.5 18.0<br />
120 2.5 5.0 7.5 9.5 11.5 13.5 15.0 17.0 18.5<br />
no limit 2.5 5.0 7.5 9.5 12.0 14.0 15.5 17.0 19.0<br />
15 3 1.0 1.5 2.0 2.5 2.5 3.0 3.5 3.5 4.0<br />
6 1.5 2.5 3.0 4.0 4.5 5.0 5.5 5.5 6.0<br />
9 2.0 3.0 4.0 5.0 5.5 6.0 6.5 7.0 7.5<br />
12 2.0 3.5 5.0 5.5 6.5 7.0 8.0 8.5 9.0<br />
15 2.0 4.0 5.5 6.5 7.0 8.0 9.0 9.5 10.0<br />
18 2.5 4.5 6.0 7.0 8.0 8.5 9.5 10.5 11.0<br />
21 2.5 5.0 6.5 7.5 8.5 9.5 10.5 11.0 12.0<br />
24 3.0 5.0 6.5 8.0 9.0 10.0 11.0 12.0 13.0<br />
27 3.0 5.5 7.0 8.5 9.5 10.5 11.5 12.5 13.5<br />
30 3.0 5.5 7.5 8.5 10.0 11.0 12.0 13.5 14.0<br />
40 3.0 6.0 8.0 9.5 11.0 12.5 13.5 15.0 16.0<br />
50 3.5 6.0 8.5 10.0 12.0 13.5 15.0 16.5 17.5<br />
60 3.5 6.5 8.5 10.5 12.5 14.0 15.5 17.0 18.0<br />
80 3.5 6.5 9.0 11.0 13.5 15.0 17.0 18.5 20.0<br />
100 3.5 6.5 9.0 11.5 14.0 16.0 18.0 19.5 21.5<br />
120 3.5 6.5 9.0 11.5 14.0 16.5 18.5 20.5 22.5<br />
no limit 3.5 6.5 9.0 12.0 14.5 17.0 19.0 21.0 23.0<br />
Note: The minimum distance from the boundary may be arrived at by interpolation between the percentages<br />
shown.<br />
Amdt: September 2001<br />
D
D<br />
(D8.1)<br />
Table B to Method 2: Permitted unprotected percentages in relation to enclosing rectangles<br />
where a Level B amount of unprotected area is permitted<br />
Height of Width of Minimum distance from relevant boundary (m) for unprotected<br />
enclosing enclosing percentage not more than -<br />
rectangle rectangle<br />
(m) (m) 20% 30% 40% 50% 60% 70% 80% 90% 100%<br />
3 3 1.0 1.5 2.0 2.0 2.5 2.5 2.5 3.0 3.0<br />
6 1.5 2.0 2.5 3.0 3.0 3.5 3.5 4.0 4.0<br />
9 1.5 2.5 3.0 3.5 4.0 4.0 4.5 5.0 5.0<br />
12 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 5.5<br />
15 2.0 2.5 3.5 4.0 4.5 5.0 5.5 6.0 6.0<br />
18 2.0 2.5 3.5 4.0 5.0 5.0 6.0 6.5 6.5<br />
21 2.0 3.0 3.5 4.5 5.0 5.5 6.0 6.5 7.0<br />
24 2.0 3.0 3.5 4.5 5.0 5.5 6.0 7.0 7.5<br />
27 2.0 3.0 4.0 4.5 5.5 6.0 6.5 7.0 7.5<br />
30 2.0 3.0 4.0 4.5 5.5 6.0 6.5 7.5 8.0<br />
40 2.0 3.0 4.0 5.0 5.5 6.5 7.0 8.0 8.5<br />
50 2.0 3.0 4.0 5.0 6.0 6.5 7.5 8.0 9.0<br />
60 2.0 3.0 4.0 5.0 6.0 7.0 7.5 8.5 9.5<br />
80 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 9.5<br />
no limit 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0<br />
6 3 1.5 2.0 2.5 3.0 3.0 3.5 3.5 4.0 4.0<br />
6 2.0 3.0 3.5 4.0 4.5 5.0 5.5 5.5 6.0<br />
9 2.5 3.5 4.5 5.0 5.5 6.0 6.0 7.0 7.0<br />
12 3.0 4.0 5.0 5.5 6.5 7.0 7.5 8.0 8.5<br />
15 3.0 4.5 5.5 6.0 7.0 7.5 8.0 9.0 9.0<br />
18 3.5 4.5 5.5 6.5 7.5 8.0 9.0 9.5 10.0<br />
21 3.5 5.0 6.0 7.0 8.0 9.0 9.5 10.0 10.5<br />
24 3.5 5.0 6.0 7.0 8.5 9.5 10.0 10.5 11.0<br />
27 3.5 5.0 6.5 7.5 8.5 9.5 10.5 11.0 12.0<br />
30 3.5 5.0 6.5 8.0 9.0 10.0 11.0 12.0 12.5<br />
40 3.5 5.5 7.0 8.5 10.0 11.0 12.0 13.0 14.0<br />
50 3.5 5.5 7.5 9.0 10.5 11.5 13.0 14.0 15.0<br />
60 3.5 5.5 7.5 9.5 11.0 12.0 13.5 15.0 16.0<br />
80 3.5 6.0 7.5 9.5 11.5 13.0 14.5 16.0 17.5<br />
100 3.5 6.0 8.0 10.0 12.0 13.5 15.0 16.5 18.0<br />
120 3.5 6.0 8.0 10.0 12.0 14.0 15.5 17.0 19.0<br />
no limit 3.5 6.0 8.0 10.0 12.0 14.0 16.0 18.0 19.0<br />
9 3 1.5 2.5 3.0 3.5 4.0 4.0 4.5 5.0 5.0<br />
6 2.5 3.5 4.5 5.0 5.5 6.0 6.5 7.0 7.0<br />
9 3.5 4.5 5.5 6.0 6.5 7.5 8.0 8.5 9.0<br />
12 3.5 5.0 6.0 7.0 7.5 8.5 9.0 9.5 10.5<br />
15 4.0 5.5 6.5 7.5 8.5 9.5 10.0 11.0 11.5<br />
18 4.5 6.0 7.0 8.5 9.5 10.0 11.0 12.0 12.5<br />
21 4.5 6.5 7.5 9.0 10.0 11.0 12.0 13.0 13.5<br />
24 5.0 6.5 8.0 9.5 11.0 12.0 13.0 13.5 14.5<br />
27 5.0 7.0 8.5 10.0 11.5 12.5 13.5 14.5 15.0<br />
30 5.0 7.0 9.0 10.5 12.0 13.0 14.0 15.0 16.0<br />
40 5.5 7.5 9.5 11.5 13.0 14.5 15.5 17.0 17.5<br />
50 5.5 8.0 10.0 12.5 14.0 15.5 17.0 18.5 19.5<br />
60 5.5 8.0 11.0 13.0 15.0 16.5 18.0 19.5 21.0<br />
80 5.5 8.5 11.5 13.5 16.0 17.5 19.5 21.5 23.0<br />
100 5.5 8.5 11.5 14.5 16.5 18.5 21.0 22.5 24.5<br />
120 5.5 8.5 11.5 14.5 17.0 19.5 21.5 23.5 26.0<br />
no limit 5.5 8.5 11.5 15.0 17.5 20.0 22.5 24.5 27.0<br />
Note: The minimum distance from the boundary may be arrived at by interpolation between the percentages<br />
shown.<br />
Amdt: September 2001<br />
50D
Table B to Method 2: Continued<br />
51D<br />
(D8.1)<br />
Height of Width of Minimum distance from relevant boundary (m) for unprotected<br />
enclosing enclosing percentage not more than -<br />
rectangle rectangle<br />
(m) (m) 20% 30% 40% 50% 60% 70% 80% 90% 100%<br />
12 3 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 5.5<br />
6 3.0 4.0 5.0 5.5 6.5 7.0 7.5 8.0 8.5<br />
9 3.5 5.0 6.0 7.0 7.5 8.5 9.0 9.5 10.5<br />
12 4.5 6.0 7.0 8.0 9.0 9.5 11.0 11.5 12.0<br />
15 5.0 6.5 8.0 9.0 10.0 11.0 12.0 13.0 13.5<br />
18 5.0 7.0 8.5 10.0 11.0 12.0 13.0 14.0 14.5<br />
21 5.5 7.5 9.0 10.5 12.0 13.0 14.0 15.0 16.0<br />
24 6.0 8.0 9.5 11.5 12.5 14.0 15.0 16.0 16.5<br />
27 6.0 8.0 10.5 12.0 13.5 14.5 16.0 17.0 17.5<br />
30 6.5 8.5 10.5 12.5 14.0 15.0 16.5 17.5 18.5<br />
40 6.5 9.5 12.0 14.0 15.5 17.5 18.5 20.0 21.0<br />
50 7.0 10.0 13.0 15.0 17.0 19.0 20.5 23.0 23.0<br />
60 7.0 10.5 13.5 16.0 18.0 20.0 21.5 23.5 25.0<br />
80 7.0 11.0 14.5 17.0 19.5 21.5 23.5 26.0 27.5<br />
100 7.5 11.5 15.0 18.0 21.0 23.0 25.5 28.0 30.0<br />
120 7.5 11.5 15.0 18.5 22.0 24.0 27.0 29.5 31.5<br />
no limit 7.5 12.0 15.5 19.0 22.5 25.0 28.0 30.5 34.0<br />
15 3 2.0 2.5 3.5 4.0 4.5 5.0 5.5 6.0 6.0<br />
6 3.0 4.5 5.5 6.0 7.0 7.5 8.0 9.0 9.0<br />
9 4.0 5.5 6.5 7.5 8.5 9.5 10.0 11.0 11.5<br />
12 5.0 6.5 8.0 9.0 10.0 11.0 12.0 13.0 13.5<br />
15 5.5 7.0 9.0 10.0 11.5 12.5 13.5 14.5 15.0<br />
18 6.0 8.0 9.5 11.0 12.5 13.5 14.5 15.5 16.5<br />
21 6.5 8.5 10.5 12.0 13.5 14.5 16.0 16.5 17.5<br />
24 6.5 9.0 11.0 13.0 14.5 15.5 17.0 18.0 19.0<br />
27 7.0 9.5 11.5 13.5 15.0 16.5 18.0 19.0 20.0<br />
30 7.5 10.0 12.0 14.0 16.0 17.0 18.5 20.0 21.0<br />
40 8.0 11.0 13.5 16.0 18.0 19.5 21.0 22.5 23.5<br />
50 8.5 12.0 15.0 17.5 19.5 21.5 23.0 25.0 26.0<br />
60 8.5 12.5 15.5 18.0 21.0 23.5 25.0 27.0 28.0<br />
80 9.0 13.5 17.0 20.0 23.0 25.5 28.0 30.0 31.5<br />
100 9.0 14.0 18.0 21.5 24.5 27.5 30.0 32.5 34.5<br />
120 9.0 14.0 18.5 22.5 25.5 28.5 31.5 34.5 37.0<br />
no limit 9.0 14.5 19.0 23.0 27.0 30.0 34.0 36.0 39.0<br />
Note: The minimum distance from the boundary may be arrived at by interpolation between the percentages<br />
shown.<br />
Amdt: September 2001<br />
D
D<br />
(D9.1)<br />
FIRE SAFETY OF ROOFS AND ROOFLIGHTS<br />
(D9.1) The requirement of D9.1 for roofs and rooflights will be met by the following classification -<br />
Low vulnerability -<br />
a. designation AA, AB or AC when tested along with the substrate in accordance with BS 476: Part 3:<br />
1958; or<br />
b. glass at least 4mm thick; or<br />
c. a roof covering or rooflight of plastics materials which is in an open canopy or over a substantially<br />
open area such as a loading bay or in the roof of a detached swimming pool enclosure which is -<br />
Amdt: September 2001<br />
i. a single-skin polycarbonate sheet not more than 3 mm thick or multi-skin polycarbonate<br />
sheet, or<br />
ii. a thermoplastic material (see Note): a specimen of which when tested in accordance with<br />
Method 508A in BS2782: 1970 (1974), performs so that the test flame does not reach the<br />
second mark within 2 minutes, the specimen thickness to be more than 1.5 mm and not more<br />
than 3.0 mm; or<br />
d. thermoplastic sheet with a level of fire safety performance (see D1.3) of low or medium risk which<br />
is -<br />
i. a plastics material, or<br />
ii. a rigid solid PVC (uPVC), or<br />
iii. a polycarbonate rigid solid sheet at least 3 mm thick, or<br />
iv. a multiskin polycarbonate sheet at least 10 mm thick overall.<br />
Medium vulnerability -<br />
a. designation BA, BB, BC, CA, CB or CC when tested along with the substrate in accordance with<br />
BS 476: Part 3: 1958; or<br />
b. a roof covering or rooflight of plastics materials which is -<br />
i. a single-skin polycarbonate sheet not more than 3 mm thick or multi-skin polycarbonate<br />
sheet, or<br />
ii. thermoplastic material (see Note): a specimen of which when tested in accordance with<br />
Method 508A in BS2782: 1970 (1974), performs so that the test flame does not reach the<br />
second mark within 2 minutes, the specimen thickness to more than 1.5 mm and not more<br />
than 3.0 mm.<br />
High vulnerability -<br />
A roof or rooflight which does not meet the criteria for medium or low vulnerability.<br />
Note:<br />
A thermoplastic material means any synthetic material that has a softening point below 200º C when<br />
tested in accordance with Method 120A in BS 2782: Part1: 1990.<br />
52D
TEST FOR THE FIRE SAFETY PERFORMANCE OF EXTERNAL CLADDING SYSTEMS<br />
(D10.1) The requirements of D10.1b. for a suitable test for the fire safety performance of external cladding<br />
systems will be met by one complying with BRE Fire Note 9 Assessing the fire performance of<br />
external cladding systems (BRE, 1999).<br />
SAFETY CURTAINS<br />
(D11.13) The requirements of D11.13 for a suitable safety curtain is one which conforms with Clause 13 of<br />
Section 5 of BS 5588: Part 6: 1991.<br />
VENTILATION SYSTEM<br />
(D11.14) The requirements of D11.14 for a suitably designed ventilation system will be met by a ventilation<br />
system which conforms to Clause 20 of Section 6 of BS 5588: Part 6: 1991.<br />
SMOKE OUTLET<br />
(D11.15) The requirements of D11.15 for a suitable high level outlet over the stage will be met by conforming<br />
to the provisions of Clause 30.2.4 of Section 7 of BS 5588: Part 6: 1991.<br />
53D<br />
(D10.1, D11.13, D11.14, D11.15)<br />
Amdt: September 2001<br />
D
D<br />
Amdt: September 2001<br />
54D
E<br />
MEANS OF ESCAPE FROM FIRE,<br />
FACILITIES FOR FIRE-FIGHTING<br />
AND MEANS OF WARNING OF FIRE
Contents<br />
INTRODUCTION<br />
REGULATION 13<br />
Means of escape from fire, facilities for fire-fighting and means of warning of fire<br />
THE STANDARDS 1997 +<br />
Equivalent<br />
E1 Application of Part E E1.1-E1.4 E1.1-E1.3<br />
E2 Means of escape from fire in a building<br />
of purpose sub-group 1A<br />
Escape routes E2.1-E2.7 E2.1, E3.1-E3.5<br />
Escape stairs E2.8-E2.14 E4.6, E8.8-E8.11<br />
Travel distance E2.15 E8.6<br />
Inner rooms E2.16 E8.2<br />
Escape windows E2.17 E8.3<br />
Basements<br />
Flats or maisonettes at a storey<br />
E2.18-E2.19 E8.12<br />
height of more than 4.5 m E2.20-E2.24 E8.1, E8.13-E8.16<br />
E3 Means of escape in a building of<br />
purpose sub-group 1B and 1C<br />
Inner rooms E3.1 E8.2<br />
Escape windows E3.2 E8.3<br />
Basements E3.3 E8.18<br />
Houses of purpose sub-group 1B E3.4-E3.7 E3.2, E8.18<br />
E4 Means of escape from fire in a building<br />
of purpose groups 2-7:<br />
(Exits and escape routes)<br />
Principles E4.1 E2.3, E2.4<br />
Independence of escape routes E4.2-E4.5 E3.10-E3.12, E8.22<br />
E5 Means of escape from fire in a building<br />
of purpose groups 2-7:<br />
(Design for horizontal escape)<br />
Travel distance E5.1-E5.8 E2.6-E2.11<br />
Escape routes E5.9-E5.11 E3.1, E3.4<br />
Height of escape routes E5.12 E3.5<br />
Width of escape routes E5.13-E5.18 E3.3, E3.6, E5.2<br />
Doors across escape routes E5.19-E5.20 E5.4<br />
Circulation in confined spaces E5.21-E5.22 E3.9<br />
Smoke control in corridors E5.23 E5.1<br />
Galleries E5.24 E7.1<br />
Escape past openings in the floor E5.25 E7.2<br />
Places of special fire risk E5.26 E7.5<br />
Air supported structures E5.27 E8.23<br />
3E<br />
Amdt: September 2001<br />
E
E<br />
Amdt: September 2001<br />
The <strong>Standards</strong> 1997 +<br />
Equivalent<br />
E6 Means of escape from fire in a building<br />
of purpose groups 2-7:<br />
(Design for vertical escape)<br />
Width of escape stairs E6.1-E6.5 E4.1-E4.5<br />
Protected zones E6.6-E6.14 E4.6-E4.11,<br />
E4.13, E4.14<br />
E7 Special means of escape requirements<br />
for enclosed shopping centres with malls<br />
Direction of travel E7.1 E8.24<br />
Escape route width E7.2-E7.7 E3.6,E8.24<br />
Crèches E7.8 E8.25<br />
E8 Special means of escape requirements<br />
for hospitals<br />
Storeys at a height of more than 7.5 m E8.1 No equivalent<br />
Storeys at a height of more than 18 m E8.2 No equivalent<br />
Compartment exits E8.3 No equivalent<br />
Escape routes E8.4-E8.5 No equivalent<br />
Escape stairs E8.6-E8.8 No equivalent<br />
Hospital street E8.9-E8.10 No equivalent<br />
E9 Lighting E9.1-E9.2 E3.13, E7.7<br />
E10 Facilities for fire-fighting<br />
Access E10.1 E9.1<br />
Ground hydrants E10.2-E10.3 E9.2, E9.3<br />
Provision of fire-fighting facilities E10.4-E10.12 E9.4, E9.8, E9.9<br />
Smoke ventilation of escape routes E10.13-E10.14 E4.8, E8.9<br />
Smoke ventilation of basement storeys E10.15 E9.18<br />
Rolling shutters E10.16 No equivalent<br />
E11 Means of warning of fire E11.1-E11.3 E10.1, E10.2<br />
+ As amended December 1999.<br />
4E
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(E2.4)(E5.11) Revolving door, sliding door or automatic door<br />
(E2.11)(E2.12) Automatic opening ventilators<br />
(E2.14) Fire detection and alarm system<br />
(E2.17)(E3.2) Emergency escape windows<br />
(E5.11) Fixed ladders<br />
(E5.19)(E5.20) Doors across escape routes<br />
(E5.23) Pressurisation<br />
(E8.6) Mattress evacuation stairs<br />
(E9.2) Emergency lighting<br />
(E10.1) Access<br />
(E10.2) Ground hydrants<br />
(E10.4)(E10.9) Fire-fighting shafts<br />
(E10.7)(E10.8) Fire mains<br />
(E10.9)(E10.11) Fire-fighting lobbies<br />
(E10.11) Fire-fighting lifts<br />
(E10.15) Venting of heat and smoke from basement storeys<br />
(E11.1) Automatic fire detection in dwellings<br />
(E11.2) Automatic fire detection in buildings of purpose group 2<br />
(E11.3) Automatic fire detection in enclosed shopping centres with malls<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A, General.<br />
5E<br />
Amdt: September 2001<br />
E
E<br />
Amdt: September 2001<br />
6E
Introduction<br />
1. The intention of this Part is to provide all users of a building with adequate<br />
means of escape from fire. It also requires the provision of certain<br />
fixed fire-fighting equipment, means of access for fire-fighting, and means<br />
of warning of fire in a dwelling, residential accommodation and enclosed<br />
shopping centres.<br />
2. The intention of the requirements for means of escape is that everyone<br />
within a building may reach either a place of safety or, in certain circumstances,<br />
a protected zone within a reasonable travel distance. The requirements<br />
for the number and width of exits assume a unit width of 530 mm<br />
per person and a rate of discharge of 40 persons per minute. The number<br />
of escape routes is determined by -<br />
a. the purpose group of the building;<br />
b. the occupancy capacity served;<br />
c. the height of a storey above ground or its depth below ground; and<br />
d. the travel distance involved.<br />
3. A building must be planned so that -<br />
a. every escape route leads to a place of safety;<br />
b. every escape stair which forms part of an escape route, except an<br />
escape stair from a gallery, is protected from fire, from smoke<br />
and hot gases which might obscure or obstruct the escape route<br />
and, in higher buildings, from the effects of weather;<br />
c. provision is made within a protected zone for a refuge for wheelchair<br />
users; and<br />
d. within those parts of a building where people are at greatest risk<br />
the layout of the building is such as to limit that risk to the utmost<br />
practical extent.<br />
4. Suitable provision must be made for access to the outside of a building<br />
for fire-fighting and rescue vehicles from a public road. A water supply<br />
installation must be available and, in the case of high buildings, suitable<br />
provision must be made for fire-fighting within the building.<br />
5. The requirements to provide early means of warning of fire in a<br />
dwelling, residential accommodation and enclosed shopping centres<br />
increase significantly the level of safety of the occupants.<br />
6. <strong>Standards</strong> are included which make specific provision for the fire<br />
safety of hospitals. However within the <strong>Technical</strong> <strong>Standards</strong> it is not possible<br />
to cover all aspects of fire safety relevant to hospitals. Fire safety is<br />
also dependent upon the way a building is furnished, staffed and managed.<br />
Designers of hospitals and other healthcare buildings will need to make<br />
reference to the full suite of documents that comprise “NHS in Scotland<br />
Firecode”.<br />
7. There are requirements to provide fire exit signs and directional signs<br />
in various other regulations, in particular the Fire Precautions (Workplace)<br />
Regulations 1997 (as amended) and the Health and Safety (Safety signs<br />
and signals) Regulations 1996. Advice on fire safety signs is given in an<br />
HSE publication: “Safety Signs and Signals: Guidance on Regulations.”<br />
7E<br />
Amdt: September 2001<br />
E
E<br />
Regulation 13<br />
Means of escape from fire, facilities for fire-fighting and<br />
means of warning of fire<br />
13. (1) Every building shall be provided with -<br />
Amdt: September 2001<br />
(a) adequate means of escape in the<br />
event of fire; and<br />
(b) adequate fire-fighting facilities.<br />
(1A) Every dwelling, all residential accommodation,<br />
and all enclosed shopping centres<br />
shall be provided with means of warning<br />
the occupants of an outbreak of fire.<br />
(2) This regulation shall not be subject to<br />
specification in a notice served under<br />
section 11 of the Act in respect of -<br />
(a) buildings of purpose sub-groups 1B<br />
and 1C; and<br />
(b) buildings to which the Fire Certificates<br />
(Special Premises) Regulations<br />
1976(a) apply.<br />
(a) SI 1976/2003, amended by SI 1985/1333<br />
and 1987/37.<br />
8E
The <strong>Standards</strong><br />
E1 Application of Part E<br />
E1.1 This Part sets out the required standards for Regulation 13.<br />
E1.2 The standards apply to all buildings as follows -<br />
Purpose sub-group 1A: E2, E9, E10 & E11<br />
Purpose sub-groups 1B and 1C: E3, E10 and E11<br />
Purpose groups 2 to 7: E4 to E11.<br />
9E<br />
E1.1 – E2.2<br />
E1.3 For the purposes of this Part a flat or maisonette entered only from the open air at ground level and with<br />
no storey at a height of more than 4.5 m shall be regarded as a building of purpose sub-group 1C; where<br />
a maisonette entered only from the open air at ground level has a storey at a height of more than 4.5 m it<br />
shall be regarded as a building of purpose sub-group 1B.<br />
E1.4 For the purposes of this Part a roof, an external balcony, or an enclosed courtyard open to the external air to<br />
which there is access for a purpose other than the maintenance of the building, shall be regarded as a room.<br />
except -<br />
where the area of the roof, the external balcony or the enclosed courtyard is not more than 8m 2 .<br />
E2 Means of escape from fire in a building of purpose sub-group 1a<br />
(flats and maisonettes)<br />
ESCAPE ROUTES<br />
E2.1 There must be at least one escape route from -<br />
a. the main entrance door of every flat or maisonette; and<br />
b. the door of every communal room; and<br />
c. from every plant room.<br />
E2.2 An escape route must lead to a place of safety or an access deck -<br />
a. directly; or<br />
b. by way of a protected zone; or<br />
c. by way of an access deck or access balcony; or<br />
d. by way of an exit to an external escape stair (see E2.8); or<br />
e. by way of a flat roof , but only where -<br />
i. there is more than 1 escape route from the storey, and<br />
ii. there are no exhausts of any kind less than 2 m from the escape route, and<br />
Amdt: September 2001<br />
E
E<br />
E2.2 – E2.9<br />
Amdt: September 2001<br />
iii. there is a wall or protective barrier at least 1.1 m high on each side of the escape route.<br />
E2.3 An escape route must have a clear headroom of at least 2 m,<br />
except -<br />
in a doorway it may be reduced to not less than 1.9 m.<br />
E2.4* An escape route must not be by way of -<br />
a. a lift; or<br />
b. a passenger conveyor; or<br />
c. a turnstile; or<br />
d. a shutter; or<br />
e. a revolving door, an automatic sliding door or an automatic door, other than one of suitable<br />
design and construction; or<br />
f. a sliding door, other than one to which the public does not have access; or<br />
g. a fixed ladder, other than a suitable fixed ladder providing access to a plant room other than a<br />
place of special fire risk which is normally unoccupied except for maintenance purposes.<br />
E2.5 Where a door across an escape route has to be secured against entry when the building is occupied it<br />
must be fitted only with a lock or fastening which is readily operated, without a key, from the side<br />
approached by people making an escape, and have a notice, on the inside, explaining the operation of<br />
the opening device.<br />
E2.6 Solid waste storage accommodation must not communicate directly with any escape route.<br />
E2.7 A communal room with an occupancy capacity of more than 60 must have -<br />
a. exits in accordance with E4.1 to E4.4; and<br />
b. escape routes with a width in accordance with E5.13 to E5.18 and E6.1.<br />
ESCAPE STAIRS<br />
E2.8 An escape stair must be within a protected zone (see D11.1) which encloses no other room,<br />
except -<br />
an external escape stair which has a total rise of not more than 6 m and leads directly to a place of<br />
safety.<br />
E2.9 A protected zone enclosing an escape stair must be provided with an unobstructed clear wheelchair<br />
space measuring not less than 700 mm x 1200 mm on every escape stair landing to which there is<br />
access from a storey,<br />
except -<br />
a. a storey which has level or ramped access to a place of safety; or<br />
b. a storey which is inaccessible to wheelchair users.<br />
10E
11E<br />
E2.10 – E2.11<br />
E2.10 Where an escape stair also serves a basement storey the protected zone enclosing the escape stair in the<br />
basement storey must be separated from the protected zone containing the escape stair serving the rest<br />
of the building by a wall or screen, with or without a door, at ground storey floor level having at least<br />
the level of fire safety performance of the protected zone (see D11.1).<br />
E2.11*There must be a protected lobby (see D11.2) with suitable automatic opening ventilators, at each storey<br />
within the protected zone between the escape stair and the accommodation, including a parking garage<br />
and any other accommodation ancillary to the dwellings (see Diagram 1 to E2.11),<br />
except -<br />
a. in relation to flats and maisonettes entered from an open access balcony or access deck having an<br />
opening or openings to the external air extending over at least four-fifths of its length and at least<br />
one-third of its height; or<br />
b. where no storey is at a height of more than 7.5 m and there are not more than 4 dwellings on each<br />
storey and not more than 8 dwellings in total served by the escape stair and each dwelling has<br />
within it a protected enclosure (see D11.3) (see Diagram 2 to E2.11); or<br />
c. at the topmost storey; or<br />
d. where there are more than one escape stairs serving each dwelling.<br />
Diagram 1 to E2.11: Single stair access to flats and maisonettes (any height)<br />
Storey at any height<br />
escape stair<br />
automatically<br />
opening<br />
ventilator<br />
for construction of<br />
separating wall<br />
see D5.1<br />
7.5m max.<br />
7.5m max.<br />
flat or maisonette<br />
protected lobby and<br />
escape stair enclosure<br />
within protected zone<br />
see D11.2<br />
possible fire<br />
fighting lift<br />
Amdt: September 2001<br />
E
E<br />
E2.11 – E2.14<br />
Diagram 2 to E2.11: Single stair access to flats and maisonettes not more than 7.5 m above ground<br />
Amdt: September 2001<br />
for construction of<br />
separating wall<br />
see D5.1<br />
escape stair<br />
Storey at a height of not more than 7.5 m with not more than 4 dwellings per storey and not more than 8<br />
dwellings in total: no protected lobby required.<br />
E2.12*Where a building has more than one escape stair and where a corridor or part of a corridor provides<br />
escape in only one direction, suitable automatic opening ventilators must be provided in that part of the<br />
corridor which provides single direction escape.<br />
E2.13 Where an open access balcony or access deck is more than 2 m wide, any soffit above it must have a<br />
downstand on the line of separation between each dwelling extending the full width of the access<br />
balcony or access deck at 90 degrees to the face of the building and extending at least 300 mm below<br />
any beam or downstand parallel to the face of the building.<br />
Note:<br />
For this purpose an access balcony is to be regarded as open where it has an opening or openings to the<br />
external air extending over at least four-fifths of its length and at least one-third of its height.<br />
E2.14*An escape stair must not communicate with any accommodation which is of a different purpose group,<br />
except -<br />
a. in a building with no storey at a height of more than 7.5 m and with not more than 1 escape stair,<br />
or in a building with more than 1 escape stair, 1 escape stair may serve both flats or maisonettes<br />
and other accommodation provided that the escape stair is separated from each occupancy in a<br />
different purpose group by a protected lobby (see D11.2); or<br />
b. any escape stair which serves a flat or maisonette which is ancillary to the main use of the building<br />
may communicate with the other accommodation provided that -<br />
i. the escape stair is separated from the other accommodation by a protected lobby (see<br />
D11.2), and<br />
ii. an alternative exit is available from the flat or maisonette, and<br />
iii. the building has a suitably installed automatic fire detection and alarm system protecting<br />
the flat or maisonette.<br />
Note:<br />
In this context ‘ancillary’ includes caretakers’, directors’, supervisors’ and similar flats or maisonettes.<br />
12E<br />
protected enclosure:<br />
see D11.3
TRAVEL DISTANCE<br />
13E<br />
E2.15 – E2.20<br />
E2.15 Travel distance from a flat or maisonette, a communal room, or a plant room is the distance, measured<br />
along the shortest route of escape from the main entrance door to the nearest protected door or place of<br />
safety, and must comply with the table to this standard -<br />
Table to E2.15: Maximum travel distance in a building of purpose sub-group 1A related to available<br />
directions of travel<br />
Situation Maximum travel distance (m)<br />
One direction of travel More than one direction of travel<br />
a storey at a height of not more than 7.5 m 7.5 [1] 32 [1]<br />
a storey at a height of more than 7.5 m 7.5 [2] 32 [1]<br />
a storey at any height with an access deck or<br />
open access balcony serving the dwellings<br />
Notes:<br />
40 [1] Unlimited<br />
1. Unlimited where a dwelling on the storey has an alternative exit.<br />
2. 32 m where a dwelling on the storey has an alternative exit.<br />
INNER ROOMS<br />
E2.16 An apartment in a storey at a height of more than 4.5 m, or in a basement storey, must not be an inner<br />
room,<br />
except -<br />
an apartment in a basement storey with an emergency escape window (see E2.17) providing access to<br />
the external air, from which there is access to a place of safety at ground level.<br />
ESCAPE WINDOWS<br />
E2.17*A suitably designed and located emergency escape window must be provided in every apartment -<br />
BASEMENTS<br />
a. in an upper storey at a height of not more than 4.5 m; or<br />
b. which is an inner room,<br />
except -<br />
where there are alternative routes from the apartment to circulation areas or other rooms.<br />
E2.18 A basement storey which contains an apartment must be provided with either –<br />
a. an alternative exit from the basement storey, which may provide access to the external air (below<br />
the adjoining ground) from which there is access to a place of safety at ground level, or<br />
b. a suitably designed and located escape window in every basement apartment.<br />
E2.19 Where a private stair serves a basement storey, the private stair must be in a protected enclosure (see D11.3).<br />
FLATS OR MAISONETTES AT A STOREY HEIGHT OF MORE THAN 4.5 m<br />
E2.20 A flat at a storey height of more than 4.5 m which is entered at the same level as the accommodation<br />
must be planned so that -<br />
a. an alternative exit is provided; or<br />
Amdt: September 2001<br />
E
E<br />
E2.20 – E2.24<br />
b. all apartments are entered directly from a protected enclosure (see D11.3) and the distance to be<br />
travelled from any door of an apartment to the exit is not more than 9 m; or<br />
c. the distance to be travelled from any point within the flat to the exit is not more than 9 m and the<br />
direction of travel is away from cooking facilities; or<br />
d. sleeping accommodation, and that part of the circulation area which serves the sleeping accommodation<br />
and the exit to the flat, is separated from any other apartment and kitchen by a construction<br />
with a level of fire safety performance equivalent to that of a protected enclosure (see<br />
D11.3); and where that flat has a storey at a height of more than 7.5 m and the distance to be<br />
travelled within the flat from any point to the exit is more than 15 m, there is an alternative exit<br />
from the living accommodation.<br />
E2.21 A flat at a storey height of more than 4.5 m which is entered from a storey below the level of the accommodation<br />
must be planned so that -<br />
a. an alternative exit is provided; or<br />
b. all apartments are entered directly from a protected enclosure (see D11.3) and the distance to be<br />
travelled from any door of an apartment to the head of the private stair is not more than 9 m; or<br />
c. the distance to be travelled from any point within the flat to the head of the private stair is not<br />
more than 9 m, and the direction of travel is away from cooking facilities.<br />
E2.22 A flat at a storey height of more than 4.5 m which is entered from a storey above the level of the accommodation<br />
must be planned so that an alternative exit is provided from the lower storey.<br />
E2.23 A maisonette with 1 or more storeys at a height of more than 4.5 m must be planned that -<br />
a. all apartments are entered directly from a protected enclosure (see D11.3); and<br />
b. where any storey is at a height of more than 7.5 m there is -<br />
Amdt: September 2001<br />
i. an alternative exit from each storey other than the entrance storey, or<br />
ii. an alternative exit from each room intended for sleeping accommodation.<br />
Note:<br />
For basement accommodation see E2.16 and E2.18.<br />
E2.24 Where a flat or maisonette has a storey at a height of more than 4.5 m or has a basement storey and is<br />
provided with a system of ducted warm air heating -<br />
a. transfer grilles must not be fitted between any room and the entrance hall or stair; and<br />
b. supply and return grilles must be not more than 450 mm above floor level; and<br />
c. where warm air is ducted to an entrance hall or stair, the return air must be ducted back to the<br />
heater; and<br />
d. where a duct passes through any wall, floor, or ceiling of an entrance hall or stair, all joints<br />
between the duct and the surrounding construction must be sealed; and<br />
14E
15E<br />
E2.24 – E3.6<br />
e. there must be a room thermostat in the living room, at a height more than 1370 mm and not more<br />
than 1830 mm, with an automatic control which will turn off the heater, and any circulation fan<br />
should the ambient temperature rise to more than 35º C; and<br />
f. where the system recirculates air, smoke detectors must be provided in every extract duct to cause<br />
the recirculation of air to stop and direct all extract air to the outside of the building in the event<br />
of fire.<br />
E3 Means of escape in a building of purpose sub-group 1b and 1c<br />
(houses)<br />
INNER ROOMS<br />
E3.1 An apartment in a storey at a height of more than 4.5 m, or in a basement storey, must not be an inner<br />
room,<br />
except -<br />
an apartment in a basement storey with an emergency escape window (see E3.2) providing access to the<br />
external air, from which there is access to a place of safety at ground level.<br />
ESCAPE WINDOWS<br />
E3.2* A suitably designed and located emergency escape window must be provided in every apartment -<br />
BASEMENTS<br />
a. in an upper storey at a height of not more than 4.5 m; or<br />
b. which is an inner room,<br />
except -<br />
where there are alternative routes from the apartment to circulation areas or other rooms.<br />
E3.3 A basement storey which contains an apartment must be provided with either -<br />
a. an alternative exit from the basement storey, which may provide access to the external air (below<br />
the adjoining ground) from which there is access to a place of safety at ground level, or<br />
b. a suitably designed and located escape window in every basement apartment.<br />
HOUSES OF PURPOSE SUB-GROUP 1B<br />
E3.4 In a house of purpose sub-group 1B, every stair must be in a protected enclosure (see D11.3),<br />
except -<br />
a stair in a house with a storey at a height exceeding 4.5 m by 1 storey which does not contain an apartment<br />
or kitchen.<br />
E3.5 In a house of purpose sub-group 1B, every storey at a height of more than 7.5 m must have an alternative<br />
exit.<br />
E3.6 In a house of purpose sub-group 1B, where the private stair also serves a basement storey, the protected<br />
enclosure (see D11.3) serving the basement storey must be separated from the protected enclosure<br />
serving the remainder of the house.<br />
Amdt: September 2001<br />
E
E<br />
E3.7 – E4.3<br />
E3.7 Where the alternative exit provided in accordance with E3.5 is by way of a flat roof, there must be -<br />
a. no exhausts of any kind less than 2 m from the route across the roof; and<br />
b. a wall or protective barrier at least 1.1 m high on each side of the route across the roof.<br />
E4 Means of escape from fire in a building of purpose groups 2-7<br />
(exits and escape routes)<br />
PRINCIPLES<br />
E4.1 The minimum number of exits from a room, storey, gallery, catwalk or openwork floor in relation to<br />
occupancy capacity must be in accordance with the table to this standard; and<br />
a. the minimum number of exits from a room not being a whole storey, shall be determined in<br />
relation to the occupancy capacity of the room; and<br />
b. the minimum number of exits from a storey shall be determined in relation to the occupancy<br />
capacity of the storey.<br />
Table to E4.1: Minimum number of exits in relation to occupancy capacity<br />
Occupancy capacity of room, storey, Minimum number of exits from a room, Minimum number of<br />
gallery, catwalk or openwork floor gallery, catwalk or openwork floor exits from a storey<br />
Not more than 60 1 2 [1,2]<br />
61-600 2 2 [3]<br />
More than 600<br />
Notes:<br />
3 3 [4,5]<br />
1. Only one exit is required from the ground storey or an upper storey at a height of not more than<br />
7.5 m, in a building of purpose sub-group 2B or purpose groups 3-7.<br />
2. Only 1 exit is required from a basement storey at a depth of not more than 4.5 m which is not<br />
intended for use by members of the public other than for access to sanitary accommodation.<br />
3. In a hospital any storey with more than 100 patient beds must have at least 3 exits.<br />
4. In a hospital any storey with more than 200 patient beds must have at least of 4 exits.<br />
5. In a hospital any storey with more than 300 patient beds must have at least of 5 exits.<br />
INDEPENDENCE OF ESCAPE ROUTES<br />
E4.2 Every escape route from a room or storey must be independent of any other escape route from that room<br />
or storey, and where more than 1 escape route is required they must provide alternative directions of<br />
escape in accordance with E5.7.<br />
E4.3 Where more than 1 exit is required from a storey or room, access from any point within the storey or<br />
room must be provided to not less than 2 exits from the storey or room,<br />
except -<br />
a. from a room on the ground storey of a building which room is required to have only 1 exit and<br />
from which room the travel distance to the nearest exit giving direct access to a place of safety<br />
complies with E5.1 as to the maximum travel distance related to 1 direction of travel from any<br />
point within the storey;<br />
b. exits from a room with an occupancy capacity of not more than 100 may be to an unprotected<br />
zone which provides escape in 2 directions as required by E5.7;<br />
c. from a room permitted inside the protected zone enclosing an escape stair (see E6.8).<br />
Amdt: September 2001<br />
16E
E4.4 Where 2 or more escape stairs in protected zones are required from a storey or room, it must be possible<br />
to reach at least 2 such protected zones without passing through either of them, or any such protected<br />
zone or any place of special fire risk.<br />
E4.5 Where a separated stage and stage area in a building containing an auditorium is equipped with a safety<br />
curtain any escape route from that part of the stage behind the curtain must be independent of that from<br />
the auditorium (see D11.13, D11.14, D11.15).<br />
E5 Means of escape from fire in a building of purpose groups 2-7<br />
(design for horizontal escape)<br />
TRAVEL DISTANCE<br />
E5.1 The maximum travel distances for a building or part of a building related to available directions of<br />
travel, measured in accordance with E5.2, are given in the table to this standard -<br />
Table to E5.1: Maximum travel distance related to available directions of travel<br />
Purpose group or Situation Maximum travel distance (m)<br />
purpose sub-group One direction More than one<br />
of travel direction of travel<br />
2A (institutional) a. generally (including hospitals) 15 32<br />
b. residential care buildings (e.g. nursing<br />
homes, and residential schools for<br />
disabled children)<br />
9 18<br />
2B (other residential, including shared residential accommodation) 15 32<br />
3 (offices) 18 45<br />
4 (shops and commercial) a. generally 15 32<br />
b. from any part of the mall of an enclosed<br />
shopping centre (except those with a<br />
mall on three or more storeys)<br />
9 45<br />
5 (assembly) a. generally 15 32<br />
b buildings primarily for disabled people or<br />
people with learning difficulties, and<br />
swimming pools in air supported<br />
structures<br />
9 18<br />
6 (industrial) 18 45<br />
7A (high hazard storage) a. generally 15 32<br />
b. bonded warehouses containing<br />
spirituous liquor<br />
18 45<br />
7B (low hazard storage) a. generally 18 45<br />
b. silage and grain stores on farms where<br />
the material is handled primarily<br />
by mechanical plant.<br />
30 45<br />
7C (open sided car parks) 18 45<br />
Any a. from a room or auditorium with provision 15<br />
for fixed seating<br />
32<br />
b. from a rooftop plant room 60 100<br />
c. within a roof top plant room 18 45<br />
d. within a place of special fire risk 18<br />
e. within a protected zone to a place of safety 100 Unlimited<br />
17E<br />
E4.4 – E5.1<br />
Amdt: September 2001<br />
E
E<br />
E5.2 – E5.6<br />
E5.2 Travel distance is the distance measured along the actual route of escape from any point within a storey -<br />
a. to the nearest protected door giving direct access to an escape stair or a place of safety,<br />
except -<br />
Amdt: September 2001<br />
in the case of building or part of a building where there are at least 2 available directions of<br />
travel, when the travel distance may be measured to any protected door; or<br />
b. to a door in a compartment wall, as described in E5.3; or<br />
c. to a door in a sub-compartment wall, as described in E5.4,<br />
except –<br />
in the case of an enclosed shopping centre provided with appropriate smoke and heat exhaust ventilation<br />
system (see D3.7) the travel distance from a mall level storey of a shop may be measured to the mall.<br />
E5.3 Where the travel distance is measured to a protected door in a compartment wall -<br />
a. there must be no fire shutter in the compartment wall; and<br />
b. the compartment must also have at least 1 other escape route which is not through another compartment,except-<br />
a compartment in a hospital; and<br />
c. in a building of purpose sub-group 2A used for bed-patient care, the escape route must not pass<br />
through any of the rooms listed in D4.2 as requiring to be enclosed with the same level of fire<br />
safety performance as a sub-compartment; and<br />
d. in a part of a building of purpose sub-group 2A used for bed-patient care each compartment must<br />
be capable of holding the occupancy capacity of that compartment and the occupancy capacity of<br />
the largest adjoining compartment; and<br />
e. in a building, or part of a building, other than one specified in E5.3d, either -<br />
i. the area of the adjoining compartment is at least the sum, in m 2 , of the occupancy capacities<br />
of both compartments multiplied by 0.3, or<br />
ii. the escape route width available from the adjoining compartment is adequate for the sum<br />
of the occupancy capacities of both compartments.<br />
E5.4 Where the travel distance is measured to a protected door in a sub-compartment wall -<br />
a. there must be no fire shutter in the sub-compartment wall; and<br />
b. the escape route must not be through any of the rooms listed in D4.2 as requiring to be enclosed<br />
with the same level of fire safety performance as a sub-compartment.<br />
E5.5 Where a floor is divided by fixed seating or other fixed obstructions the travel distance must be measured<br />
by way of the shortest route along open seatways, gangways or circulation areas.<br />
E5.6 Where a measurement of travel distance includes an escape stair not in a protected zone within the<br />
building, as permitted by E6.6a. and b., the travel distance must be measured along the pitch line from<br />
the centre of the nosing of the topmost tread to the lower landing, including the length of any intermediate<br />
landings, measured throughout along the centre line of travel.<br />
18E
19E<br />
E5.7 – E5.9<br />
E5.7 Where more than 1 exit is required, the directions of travel from any point within the storey or a room<br />
must -<br />
a. diverge at an angle of at least 45º; or<br />
b. be combined for a distance not exceeding that allowed for single direction of travel (see Table to<br />
E5.1) and then diverge to 2 exits at an angle of at least 45º plus 2 1 /2º for every metre in the combined<br />
distance, provided the distance between the exits is also more than twice the combined<br />
distance.<br />
E5.8 In a building in purpose sub-group 2A, the maximum travel distance from any point within a compartment<br />
must be not more than 64 m to -<br />
a. each of 2 adjoining compartments; or<br />
b. an adjoining compartment and an escape stair or a final exit; or<br />
c. an adjoining compartment and a final exit; or<br />
d. an escape stair and a final exit.<br />
ESCAPE ROUTES<br />
E5.9 An escape route must give access to a place of safety or to another compartment (see E5.3) -<br />
a. directly; or<br />
b. by way of a protected zone or unprotected zone; or<br />
c. by way of an unprotected zone to a protected zone; or<br />
d. by way of an access deck, or<br />
e. by way of an exit to an external escape stair (see E6.6); or<br />
f. in the case of escape from an inner room not intended to be used as sleeping accommodation, by<br />
way of one other room, other than a place of special fire risk; the escape route from that other<br />
room must comply with a, b, c, d or e above; or<br />
g. by way of a flat roof, but only where -<br />
i. there is more than 1 escape route from the storey; unless the storey consists of a roof top<br />
plant room which is not a place of special fire risk, and<br />
ii. it serves a building of purpose group 3, 6 or 7 or part of a building of purpose group 2, 4<br />
or 5 to which the public has no access, and<br />
iii. there are no exhausts of any kind less than 2 m from the escape route, and<br />
iv. there is a wall or protective barrier at least 1.1 m high on each side of the escape route,<br />
except -<br />
an escape route from a hospital department to which patients have access, complying with E8.4.<br />
Amdt: September 2001<br />
E
E<br />
E5.10 – E5.14<br />
E5.10 In a building of purpose sub-group 2A, where a compartment is divided into sub- compartments, each<br />
sub-compartment must be provided with at least 2 exits by way of protected zones and unprotected zones<br />
to adjoining but separate compartments or sub-compartments,<br />
except -<br />
in the case of an escape route from a ward bedroom it may be to another ward bedroom in a different<br />
compartment or sub-compartment.<br />
E5.11*An escape route must not be by way of -<br />
a. a lift; or<br />
b. a passenger conveyor; or<br />
c. a turnstile, other than a suitably designed and installed turnstile unit with an emergency pressure<br />
operated facility enabling the entire unit to open in the direction of escape; or<br />
d. a shutter, other than a shutter which is installed for security purposes across a shop front and<br />
which does not close automatically in the event of fire, but not a shutter across an opening<br />
between a protected zone and a place of safety; or<br />
e. a revolving door, an automatic sliding door or an automatic door, other than one of suitable<br />
design and construction; or<br />
f. a sliding door, other than one to which the public does not have access; or<br />
g. a fixed ladder, other than a suitable fixed ladder providing access to a plant room other than a<br />
place of special fire risk which is normally unoccupied except for maintenance purposes.<br />
HEIGHT OF ESCAPE ROUTES<br />
E5.12 An escape route or circulation area must have a clear headroom of at least 2 m,<br />
except -<br />
in a doorway it may be reduced to not less than 1.9 m.<br />
WIDTH OF ESCAPE ROUTES<br />
E5.13 The aggregate unobstructed width in mm of all escape routes from a room, or storey must be at least<br />
5.3 x the occupancy capacity of the room or storey,<br />
except-<br />
in an enclosed shopping centre with a mall on not more than 2 storeys complying with E7.2, E7.3 and<br />
E7.4.<br />
E5.14 The unobstructed width of each individual escape route from a room or storey must be at least 1200 mm,<br />
except -<br />
a. where the room or storey is inaccessible to wheelchair users the width may be reduced to not less<br />
than 1100 mm; and<br />
b. where the occupancy capacity of the room or storey is not more than 100 and it is inaccessible to<br />
wheelchair users the width may be reduced to not less than 1000 mm.<br />
Amdt: September 2001<br />
20E
21E<br />
E5.15 – E5.19<br />
E5.15 An escape route must be free of any obstruction or barrier, other than a doorway which has a clear<br />
opening width in accordance with the diagram to this standard, not more than 150 mm less than the<br />
minimum width of the escape route,<br />
except-<br />
a. where the number of people using the escape route is not more than 225, the clear opening width<br />
of the doorway may be reduced to 850 mm; and<br />
b. where the number of people using the escape route is not more than 100, the clear opening width<br />
of the doorway may be reduced to 750 mm.<br />
Diagram to E5.15: Measurement of clear opening width<br />
E5.16 An escape route must not narrow in the direction of escape,<br />
except-<br />
a. an escape route may pass through a wider circulation area leading to a narrower circulation area<br />
provided the latter is of a width at least that required for the escape route; and<br />
b. where permitted by E6.1a.<br />
E5.17 A door opening into an escape route must not when being opened and when fully open, reduce the<br />
width of the escape route to less than that required by E5.14.<br />
E5.18 An emergency door, and a door across an escape route, must open in the direction of escape,<br />
except -<br />
a. a door other than an emergency door which is a revolving door, an automatic sliding door or an<br />
automatic door, as permitted by E5.11e, and a sliding door across an escape route to which the<br />
public does not have access; and<br />
b. a door other than an emergency door across an escape route where the escape route is from a<br />
room or storey, other than a place of special fire risk, having an occupancy capacity not more<br />
than -<br />
i. in a building of purpose groups 2 to 5 or purpose sub-group 7C, 60, or<br />
ii. in a building of purpose group 6 or purpose sub-group 7A or 7B, 10.<br />
DOORS ACROSS ESCAPE ROUTES<br />
E5.19*Where a door across an escape route has to be secured against entry when the building is occupied it<br />
must be fitted only with a suitable lock or fastening which is readily operated, without a key, from the<br />
side approached by people making an escape,<br />
except -<br />
in the case of a place of lawful detention.<br />
clear opening width<br />
Amdt: September 2001<br />
E
E<br />
E5.20 – E5.22<br />
E5.20*In a building of purpose group 2 to 5 with an occupancy capacity more than 60, where a door across an<br />
escape route has to be secured against entry when the building is occupied, every lock or fastening must<br />
be suitable, and be capable of being over-ridden when depressed by hand or body pressure,<br />
except -<br />
in the case of a place of lawful detention.<br />
CIRCULATION IN CONFINED SPACES<br />
E5.21 In any building the width of any gangways and stairways within a storage area containing fixed obstructions<br />
(including fixed racking or shelving and high-bay storage) must be not less than 530 mm,<br />
except -<br />
in a store for the bulk storage of spirituous liquor, gangways may be reduced to not less than 400 mm.<br />
E5.22 In a building, or part of a building with fixed seating or fixed seating and fixed tables or other floor<br />
fixtures, there must be access to an exit by way of a gangway or a seatway, or a circulation area in<br />
accordance with the table and diagram to this standard, and -<br />
a. escape from any point shall be by way of a gangway or from a seatway by way of a gangway to<br />
an exit or from a seatway directly to an exit; and<br />
b. in the case of a room in an auditorium that requires more than 1 exit -<br />
Amdt: September 2001<br />
i. at least 1 exit must be provided not less than two-thirds of the distance from any stage,<br />
screen or performing area to the back of the room, and<br />
ii. a gangway must be provided at each end of a row of more than 12 fixed seats; and<br />
c. in the case of a building of purpose group 4 where the room or part of the room has an occupancy<br />
capacity of more than 100, the minimum width of a circulation area must comply with<br />
E5.13 as if the circulation area were an escape route.<br />
Table to E5.22: Minimum width of gangways and seatways in a room with fixed seating<br />
Situation Number of seats in row Minimum width or<br />
Gangway one side Gangway on both sides effective width (mm)<br />
Gangway Not applicable Not applicable 1200 [1]<br />
Gangway and seatway<br />
combined<br />
Not applicable Not applicable 1350<br />
Seatway 2 2-4 Not applicable<br />
3-7 5-14 300<br />
8 15, 16 325<br />
9 17, 18 350<br />
10 19, 20 375<br />
11 21, 22 400<br />
12 23, 24 425<br />
- 25, 26 450<br />
- 27, 28 475<br />
- More than 28 (limited by<br />
travel distance)<br />
500<br />
Note:<br />
1. May be reduced to 900 mm where the occupancy capacity of the room is not more than 60.<br />
22E
Diagram to E5.22: Minimum width of gangways and seatways in a room or space with fixed seating<br />
gangway and<br />
seatway<br />
combined<br />
at least<br />
1350mm<br />
23E<br />
E5.22, E5.23<br />
Plan of room with provision for<br />
Method of measuring seatway widths<br />
fixed seating<br />
Note:<br />
1. 900 mm where the room or the space has an occupancy capacity of not more than 60 persons.<br />
SMOKE CONTROL IN CORRIDORS<br />
E5.23*For purposes of smoke control a corridor must be subdivided with a wall or screen with fire doors (see<br />
D11.4) as follows -<br />
a. where the corridor provides at least 2 directions of escape and is more than 12 m in length<br />
between the exits it serves, it must be divided in the middle third of the corridor; and<br />
b. where the corridor is a dead end more than 4.5 m long and provides access to a point from which<br />
more than 1 direction of escape is possible, it must be divided at that point or points, as shown in<br />
the diagram to this standard,<br />
except -<br />
seatways<br />
at least<br />
1200mm [1]<br />
at least<br />
1200mm [1]<br />
effective width<br />
of seatway<br />
a. fixed seating<br />
effective width<br />
of seatway<br />
b. automatic tip-up fixed seating<br />
effective width<br />
of seatway<br />
c. fixed seating<br />
and fixed table<br />
in a building of purpose sub-group 2B or purpose groups 3 to 7 where the corridor has a suitable system<br />
of pressurisation.<br />
Amdt: September 2001<br />
E
E<br />
E5.23 – 5.25<br />
Diagram to E5.23b: Doors across escape routes<br />
GALLERIES<br />
to<br />
exit<br />
E5.24 A gallery must be open above and below to the room into which it projects and must not give access to<br />
any other room other than a room with a means of escape independent of the gallery,<br />
except -<br />
it may be wholly or partly enclosed below where -<br />
a. the floor of the gallery has the level of fire safety performance as set out in D11.6; and<br />
b. at least 1 escape route is by way of a protected zone.<br />
ESCAPE PAST OPENINGS IN THE FLOOR<br />
E5.25 In a building where there is an opening in any floor, not being a separating floor or compartment floor<br />
(for these see D3 and D5) -<br />
a. escape from any point on the floor not more than 4.5 m from the opening must be directly away<br />
from the opening; and<br />
Amdt: September 2001<br />
no max. length<br />
but controlled<br />
by max. for<br />
single direction<br />
travel distance.<br />
single direction<br />
travel to EXIT<br />
A<br />
2 - direction travel<br />
B<br />
A<br />
EXIT<br />
A<br />
24E<br />
to<br />
exit<br />
this door must be provided<br />
at junction shown<br />
single direction travel<br />
max. travel distance<br />
from any point in a<br />
room to centre line<br />
of corridor B = max. for single<br />
direction travel<br />
2 - direction travel<br />
to EXITS A and<br />
fire door at point where 2-direction<br />
travel is possible<br />
B<br />
EXIT<br />
B
25E<br />
E5.25 – 5.27<br />
b. the escape route from any point on the storey more than 4.5 m from the opening must pass no<br />
closer to the opening than 4.5 m (see Diagram to this standard),<br />
except -<br />
where more than one escape route is provided and at least 1 escape route is at least 4.5 m from the<br />
opening.<br />
Diagram to E5.25: Openings between floors<br />
PLACES OF SPECIAL FIRE RISK<br />
E5.26 A place of special fire risk must be separated from an escape route by a protected lobby (see D11.2)<br />
where the escape route is in a protected zone serving another part of the building.<br />
AIR SUPPORTED STRUCTURES<br />
at least 4.5m<br />
at least 4.5m<br />
E5.27 An air supported structure must be designed and constructed so that -<br />
a. travel distance in one direction is not more than 9 m; and<br />
b. every exit is at least 3 m, or one quarter of the smallest plan dimension, whichever is less, from<br />
any corner of the structure; and<br />
c. every exit has a rigid supporting framework and be clearly marked ‘EXIT’ by means of an illuminated<br />
sign; and<br />
d. inflation equipment includes a standby power system which -<br />
i. will start up automatically on any failure of the main power supply, and<br />
ii. is independent of the main power supply, and<br />
B<br />
A<br />
opening<br />
iii. includes weather protected, non-return dampers in the ducts, outside the structure; and<br />
e. where the occupancy capacity exceeds 100, or in the case of a swimming pool 50, an emergency<br />
support system is provided which will -<br />
i. support the membrane in a deflated state under short term loading conditions, and<br />
ii. give escape routes a headroom of at least 2.5 m for at least 10 m adjacent to every exit;<br />
and<br />
f. where it covers a swimming pool, egress steps from the water are adjacent to an exit from the<br />
building.<br />
A<br />
B<br />
Storey Exit<br />
See E5.25a<br />
See E5.25b<br />
Amdt: September 2001<br />
E
E<br />
E6.1, E6.2<br />
E6 Means of escape from fire in a building of purpose groups 2-7<br />
(design for vertical escape)<br />
WIDTH OF ESCAPE STAIRS<br />
E6.1 The width of an escape stair must be at least the width required for any escape route giving access to it,<br />
except -<br />
a. where the number of people using the escape route is not more than 225, it may be reduced to<br />
not less than 1100 mm; and<br />
b. where the number of people using the escape route is not more than 100, it may be reduced to<br />
not less than 1000 mm.<br />
Note:<br />
See S3.4 for method of measurement.<br />
E6.2 Where the escape routes from a storey consist solely of escape stairs, and the storey requires 2 or more<br />
escape stairs, the width of every escape stair in mm from that storey must be at least 5.3 x the appropriate<br />
capacity (see E6.4) divided by the number of such stairs, less one,<br />
except -<br />
a. where there is a protected lobby (see D11.2) between each escape stair in a protected zone and<br />
any part of the building at any storey from which there is access to the escape stair, other than<br />
the topmost storey, the provision as to less one escape stair does not apply;<br />
b. where the topmost storey contains plant and it is not accessible for a purpose other than the<br />
maintenance of the plant the width of any escape stair from this storey to the storey immediately<br />
below needs to comply only with the requirements of Part S for industrial stairs and fixed<br />
ladders;<br />
c. where escape routes from a storey consist of a combination of escape stairs and other escape<br />
routes (see Diagram to this standard) the width of any escape stair from that storey may be<br />
designed to take into account that proportion of the number of occupants on that storey who may<br />
escape by way of the other escape routes.<br />
Amdt: September 2001<br />
26E
Diagram to E6.2: Width of escape stairs<br />
escape to place of<br />
safety or to<br />
escape stair<br />
place of safety<br />
access to<br />
escape stair<br />
ground storey<br />
27E<br />
escape stair<br />
E6.2 – E6.4<br />
storey which has escape by<br />
way of an escape stair and<br />
another escape route.<br />
[see E4.2]<br />
place of safety<br />
E6.3 Where the escape route from an escape stair is also the escape route from the ground and/or basement<br />
storey its width shall be increased to take account of that proportion of the occupancy capacity of the<br />
ground and/or basement storey served by the escape route, and unless access to the escape route on the<br />
ground storey is by way of a protected lobby (see D11.2) 1 escape route from the ground storey into a<br />
protected zone containing an escape stair must be discounted.<br />
E6.4 The appropriate capacity in relation to a suitable escape stair at any storey above or below the place of<br />
safety is -<br />
a. the occupancy capacity of the part of the storey or room served by the escape stair, provided the<br />
escape stair does not also serve the next storey or room above or in the case of a basement storey,<br />
the next storey below; or<br />
b. where the escape stair serves 2 or more storeys including any rooms, or part of a building, which<br />
is not divided by compartment floors, the occupancy capacity of the part of each storey, including<br />
any room, served at and above or below as the case may be, by the escape stair less 20% (20%<br />
represents standing capacity within the protected zone containing the escape stair). At each<br />
storey level the appropriate capacities must be accumulated in respect of those storeys which at<br />
that level have been served by the escape stair. The total appropriate capacity for all the storeys<br />
served by the escape stair must be taken into account at the storey level where the escape route<br />
leads to a place of safety; or<br />
c. in a building, or part of a building, which is divided by 1 or more compartment floors, the total<br />
occupancy capacity, less 20%, of -<br />
i. each of the 2 adjacent upper storeys, 1 or both of which may be a room, served by the<br />
escape stair, or in the case of an escape stair serving a basement storey the 2 adjacent<br />
basement storeys served by that escape stair, having in either case the greatest combined<br />
occupancy capacity, or<br />
Amdt: September 2001<br />
E
E<br />
E6.4, E6.5<br />
Amdt: September 2001<br />
ii. the compartment either above or below ground level served by the escape stair having the<br />
greatest occupancy capacity, discounting the occupancy capacity of any storey within the<br />
compartment which is not served by the escape stair, whichever is the greater of either<br />
sub-clause c.i. or c.ii.<br />
Diagram to E6.4: Calculation of appropriate capacity<br />
1<br />
G<br />
B b. L = OC of storeys 1, 2, 3<br />
a. L 1 = OC of storey 1<br />
L 2 = OC of storey B<br />
5<br />
4<br />
3<br />
2<br />
1<br />
G<br />
100<br />
200<br />
400<br />
200<br />
200<br />
c.ii. L = OC of compartment ll (700)<br />
3<br />
2<br />
1<br />
G<br />
compartment ll<br />
compartment l<br />
Notes:<br />
1. L = Appropriate capacity.<br />
2. OC = Occupancy capacity of storey.<br />
3. G = Ground storey.<br />
4. B = Basement storey.<br />
5. Numbers 100, 150 etc. relate to occupancy capacity of each storey.<br />
6. Figure numbers refer to paragraph numbers in E6.4.<br />
7. For simplicity, the 20% reduction factor has not been applied to above examples.<br />
E6.5 Where the escape routes from a storey consist of a combination of escape stairs and other escape routes,<br />
the appropriate capacity of the storey is that proportion of the occupancy capacity of the storey which<br />
the aggregate width of escape routes discharging to the stairs bears to the aggregate width of all escape<br />
routes from the storey.<br />
28E<br />
compartment lll<br />
compartment ll<br />
compartment l<br />
5<br />
4<br />
3<br />
2<br />
1<br />
G<br />
3<br />
2<br />
1<br />
G<br />
150<br />
200<br />
100<br />
c.i. L = OC of storeys 2, 3 (350)<br />
105<br />
200<br />
200<br />
600<br />
300<br />
c.ii. L = OC of compartment l (900)
PROTECTED ZONES<br />
E6.6 An escape stair must be within a protected zone (see D11.1),<br />
except -<br />
a. an escape stair which connects 2 or more levels within a single storey where the difference in<br />
height between the highest and lowest level is not more than 1.8 m; or<br />
b. an escape stair which leads from a gallery, catwalk or openwork floor to a room in which the<br />
gallery, catwalk or openwork floor is situated and the gallery, catwalk or openwork floor -<br />
i. has an occupancy capacity of not more than 60, or<br />
ii. has an occupancy capacity of 61 to 100, and at least 1 escape stair from the gallery,<br />
catwalk or openwork floor is within a protected zone, or<br />
iii. has an occupancy capacity of 61 to 100, and at least 1 external escape stair which complies<br />
with sub-clauses d. or e. below, and<br />
29E<br />
E6.6<br />
iv. where there is a gallery, catwalk or openwork floor complying with sub-clauses b.ii. or iii.<br />
above at more than 1 level within the room an unenclosed escape stair may be provided<br />
only between the floor of the room and the lowest gallery, catwalk or openwork floor; or<br />
c. a fixed ladder as permitted by E5.11g; or<br />
d. an external escape stair which has a total rise of not more than 1.6 m and leads directly to a<br />
place of safety; or<br />
e. an external escape stair which has a total rise more than 1.6 m but not more than 6 m and -<br />
i. the escape stair leads directly to a place of safety, and<br />
ii. in the case of a building of purpose sub-group 2A the escape stair is intended to serve<br />
accommodation occupied only by staff, and<br />
iii. in the case of a building of purpose group 4 and 5 the escape stair is not intended for use<br />
by members of the public.<br />
Amdt: September 2001<br />
E
E<br />
E6.6 – E6.9<br />
Diagram to E6.6: Escape stair enclosure and external escape stairs<br />
Amdt: September 2001<br />
at least 2m escape route height<br />
in room with fixed seating<br />
MAIN FLOOR<br />
OF ROOM<br />
E6.7 A protected zone enclosing an escape stair must be provided with an unobstructed clear wheelchair<br />
space measuring not less than 700 mm x 1200 mm on every escape stair landing to which there is<br />
access from a storey,<br />
except -<br />
a. a storey which has level or ramped access to a place of safety; or<br />
b. a storey in a hospital; or<br />
c. a storey which is inaccessible to wheelchair users.<br />
E6.8 A protected zone enclosing an escape stair must enclose no other rooms,<br />
except-<br />
a. a toilet or toilets;<br />
b. a washroom or washrooms;<br />
c. where the escape stair serves part of a building which has at least one other escape route,<br />
i. a reception room, but not a waiting area,<br />
ii. an office,<br />
iii. a cleaner’s room of not more than 3 m 2 ,<br />
iv. a store which has a floor area of not more than 10 m 2 .<br />
E6.9 Every escape stair must give access directly to -<br />
a. a place of safety; or<br />
b. an escape route across a flat roof (see E5.9g); or<br />
c. an access deck; or<br />
30E<br />
GALLERY<br />
at least 2m escape route<br />
height in room with<br />
fixed seating<br />
RAISED FLOOR<br />
un-enclosed escape stair<br />
not more than 1.8m<br />
at least 1.8m<br />
for gallery
d. a hospital street; or<br />
31E<br />
E6.9 – E6.13<br />
e. in the case of an enclosed shopping centre provided with appropriate smoke and heat exhaust<br />
ventilation system (see D3.7), the mall, provided alternative escape not via the mall is also provided<br />
from each shop or other unit having a frontage to the mall.<br />
E6.10 Where 2 protected zones enclosing escape stairs share a common wall, any access between them must<br />
be by way of a protected lobby (see D11.2).<br />
E6.11 A building with more than 1 escape route contained in a central core must be planned so that the exits<br />
from the storey are remote from one another, and so that no 2 exits are approached from the same lift<br />
hall, common lobby or undivided corridor or linked by any of these except through fire doors as shown<br />
in the diagram to this standard -<br />
Diagram to E6.11: Protected zone: escape stairs in a central core<br />
Notes:<br />
1. Possible alternative position of fire doors shown dotted.<br />
2. If escape stair serves a storey at a height of more than 18 m, a lobby is<br />
required (see E6.14).<br />
E6.12 Where an escape stair also serves a basement storey the protected zone enclosing the escape stair in the<br />
basement storey must be separated from the protected zone containing the escape stair serving the rest<br />
of the building by a wall or screen, with or without a door, at ground storey floor level having at least<br />
the level of fire safety performance of the protected zone (see D11.1).<br />
E6.13 Where a building has not more than 1 escape stair, access to it must be by way of a protected lobby (see<br />
D11.2),<br />
except -<br />
a. in shared residential accommodation; or<br />
lift<br />
lift<br />
lift lobby<br />
(may also<br />
serve<br />
washrooms,<br />
services etc)<br />
lift<br />
lift<br />
doors to accomodation (not shown) may<br />
be placed anywhere in this wall<br />
Amdt: September 2001<br />
E
E<br />
E6.13 – E7.5<br />
b. at the topmost storey not being the escape stair exit storey; or<br />
c. where the escape stair serves not more than 1 basement storey.<br />
E6.14 Where an escape stair serves a storey at a height of more than 18 m access to the protected zone containing<br />
the escape stair must be by way of a protected lobby (see D11.2).<br />
E7 Special requirements for means of escape for enclosed<br />
shopping centres with malls<br />
DIRECTION OF TRAVEL<br />
E7.1 An enclosed shopping centre with a mall must be designed so that from every part of the mall and from<br />
every mall-level shop there must be at least 2 directions of travel leading to a place of safety without<br />
passing through any space in single occupation,<br />
except -<br />
a kiosk not more than 25 m 2 and in which either the public are not admitted, or the depth from the mall<br />
is not greater than 5 m.<br />
ESCAPE ROUTE WIDTH<br />
E7.2 The aggregate unobstructed width in mm of all escape routes from the mall in an enclosed shopping<br />
centre with a mall, must be at least 2.65 x the occupancy capacity of the entire shopping centre, (i.e. the<br />
mall and all shops),<br />
except -<br />
a shop, or shops, with a floor area more than 1300 m 2 and where the means of escape has been designed<br />
independently of the mall need not be included in the calculation.<br />
E7.3 The aggregate unobstructed exit width in mm from each shop in an enclosed shopping centre with a<br />
mall, to the mall must be at least 5.3 x the occupancy capacity of the shop.<br />
except -<br />
a shop, or shops, with a floor area more than 1300 m 2 and where the means of escape has been designed<br />
independently of the mall.<br />
E7.4 The aggregate unobstructed exit width in mm from each shop in an enclosed shopping centre with a<br />
mall, to a route which does not enter the mall must be at least 5.3 x the occupancy capacity of the shop.<br />
except -<br />
a. a shop, or shops, with a floor area more than 1300 m 2 and where the means of escape has been<br />
designed independently of the mall, and<br />
b. a kiosk not exceeding 25 m 2 and in which either the public are not admitted, or the depth from<br />
the mall is not more than 5 m.<br />
E7.5 The unobstructed width of each individual exit from the mall in an enclosed shopping centre with a mall<br />
must be at least 1.8 m wide.<br />
Amdt: September 2001<br />
32E
33E<br />
E7.6 – E8.3<br />
E7.6 In an enclosed shopping centre with a mall, where a service corridor is used for means of escape directly<br />
from a shop or shops, the unobstructed width must be based on the total number of occupants of the largest<br />
shop that evacuates into the corridor, plus, other than at column positions, an additional width of 1 m.<br />
E7.7 In an enclosed shopping centre with a mall, where a service corridor is used for means of escape directly<br />
from a shop or shops, such service corridor must not be used for any form of storage.<br />
CRÈCHES<br />
E7.8 Every crèche provided within an enclosed shopping centre with a mall must be designed so that it is -<br />
a. at ground level or exit level; and<br />
b. not sited on a storey higher than those where parents or guardians may be located, unless escape<br />
is via the upper storey itself; and<br />
c. located adjacent to an external wall and has at least 2 exits, one of which must be directly to a<br />
place of safety.<br />
E8 Special requirements for means of escape for hospitals<br />
STOREYS AT A HEIGHT OF MORE THAN 7.5 m<br />
E8.1 In a hospital every storey at a height of more than 7.5 m containing departments to which patients have<br />
access, must either:<br />
a. comprise at least 4 compartments, each of which must have an area of at least 500 m 2 ; or<br />
b. have a hospital street (see E8.9) and at least 3 other compartments.<br />
STOREYS AT A HEIGHT OF MORE THAN 18 m<br />
E8.2 In a hospital every storey at a height of more than 18 m containing departments to which patients have<br />
access, must either -<br />
a. comprise at least 4 compartments, each of which must have an area of at least 500 m 2 ; or<br />
b. have a hospital street (see E8.9) and at least 3 other compartments each of which must have an<br />
area of at least 500 m 2 .<br />
COMPARTMENT EXITS<br />
E8.3 In a hospital where a storey is divided into three or more compartments, each compartment must have<br />
exits to -<br />
a. a compartment and a hospital street; or<br />
b. a compartment and an escape stair; or<br />
c. a compartment and a final exit.<br />
Amdt: September 2001<br />
E
E<br />
E8.4 – E8.9<br />
ESCAPE ROUTES<br />
E8.4 An escape route from a hospital department to which patients have access, must be (see E5.3 and E5.4)<br />
to -<br />
a. a place of safety; or<br />
b. a protected zone; or<br />
c. an unprotected zone in another compartment or sub-compartment,<br />
except -<br />
in the case of an escape route from a ward bedroom it may be to another ward bedroom in a different<br />
compartment or sub-compartment.<br />
E8.5 In a hospital the unobstructed width of every escape route intended to be used by patients who require<br />
bed evacuation must be at least 1500 mm.<br />
ESCAPE STAIRS<br />
E8.6* In areas of hospitals providing patient sleeping accommodation, an escape stair must be not less than<br />
1300 mm and designed to facilitate mattress evacuation.<br />
E8.7 In a hospital where an escape stair in a protected zone serves an upper storey containing a department<br />
to which patients have access, access to the protected zone must be by way of a protected lobby (see<br />
D11.2),<br />
except -<br />
in the case of a storey at a height of not more than 18m, where access can be from the hospital street<br />
(see E8.9).<br />
E8.8 Every escape stair opening into the hospital street must be located so that the travel distance from an<br />
escape stair exit to a door leading directly to a place of safety is not more than 64 m.<br />
HOSPITAL STREET<br />
E8.9 A hospital street must -<br />
a. be a protected zone; and<br />
b. have an unobstructed width of at least 3 m; and<br />
c. be divided into at least 3 sub-compartments; and<br />
d. at ground storey have at least 2 final exits; and<br />
e. at upper storeys, have access to at least 2 escape stairs accessed from separate subcompartments,<br />
which are located so that -<br />
Amdt: September 2001<br />
i. the distance between escape stairs is not more than 64 m, and<br />
ii. the distance of single direction of travel within the hospital street is not more than 15 m,<br />
and<br />
iii. the distance from a compartment exit to an escape stair is not more than 32 m; and<br />
f. not contain a shop or other commercial enterprise.<br />
34E
E8.10 A door from a hospital street to an adjoining compartment must -<br />
35E<br />
E8.10 – E9.1<br />
a. be located so that an alternative independent means of escape from each compartment is always<br />
available; and<br />
b. not be located in the same sub-compartment as a door to a protected zone containing a stairway<br />
or lift.<br />
E9 Lighting<br />
E9.1 Every part of an escape route must have artificial lighting providing a level of illumination not less than<br />
that provided by suitable emergency lighting supplied with electric current -<br />
a. by a protected circuit; and<br />
b. where it serves a protected zone, by a separate circuit from that supplying any other part of the<br />
escape route,<br />
except -<br />
except -<br />
a protected circuit is not required where emergency lighting is installed in accordance with E9.2,<br />
in a building to which Part 1 of the Cinematographic (Safety) (Scotland) Regulations 1955 apply.<br />
Amdt: September 2001<br />
E
E<br />
E9.2<br />
E9.2* Suitable emergency lighting must be provided in accordance with the table to this standard -<br />
Table to E9.2: Emergency lighting<br />
Purpose group or Part of building requiring emergency lighting<br />
sub-group<br />
1A (other than 1. A protected zone or unprotected zone in a building with a storey at a<br />
a dwelling), 2-7 height of more than 18 m.<br />
2. A room with an occupancy capacity of more than 60 or any room containing<br />
an inner room with an occupancy capacity of more than 60, and<br />
any protected zone or unprotected zone serving such a room.<br />
3. An underground car park including any protected zone or unprotected<br />
zone serving it where less than 30% of the perimeter of the car park is<br />
open to the external air.<br />
4. A protected zone or unprotected zone serving a basement storey.<br />
5. A place of special fire risk (other than one requiring access only for the<br />
purposes of maintenance) and any protected zone or unprotected zone<br />
serving it.<br />
6. Any part of an air supported structure, other than one ancillary to a<br />
dwelling.<br />
Purpose group or Requirements additional to 1-6 above<br />
sub-group<br />
2 (other than a hospital) 7. A room with an occupancy capacity of more than 10 and any protected<br />
zone or unprotected zone serving such a room.<br />
8. A protected zone or unprotected zone serving a storey required to have 2<br />
or more escape routes other than, subject to 1. above, a storey in a building<br />
not more than 2 storeys high with a floor area of not more than<br />
300 m2 .<br />
9. A protected zone or unprotected zone in a single stair building of<br />
2 storeys or more with an occupancy capacity of 10 or more.<br />
2A hospital 10. Essential lighting circuits must be provided throughout and designed to<br />
provide not less than 30 percent of the normal lighting level. [1, 2]<br />
4 11. In shop premises, a protected zone or unprotected zone serving a storey<br />
required to have 2 or more escape routes.<br />
12. In an enclosed shopping centre with a mall on 2 or more storeys or<br />
having a total floor area more than 5,600 m2 , the mall and any protected<br />
zones or unprotected zones required to have at least 2 escape routes.<br />
5 13. A protected zone or unprotected zone serving -<br />
a. a storey required to have at least 2 escape routes; or<br />
b. any storey in a non-residential school of more than one storey.<br />
6 14. A protected zone or unprotected zone serving a storey required to have at<br />
least 2 escape routes.<br />
7A 15. A protected zone or unprotected zone serving a storey required to have at<br />
least 2 escape routes, other than in a single-storey building with a floor<br />
area of not more than 500 m2 .<br />
7C 16. A protected zone or unprotected zone serving any storey.<br />
Notes:<br />
1 In an area where a 15 second response time would be considered hazardous, (e.g. a stairway),<br />
emergency lighting must be provided by battery back-up giving a response time of not more than<br />
0.5 seconds.<br />
2. The distribution boards for essential and non-essential circuits may be in the same location but<br />
must be in separate cabinets.<br />
Amdt: September 2001<br />
36E
E10 Facilities for fire-fighting<br />
ACCESS<br />
E10.1*Every building must be provided with suitable access for fire-fighting purposes.<br />
GROUND HYDRANTS<br />
37E<br />
E10.1 – E10.4<br />
E10.2*A building having a floor area more than 280 m 2 must be provided with suitably positioned and constructed<br />
ground hydrants,<br />
except -<br />
where no piped water supply is available and a suitable and adequate alternative source of supply is<br />
provided.<br />
E10.3 A ground hydrant must be connected to a water service pipe capable of delivering water at a flow rate of<br />
at least 1500 litres per minute, provided by -<br />
a. a water main vested in a public water authority; or<br />
b. a supply provided under the Fire Services Act 1947.<br />
PROVISION OF FIRE-FIGHTING FACILITIES<br />
E10.4*In a building of purpose sub-group 1A and purpose groups 2–7, at least 2 escape stairs must be provided<br />
with fire fighting facilities in accordance with the table to this standard and located so that they<br />
are,<br />
a. at least 20 m apart; and<br />
b. so that no point on any storey is further from a fire-fighting outlet than -<br />
i. 1 storey height, and<br />
ii. 60 m measured along an unobstructed route for fire hose.<br />
Amdt: September 2001<br />
E
E<br />
E10.4<br />
Table to E10.4: Provision of fire-fighting facilities<br />
Storey height Purpose groups and Purpose groups and Purpose sub-group Purpose subpurpose<br />
sub-groups purpose sub-groups 2A with a hospital group 7C<br />
1A, 2A (except those 4, 7A and 7B where street<br />
with a hospital the storey has an<br />
street), 2B, 3, 5 and 6 area of more than<br />
and 4, 7A and 7B 900 m2 where the storey has<br />
an area not more<br />
than 900 m2 Basements at a Fire-fighting shaft; Fire-fighting shaft; Fire-fighting lift; Dry fire main<br />
depth more Fire-fighting lift; Fire-fighting lift; Suitable pressure (outlet located in<br />
than 10 m Suitable pressure Suitable pressure differential control; protected zone<br />
differential control; differential control; Dry fire main (outlet enclosing escape<br />
Dry fire main (outlet Dry fire main (outlet located at every stair).<br />
located in fire-fighting located in fire-fighting departmental<br />
lobby). lobby). entrance).<br />
Basements at a No provision Fire-fighting shaft; Dry fire main (outlet Dry fire main<br />
depth not more Dry fire main (outlet located at every (outlet located in<br />
than 10 m located in fire-fighting departmental protected zone<br />
lobby). entrance). enclosing escape<br />
stair).<br />
Upper storey No provision Protected lobby; Dry fire main (outlet No provision<br />
not more Dry fire main (outlet located at every<br />
than 7.5 m located in protected departmental<br />
lobby) [1]. entrance).<br />
Storey more Protected lobby; Protected lobby; Dry fire main (outlet Dry fire main<br />
than 7.5 m and Dry fire main (outlet Dry fire main (outlet located at every (outlet located in<br />
not more than located in protected located in protected departmental protected zone<br />
18 m lobby) [1]. lobby) [1]. entrance). enclosing<br />
escape stair).<br />
Storey more Fire-fighting shaft; Fire-fighting shaft; Fire-fighting shaft; Fire-fighting lift[2];<br />
than 18 m and Fire-fighting lift [2]; Fire-fighting lift [2]; Fire-fighting lift [2]; Dry fire main<br />
not more than Dry fire main (outlet Dry fire main (outlet Dry fire main (outlet (outlet located in<br />
60 m located in fire-fighting located in fire-fighting located at every protected zone<br />
lobby). lobby). departmental enclosing<br />
entrance). escape stair).<br />
Storey more Fire-fighting shaft; Fire-fighting shaft; Fire-fighting shaft; Fire-fighting lift [2];<br />
than 60 m Fire-fighting lift [2]; Fire-fighting lift [2]; Fire-fighting lift [2]; Wet fire main<br />
Wet fire main (outlet Wet fire main (outlet Wet fire main (outlet (outlet located in<br />
located in fire-fighting located in fire-fighting located at every protected zone<br />
lobby). lobby). departmental enclosing escape<br />
entrance). stair).<br />
Notes:<br />
1 The protected lobby provided must have an area of at least 5 m 2 .<br />
2 A fire-fighting lift need not serve the top storey of a building where the top storey is for service<br />
plant use only and is equipped with a wet or dry fire main and a fire-fighting outlet wherea.<br />
there is access to an escape stair from the storey below, and<br />
b. the foot of the escape stair is not more than 4.5 m from a fire-fighting lift.<br />
Amdt: September 2001<br />
38E
39E<br />
E10.5 – E10.11<br />
E10.5 Every single storey hospital with a hospital street must be provided with a dry fire main with an outlet<br />
located in the hospital street at every hospital departmental entrance,<br />
except -<br />
a dry fire main need not be provided where no part of the storey is more than 60 m measured along an<br />
unobstructed route, not being a protected zone, for the fire hose from the access point or points.<br />
E10.6 Every single storey shopping mall must be provided with a dry fire main with an outlet located not more<br />
than 5 m from a Fire Brigade access point,<br />
except-<br />
a dry fire main need not be provided where no part of the storey is more than 60 m measured along an<br />
unobstructed route, not being a protected zone, for the fire hose from the access point or points.<br />
E10.7*A wet fire main must be of suitable construction and, where an inlet is provided for the emergency<br />
replenishment of the suction tank, provided with a parking space for a pumping appliance located -<br />
a. i. when one such inlet is provided, not more than 18 m from the inlet, or<br />
ii. when more than 1 such inlet is provided, not more than 18 m from the inlet nearest an<br />
appropriately located entrance, and sited not more than 60 m from all other inlets; and<br />
b. sited so that there is a clear route for the hose between the pumping appliance access and the wet<br />
riser inlet.<br />
E10.8*A dry fire main must be of suitable construction, and where there is -<br />
a. i. 1 such fire main, the inlet must be located not more than 18 m from a parking space for a<br />
pumping appliance, or<br />
ii. more than 1 such fire main, the inlet must be located not more than 18 m from a parking<br />
space for a pumping appliance to the inlet at an appropriately located entrance, and sited<br />
not more than 60 m from all other inlets; and<br />
b. sited so that there is a clear route for the hose between the pumping appliance access and the dry<br />
riser inlet.<br />
E10.9*A fire-fighting shaft must be provided with -<br />
a. a suitably constructed and ventilated fire-fighting lobby, having not more than 1 door to the room<br />
or storey it serves; and<br />
b. suitable provision for the control of smoke.<br />
E10.10 A fire-fighting shaft must serve all storeys in a building,<br />
except -<br />
a. a fire-fighting shaft serving an upper storey need not serve a basement storey unless it is required<br />
by the Table to E10.4; and<br />
b. a fire-fighting shaft serving a basement storey need not serve an upper story unless it is required<br />
by the Table to E10.4.<br />
E10.11*A fire-fighting lift must be of a suitable construction and entered only from -<br />
a. a fire-fighting lobby having not more than 1 door to the room or storey it serves; or<br />
b. an open access balcony or an access deck.<br />
Amdt: September 2001<br />
E
E<br />
E10.12 – E10.16<br />
E10.12An enclosed shopping centre with a mall on 2 or more storeys or having a total floor area more than<br />
5600 m 2 must have a fire control room -<br />
a. constructed as a separate compartment (see D3); and<br />
b. with access points away from the discharge points for the public and with an alternative means of<br />
escape; and<br />
c. located adjacent to a fire service access point and accessible from open air.<br />
SMOKE VENTILATION OF ESCAPE ROUTES<br />
E10.13 An escape stair within a protected zone must have -<br />
a. a ventilator of not less than 1 m 2 at the top of the stair; or<br />
b. an opening window at each storey.<br />
E10.14 Every access corridor or part of an access corridor, in a building of purpose sub-group 1A, must be<br />
provided with openable ventilators, with an aggregate opening area to the external air of at least 1.5 m 2<br />
and providing for exhaust at or near ceiling level and for supply at or near floor level,<br />
except -<br />
an open access balcony or an access deck having an opening or openings to the external air extending<br />
over at least four-fifths of its length and at least one third of its height.<br />
SMOKE VENTILATION OF BASEMENT STOREYS<br />
E10.15*Suitable smoke outlets, communicating directly with the external air, must be provided from every<br />
basement storey, and where the basement storey is divided into compartments from every compartment<br />
of the basement storey,<br />
except -<br />
a. in a building of purpose sub-groups 1B, 1C or 7C; or<br />
b. where the floor area of the basement storey is not more than 200 m 2 ; or<br />
c. where the basement storey is at a depth of not more than 4.5 m; or<br />
d. where a window or windows opening direct to the external air have a total area not less than 1%<br />
of the floor area; or<br />
e. where the basement storey or part of the basement storey is used as a strong room; or<br />
f. where the basement storey has an appropriate fire control system and is ventilated by a suitable<br />
mechanical smoke and heat extraction system.<br />
ROLLING SHUTTERS<br />
E10.16 All rolling shutters in compartment walls (see D3.14) must be capable of being opened and closed<br />
manually by the Fire Brigade.<br />
Amdt: September 2001<br />
40E
E11 Means of warning of fire<br />
E11.1*A dwelling must be provided with -<br />
41E<br />
E11.1 – E11.3<br />
a. where any storey is not more than 200 m 2 , at least 1 smoke alarm suitably located on each storey;<br />
or<br />
b. where any storey is more than 200 m 2 , a suitable fire detection and alarm system.<br />
E11.2*A building in purpose group 2 must be provided with a suitable fire detection and alarm system.<br />
E11.3*An enclosed shopping centre with a mall on 2 or more storeys or having a total floor area more than<br />
5600 m 2 , must be provided with a suitable fire detection and alarm system.<br />
Amdt: September 2001<br />
E
E<br />
(E2.4, E5.11, E2.11, E2.12)<br />
Provisions deemed to satisfy the standards<br />
REVOLVING DOOR, SLIDING DOOR OR AUTOMATIC DOOR<br />
(E2.4)(E5.11)<br />
The requirements of E2.4e and E5.11e for a revolving door, sliding door or automatic door will be met<br />
by a door which complies with BS 7036: 1996; and<br />
a. is arranged to fail safely to outward opening from any position of opening; or<br />
b. i. is provided with a monitored fail-safe system for opening the door from any position in<br />
the event of mains supply failure and also in the event of a failure of the opening sensing<br />
device, and<br />
Amdt: September 2001<br />
ii opens automatically from any position in the event of the actuation of any fire alarm in the<br />
fire alarm zone within which the door is situated, and<br />
iii. permits easy manual opening from any position.<br />
AUTOMATIC OPENING VENTILATORS<br />
(E2.11)(E2.12)<br />
Where suitable automatic opening ventilators are required under E2.11 and E2.12, they should -<br />
a. have an aggregate opening area of at least 1.5 m 2 ; and<br />
b. provide for exhaust at or near ceiling level and for supply at or near floor level; and<br />
c. be activated by automatic smoke detection fixed to the ceiling of -<br />
i. the protected lobby in the case of E2.11, or<br />
ii. located in the corridor in the case of E2.12 and fitted with a manual override for fire<br />
service use.<br />
Note:<br />
Detectors should be evenly spaced and -<br />
A. with the distance between the detectors not more than 20 m; and<br />
B. at least 500 mm from any side of the lobby or corridor; and<br />
C. with the detector-sensing element more than 35 mm and not more than 300 mm from the<br />
soffit of the ceiling; and<br />
D. with a detector situated not more than 5 m from any change of direction in the lobby or<br />
corridor exceeding 45º; and<br />
E. with any part of a lobby or corridor divided from any other part by a beam or other<br />
obstruction projecting more than 600 mm below the soffit of the ceiling shall be deemed<br />
to be a separate lobby or corridor.<br />
42E
FIRE DETECTION AND ALARM SYSTEM<br />
43E<br />
(E2.14 – E8.6)<br />
(E2.14)The requirements of E2.14b.iii will be met when smoke alarms are provided in each dwelling as specified<br />
in E11.1, and an alarm and detection system complying with BS 5839: Part 1: 1988 Type L2 is<br />
installed in the common areas.<br />
EMERGENCY ESCAPE WINDOWS<br />
(E2.17)(E3.2)<br />
The requirements of E2.17 and E3.2 will be met by a window, or a door (french window) -<br />
a. situated in an external wall or roof; and<br />
b. having an unobstructed openable area that is at least 0.33 m 2 and at least 450 mm high and<br />
450 mm wide (the route through the window maybe at an angle rather than straight through); and<br />
c. where the bottom of the openable area is not more than 1100 mm above the floor.<br />
FIXED LADDERS<br />
(E5.11)The requirements of E5.11g will be met by a fixed ladder which complies with the recommendations of<br />
BS 5395: Part 3: 1985.<br />
DOORS ACROSS ESCAPE ROUTES<br />
(E5.19)(E5.20)<br />
The requirements of E5.19 and E5.20 for a suitable lock or fastening will be met when it is in accord<br />
with the guidance in the Builders Hardware Industry Federation, Code of Practice, “Hardware for<br />
Timber Fire and Escape Doors”.<br />
PRESSURISATION<br />
(E5.23) The requirements of E5.23 for pressurisation will be met by a smoke control system employing pressure<br />
differentials in accordance with BS 5588: Part 4: 1998, but assuming a minimum pressure of 25 Pa<br />
based on a wind speed of 22 m/sec.<br />
MATTRESS EVACUATION STAIRS<br />
(E8.6) The requirement of E8.6 will be met by a stair having the landing configuration appropriate to its width<br />
as specified in the table to this specification -<br />
Table to (E8.6): Stair and landing configuration for mattress evacuation<br />
Stair width (mm) Minimum landing width (mm) Minimum landing depth (mm)<br />
1300 2800 1850<br />
1400 3000 1750<br />
1500 3200 1550<br />
1600 3400 1600<br />
1700 3600 1700<br />
1800 3800 1800<br />
Amdt: September 2001<br />
E
E<br />
(E9.2, E10.1)<br />
EMERGENCY LIGHTING<br />
(E9.2) The requirements of E9.2 will be met where emergency lighting is installed in -<br />
ACCESS<br />
a. cinemas, bingo halls, ballrooms, dance halls and bowling alleys, in accordance with CP1007:<br />
1955; and<br />
b. any other building, in accordance with BS 5266: Part 1: 1999.<br />
In the case of a building with a smoke and heat exhaust ventilation system the emergency lighting<br />
should be installed so that it is not rendered ineffective by smoke filled reservoirs.<br />
(E10.1) The requirements of E10.1 will be met in the case of a house where an access route is provided from a<br />
public road, in accordance with the table to this specification, to not more than 45 m from a door giving<br />
direct access to the interior of the house.<br />
The requirements of E10.1 will be met in the case of a building, other than a house, where -<br />
a. an access route is provided, or in the case of a hospital more than 1 access route, from a public<br />
road, in accordance with the table to this specification, as prescribed in E10.2, E10.7 and E10.8<br />
and to the rear of the building when -<br />
Amdt: September 2001<br />
i. the building has any storey more than 900 m 2 , or<br />
ii. the building has a perimeter more than 150 m, or<br />
iii. pedestrian access is not possible around the building; and<br />
b. in consultation with the Fire Authority, it is determined that an operating space or spaces for a<br />
high reach appliance is required, the operating space(s) -<br />
i. is at least 6 m wide and 20 m long, with the nearer edge at least 2.2 m from the face of the<br />
building, and<br />
ii. has an unobstructed air space of at least 2.2 m beyond the further edge of the operating<br />
space (see diagram below), and<br />
iii. has a ground loading capacity of the operating space not less than 8.3 kg/cm 2 , and<br />
iv. is level or does not have a gradient more than 1 in 12; and<br />
c. every perimeter wall (elevation) to which vehicle access is required has a door giving access to<br />
the interior of the building.<br />
The requirements of E10.1 will be met, in the case of every building where a turning facility is provided<br />
in any dead-end route that is more than 20 m long. This may be a hammerhead or turning circle,<br />
designed on the basis of the table to this standard as appropriate.<br />
44E
45E<br />
(E10.1, E10.2)<br />
Table to (E10.1): Access route requirements for fire-fighting vehicles<br />
Minimum Minimum Minimum Minimum Minimum Surface capable<br />
width of width of clearance turning turning of supporting a<br />
road gateways height (m) circle circle minimum axle<br />
between etc (m) between between loading (tonnes)<br />
kerbs (m) kerbs (m) walls (m)<br />
House 3.7 3.5 3.7 16.8 19.2 14<br />
Building other<br />
than a house [1]<br />
Note:<br />
3.7 3.5 4.0 26.0 29.0 14<br />
1. Where, in consultation with the Fire Authority, access is provided for pumping appliances only,<br />
the dimensions for a house may be used.<br />
Diagram to (E10.1): Dimensions of operating space for high reach fire appliances<br />
GROUND HYDRANTS<br />
building<br />
OPERATING<br />
SPACE at least 6 m wide<br />
not more than 2.2 m from the building<br />
at least 20 m long<br />
at least 2.2 m clear space for platform swing<br />
(E10.2)The requirement of E10.2 for suitably positioned and constructed ground hydrants will be met where the<br />
hydrants are -<br />
a. positioned externally, for each building or common to more than 1 building -<br />
i. not more than 60 m from an entrance to the building, and<br />
ii. distributed around the building so that no external elevation of the building is more than<br />
60 m from a hydrant, and<br />
iii. so that hydrants are at least 6 m from the building, and<br />
iv. located adjacent to a parking space for a pumping appliance, and<br />
v. where a parking space is required in E10.7 or E10.8 for a fire appliance, adjacent to the<br />
parking space, and<br />
vi so as to be accessible for use at all times, and<br />
vii. so that there is a clear route for the fire hose between the hydrant and the building; and<br />
b. constructed in accordance with BS 750: 1984.<br />
Amdt: September 2001<br />
E
E<br />
(E10.2 – E10.11)<br />
The requirements of E10.2 for an alternative source of water will be met by -<br />
a. a charged static water tank of at least 45,000 litre capacity; or<br />
b. a spring, river, canal, loch or pond, to which access and space are available for a pumping appliance,<br />
capable of providing or storing at least 45,000 litres of water for fire-fighting purposes.<br />
Note:<br />
Consultation with the Fire Authority is advised on all matters concerning ground hydrants and water<br />
supplies.<br />
FIRE-FIGHTING SHAFTS<br />
(E10.4)(E10.9)<br />
FIRE MAINS<br />
The requirement of E10.4 for suitable stair pressure differential control, of E10.9 for ventilation and of<br />
E10.9 for smoke control will be met where pressurisation and ventilation is provided in accordance with<br />
Clause 8 of BS 5588: Part 5: 1991.<br />
(E10.7)The requirements of E10.7 will be met where -<br />
a. the wet fire main is in accordance with BS 5306: Part1: 1976 (1988); and<br />
b. the landing valves conform to BS 5041: Part 1: 1987.<br />
(E10.8) The requirements of E10.8 will be met where the main is in accordance with BS 5306: Part 1: 1976<br />
(1988); and where there are -<br />
a. landing valves for dry fire mains, they conform to BS 5041: Part 2: 1987; and<br />
b. inlet breechings for dry fire mains, they conform to BS 5041: Part 3: 1975 (1987); and<br />
c. boxes for landing valves for dry fire mains, they conform to BS 5041: Part 4: 1975 (1987); and<br />
d. boxes for dry fire mains, they conform to BS 5041: Part 5: 1974 (1987).<br />
The requirements of E10.7 and E10.8 for an appropriately located entrance will be met where it is<br />
established in consultation with the Fire Authority.<br />
FIRE-FIGHTING LOBBIES<br />
(E10.9)(E10.11)<br />
The requirements of E10.9 and E10.11 for a suitably constructed fire-fighting lobby will be met by a<br />
lobby constructed in accordance with Clause 6 of BS 5588: Part 5: 1991.<br />
FIRE-FIGHTING LIFTS<br />
(E10.11) The requirements of E10.11 for a lift of a suitable construction will be met where the fire-fighting lift<br />
complies with Section 3 and 4 of BS 5588: Part 5: 1991.<br />
Amdt: September 2001<br />
46E
VENTING OF HEAT AND SMOKE FROM BASEMENT STOREYS<br />
(E10.15)The requirements of E10.15 will be met by smoke outlets that -<br />
a. are sited at ceiling level within the room they serve; and<br />
47E<br />
(E10.15, E11.1)<br />
b. have an aggregate cross-sectional area of at least 2.5% of the floor area of the room they serve;<br />
and<br />
c. are evenly distributed around the perimeter of the building; and<br />
d. discharge directly to the open air at a point at least 2 m, measured horizontally, from any part of<br />
an escape route or exit, and have a sign stating SMOKE OUTLET FROM BASEMENT, DO<br />
NOT OBSTRUCT fixed adjacent to each external outlet point; and<br />
e. where they serve a place of special fire risk are separate from the smoke outlets from other areas;<br />
and<br />
f. discharge by means of windows, panels or pavement lights which are readily accessible to the<br />
Fire Brigade and which can be opened or knocked out by the Fire Brigade; and<br />
g. where required are enclosed by a smoke venting shaft as specified in Part D3.11; and<br />
h. where there are smoke venting shafts from different parts of the same basement storey, or from<br />
different basement storeys, they are separated; and<br />
i. are covered with a metal grille or louvre.<br />
The requirements of E10.15f. for a suitable mechanical smoke and heat extraction system will be met by<br />
incorporating a powered smoke and heat exhaust ventilator which has a capacity of at least 10 air<br />
changes per hour and conforms to BS 7346: Part 2: 1990 with a class D level of performance.<br />
The requirements of E10.15f. for an appropriate fire control system will be met by a sprinkler system<br />
which conforms to BS 5306: Part 2: 1990.<br />
AUTOMATIC FIRE DETECTION IN DWELLINGS<br />
(E11.1) The requirements of E11.1a will be met by a smoke alarm with a standby supply, complying with<br />
BS 5446: Part 1: 1990 and installed in accordance with the provisions of a. to e. below -<br />
a. The standby power supply for the smoke alarm should take the form of a primary battery, a secondary<br />
battery or a capacitor. The capacity of the standby supply should be sufficient to power the<br />
smoke alarm when the mains power supply is off for at least 72 hours while giving an audible<br />
warning of mains power supply being off. There should remain sufficient capacity to provide a<br />
warning of smoke for a further 4 minutes. An audible warning should be given at least once every<br />
minute where the capacity of the standby power supply falls below that required to satisfy the<br />
recommended standby duration when the mains power supply is on; or persist for at least 15 days<br />
when the mains power supply is off.<br />
b. A smoke alarm should be located -<br />
i. in a circulation area which will be used as a route along which to escape, not more than<br />
7 m from the door to a living room or kitchen and not more than 3 m from the door to a<br />
room intended to be used as sleeping accommodation, the dimensions to be measured<br />
horizontally,<br />
ii. where the circulation area is more than 15 m long, not more than 15 m from another<br />
smoke alarm on the same storey,<br />
Amdt: September 2001<br />
E
E<br />
(E11.1, E11.2)<br />
Amdt: September 2001<br />
iii. where designed for ceiling mounting, at least 300 mm away from any wall or light fitting,<br />
or if designed for wall mounting, more than 150 mm and not more than 300 mm below<br />
the ceiling,<br />
iv. at least 300 mm away from, and not directly above, a heater or air conditioning outlet, and<br />
v. on a surface which is normally at the ambient temperature of the rest of the room or<br />
circulation area in which the smoke alarm is situated.<br />
Note:<br />
The above provisions are broadly in line with the recommendations of BS 5839: Part 6: 1995 for<br />
a Grade D Type LD3 system.<br />
c. Where more than 1 smoke alarm is installed in a dwelling they should be interconnected so that<br />
detection of a fire by any one of them operates the alarm signal in all of them.<br />
d. A smoke alarm should be permanently wired to a circuit. The mains supply to the smoke alarm<br />
should take the form of either -<br />
i. an independent circuit at the dwelling’s main distribution board, in which case no other<br />
electrical equipment should be connected to this circuit (other than a dedicated monitoring<br />
device installed to indicate failure of the mains supply to the smoke alarms), or<br />
ii. a separately electrically protected, regularly used local lighting circuit.<br />
Note:<br />
Where smoke alarms are of a type that may be interconnected, all smoke alarms should be connected<br />
on a single final circuit.<br />
e. Any smoke alarm in a dwelling which forms part of residential accommodation with a warden or<br />
supervisor, should have a connection to a central monitoring unit so that in the event of fire the<br />
warden or supervisor can identify the dwelling concerned, and the system should comply with the<br />
recommendations in BS 5839: Part 6: 1995 for a Grade C Type LD3 installation.<br />
The requirements of E11.1b will be met by an automatic fire detection and alarm system complying<br />
with BS 5839: Part 1: 1988: Type L3.<br />
AUTOMATIC FIRE DETECTION IN BUILDINGS OF PURPOSE GROUP 2<br />
(E11.2)The requirements of E11.2 for a suitable fire detection and alarm system in the case of a building of<br />
purpose sub-group 2A, will be met by an automatic detection and alarm system where -<br />
a. manual fire alarm call points are provided and sited as specified in BS 5839: Part 1: 1988; and<br />
b. automatic detection is provided to the L1 standard, complying with BS 5839: Part 1: 1988,<br />
except -<br />
detection need not be provided in -<br />
i. sanitary accommodation, and<br />
ii. a lockable cupboard with a plan area not more than 1 m 2 , and<br />
iii. a void and roof space which contain only mineral insulated wiring or wiring laid on metal<br />
trays or in metal conduits, metal pipes or plastic pipes used for water supply or drainage,<br />
and ventilating ducts; and<br />
48E
49E<br />
(E11.2, 11.3)<br />
c. the fire alarm is activated upon the operation of manual call points, automatic detection or the<br />
operation of any sprinkler system installed; and<br />
d. the building should be divided into detection zones not extending beyond a single compartment,<br />
except -<br />
in a hospital the detection zone should not extend beyond a single sub-compartment; and<br />
e. the audibility level of the fire alarm sounders complies with BS 5839: Part 1: 1988,<br />
except -<br />
i. in a hospital department to which patients have access, when the audibility need only be<br />
55dB(A) or 5 dB(A) above the level of background noise, whichever is greater, or<br />
ii. in a place of lawful detention, the alarm need not be sounded; and<br />
f. a main fire alarm control panel is provided at -<br />
i. the main entrance, or a suitably located entrance, to the building, and;<br />
ii. in hospitals, repeater panels should be provided at all other Fire Brigade access points; and<br />
g. on the actuation of the fire alarm a signal is transmitted automatically to the Fire Brigade, either<br />
directly or by way of a remote centre, designed and operated in accordance with BS 5979: 1993,<br />
except -<br />
in the case of a building in purpose sub-group 2A designed to accommodate not more than 10 residents,<br />
where the fire detection and alarm system complies with that for a building of purpose sub-group 2B.<br />
The requirements of E11.2 for a suitable fire detection and alarm system in the case of a building of<br />
purpose sub-group 2B, will be met by an automatic detection and alarm system where -<br />
a. manual fire alarm call points are provided and sited as specified in BS 5839 Part1 1988; and<br />
b. automatic detection is provided to the L2 standard, complying with BS5839: Part 1: 1988; and<br />
c. the fire alarm is activated upon the operation of manual call points, automatic detection or the<br />
operation of any sprinkler system installed; and<br />
d. the audibility level of the fire alarm sounders complies with BS 5839: Part 1: 1988,<br />
except -<br />
in the case of shared residential accommodation designed to provide sleeping accommodation for not<br />
more than 6 persons, and having no sleeping accommodation below ground level or above first floor<br />
level, a smoke alarm system as specified in E11.1a. may be provided.<br />
AUTOMATIC FIRE DETECTION IN ENCLOSED SHOPPING CENTRES WITH MALLS<br />
(E11.3)The requirements of E11.3 for a suitable fire detection and alarm system will be met by an automatic<br />
detection and alarm system where -<br />
a. automatic detection is provided to the L2 standard, complying with BS 5839: Part 1:1988; and<br />
b. the fire alarm is also activated upon the operation of the sprinklers, or manual call points (complying<br />
with BS 5839 Part 1: 1988); and<br />
Amdt: September 2001<br />
E
E<br />
(E6.1)<br />
c. on the activation of the alarm in a shop, evacuation may be restricted to the shop concerned for a<br />
grace period not more than 4 minutes, unless during that time there is further detection in the<br />
mall, in which case the evacuation of the shopping centre should be commenced; and<br />
d. notwithstanding this grace period, immediately upon activation of the alarm a message should be<br />
sent to an appropriate fire station or manned agency; and<br />
e. in the case of the activation of the alarm anywhere other than in an individual shop, or on activation<br />
of sprinklers anywhere within the shopping centre, evacuation should be commenced immediately<br />
and there is no grace period; and<br />
f. all areas of the shopping centre, including shops, are alerted using a voice alarm system complying<br />
with BS 5839: Part 8: 1998, however individual shops may use conventional sounders for the<br />
internal fire alarm; and<br />
g. the fire alarm system is interfaced with other fire safety systems, to operate in the correct zones;<br />
and<br />
h. on the operation of the fire alarm -<br />
Amdt: September 2001<br />
i. all escalators come to a controlled halt and lifts should return to the ground storey (or exit<br />
level),<br />
ii. all systems within the mall or shops which play amplified music are silenced,<br />
iii. any smoke dampers required to prevent the siphoning of smoke are activated, and<br />
iv. (subject to the grace period where appropriate) all air-moving systems, mains and pilot<br />
gas outlets, combustion air blowers and gas, electrical and other heating appliances in the<br />
reservoir are shutdown; and<br />
i. the main fire alarm system control panel is within the control room; and<br />
j. indicator panels are provided at each of the fire-fighting accesses.<br />
50E
COMBUSTION APPLIANCE INSTALLATIONS AND<br />
STORAGE OF LIQUID AND GASEOUS FUELSF
Contents<br />
INTRODUCTION<br />
REGULATION 14<br />
Combustion appliance installations<br />
REGULATION 15<br />
Storage of liquid and gaseous fuels<br />
THE STANDARDS<br />
F1 Application of Part F F1.1-F1.2<br />
F2 Large combustion appliance installations F2.1<br />
F3 General standards for small combustion appliance installations<br />
Installations F3.1-F3.2<br />
Removal of products of combustion F3.3-F3.4<br />
Protection from products of combustion F3.5-F3.8<br />
Relationship to combustible materials F3.9<br />
Extract fans F3.10-F3.11<br />
Identification of combustion appliance installations F3.12<br />
Incinerators F3.13<br />
F4 Solid fuel combustion appliance installations with an output<br />
rating not more than 50 kW<br />
Installations F4.1<br />
Appliances F4.2<br />
Supply of air for combustion F4.3<br />
Removal of products of combustion F4.4-F4.10<br />
Protection from products of combustion F4.11-F4.13<br />
Relationship to combustible materials F4.14-F4.21<br />
F5 Oil-fired combustion appliance installations with a net input<br />
rating not more than 70 kW<br />
Installations F5.1<br />
Appliances F5.2<br />
Supply of air for combustion F5.3<br />
Supply of air for cooling F5.4<br />
Removal of products of combustion F5.5-F5.10<br />
Relationship to combustible materials F5.11-F5.13<br />
F6 Gas-fired combustion appliance installations with a net input<br />
rating not more than 70 kW<br />
Installations F6.1<br />
Appliances F6.2<br />
Supply of air for combustion F6.3<br />
Supply of air for cooling F6.4<br />
Removal of products of combustion F6.5-F6.10<br />
Protection from products of combustion F6.11-F6.13<br />
Relationship to combustible materials F6.14-F6.17<br />
F7 Storage of liquid and gaseous fuels<br />
Oil storage<br />
Liquefied petroleum gas storage more than<br />
F7.1-F7.3<br />
9000 litres capacity<br />
Liquefied petroleum gas storage not more than<br />
F7.4<br />
9000 litres capacity F7.5<br />
3F<br />
Amdt: December 1999<br />
F
F<br />
Amdt: December 1999<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(F2.1) Large combustion appliance installations<br />
(F3.1) Installations<br />
(F3.4) Removal of products of combustion<br />
(F3.5- Protection from products of combustion<br />
F3.8)<br />
(F3.9) Relationship to combustible materials<br />
(F3.11) Extract fans<br />
(F3.12) Identification of combustion appliance installations<br />
(F4.2) Appliances<br />
(F4.3) Supply of air for combustion<br />
(F4.5, Removal of products of combustion<br />
F4.8,<br />
F4.10)<br />
(F4.11, Protection from products of combustion<br />
F4.12)<br />
(F4.17- Relationship to combustible materials<br />
F4.19,<br />
F4.21)<br />
(F5.2) Appliances<br />
(F5.3) Supply of air for combustion<br />
(F5.4) Supply of air for cooling<br />
(F5.7, Removal of products of combustion<br />
F5.8,<br />
F5.10)<br />
(F5.11- Relationship to combustible materials<br />
F5.13)<br />
(F6.2) Appliances<br />
(F6.3) Supply of air for combustion<br />
(F6.4) Supply of air for cooling<br />
(F6.5- Removal of products of combustion<br />
F6.7,<br />
F6.9,<br />
F6.10)<br />
(F6.11, Protection from products of combustion<br />
F6.13)<br />
(F6.16, Relationship to combustible materials<br />
F6.17)<br />
(F7.1- Oil storage<br />
F7.3)<br />
(F7.4) Liquefied petroleum gas storage more than 9000 litres capacity<br />
(F7.5) Liquefied petroleum gas storage not more than 9000 litres capacity<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in<br />
Part A, General.<br />
4F
Introduction<br />
1. The intention of this Part is to ensure that combustion appliance installations,<br />
liquefied petroleum gas tanks and fuel oil storage tanks are properly<br />
constructed and safely installed.<br />
2. The requirements do not apply to liquefied petroleum gas storage tanks<br />
with a capacity not more than 150 litres water equivalent as these have to<br />
satisfy the Health and Safety Executive requirements. Nor do they apply<br />
to oil storage containers less than 90 litres.<br />
3. Measures must be taken to ensure that -<br />
a. combustion appliance installations are safe and are of an acceptable<br />
standard;<br />
b. the installation does not create a fire risk;<br />
c. sufficient air for combustion and appliance cooling where necessary,<br />
is available;<br />
d. the products of combustion are conveyed safely to the outside air;<br />
and<br />
e. chimneys, flue-pipes and hearths are constructed of materials suitable<br />
for their purpose.<br />
4. For large combustion appliance installations generalised standards are<br />
given. Such installations will be dealt with by specialists, usually with reference<br />
to British <strong>Standards</strong> or other recognised codes, to meet Regulation 14.<br />
5. For small combustion appliance installations the standards cover in<br />
detail all the areas of concern listed in paragraph 3. However, the requirements<br />
are intended to reduce risk and do not attempt to cover such matters<br />
as the efficient functioning of flues, which may depend on pressure zones<br />
peculiar to a location and building. The appropriate British Standard or<br />
other recognised code may have to be consulted.<br />
6. The measures included in this Part are intended to address concerns<br />
about the risk from flue gases, that may contain carbon monoxide, escaping<br />
into the building. As buildings become more airtight and there is less<br />
fortuitous or adventitious ventilation, care should be taken to ensure there<br />
is sufficient air for combustion, the flue is functioning properly and there<br />
is no conflict with the operation of any air extract fan(s).<br />
7. The Gas Safety (Installation and Use) Regulations, enforced by the<br />
Health and Safety Executive, apply to all gas installations covered by this<br />
Part. Part F includes requirements with regard to such installations, but<br />
avoids duplication of information contained in the HSE regulations.<br />
8. There are other requirements that will have to be taken into account in<br />
certain cases. Part D (Structural Fire Precautions) for example, has<br />
requirements for large combustion appliance installations, other than<br />
kitchen appliances, to be located in a place of special fire risk. Part K<br />
(Ventilation of buildings) has requirements relating to the provision of air<br />
for human occupation. These requirements are in addition to, and must be<br />
kept separate from, any air supply required by this Part. Part K also has<br />
requirements relating to a flue in an open-flued combustion appliance<br />
being used as a passive stack ventilation system.<br />
5F<br />
Amdt: December 1999<br />
F
F<br />
Regulations 14 & 15<br />
Combustion appliance installations<br />
14. Every fixed combustion appliance installation<br />
incorporating an appliance designed to burn<br />
solid fuel (namely, fuel in solid form including<br />
wood and peat) or gaseous or liquid fuel shall<br />
be so constructed and installed that -<br />
(a) it operates safely;<br />
(b) its operation does not cause damage by<br />
heat or fire to the building in which it is<br />
installed;<br />
(c) the products of combustion do not cause a<br />
risk to health; and<br />
(d) it receives sufficient air for its safe<br />
operation.<br />
Storage of liquid and gaseous fuels<br />
15. (1.) Every oil storage intallation with a tank<br />
capacity more than 90 litres, for the<br />
storage of fuel oil used principally to<br />
serve a combustion appliance providing<br />
space or water heating, or cooking facilities,<br />
shall be so constructed and installed<br />
as to minimise the risk of -<br />
(a) fire spreading to the tank; and<br />
(b) the contents of the tank contaminating<br />
any water supply, watercourse, drain<br />
or sewer.<br />
(2.) Every liquefied petroleum gas storage<br />
installation with a container capacity more<br />
than 150 litres (water equivalent), for the<br />
storage of liquified petroleum gas used<br />
principally to serve a combustion appliance<br />
providing space or water heating, or<br />
cooking facilities, shall be so constructed<br />
and installed as to minimise the risk of -<br />
(a) fire spreading to the container; and<br />
(b) the contents of the container forming<br />
explosive gas pockets in the vicinity<br />
of any liquefied petroleum gas storage<br />
container.<br />
Amdt: December 1999<br />
6F
The standards<br />
F1 Application of Part F<br />
F1.1 This Part sets out the required standards for Regulations 14 and 15.<br />
F1.2 The standards apply to all buildings in respect of their -<br />
a. combustion appliance installations; and<br />
b. oil storage systems where the tank capacity is more than 90 litres; and<br />
c. liquefied petroleum gas storage installations where the tank or cylinder capacity is more than 150<br />
litres water equivalent.<br />
F2 Large combustion appliance installations<br />
F2.1* A large combustion appliance installation (solid fuel with an output rating more than 50 kW and oilfired<br />
and gas-fired, with a net input rating more than 70 kW) must be suitably constructed and installed<br />
so that -<br />
a. it operates safely; and<br />
b. its operation does not cause damage by heat or fire to the building in which it is installed; and<br />
c. the products of combustion do not cause a risk to health; and<br />
d. it receives sufficient air for its safe operation; and<br />
e. any associated chimney or flue-pipe will prevent, as far as is reasonably practicable, the escape of<br />
smoke, grit, dust or gases into any building.<br />
F3 General standards for small combustion appliance installations<br />
INSTALLATIONS<br />
F3.1* A small combustion appliance installation (solid fuel with an output rating not more than 50 kW and oilfired<br />
and gas-fired, with a net input rating not more than 70 kW) must be suitably constructed and<br />
installed so that it operates safely.<br />
F3.2 Where a combustion appliance installation is intended to operate with more than one type of fuel, each<br />
component must be constructed and installed to meet the most onerous requirement for the relevant<br />
fuels.<br />
7F<br />
F1.1 – F3.2<br />
Amdt: December 1999<br />
F
F<br />
F3.3 – F3.9<br />
REMOVAL OF PRODUCTS OF COMBUSTION<br />
F3.3 A combustion appliance must be connected to a chimney or flue-pipe that discharges to the external air,<br />
except -<br />
where the combustion appliance is designed to operate without discharging the products of combustion<br />
to the outside air.<br />
F3.4* A flue terminal not more than 2m above ground level, or where people are likely to come into contact<br />
with it, must be -<br />
a. designed so as to resist the entry of any matter that may restrict the flue; and<br />
b. protected by a suitable terminal guard.<br />
PROTECTION FROM PRODUCTS OF COMBUSTION<br />
F3.5* A chimney must be -<br />
a. suitably constructed of a masonry material with a flue liner; or<br />
b. suitably constructed of prefabricated block components; or<br />
c. a factory-made chimney.<br />
F3.6* A factory-made chimney must be suitable for its purpose.<br />
F3.7* A factory-made chimney must be suitably installed and must not -<br />
a. pass through a compartment wall, compartment floor, separating wall or separating floor,<br />
except -<br />
where the chimney, or a non-combustible casing totally enclosing the chimney, is constructed in<br />
such a way that, in the event of fire the level of fire safety performance required of the compartment<br />
wall, compartment floor, separating wall or separating floor is maintained (see D1.3);<br />
b. pass through any storage space, cupboard or roof space,<br />
except -<br />
where the chimney is suitably shielded by a removable casing;<br />
c. incorporate joints within any wall, floor, ceiling or roof.<br />
F3.8* A flue system must be essentially uniform, suitably gas-tight, free from obstructions and resistant to<br />
corrosion from combustion products.<br />
RELATIONSHIP TO COMBUSTIBLE MATERIALS<br />
F3.9* A factory-made chimney must be placed at a safe distance from any combustible material.<br />
Amdt: September 2001<br />
8F
EXTRACT FANS<br />
F3.10 An extract fan must not be fitted in the same room as an open-flued solid fuel appliance.<br />
F3.11*Where an open-flued combustion appliance draws air for combustion or cooling from a room or space in<br />
which a fan is fitted, the appliance and associated flue must be able to operate safely.<br />
IDENTIFICATION OF COMBUSTION APPLIANCE INSTALLATIONS<br />
F3.12*Every combustion appliance installation must have a suitably positioned label of durable material,<br />
indelibly marked to indicate its limitations of use.<br />
INCINERATORS<br />
F3.13 An incinerator, together with any associated chimney, flue-pipe and hearth must be constructed and<br />
installed, irrespective of the type of fuel used, in accordance with the requirements of F4.2 to F4.20<br />
(solid fuel).<br />
F4 Solid fuel combustion appliance installations with an output rating<br />
not more than 50 kW<br />
INSTALLATIONS<br />
F4.1 A solid fuel (namely, fuel in solid form including wood and peat) appliance with an output rating not<br />
more than 50 kW, and any associated chimney, flue-pipe and hearth, must be constructed and installed in<br />
accordance with the requirements of F3.1 to F3.12 (general) and F4.2 to F4.21.<br />
APPLIANCES<br />
F4.2* A solid fuel appliance must be suitable for its purpose and for the type of fuel that it will burn.<br />
SUPPLY OF AIR FOR COMBUSTION<br />
F4.3* A solid fuel appliance installed in a room or space must have an adequate supply of air for combustion<br />
by way of permanent ventilation either direct to the open air or to an adjoining space (including a subfloor<br />
space) that is itself permanently ventilated direct to the open air. (See also F3.10 and F3.11)<br />
REMOVAL OF PRODUCTS OF COMBUSTION<br />
F4.4 Each solid fuel appliance must be connected to a separate flue.<br />
F4.5* The area of a flue must be suitable for the type of solid fuel appliance served.<br />
F4.6 The angle of any change of direction in a flue must not be more than 45º from the vertical,<br />
except -<br />
where a back-entry appliance discharges into a flue, the horizontal length of flue-pipe at the point of<br />
discharge must not exceed 150mm.<br />
9F<br />
F3.10 – F4.6<br />
Amdt: December 1999<br />
F
F<br />
F4.6 – F4.12<br />
Diagram to F4.6: Flue-pipe connection to back-entry solid fuel appliance<br />
F4.7 A flue must have no intermediate openings,<br />
except -<br />
a. a draught stabiliser or draught diverter that is in the same room or space as the solid fuel appliance<br />
being served;<br />
b. an explosion door;<br />
c. an opening for inspection or cleaning that is fitted with a non-combustible, rigid, gas-tight cover.<br />
F4.8* Suitable access must be provided for inspection and cleaning of a flue and appliance.<br />
F4.9 A flue-pipe must not be fixed externally to a building.<br />
F4.10*The outlet from a flue must be positioned at a safe distance from any obstructions or flammable or<br />
vulnerable materials.<br />
PROTECTION FROM PRODUCTS OF COMBUSTION<br />
F4.11*A flue in a chimney must -<br />
a. be separated from every other flue; and<br />
chimney<br />
flue<br />
flue-pipe<br />
explosion door or not more than 45˚<br />
inspection opening<br />
as F4.7b or c appliance<br />
150 mm maximum<br />
horizontal length<br />
Section through appliance and flue-pipe<br />
b. extend from the solid fuel appliance to the top of the chimney; and<br />
c. be surrounded by non-combustible material that is capable of withstanding the effects of a<br />
chimney fire, without any structural change that would impair the stability or performance of the<br />
chimney,<br />
except -<br />
the chimney may include damp proof course(s) of combustible material.<br />
F4.12*A flue-pipe must be non-combustible and of suitable materials and construction capable of withstanding<br />
the effects of a chimney fire, without any structural change that would impair the stability or performance<br />
of the flue-pipe.<br />
Amdt: December 1999<br />
10F
F4.13 A flue-pipe may only be used to connect a solid fuel appliance to a chimney and must not pass through -<br />
a. a roof space;<br />
b. an internal wall,<br />
except -<br />
where the flue-pipe discharges into a flue in a chimney formed wholly or partly by a non-combustible<br />
wall;<br />
c. a ceiling or floor,<br />
except -<br />
where the ceiling or floor is non-combustible and the flue-pipe discharges into a chimney immediately<br />
above.<br />
RELATIONSHIP TO COMBUSTIBLE MATERIALS<br />
F4.14 A flue-pipe must be separated from combustible material by a distance equivalent to at least 3 times the<br />
diameter of the flue-pipe,<br />
except -<br />
a. the distance may be reduced to 1.5 times the diameter of the flue-pipe where there is, between the<br />
flue-pipe and the combustible material, a non-combustible shield that -<br />
i. extends a distance equivalent to at least 1.5 times the diameter of the flue-pipe from any<br />
part of the flue-pipe, and<br />
ii. is separated by an air space of at least 12mm from the combustible material; or<br />
b. the distance may be reduced to 0.75 times the diameter of the flue-pipe where the flue-pipe is<br />
totally enclosed in non-combustible material at least 12mm thick and having a thermal conductivity<br />
of not more than 0.065 W/mK.<br />
Diagrams to F4.14a: Flue-pipe separation from combustible material<br />
at least air space of at least at least<br />
3 x D D at least 12 mm 3 x D D 1.5 x D<br />
at least flue-pipe<br />
3 x D<br />
combustible non-combustible<br />
material shield<br />
at least<br />
1.5 x D<br />
combustible at least<br />
material 1.5 x D<br />
at least<br />
1.5 x D<br />
air space of at least 12 mm<br />
at least<br />
1.5 x D Plan without shield Plan with shield<br />
Section without shield Section with shield<br />
11F<br />
F4.13 – F4.14<br />
Amdt: December 1999<br />
F
F<br />
F4.15 – 4.19<br />
F4.15 All combustible materials must be at least 200mm from the surface surrounding a flue in a chimney or<br />
the inside surface of a fireplace recess,<br />
except -<br />
a. damp proof course(s) firmly bedded in mortar;<br />
b. small combustible fixings located at least 150mm from the surface surrounding the flue or the<br />
inside surface of the fireplace recess;<br />
c. combustible structural material, that may be located at least 40mm from the outer face of a<br />
masonry chimney;<br />
d. flooring, strapping, sarking or similar non-structural combustible material located on the outer<br />
face of a masonry chimney;<br />
e. under a constructional hearth as described in F4.20;<br />
f. where the flue is in a factory-made chimney.<br />
F4.16 Any metal fastening in contact with combustible material must be at least 50mm from the surface surrounding<br />
a flue or the inside surface of a fireplace recess.<br />
Diagram to F4.15 and F4.16: Minimum separation distances for combustible material relative to a<br />
masonry chimney<br />
combustible material on<br />
metal fastening or support<br />
combustible material<br />
e.g. dook metal fastening or support<br />
at least at least<br />
150 mm 50 mm<br />
combustible material combustible material<br />
built in e.g. strapping or flooring<br />
flue less than<br />
at least 200 mm liner 200 mm<br />
Plan view through masonry chimney<br />
at least at least<br />
200 mm 40 mm<br />
combustible structural material<br />
F4.17*A solid fuel appliance must be provided with a solid, non-combustible hearth of suitable dimensions.<br />
F4.18*A solid fuel appliance must be positioned on a hearth in such a way as to minimise the risk of ignition<br />
of any part of a floor by direct radiation, conduction or falling embers.<br />
F4.19*Any part of a building, other than a floor, that abuts or is adjacent to a hearth, must be constructed in<br />
such a way as to minimise the risk of ignition by direct radiation or conduction from a solid fuel appliance<br />
located upon the hearth.<br />
Amdt: December 1999<br />
12F
F4.20 All combustible material under a constructional hearth must be separated from the hearth by an air space<br />
of at least 50mm,<br />
except -<br />
a. where the combustible material is separated from the top surface of the hearth by solid, noncombustible<br />
material of at least 250mm; or<br />
b. where the combustible material supports the front and side edges of the hearth.<br />
Diagram to F4.20: Combustible materials under a hearth<br />
F4.21*A fireplace recess must be suitably constructed of solid, non-combustible material.<br />
F5 Oil-fired combustion appliance installations with a net input rating<br />
not more than 70 kW<br />
INSTALLATIONS<br />
F5.1 An oil-fired appliance with a net input rating not more than 70 kW, and any associated chimney, fluepipe<br />
and hearth, must be constructed and installed in accordance with the requirements of F3.1 to F3.12<br />
(general) and F5.2 to F5.13.<br />
APPLIANCES<br />
at least<br />
250 mm<br />
F5.2* An oil-fired appliance must be suitable for its purpose and the class of oil that it will burn.<br />
SUPPLY OF AIR FOR COMBUSTION<br />
top surface of hearth<br />
Section through hearth<br />
at least 125 mm<br />
F5.3* An oil-fired appliance installed in a room or space must have an adequate supply of air for combustion<br />
by way of permanent ventilation either direct to the open air or to an adjoining space (including a subfloor<br />
space) which is itself permanently ventilated direct to the open air, (see also F3.11)<br />
except -<br />
where the appliance is a room-sealed appliance.<br />
air space of combustible material<br />
at least 50 mm supporting edge of hearth<br />
combustible material<br />
13F<br />
F4.20 – F5.3<br />
Amdt: December 1999<br />
F
F<br />
F5.4 – F5.12<br />
SUPPLY OF AIR FOR COOLING<br />
F5.4* An oil-fired appliance installed in an appliance compartment must have an adequate supply of air for<br />
cooling by way of permanent ventilation, in addition to air for combustion, either direct to the open air<br />
or to an adjoining space (including a sub-floor space).<br />
REMOVAL OF PRODUCTS OF COMBUSTION<br />
F5.5 Each oil-fired appliance must be connected to a separate flue,<br />
except -<br />
where the appliance has a pressure jet burner and is connected into a suitable shared flue.<br />
F5.6 An oil-fired appliance installed in a bathroom, shower-room or room intended for use as sleeping<br />
accommodation must be a room-sealed appliance.<br />
F5.7* A chimney or flue-pipe serving an oil-fired appliance must be suitable for use with the type of appliance<br />
served.<br />
F5.8* A chimney or flue-pipe serving an oil-fired appliance must be constructed and installed in accordance<br />
with the requirements of F4.7 to F4.9, and F4.11 to F4.16 (solid fuel),<br />
except -<br />
a. where the flue gas temperature will be not more than 250º C under normal working conditions (as<br />
determined by an appropriate test procedure), the chimney or flue-pipe may be in accordance with<br />
the requirements of F6.8, F6.9 and F6.11 to F6.15 (gas); and<br />
b. where the oil-fired appliance burns Class D fuel, the inner surfaces of the chimney or flue-pipe<br />
must not be manufactured from aluminium.<br />
F5.9 The angle of any change of direction in a flue must not be more than 45º from the vertical,<br />
except -<br />
where the flue serves an appliance employing a pressure jet burner.<br />
F5.10*The outlet from a flue must be situated externally at a safe distance from any opening, obstruction or<br />
combustible material.<br />
RELATIONSHIP TO COMBUSTIBLE MATERIALS<br />
F5.11*An oil-fired appliance must stand on a hearth constructed and installed in accordance with the requirements<br />
of F4.17 and F4.20 (solid fuel),<br />
except -<br />
a. where the appliance will not cause the temperature of the floor to be more than 100º C under<br />
normal working conditions (as determined by an appropriate test procedure), the appliance may<br />
stand on, or incorporate, a rigid, non-combustible, non-absorbent, imperforate base, of at least the<br />
plan dimensions of the appliance; or<br />
b. where the appliance is designed not to stand on a hearth it must incorporate a rigid, noncombustible,<br />
non-absorbent, imperforate base of at least the plan dimensions of the appliance.<br />
F5.12*Where an oil-fired appliance is installed on a hearth it must be positioned on the hearth in such a way as<br />
to minimise the risk of ignition of any part of the floor by direct radiation or conduction.<br />
Amdt: December 1999<br />
14F
F5.13*An oil-fired appliance must be separated from any combustible material, where the temperature of the<br />
back, sides or top of the appliance will be more than 100º C under normal working conditions (as determined<br />
by an appropriate test procedure) by -<br />
a. a shield of non-combustible material at least 25mm thick; or<br />
b. an air space of at least 75mm.<br />
Diagram to F5.13: Appliance separation from combustible material<br />
F6 Gas-fired combustion appliance installations with a net input rating<br />
not more than 70 kW<br />
INSTALLATIONS<br />
F6.1 A gas-fired appliance with a net input rating not more than 70 kW, and any associated chimney, fluepipe<br />
and hearth, must be constructed and installed in accordance with the requirements of F3.1 to F3.12<br />
(general) and F6.2 to F6.17.<br />
APPLIANCES<br />
F6.2* A gas-fired appliance must be suitable for its intended purpose.<br />
SUPPLY OF AIR FOR COMBUSTION<br />
F6.3* A gas-fired appliance installed in a room or space must have an adequate supply of air for combustion.<br />
(See also F3.11)<br />
SUPPLY OF AIR FOR COOLING<br />
air space at shield at<br />
least 75 mm least 25 mm<br />
combustible combustible<br />
material material<br />
appliance non-combustible<br />
material<br />
Plan/section Plan/section<br />
without shield with shield<br />
F6.4* A gas-fired appliance installed in an appliance compartment must have an adequate supply of air for<br />
cooling.<br />
15F<br />
F5.13 – F6.4<br />
Amdt: December 1999<br />
F
F<br />
F6.5 – F6.14<br />
REMOVAL OF PRODUCTS OF COMBUSTION<br />
F6.5* Each gas-fired appliance that requires a flue, must connect into a separate flue,<br />
except -<br />
where it connects into a suitable shared flue.<br />
F6.6* A chimney or flue-pipe serving a gas-fired appliance must be suitable for use with the type of appliance<br />
served.<br />
F6.7* The area of a flue must be suitable for the type of gas-fired appliance(s) served.<br />
F6.8 A flue must have no intermediate openings,<br />
except -<br />
a. a draught stabiliser, draught diverter or relief air opening, that is in the same room or space as the<br />
gas-fired appliance being served;<br />
b. an opening for inspection or cleaning, that is fitted with a non-combustible, rigid, gas-tight cover.<br />
F6.9* A flue-pipe must not be fixed externally to a building,<br />
except -<br />
where the flue-pipe is a double-walled flue-pipe suitable for external use.<br />
F6.10*The outlet from a flue must be situated externally at a safe distance from any opening, obstruction or<br />
combustible material.<br />
PROTECTION FROM PRODUCTS OF COMBUSTION<br />
F6.11*A flue-pipe must be of suitable material.<br />
F6.12 A flue-pipe must not pass through a compartment wall, compartment floor, separating wall or separating<br />
floor,<br />
except -<br />
where the chimney is totally enclosed within a non-combustible casing in such a way that, in the event of<br />
fire, the level of fire safety performance required of the compartment wall, compartment floor, separating<br />
wall or separating floor is maintained. (see D1.3)<br />
F6.13*A flue-pipe must be adequately protected, to prevent damage to the pipe or danger to people, where it<br />
passes through a room or accessible space other than that containing the gas-fired appliance that it<br />
serves.<br />
RELATIONSHIP TO COMBUSTIBLE MATERIALS<br />
F6.14 A flue-pipe must not pass through a wall, floor, roof, ceiling or partition constructed of combustible<br />
material,<br />
except -<br />
a. where the temperature of the flue gases in the flue-pipe will be not more than 100º C; or<br />
b. where the flue-pipe is enclosed in a sleeve of non-combustible material and separated from the<br />
sleeve by an air space of at least 25mm; or<br />
c. where flue-pipe is a double-walled flue-pipe.<br />
Amdt: September 2001<br />
16F
Diagrams to F6.14b and c: Flue-pipes passing through combustible material<br />
at least<br />
25 mm<br />
F6.15 A flue-pipe must be placed -<br />
combustible<br />
material<br />
non-combustible flue-pipe<br />
sleeve<br />
Section through Section through<br />
single-walled flue-pipe double-walled flue-pipe<br />
a. where it is a single-walled flue-pipe, with its outer surface at least 25mm from any combustible<br />
material;<br />
b. where it is a double-walled flue-pipe, with the inner surface of its inner wall at least 25mm from<br />
any combustible material,<br />
except -<br />
where the temperature of the flue gases will be not more than 100º C.<br />
Diagram to F6.15: Flue-pipes in relationship to combustible material<br />
at least at least<br />
25 mm 25 mm<br />
combustible material<br />
Section through Section through<br />
single-walled flue-pipe double-walled flue-pipe<br />
F6.16* A gas-fired appliance must be provided with a suitable hearth,<br />
except -<br />
a. where every part of any flame or incandescent material in the appliance is at least 225mm above<br />
the floor;<br />
b. where the appliance is designed not to stand on a hearth.<br />
F6.17*A gas-fired appliance and any associated draught diverter must be placed at a safe distance from any<br />
combustible material.<br />
17F<br />
F6.14 – F6.17<br />
Amdt: December 1999<br />
F
F<br />
F7.1 – F7.5<br />
F7 Storage of liquid and gaseous fuels<br />
OIL STORAGE<br />
F7.1* An oil storage tank with a capacity more than 90 litres, including any pipework connecting the tank to a<br />
combustion appliance providing space or water heating, or cooking facilities must be suitably<br />
constructed and installed.<br />
F7.2* An oil storage tank with a capacity more than 90 litres must be -<br />
a. adequately separated from any building or part of a building in the same occupation; and<br />
b. adequately separated from any boundary; and<br />
c. provided, where necessary, with an adequate catchpit to retain its contents in the event of leakage.<br />
F7.3* A fire valve must be suitably installed in any pipework connecting an oil storage tank to the combustion<br />
appliance that it serves.<br />
LIQUEFIED PETROLEUM GAS STORAGE MORE THAN 9000 LITRES CAPACITY<br />
F7.4* A liquefied petroleum gas storage tank with a capacity more than 9000 litres (or tanks of a total capacity<br />
more than 27 500 litres) (water equivalent) and any associated pipework connecting the system to a<br />
combustion appliance providing space or water heating, or cooking facilities, must be suitably constructed<br />
and installed as to minimise the risk of fire spreading to the tank and the contents of the tank<br />
forming explosive gas pockets in the vicinity of any liquefied petroleum gas storage container.<br />
LIQUEFIED PETROLEUM GAS STORAGE NOT MORE THAN 9000 LITRES CAPACITY<br />
F7.5* A liquefied petroleum gas storage container, or containers, with a capacity more than 150 litres but not<br />
more than 27 500 litres (water equivalent) and any associated pipework connecting the system to a<br />
combustion appliance providing space or water heating, or cooking facilities, must be -<br />
a. suitably constructed and installed; and<br />
b. where the container is a tank, adequately separated from -<br />
i. a building, boundary, or fixed source of ignition, and<br />
ii. any other such tank; and<br />
c. where a group of tanks are sited together, limited in the number of such tanks.<br />
Amdt: December 1999<br />
18F
Provisions deemed to satisfy the standards<br />
LARGE COMBUSTION APPLIANCE INSTALLATIONS<br />
(F2.1) The requirements of F2.1 will be met where the large combustion appliance installation is constructed<br />
and installed in accordance with the guidance contained in the Chartered Institution of Building<br />
Service Engineers (CIBSE) Design Guide and the Practice <strong>Standards</strong> produced by the British <strong>Standards</strong><br />
Institution (BSI) and the Institution of Gas Engineers (IGE).<br />
GENERAL REQUIREMENTS FOR SMALL COMBUSTION APPLIANCE INSTALLATIONS<br />
INSTALLATIONS<br />
(F3.1) The requirements of F3.1 will be met where -<br />
a. the solid fuel appliance installation is in accordance with BS8303: Parts 1 to 3: 1994;<br />
b. the oil-fired appliance installation is in accordance with BS5410: Part 1: 1997 or BS5410:<br />
Part 2: 1978 as appropriate;<br />
c. the gas-fired appliance installation is in accordance with -<br />
i. the requirements of the Gas Appliances (Safety) Regulations 1995, and<br />
ii. the Gas Safety (Installations & Use) Regulations 1998.<br />
REMOVAL OF PRODUCTS OF COMBUSTION<br />
(F3.4) The requirements of F3.4b will be met by a terminal guard that will prevent a sphere more than 16mm<br />
from passing through and has no sharp edges.<br />
PROTECTION FROM PRODUCTS OF COMBUSTION<br />
(F3.5) The requirements of F3.5a will be met where the chimney is constructed and installed in accordance<br />
with BS6461: Part 1: 1984.<br />
The requirements of F3.5b will be met where the chimney is constructed and installed in accordance<br />
with -<br />
a. for a precast concrete flue-block chimney, Clause 5.6 of BS6461: Part 1: 1984;<br />
b. for a precast concrete flue-block chimney serving a gas-fired appliance, BS1289: Part 1: 1986;<br />
c. for a clay flue-block chimney serving a gas-fired appliance, BS1289: Part 2: 1989.<br />
19F<br />
(F2.1) – (F3.5)<br />
Amdt: December 1999<br />
F
F<br />
(F3.6) – (F3.9)<br />
(F3.6) The requirements of F3.6 will be met where the factory-made chimney is manufactured in accordance<br />
with -<br />
a. BS4543: Part 2: 1990;<br />
b. where it serves a decorative fuel-effect gas appliance, BS4543: Parts 2 or 3: 1990;<br />
c. where it serves an oil-fired appliance producing a flue gas temperature not more than 450º C or<br />
any other gas-fired appliance, BS4543: Part 3: 1990.<br />
(F3.7) The requirements of F3.7 will be met where the factory-made chimney is installed in accordance with<br />
BS7566: Parts 1 to 4: 1992.<br />
The requirements of F3.7b will be met where the casing is located at a distance Xmm (as declared by<br />
the chimney manufacturer when testing to the procedures specified in Section 3 of BS4543: Part 1:<br />
1990) from any part of a factory-made chimney; and<br />
a. where the chimney passes through the storage space or cupboard, by an imperforate casing;<br />
b. where the chimney passes through the roof space, by a casing of rigid mesh that will prevent a<br />
sphere more than 8mm diameter from passing through.<br />
(F3.8) The requirements of F3.8 will be met where the flue system is installed in accordance with -<br />
a. for masonry and flue block chimneys, BS6461: Part 1: 1984;<br />
b. for factory-made chimneys, BS7566: Part 4 1992;<br />
c. where serving an oil-fired appliance, BS5410 Part 1: 1997;<br />
d. where serving a gas-fired appliance, BS5440 Part 1: 2000.<br />
RELATIONSHIP TO COMBUSTIBLE MATERIAL<br />
(F3.9) The requirements of F3.9 will be met by maintaining a distance Xmm (as declared by the chimney<br />
manufacturer when testing to the procedures specified in Section 3 of BS4543: Part 1: 1990) between<br />
the outer face of a factory-made chimney and combustible material.<br />
Diagram to (F3.9): Relationship of a factory-made chimney to combustible materials<br />
Amdt: September 2001<br />
X mm (manufacturer’s specified clearance)<br />
factory-made chimney<br />
X mm (manufacturer’s specified clearance)<br />
casing to F3.7b<br />
combustible material<br />
Plan of casing round a factory-made chimney<br />
20F
EXTRACT FANS<br />
(F3.11) The requirements of F3.11 will be met, in a building containing an open-flued combustion appliance<br />
and a mechanical extract fan(s), by testing to the procedures set out in -<br />
a. for a solid fuel appliance, BRE Information Paper IP 7/94;<br />
b. for an oil-fired appliance, Clause 4.4.7 of BS5410: Part 1: 1997 and OFTEC <strong>Technical</strong> Information<br />
Note TI/112;<br />
c. for a gas-fired appliance, Clause 4.3.2.3 of BS5440: Part 1: 2000.<br />
IDENTIFICATION OF COMBUSTION APPLIANCE INSTALLATIONS<br />
(F3.12) The requirements of F3.12 will be met where the label is provided in accordance with the diagram to<br />
this specification -<br />
Diagram to (F3.12): Identification of combustion appliance installation<br />
The label should be fixed in a secure position, such as adjacent to the gas or electricity consumer unit,<br />
the water supply stopcock or next to the chimney or hearth described.<br />
SOLID FUEL COMBUSTION APPLIANCE INSTALLATIONS<br />
APPLIANCES<br />
(F4.2) The requirements of F4.2 will be met where the solid fuel appliance is included in ‘The official guide<br />
to approved solid fuel products and services’, published by HETAS Ltd. (Heating Equipment Testing<br />
and Approval Scheme).<br />
SUPPLY OF AIR FOR COMBUSTION<br />
IMPORTANT SAFETY INFORMATION<br />
This label must not be removed or covered<br />
Property address................................................. 20 Main Street<br />
New Town<br />
The hearth and chimney liner installed in the.... name of room<br />
are suitable for.................................................... dfe gas fire<br />
Suitable for condensing mode............................ yes/no<br />
Chimney liner..................................................... xx mm diameter<br />
Installed on......................................................... date<br />
Any other information (optional).......................<br />
(F4.3) The requirements of F4.3 will be met where air is provided in accordance with the table to this specification<br />
-<br />
21F<br />
(F3.11) – (F4.3)<br />
Amdt: September 2001<br />
F
F<br />
(F4.3), (F4.5)<br />
Table to (F4.3): Supply of air for combustion<br />
Type of appliance Minimum ventilation opening sizes [Note 2]<br />
Open appliance without A permanent air entry opening or openings with a total free area of<br />
a throat [Note 1] 50% of the cross-sectional area of the flue.<br />
Open appliance with a permanent air entry opening or openings with a total free area of<br />
a throat [Note 1] 50% of the throat opening area.<br />
Any other solid fuel appliance a permanent air entry opening or openings with a total free area of<br />
550mm 2 for each kW of combustion appliance rated output more<br />
than 5 kW. (A combustion appliance with an output rating of not<br />
more than 5 kW has no minimum requirement, unless stated by the<br />
appliance manufacturer)<br />
Notes:<br />
1. In the table -<br />
THROAT means the contracted part of the chimney flue lying between the fireplace opening and<br />
the main chimney flue.<br />
2. Where a draught stabiliser is fitted to a solid fuel appliance, or to a chimney or flue-pipe in the<br />
same room as a solid fuel appliance, additional ventilation opening must be provided with a free<br />
area of at least 300mm 2/kW of solid fuel appliance rated output.<br />
3. Nominal fire size is related to the free opening width at the front of the fireplace opening.<br />
REMOVAL OF PRODUCTS OF COMBUSTION<br />
(F4.5) The requirements of F4.5 will be met where the minimum area of the flue is the greater of either -<br />
Amdt: December 1999<br />
a. the outlet to the solid fuel appliance; or<br />
b. that set out in the table and diagram to this specification -<br />
22F
Table to (F4.5): Minimum area of flues<br />
Appliance Position Minimum area [Note 2]<br />
Open fire a. within a fireplace recess a. 15% of the total face area<br />
capable of accepting an of the fireplace opening(s); or<br />
open fire more than b. in accordance with the<br />
500mm x 550mm; or Diagram to (F4.5). [Note 3]<br />
b. free standing<br />
Open fire within a fireplace recess capable 200mm diameter or square<br />
of accepting an open fire of not section of equivalent area.<br />
more than 500mm x 550mm<br />
Closed appliance with output free standing 175mm diameter or square<br />
capacity more than 30 kW but section of equivalent area.<br />
not more than 50 kW<br />
Closed appliance with output free standing 150mm diameter or square<br />
capacity not more than 30 kW section of equivalent area.<br />
Closed appliance burning free standing 125mm diameter or square<br />
smokeless fuel with output section of equivalent area.<br />
capacity not more than 20 kW<br />
Notes:<br />
1. In the table -<br />
SMOKELESS FUEL means solid mineral fuel that produces combustion products containing<br />
particulate matter that does not exceed a specified low amount.<br />
2. Any chimney pot or terminal must maintain the same cross-sectional area as the flue.<br />
3. Diagram 1 must only be used for the range of sizes shown within the shaded area.<br />
4. Fire size is related to the free opening area at the front of the fireplace opening.<br />
23F<br />
(F4.5)<br />
Amdt: December 1999<br />
F
F<br />
(F4.5)<br />
Diagram 1 to (F4.5): Flue sizing for larger solid fuel open fires<br />
Diagram 2 to (F4.5): Fireplace opening areas<br />
L<br />
H<br />
Amdt: September 2001<br />
L<br />
Fireplace opening area in square metres<br />
3.0<br />
2.0<br />
1.5<br />
1.0<br />
0.9<br />
0.8<br />
0.7<br />
0.6<br />
0.5<br />
0.4<br />
0.3<br />
0.2<br />
0.02<br />
Chimney height in metres<br />
(measured from the highest<br />
point of fireplace opening)<br />
Example<br />
0.03<br />
H<br />
Fireplace opening area = height (H) x total length (L)<br />
L<br />
H H<br />
L<br />
0.04<br />
0.05<br />
Flue area in square metres<br />
200<br />
225<br />
0.06<br />
0.07<br />
Recommended flue diameter in mm<br />
24F<br />
250<br />
300<br />
L<br />
0.10<br />
0.09<br />
0.08<br />
375<br />
400<br />
0.14<br />
0.12<br />
15<br />
12<br />
10<br />
8<br />
6<br />
5<br />
4<br />
3
(F4.8) The requirements of F4.8 will be met by providing access for cleaning in accordance with Clauses 5.4,<br />
9.5 and 10 of BS8303: Part 1: 1994.<br />
(F4.10) The requirements of F4.10 will be met where the outlet is positioned in accordance with the diagrams<br />
and table to this specification -<br />
Diagram 1 to (F4.10): Flue terminal positions<br />
B E<br />
A C D<br />
B<br />
more<br />
than 10˚ B C&E<br />
openable adjacent<br />
rooflight building<br />
or structure,<br />
whether<br />
connected<br />
or not<br />
Table to diagrams (F4.10): Minimum dimension to flue outlets<br />
A 2 300mm horizontally clear of the weather skin.<br />
B 1000mm provided A is satisfied; or<br />
600mm where above the ridge,<br />
except -<br />
where the roof is thatch or shingles, as Diagram 2 to (F4.10).<br />
C 1000mm above the top of any flat roof; and<br />
1000mm above any openable rooflight, dormer or ventilator, etc. within 2 300mm.<br />
D/E where D is not more than 2 300mm, E must be at least 600mm.<br />
Notes:<br />
1. Horizontal dimensions are to the surface surrounding the flue.<br />
2. Vertical dimensions are to the top of the chimney-stack.<br />
25F<br />
(F4.8), (F4.10)<br />
A<br />
Amdt: December 1999<br />
F
F<br />
(F4.10) – (4.12)<br />
Diagram 2 to (F4.10): Flue terminal outlets relative to easily ignited roof coverings<br />
PROTECTION FROM PRODUCTS OF COMBUSTION<br />
(F4.11) The requirements of F4.11c will be met where the chimney -<br />
a. is constructed of concrete chimney blocks capable of withstanding a temperature of at least<br />
1000º C and made of, or having inside walls made of, kiln burnt aggregate and high alumina<br />
cement jointed and pointed in cement mortar so that no joints, other than bedding joints,<br />
directly adjoin the flue; or<br />
b. has purpose made flue linings in accordance with Clause 5.1.5 of BS6461: Part 1: 1984 and any<br />
space between the lining and the chimney wall filled with weak mortar; or<br />
c. is a factory-made chimney meeting the requirements of BS4543: Part 2: 1990 and installed in<br />
accordance with BS7566: Parts 1 to 4: 1992; or<br />
d. has a lining accepted for the purpose after testing of the chimney under the relevant conditions<br />
by a notified body.<br />
(F4.12) The requirements of F4.12 will be met by a flue-pipe that is -<br />
Amdt: December 1999<br />
1 800 mm A<br />
B 2 300 mm B<br />
a. manufactured from -<br />
600 mm<br />
i. cast-iron pipe to BS41: 1973 (1981), or<br />
ii. mild steel at least 3mm thick to Section 1.1 of BS1449: Part 1: 1991, or<br />
iii. vitreous enamelled steel to BS6999: 1989, or<br />
Location of flue terminal outlets<br />
iv. stainless steel numbers 1.4401, 1.4404 or 1.4406 at least 1mm thick to BS EN 10088-1:<br />
1995; and<br />
b. constructed in accordance with Clause 9 of BS8303: Part 1: 1994.<br />
26F<br />
Flue outlets must terminate outwith zones A & B<br />
Zone A at least 1 800 mm vertically above<br />
the weather skin; and<br />
at least 600 mm above the ridge.<br />
Zone B at least 1 800 mm vertically above<br />
the weather skin; and<br />
at least 2 300 mm horizontally from<br />
the weather skin.
RELATIONSHIP TO COMBUSTIBLE MATERIALS<br />
(F4.17) The requirements of F4.17 will be met by -<br />
a. a constructional hearth at least 125mm thick and with plan dimensions in accordance with the<br />
diagrams to this specification; or<br />
b. where the appliance will not cause the temperature of the top surface of the hearth on which it<br />
stands to be more than 100º C, a free-standing, solid, non-combustible hearth at least 12mm<br />
thick.<br />
Diagrams to (F4.17a): Constructional hearth sizes<br />
at least 840 mm at least<br />
at least at least 840 mm<br />
500 mm 150 mm<br />
Plan of hearth in fireplace recess Plan of free-standing constructional hearth<br />
(F4.18) The requirements of F4.18 will be met where the appliance is positioned on a hearth in accordance<br />
with the diagrams to this specification -<br />
Diagram 1 to (F4.18): Locating a solid fuel appliance on a hearth<br />
at least<br />
150 mm<br />
[Note 1]<br />
front<br />
appliance<br />
Plan of appliance on a hearth<br />
at least 225 mm<br />
for a closed appliance<br />
extent of solid,<br />
non-combustible material<br />
At least 300 mm for an open appliance and for<br />
a closed appliance that may properly be used<br />
with its front open.<br />
Notes:<br />
1. The 150mm does not apply where the appliance is located in a fireplace recess, nor does it<br />
apply where the back or sides of the hearth either abut or are carried into a solid, non-combustible<br />
wall complying with (F4.19b).<br />
2. A solid fuel appliance may be located on a superimposed hearth provided the superimposed<br />
hearth is positioned partly or wholly on a constructional hearth in accordance with Diagram 2 to<br />
(F4.18).<br />
27F<br />
(F4.17), (F4.18)<br />
Amdt: December 1999<br />
F
F<br />
(F4.18), (4.19)<br />
Diagram 2 to (F4.18): Locating a solid fuel appliance on a superimposed hearth<br />
Notes:<br />
1. In this specification -<br />
SUPERIMPOSED HEARTH means a finish of solid, non-combustible material, usually decorative,<br />
at least 50mm thick and positioned on a constructional hearth.<br />
2. The 150mm does not apply where the appliance is located in a fireplace recess, nor does it<br />
apply where the back or sides of the hearth either abut or are carried into a solid, non-combustible<br />
wall complying with (F4.19b).<br />
3. At least 225mm for a closed appliance.<br />
4. At least 300mm for an open appliance and for a closed appliance that may properly be used<br />
with its front open.<br />
5. No part of the appliance shall project over any edge of the constructional hearth.<br />
6. At least 150mm to combustible material measured horizontally.<br />
(F4.19) The requirements of F4.19 will be met where -<br />
a. the hearth is located in a fireplace recess in accordance with BS8303: Part 1: 1994; or<br />
b. any part of the building, other than the floor, not more than 150mm from the hearth, is constructed<br />
of solid, non-combustible material in accordance with the diagram and table to this<br />
specification -<br />
Diagram to (F4.19b): Solid fuel appliance or hearth adjacent to any part of a building<br />
Amdt: December 1999<br />
front<br />
at least<br />
150 mm<br />
[Note 2] [Notes 3 & 4]<br />
superimposed hearth appliance<br />
combustible material<br />
constructional hearth<br />
solid, non-combustible<br />
material e.g. masonry<br />
or concrete<br />
at least<br />
150 mm<br />
H<br />
at least 125 mm<br />
Section through superimposed hearth<br />
[Notes 5 & 6]<br />
see table (F4.19b)<br />
at least 150 mm (F4.18)<br />
appliance<br />
X [Note 1]<br />
X [Note 1] at least 150 mm where X<br />
hearth is not more than 150 mm<br />
28F<br />
T
Table to diagram (F4.19b): Hearth and appliance adjacent to any part of a building<br />
Location of hearth or appliance Thickness (T) of solid, Height (H) of solid<br />
non-combustible material non-combustible material.<br />
where the hearth abuts a wall and the 200mm at least 300mm above the<br />
appliance is not more than 50mm appliance or 1.2 m above the<br />
from the wall hearth whichever is the greater.<br />
where the hearth abuts a wall and the 75mm at least 300mm above the<br />
appliance is more than 50mm but appliance or 1.2 m above the<br />
not more than 300mm from the wall hearth whichever is the greater.<br />
where the hearth does not abut a wall 75mm at least 1.2 m above the hearth.<br />
and is not more than 150mm from<br />
the wall [Note 1]<br />
Note:<br />
1. There is no requirement for protection of the wall where X is more than 150mm.<br />
(F4.21) The requirements of F4.21 will be met by -<br />
a. a fireplace recess, incorporating a constructional hearth, constructed in accordance with Clauses<br />
7 and 8 of BS8303: Part 1: 1994, and to the minimum thickness shown in Figure 2 to BS8303:<br />
Part 3: 1994; or<br />
b. a prefabricated appliance chamber of solid concrete components which -<br />
i. is connected to a chimney or flue-pipe, and<br />
ii. is supplied by the same manufacturer, with pre-made jointing arrangements, assembled<br />
on site using a cement specified for the purpose by the manufacturer, and<br />
iii. is of insulating concrete with a density of between 1 200 and 1 700 kg/m 3, and<br />
iv. is installed on a constructional hearth, and<br />
v. has components of the minimum thickness shown in the table to this specification -<br />
Table to (F4.21b): Thickness of solid fuel appliance chamber components<br />
Component Minimum thickness (mm)<br />
Base 50<br />
Sides 75<br />
Back panel and top slab 100<br />
Hood and bar lintels 100<br />
29F<br />
(F4.19), (4.21)<br />
Amdt: December 1999<br />
F
F<br />
(F5.2) – (F5.10)<br />
OIL-FIRED COMBUSTION APPLIANCE INSTALLATIONS<br />
APPLIANCES<br />
(F5.2) The requirements of F5.2 will be met by an appliance that complies with the OFTEC Standard appropriate<br />
for the class of the appliance.<br />
SUPPLY OF AIR FOR COMBUSTION<br />
(F5.3) The requirements of F5.3 will be met where the oil-fired appliance is provided with an air supply in<br />
accordance with Section 4 of BS5410: Part 1: 1997.<br />
SUPPLY OF AIR FOR COOLING<br />
(F5.4) The requirements of F5.4 will be met where the oil-fired appliance, located in an appliance compartment,<br />
is provided with air for cooling in accordance with Clause 4.4.3 of BS5410: Part 1: 1997.<br />
REMOVAL OF PRODUCTS OF COMBUSTION<br />
(F5.7) The requirements of F5.7 will be met where the chimney or flue-pipe is constructed and installed in<br />
accordance with the requirements of BS5410: Part 1: 1997.<br />
(F5.8) The requirements of F5.8 will be met where the flue gas temperature is measured in accordance with<br />
OFTEC Appliance Standard OFS A100 for boilers or OFS A101 for cookers.<br />
(F5.10) The requirements of F5.10 will be met where the terminal is separated from openings, obstructions or<br />
combustible material by at least the distance shown in the diagrams and table to this specification -<br />
Diagram 1 to (F5.10): Flue terminal positions for oil-fired appliances<br />
Amdt: December 1999<br />
J<br />
M<br />
H E<br />
P<br />
G<br />
30F<br />
C,D<br />
N<br />
O<br />
A B K<br />
F<br />
F L
Table to diagram (F5.10): Flue terminal positions for oil-fired appliances<br />
Location Minimum distance to<br />
terminal in mm<br />
Pressure Jet Vaporising<br />
A Directly below an opening, air brick, opening window etc 600 n/all<br />
B Horizontally to an opening, air brick, opening window etc 600 n/all<br />
C Below a plastic/painted gutter, drainage pipe or eaves, with protection 75 [5] n/all<br />
D Below a balcony or a plastic/painted gutter, drainage pipe or eaves 600 n/all<br />
E From vertical sanitary pipe work 300 n/all<br />
F From an internal or external corner 300 n/all<br />
G Above ground or balcony level 300 n/all<br />
H From a surface or boundary facing the terminal 600 [6] n/all<br />
J From a terminal facing the terminal 1200 n/all<br />
K Vertically from a terminal on the same wall 1500 n/all<br />
L Horizontally from a terminal on the same wall 750 n/all<br />
M Above the highest point of an intersection with the roof 600 [1] 1000 [7]<br />
N From a vertical structure to the side of the terminal 750 [1] 2300<br />
O Above a vertical structure not more than 750mm from the side of 600 [1] 1000 [7]<br />
the terminal<br />
P From a ridge terminal to a vertical structure on the roof 1500 n/all<br />
Notes:<br />
1. Terminating positions M, N, and O for vertical balanced flues should be in accordance with<br />
manufacturer’s instructions.<br />
2. Vertical structure in N, O and P includes tank or lift rooms, parapets, dormers etc.<br />
3. Terminating positions A to L are only permitted for appliances that have been approved for low<br />
level flue discharge when tested to OFTEC Standard OFS A100 for boilers or OFS A101 for<br />
cookers.<br />
4. Terminating positions must be at least 1 800mm from an oil storage tank unless a wall with at<br />
least 30 minutes fire resistance and more than 300mm higher and wider than the tank is provided<br />
between the tank and the terminating position.<br />
5. Where a flue terminates not more than 600mm below a projection and the projection is plastic<br />
or has a combustible finish, then a heat shield of at least 750mm wide must be fitted.<br />
6. The distance from an appliance terminal installed at right angles to a boundary may be reduced<br />
to 300mm in accordance with Diagram 2 to (F5.10).<br />
7. Where a terminal is used with a vaporising burner, a horizontal distance of at least 2 300mm is<br />
required between the terminal and the roof line.<br />
8. Notwithstanding the dimensions above, a terminal should be at least 300mm from combustible<br />
material.<br />
9. n/all = not allowed.<br />
31F<br />
(F5.10)<br />
Amdt: December 1999<br />
F
F<br />
(F5.10) – (F5.13)<br />
Diagram 2 to (F5.10) Separation between a boundary and terminal at right angles<br />
Plan at party wall<br />
RELATIONSHIP TO COMBUSTIBLE MATERIALS<br />
(F5.11) The requirements of F5.11 will be met where the temperature beneath the oil-fired appliance has been<br />
tested to, and is in accordance with, OFTEC Standard OFS A100 for boilers or OFS A101 for cookers.<br />
(F5.12) The requirements of F5.12 will be met where the appliance is located on a hearth in accordance with<br />
the diagram to this specification -<br />
Diagram to (F5.12): Locating an oil-fired appliance on a hearth<br />
at least 150 mm at least 150 mm<br />
[Note 1] for a closed appliance<br />
front<br />
appliance<br />
at least<br />
300 mm<br />
pressure boundary<br />
jet as party wall<br />
appliance<br />
Plan of appliance on a hearth<br />
extent of solid,<br />
non-combustible material<br />
at least 225 mm for an appliance with<br />
visible flames or radiating elements<br />
Note:<br />
1. The 150mm does not apply where the appliance is located in a fireplace recess, nor does it<br />
apply where the back or sides of the hearth either abut or are carried into a solid, non-combustible<br />
wall complying with (F4.19b).<br />
(F5.13) The requirements of F5.13 will be met where the back, sides and top of the oil-fired appliance has been<br />
tested to and are in accordance with the OFTEC Standard OFS A100 for boilers or OFS A101 for<br />
cookers.<br />
Amdt: December 1999<br />
32F
GAS-FIRED COMBUSTION APPLIANCE INSTALLATIONS<br />
APPLIANCES<br />
(F6.2) The requirements of F6.2 will be met where the gas-fired appliance carries a CE mark under the Gas<br />
Appliances (Safety) Regulations 1995.<br />
SUPPLY OF AIR FOR COMBUSTION<br />
(F6.3) The requirements of F6.3 will be met where air for combustion is provided in accordance with -<br />
a. for a decorative fuel-effect gas appliance, BS5871: Part 3: 1991;<br />
b. for an inset live fuel-effect gas appliance, BS5871: Part 2: 1991;<br />
c. for any other gas-fired appliance, BS5440: Part 2: 2000.<br />
SUPPLY OF AIR FOR COOLING<br />
(F6.4) The requirements of F6.4 will be met where the gas-fired appliance, located in an appliance compartment,<br />
is provided with air for cooling in accordance with BS5440: Part 2: 2000.<br />
REMOVAL OF PRODUCTS OF COMBUSTION<br />
(F6.5) The requirements of F6.5 will be met where the shared flue is constructed and installed in accordance<br />
with BS 5440: Part 1: 2000.<br />
(F6.6) The requirements of F6.6 will be met where the chimney or flue-pipe is constructed and installed in<br />
accordance with -<br />
a. for a decorative fuel-effect gas appliance, Clause 8 of BS5871: Part 3: 1991;<br />
b. where the chimney or flue-pipe is in a timber frame building, Section 8 of publication<br />
‘IGE/UP/7: ‘Gas Installation in Timber Framed Buildings’;<br />
c. where the flue-pipe is supplied as an integral part of the combustion appliance, the appropriate<br />
recommendations of the combustion appliance manufacturer;<br />
d. for any other gas-fired appliance, BS5440: Part 1: 2000.<br />
(F6.7) The requirements of F6.7 will be met where the minimum area of the flue is provided in accordance with -<br />
a. for a decorative fuel-effect gas appliance, Clause 8 of BS5871: Part 3: 1991;<br />
b. for an inset live fuel-effect gas appliance, BS5871: Part 2: 1991;<br />
c. for any other gas-fired appliance, BS5440: Part 1: 2000.<br />
(F6.9) The requirements of F6.9 will be met where the outer wall of a double-walled flue-pipe is manufactured<br />
from -<br />
a. aluminium, designation EN AW-1200 conforming to BS EN 573: Part 1: 1995;<br />
b. aluminium alloy, designation EN AW-3103 or EN AW-5251 conforming to BS EN 573: Part 1:<br />
1995;<br />
c. stainless steel, number 1.4335 to BS EN 10088: 1995;<br />
d. aluminium/zinc alloy coated steel of grades DX51D, DX52D, DX53D or DX54D with coating<br />
AZ185 or AZ150 conforming to BS EN 10215: 1995.<br />
33F<br />
(F6.2) – (F6.9)<br />
Amdt: September 2001<br />
F
F<br />
(F6.10)<br />
(F6.10) The requirements of F6.10 will be met where the outlet is separated from openings, obstructions or<br />
combustible material by at least the distances shown in the diagrams and tables to this specification -<br />
Diagram 1 to (F6.10): Flue terminal positions for gas-fired appliances<br />
S<br />
G S<br />
2000mm<br />
D,E<br />
F B<br />
Table 1 to diagram (F6.10): Flue terminal positions for gas-fired appliances<br />
Location Minimum distance to terminal in millimetres<br />
R<br />
600mm<br />
600mm<br />
C<br />
P A M<br />
J<br />
H A L<br />
J<br />
G<br />
no flue must penetrate<br />
area within dotted lines<br />
round roof light<br />
Balanced flue, room-sealed appliance Open flue<br />
Natural Fanned Natural Fanned<br />
draught draught draught draught<br />
A Directly below an opening, (0-7 kW) 300 300 n/all 300<br />
air brick, opening window, etc (>7-14 kW) 600<br />
(>14-32 kW) 1500<br />
(>32-70 kW) 2000<br />
B Above an opening, air brick, (0-32 kW) 300 300 n/all 300<br />
opening window, etc (>32-70 kW) 600<br />
C Horizontally to an opening, (0-7 kW) 300 300 n/all 300<br />
air brick, opening window, etc (>7-14 kW) 400<br />
(>14-70 kW) 600<br />
D Below a gutter, or sanitary 300 [2] 75 [1] n/all 75 [1]<br />
pipe work<br />
E Below the eaves 300 [2] 200 n/all 200<br />
Amdt: September 2001<br />
34F<br />
K,N
Table 1 to diagram (F6.10): Flue terminal positions for gas-fired appliances<br />
Location Minimum distance to terminal in millimetres<br />
Balanced flue, room-sealed appliance Open flue<br />
Natural Fanned Natural Fanned<br />
draught draught draught draught<br />
F Below a balcony or carport roof 600 200 n/all 200<br />
G Above ground, roof or 300 300 n/all 300<br />
balcony level<br />
H From vertical drain/soil pipe work 75 [1] 75 [1] n/all 75 [1]<br />
J From an internal or external corner 600 300 n/all 200 [1]<br />
K From a surface or boundary facing 600 600 [3] n/all 600<br />
the terminal<br />
L Vertically from terminal on same wall 1500 1500 n/all 1500<br />
M Horizontally from terminal on same wall 300 300 n/all 300<br />
N From a terminal facing the terminal 600 1200 n/all 1200<br />
P From an opening in a carport 1200 1200 n/all 1200<br />
(e.g. door, window) into the building<br />
R From a vertical structure on the n/app n/app [Note 5] n/app<br />
roof [Note 4]<br />
S Above an intersection with the roof n/app n/app [Note 5] 150 [1]<br />
Notes:<br />
1. Notwithstanding the dimensions above, a terminal serving a natural draught and fanned draught<br />
appliance more than 5kW heat input should be at least 300mm and 150mm respectively from<br />
combustible material.<br />
2. Where a natural draught flue terminates not more than 1m below a plastic projection or not more<br />
than 500mm below a projection with a painted surface, then a heat shield at least 1m long should<br />
be fitted.<br />
3. The distance from a fanned draught appliance terminal installed at right angles to a boundary<br />
may be reduced to 300mm in accordance with Diagram 2 to (F6.10).<br />
4. Vertical structure includes a chimney-stack, dormer window, tank room, lift motor room or<br />
parapet.<br />
5. See Table 2 to (F6.10).<br />
6. n/all = not allowed. n/app = not applicable.<br />
35F<br />
(F6.10)<br />
Amdt: December 1999<br />
F
F<br />
(F6.10) – (F6.16)<br />
Diagram 2 to (F6.10) Separation between a boundary and terminal at right angles<br />
Table 2 to diagram (F6.10): Minimum height S to the base of the terminal for roof mounted individual<br />
natural draught open-flued systems<br />
Type of Roof Where R is more than 1.5 m Where R is not more than 1.5 m<br />
(a) where the flue system is internal All flue systems internal and external.<br />
Flat roof where the roof has a parapet - 600mm<br />
where the roof has no parapet - 250mm<br />
Pitched roof where the roof pitch is more than 45º<br />
from the horizontal - 1 m;<br />
where the roof pitch is not more than 45º<br />
from the horizontal - 600mm,<br />
except -<br />
where the terminal is a ridge terminal,<br />
situated on or above the roof ridge, no<br />
minimum dimension for S is required.<br />
(b) where the flue system is external<br />
All roofs 600mm above the level of the 600mm above the level of the vertical<br />
adjacent roof edge structure.<br />
PROTECTION FROM PRODUCTS OF COMBUSTION<br />
(F6.11) The requirements of F6.11 will be met where the flue-pipe is manufactured from -<br />
Amdt: September 2001<br />
Plan at party wall<br />
a. any material described in (F4.12a) (solid fuel); or<br />
b. sheet metal as listed in BS715: 1993; or<br />
at least 300 mm at least 600 mm<br />
fanned natural<br />
draught draught<br />
c. fibre cement as described in BS7435: Part 1: 1991,<br />
except -<br />
boundary<br />
when serving a gas-fired appliance that can operate in condensing mode; or<br />
d. any other suitable material approved and tested under the relevant conditions by a notified body.<br />
36F
(F6.13) The requirements of F6.13 will be met where the flue-pipe is protected in accordance with BS 5440:<br />
Part 1: 2000.<br />
RELATIONSHIP TO COMBUSTIBLE MATERIALS<br />
(F6.16) The requirements of F6.16 will be met where the hearth is provided -<br />
a. for a gas fire, convector heater and fire/back boiler, in accordance with Clause 11 of BS5871:<br />
Part 1: 1991;<br />
b. for an inset live fuel-effect gas appliance, in accordance with Clause 11 of BS5871: Part 2: 1991;<br />
c. for a decorative fuel-effect gas appliance, in accordance with Clause 10 of BS5871: Part 3: 1991;<br />
d. for any other gas-fired appliance, by a solid, heat resistant, non-combustible, non-friable material<br />
at least 12mm thick and at least the plan dimension shown in the diagram to this specification -<br />
Diagram to (F6.16d): Hearth size suitable for any other gas-fired appliance<br />
at least 150 mm at least 225 mm<br />
[Note 1] beyond front<br />
front<br />
appliance<br />
hearth<br />
Plan of appliance on a hearth<br />
Note:<br />
1. The 150mm does not apply where the appliance is located in a fireplace recess, nor does it<br />
apply where the back or sides of the hearth either abut or are carried into a solid, non-combustible<br />
wall complying with (F4.19b).<br />
(F6.17) The requirements of F6.17 will be met where the gas-fired appliance and any associated draught diverters -<br />
a. are separated from combustible material by a shield of non-combustible material at least 25mm<br />
thick or an air space of at least 75mm; or<br />
b. where the appliance is CE marked, is installed in accordance with the manufacturer’s instructions.<br />
Diagram to (F6.17a): Appliance separation from combustible material<br />
air space at shield at<br />
least 75 mm least 25 mm<br />
combustible combustible<br />
material material<br />
appliance non-combustible<br />
material<br />
Plan/section Plan/section<br />
without shield with shield<br />
37F<br />
extent of solid,<br />
non-combustible material<br />
(F6.16), (F6.17)<br />
Amdt: September 2001<br />
F
F<br />
(F7.1), (F7.2)<br />
OIL STORAGE<br />
(F7.1) The requirements of F7.1 will be met where the tank is<br />
a. constructed in accordance with -<br />
i. for a steel tank, BS799: Part 5: 1987,<br />
ii. for a polyethylene tank with or without integral bunding, OFTEC <strong>Technical</strong> Standard<br />
OFS T100,<br />
iii. a European harmonised product standard and assessed by a notified body; and<br />
b. installed, together with the fuel feed system from the tank to the combustion appliance, in<br />
accordance with -<br />
i. for a tank with a capacity more than 3 500 litres, BS5410: Part 2: 1978,<br />
ii. for a tank with a capacity not more than 3 500 litres, BS5410: Part 1: 1997.<br />
(F7.2) The requirements of F7.2a and b will be met where the tank with a capacity -<br />
Amdt: September 2001<br />
a. more than 3 500 litres, is located in accordance with Clauses 45.2 and 45.3 of BS5410: Part 2:<br />
1978;<br />
b. not more than 3 500 litres and located within a building, is installed within a place of special<br />
fire risk ventilated to the external air and having -<br />
i. an outward opening door that is readily openable, without a key, from the side<br />
approached by people making an escape, and<br />
ii. sufficient space for access to the tank and its mountings and fittings;<br />
c. not more than 3 500 litres and not located within a building, is installed in accordance with the<br />
table to this specification -<br />
38F
Table to (F7.2b): Location of an oil storage tank not more than 3 500 litres capacity<br />
Location of tank Protection required<br />
Building without openings Building with openings<br />
not more than 1.8 m from non-combustible base; and non-combustible base, and<br />
any part of any building<br />
any part of the eaves not more than any part of the eaves not more than<br />
1.8 m from the tank and extending 1.8 m from the tank and extending<br />
300 mm beyond each side of the 300 mm beyond each side of the<br />
tank must be non-combustible; and tank must be non-combustible; and<br />
either - a barrier between the tank and any<br />
a. any part of a building not more part of a building not more than<br />
than 1.8 m from the tank must 1.8 m from the tank that does not<br />
meet the fire safety performance meet the fire safety performance<br />
required of an external wall with a required of an external wall with a<br />
short duration within 1 m of the short duration within 1 m of the<br />
boundary, (see D1.3) or boundary. (see D1.3)<br />
b. a barrier.<br />
More than 1.8 m from non-combustible base.<br />
any building<br />
Not more than 760mm non-combustible base, and a barrier, or a wall meeting<br />
from a boundary the fire safety performance required of an external wall<br />
with a short duration within 1 m of the boundary (see D1.3).<br />
More than 760mm non-combustible base.<br />
from a boundary<br />
Externally and wholly no protection required.<br />
below ground<br />
Note:<br />
1. In the table -<br />
NON-COMBUSTIBLE BASE means a solid base of concrete or of paving slabs at least 42mm thick<br />
that extends at least 300mm beyond all sides of the tank,<br />
except -<br />
where the tank is not more than 300 mm from a barrier, or a wall meeting the fire safety performance<br />
required of an external wall with a short duration within 1 m of the boundary (see D1.3),<br />
the base need only extend as far as the wall;<br />
BARRIER means an imperforate, non-combustible wall or screen at least 300mm higher and wider<br />
than any part of the tank, constructed so as to prevent the passage of direct radiated heat to the tank;<br />
39F<br />
(F7.1), (F7.2)<br />
Amdt: September 2001<br />
F
F<br />
(F7.2), (F7.5)<br />
The requirements of F7.2c will be met where the catchpit is provided in accordance with the requirements<br />
of Clause 6.5 of BS5410: Part 1: 1997 and the table to this specification -<br />
Table to (F7.2c): Provision of catchpits<br />
Location of tank Catchpit or integrally bunded tank [Note 1]<br />
Within a building required<br />
External, above ground (more than 2 500 litres) required<br />
External, above ground (not more than 2 500 litres) [Note 2]<br />
External, wholly below ground not required<br />
Notes:<br />
1. In the table -<br />
CATCHPIT means a pit, without a drain, which is capable of containing the contents of the<br />
tank, plus 10%;<br />
INTEGRALLY BUNDED TANK is a tank, together with a catchpit, manufactured as a selfcontained<br />
unit complete with a removable lid and designed to contain the escape of any liquid<br />
escaping from the tank in an overfill situation.<br />
2. Every tank located not more than 50 m from a spring or bore hole, 10 m from controlled waters or where it is<br />
likely to constitute a hazard as decided by a risk assessment described in OFTEC <strong>Technical</strong> Information Note<br />
TI/133 requires a catchpit or should be of the integrally bunded type.<br />
(F7.3) The requirements of F7.3 will be met where the fire valve is installed in accordance with -<br />
a. for tanks more than 3 500 litres, Clause 67 of BS5410: Part 2: 1978;<br />
b. for tanks not more than 3 500 litres, Clause 8.3 of BS 5410: Part 1: 1997.<br />
LIQUEFIED PETROLEUM GAS STORAGE<br />
(F7.4) The requirements of F7.4 will be met where the installation is constructed and installed in accordance<br />
with the requirements of the Health and Safety Executive.<br />
(F7.5) The requirements of F7.5a will be met by a container -<br />
a. constructed in accordance with the requirements set out in Section 3.1 of the LPGA Code of<br />
Practice 1: ‘Bulk LPG Storage at Fixed Installations’: Part 1; and<br />
b. installed in accordance with -<br />
i. for fixed storage tank(s), the LPGA Code of Practice 1: ‘Bulk LPG Storage at Fixed<br />
Installations’: Part 1,<br />
ii. for cylinder(s), the LPGA Code of Practice 24: ‘Use of LPG cylinders’: Parts 1 and 2.<br />
The requirements of F7.5b will be met where the tank(s) is located in accordance with the table and<br />
Diagram 1 to this specification -<br />
Amdt: September 2001<br />
40F
Table to (F7.5b): Separation distances for liquefied petroleum gas storage tanks<br />
Maximum capacity in litres (water equivalent) Minimum separation distance in metres<br />
of any single tank of any group of tanks for above ground tanks<br />
from building, boundary or fixed between tanks<br />
source of ignition to the tank -<br />
without a fire wall with a fire wall<br />
(A) (B)<br />
500 1 500 2.5 0.3 [2] 1.0<br />
2 500 7 500 3.0 1.5 [2] 1.0<br />
9 000 27 500 7.5 4.0 1.0<br />
Notes:<br />
1. In the table -<br />
FIRE WALL means a wall or screen meeting the fire safety performance required of an external<br />
wall with a short duration within 1 m of the boundary, (see D1.3) and located between 1 m and<br />
1.5 m from the tank and extending -<br />
a. longitudinally: so that the distance specified above without the fire wall is maintained<br />
when measured around the ends of the fire wall; and<br />
b. vertically: 2 m or the height to the top of the pressure relief valve, whichever is greater,<br />
except -<br />
where the tank capacity is not more than 2 500 litres, the fire wall need be no higher than<br />
the top of the pressure relief valve and may form part of the site boundary.<br />
2. Where a tank(s) not more than 2 500 litres total capacity is located closer to a building than the<br />
separation distance in column A, the fire wall should form part of the wall of the building in<br />
accordance with Diagram 2 to this specification.<br />
3. Motor vehicles under the control of the site occupier should be parked at least 6 m from LPG<br />
tanks or the separation distance in column A of Table to (F7.5b), whichever is the smaller. This<br />
does not apply to the loading/unloading of vehicles. Motor vehicles not under site control (eg<br />
those belonging to members of the public) should be parked no closer than the separation distance<br />
in column A to Table to (F7.5b).<br />
Diagram 1 to (F7.5b): Separation or shielding of a liquefied petroleum gas tank from a building,<br />
boundary or fixed source of ignition<br />
building, boundary or<br />
fixed source of ignition boundary<br />
table to (F7.5b) table to (F7.5b) table to (F7.5b)<br />
column A column A column B<br />
tank not more<br />
than 9 000 litres<br />
table to (F7.5b) table to (F7.5b)<br />
column B 1-1.5 m column A tank(s) not more than<br />
2 500 litres total capacity<br />
Plan view with and without a fire wall Fire wall as part of the boundary<br />
41F<br />
(F7.5)<br />
Amdt: September 2001<br />
F
F<br />
(F7.5)<br />
Diagram 2 to (F7.5b): Small liquefied petroleum gas storage tank close to a building<br />
Amdt: September 2001<br />
9 m or to the eaves<br />
To be 1 m either side<br />
of pressure relief valve<br />
the wall must meet the fire safety<br />
performance required of an<br />
external wall within 1m of the<br />
boundary (see D1.3) -<br />
for a building of purpose group 1<br />
and 2, medium duration; or<br />
for any other building, short<br />
duration. (see D1.3) LPG tank(s) not more than<br />
2 500 litres total capacity<br />
height to top of pressure relief valve<br />
The requirements of F7.5c will be met where the number of tanks in a group is not more than six.<br />
42F<br />
2 m<br />
0.3 m for a tank(s) not more than 500 litres<br />
1.5 m for a tank(s) not more than 2 500 litres<br />
Table to (F7.5b) Table to (F7.5b)<br />
column A LPG tank column A<br />
Plan of Diagram 2 to (F7.5)b
PREPARATION OF SITES,<br />
RESISTANCE TO MOISTURE AND<br />
RESISTANCE TO CONDENSATIONG
Contents<br />
INTRODUCTION<br />
REGULATION 16<br />
Preparation of sites<br />
REGULATION 17<br />
Resistance to moisture<br />
REGULATION 18<br />
Resistance to condensation<br />
THE STANDARDS<br />
G1 Application of Part G G1.1-G1.5<br />
G2 Preparation of a site and resistance to<br />
moisture from the ground<br />
Preparation of a site G2.1-G2.4<br />
Resistance to moisture from the ground G2.5-G2.6<br />
G3 Resistance to precipitation<br />
Resistance to precipitation G3.1<br />
G4 Condensation<br />
Interstitial condensation G4.1<br />
Surface condensation G4.2<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(G2.2, Preparation of a site and resistance to moisture from the<br />
G2.3, ground<br />
G2.5,<br />
G2.6)<br />
(G3.1) Resistance to precipitation<br />
(G4.1) Interstitial condensation<br />
(G4.2) Surface condensation<br />
PART G APPENDIX<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A (General).<br />
3G<br />
Amdt: December 1999<br />
G
5G<br />
Introduction<br />
1. The intention of this Part is to ensure that measures are<br />
taken to protect people, and the fabric of a building, from<br />
harm which could be caused by site conditions or the effects<br />
of moisture in various forms.<br />
2. In addition to surface soil and decaying or organic matter<br />
being removed from a site, thorough investigation is necessary<br />
to ensure that appropriate measures can be taken where<br />
there is evidence of any harmful or dangerous substances.<br />
An Appendix giving outline guidance is included at the end<br />
of this Part.<br />
3. Subsoil drainage of the site is required where necessary to<br />
help prevent the penetration of ground water and flood water<br />
to the interior of a building and damage to the building fabric.<br />
Any existing drains which will be affected by the construction<br />
of a building must also continue to function properly.<br />
4. A building must be constructed so that moisture in the<br />
ground and from the weather will not damage the fabric or<br />
penetrate to the inner surface of the building.<br />
5. For the control of condensation in roofs the<br />
deemed-to-satisfy specification quotes BS5250 which provides<br />
guidance on the principal forms of construction<br />
including cold deck roofs. There is evidence which suggests<br />
that condensation in this type of roof system is a problem.<br />
The <strong>Scottish</strong> Executive considers that in the climatic conditions<br />
of Scotland ventilation of the roof void in flat roofs<br />
should not be endorsed as many instances of failure in cold<br />
deck roof systems have been recorded. Both the warm deck<br />
and warm deck inverted roof constructions, where the insulation<br />
is placed above the roof deck, are considered preferable.<br />
While the Regulations do not prevent the use of cold<br />
deck roof constructions, it is considered that much more reliable<br />
forms of construction are likely to result from over-roof<br />
insulation whenever this is possible.<br />
6. A building of purpose group 1, a dwelling (ie a house,<br />
flat or maisonette) must be constructed to reduce the risk of<br />
both interstitial and surface condensation in order to prevent<br />
damage to the fabric and harmful effects on the health of<br />
people using the building. The requirements for both interstitial<br />
and surface condensation are deemed to be satisfied by<br />
the guidance given in BS5250: 1989 “British Standard Code<br />
of Practice for the Control of condensation in buildings”.<br />
However, the guidance in BS5250, which covers buildings<br />
generally, should be followed for other buildings where the<br />
internal climate is quite stable.<br />
Amdt: December 1999<br />
G
G<br />
Regulations 16,17 & 18<br />
Preparation of sites<br />
16.(1) Subject to paragraph (3), a site and ground<br />
immediately adjoining a site shall be so prepared<br />
and treated as to protect the building<br />
and its users from harmful effects caused by -<br />
(a) harmful or dangerous substances;<br />
(b) matter in the surface soil; and<br />
(c) vegetable matter.<br />
(2) Subject to paragraph (3), a site and ground<br />
immediately adjoining a site shall be so<br />
drained or otherwise treated as to protect the<br />
building and its users, so far as may be reasonably<br />
practicable, from harmful effects<br />
caused by -<br />
(a) ground water;<br />
(b) flood water; and<br />
(c) existing drains.<br />
(3) Paragraphs (1)(b), (1)(c) and (2)(c) shall not<br />
apply to a limited-life building of purpose<br />
groups 2 to 7 inclusive.<br />
(4) In paragraph (1)(a) “harmful or dangerous<br />
substances” includes deposits of faecal or<br />
animal matter and any substance or mixture of<br />
substances which is or could become corrosive,<br />
explosive, flammable, radioactive or<br />
toxic or which produces or could produce any<br />
gas likely to have any such characteristic.<br />
Resistance to moisture<br />
17.(1) Subject to paragraph (2), a building shall be so<br />
constructed as to protect the building and its<br />
users from harmful effects caused by -<br />
(a) moisture rising from the ground; and<br />
(b) precipitation.<br />
(2) This regulation shall not apply to a building<br />
where penetration of moisture from outside<br />
will result in effects no more harmful than<br />
those likely to arise from use of the building.<br />
Resistance to condensation<br />
18. A building of purpose group 1 shall be so<br />
constructed as to protect the building and its<br />
users, so far as may be reasonably practicable,<br />
from harmful effects caused by condensation.<br />
Amdt: December 1999<br />
6G
The standards<br />
G1 Application of Part G<br />
G1.1 This Part sets out the required standards for Regulations 16 to 18.<br />
G1.2 The standards in G2 apply to all buildings,<br />
except -<br />
G2.3 and G2.4 do not apply to a limited-life building of purpose groups 2 to 7 inclusive.<br />
G1.3 The standards in G3 apply to a building of any purpose group,<br />
except -<br />
to a building where the penetration of moisture from outside would be no more harmful than that likely<br />
to arise from the use of the building.<br />
G1.4 The standards in G4 apply to a building of purpose group 1.<br />
G1.5 In this Part -<br />
FLOOR means any construction between the surface of the ground, or the surface of any hardcore<br />
laid upon the ground, and the upper surface of the floor, together with any floor finishes<br />
which are laid as part of the permanent construction;<br />
WALL means any wall, including piers, chimneys, columns and parapets which form part of the<br />
wall.<br />
ROOF means any roof, including eaves and junctions with other elements penetrating, or connected<br />
to, the roof; and<br />
G2 Preparation of a site and resistance to moisture from the ground<br />
PREPARATION OF A SITE<br />
G2.1* A site, and ground immediately adjoining a site, must have harmful or dangerous substances removed or<br />
made safe.<br />
G2.2* A site, and ground immediately adjoining a site, which is liable to accumulate ground or flood water<br />
must be drained, or treated, to overcome the effects of any such water.<br />
G2.3* A site, and ground immediately adjoining a site, must be cleared of any surface soil and vegetable matter<br />
(including wood) to the extent necessary to prevent any harmful effect on a building and the solum (the<br />
prepared area within the containing walls of a building) treated to prevent vegetable growth.<br />
G2.4 Where a building is erected over an existing drain, including a field drain, which is to remain active, the<br />
drain must be re-routed if reasonably practicable or re-constructed in a manner appropriate to the conditions<br />
of the site.<br />
7G<br />
G1.1 – G2.4<br />
Amdt: December 1999<br />
G
G<br />
G2.5 – G4.2<br />
RESISTANCE TO MOISTURE FROM THE GROUND<br />
G2.5* The solum (the prepared area within the containing walls of a building) must be treated to reduce the<br />
evaporation of moisture from the ground to the inner surface of any part of a building which it could<br />
damage.<br />
G2.6* A floor, wall or other building element adjoining the ground must prevent moisture from the ground<br />
reaching the inner surface of any part of a building which it could damage.<br />
G3 Resistance to precipitation<br />
RESISTANCE TO PRECIPITATION<br />
G3.1* A floor, wall, roof or other building element exposed to precipitation must prevent penetration of moisture<br />
to the inner surface of any part of a building which it could damage.<br />
G4 Condensation<br />
INTERSTITIAL CONDENSATION<br />
G4.1* A floor, wall, roof or other building element of a dwelling must minimise the risk of interstitial condensation<br />
in any part of a dwelling which it could damage.<br />
SURFACE CONDENSATION<br />
G4.2* A floor, wall, roof or other building element of a dwelling must minimise the risk of condensation on<br />
any inner surface where it could damage the health of people.<br />
Amdt: December 1999<br />
8G
Provisions deemed to satisfy the standards<br />
PREPARATION OF A SITE AND RESISTANCE TO MOISTURE FROM THE GROUND<br />
(G2.1) The requirements of G2.1 will be met where protection against the ingress of radon gas into dwellings<br />
is provided in accordance with the recommendations in ‘Radon: guidance on protection measures for<br />
new dwellings in Scotland’.<br />
(G2.2) The requirements of G2.2 will be met where sub-soil drains are provided and laid in accordance with<br />
the relevant clauses of BS8301: 1985.<br />
(G2.3, The requirements of G2.3, G2.5 and G2.6 will be met where the solum and building are constructed as<br />
G2.5, specified below (but note that the diagrams do not show all the structural bracing that might be required).<br />
G2.6)<br />
Specified constructions<br />
The thickness and other dimensions specified are the minimum required unless otherwise stated;<br />
greater figures are therefore permissible.<br />
Ground supported concrete floors<br />
A. The solum is brought to a level surface.<br />
Hardcore bed 100mm thick of clean broken<br />
brick or similar inert material free from fine<br />
material and water soluble sulphates in<br />
quantities which would damage the concrete;<br />
blinded with suitable fine material<br />
and consolidated to form a level crack-free<br />
surface.<br />
Concrete slab 100mm thick with insulation,<br />
if any, laid above or below the slab; with or<br />
without a screed or floor finish.<br />
Damp-proof membrane above or below the<br />
slab or as a sandwich; jointed and sealed to<br />
the damp-proof course or damp-proof<br />
structure in walls, columns and other<br />
adjacent elements in accordance with the<br />
relevant clauses in Section 3 of<br />
CP 102: 1973.<br />
9G<br />
insulation<br />
above or<br />
below<br />
(if required)<br />
(G2.1 – G2.6)<br />
;damp proof<br />
membrane<br />
concrete slab<br />
hardcore<br />
solum<br />
insulation<br />
above or<br />
concrete slab<br />
below<br />
(if required) ;damp proof<br />
membrane<br />
hardcore<br />
solum<br />
concrete slab<br />
insulation;damp<br />
proof<br />
above or<br />
membrane<br />
below<br />
concrete slab<br />
(if required)<br />
hardcore<br />
;<br />
solum<br />
A. Ground supported concrete floor<br />
Amdt: December 1999<br />
G
G<br />
(G2.3 – G2.6)<br />
Suspended timber floors<br />
Amdt: December 1999<br />
B. The solum is brought to an even surface; any<br />
upfilling to be of hard, dry material.<br />
Hardcore bed as for A. above; with either a<br />
damp-proof membrane in accordance with<br />
Section 3 of CP 102: 1973; or concrete<br />
;150<br />
50mm thick laid on 0.25mm (1000 gauge)<br />
polyethylene sheet; or concrete 100mm thick;<br />
so that in any case the top surface is not below<br />
100<br />
that of the adjacent ground.<br />
Suspended timber floor with or without insulation<br />
as required. Floor joists carried on<br />
wall-plates supported as necessary by sleeper<br />
walls with a damp-proof course under the<br />
wall-plates.<br />
Permanent ventilation of the underfloor space<br />
direct to the outside air by ventilators in 2<br />
external walls on opposite sides of the building<br />
to provide an open area in each wall of either<br />
1500mm 2 for at least every metre run of the<br />
wall, or 500mm 2 for at least every square metre<br />
of floor area, this open area also being provided<br />
in internal sleeper walls or similar<br />
obstructions to maintain the underfloor ventila-<br />
tion; the ventilated space to be 75mm in height<br />
;150<br />
from the site covering to the underside of any<br />
wall-plates and 150mm to the underside of the<br />
floor joists.<br />
100<br />
Suspended concrete floors<br />
C. The solum is brought to an even surface; any<br />
upfilling to be of hard, dry material.<br />
;<br />
;<br />
;150<br />
10G<br />
50<br />
B. Suspended timber floor<br />
insulation<br />
anywhere<br />
in this space<br />
damp proof<br />
membrane<br />
hardcore<br />
solum<br />
insulation<br />
anywhere<br />
in this space<br />
concrete<br />
polyethylene<br />
sheet<br />
solum<br />
insulation<br />
anywhere<br />
in this space<br />
concrete<br />
solum<br />
Suspended concrete floor of in-situ or precast<br />
concrete slabs or beams with concrete or clay<br />
infill units; with insulation, if any; with or<br />
without a screed or floor finish, or with boards.<br />
Permanent ventilation of the underfloor space<br />
direct to the outside air by ventilators in 2<br />
external walls on opposite sides of the building<br />
to provide an open area in each wall of<br />
1500mm2 for at least every metre run of the<br />
wall, or 500mm2 insulation<br />
;150<br />
for at least every square metre<br />
of floor area, this open area also being pro-<br />
solum<br />
vided in internal sleeper walls or similar<br />
obstructions to maintain the underfloor ventilation;<br />
the ventilated space to be 150mm to the<br />
underside of the floor slab or beams.<br />
C. Suspended concrete floor
Walls and floors at or near ground level<br />
D. Walls constructed in accordance with clause 10 of CP 102: 1973.<br />
Floors constructed in accordance with clause 11 of CP 102: 1973,<br />
except -<br />
ventilation of the sub-floor (clause 11. 8. 4) is to be as in B above.<br />
Structures below ground including basements<br />
E. Structures constructed in accordance with the relevant clauses in Section 2 of CP 102: 1973.<br />
RESISTANCE TO PRECIPITATION<br />
(G3.1) The requirements of G3.1 will be met where the exposed elements are constructed as specified in the<br />
relevant provisions below (but note that the diagrams do not show all the structural bracing that may be<br />
required).<br />
Specified constructions<br />
The thickness and other dimensions specified are the minimum required unless otherwise stated;<br />
greater figures are therefore permissible.<br />
General<br />
In using any of the constructions on the following pages under ‘Wall types’ and ‘Roof types’, the<br />
following general provisions apply for walls or roofs as appropriate.<br />
a. Masonry walls of bricks and/or blocks incorporating damp-proof courses, flashings and other<br />
materials and components constructed in accordance with the relevant recommendations of<br />
BS5628: Part 3: 1985, using a construction to suit the degree of exposure to wind and rain in<br />
accordance with clause 21 and as described in BS8104: 1992.<br />
b. Masonry walls incorporating external rendering which conforms to the relevant recommendations<br />
of BS5262: 1991, to suit the degree of exposure and the type of masonry.<br />
c. Masonry walls of natural stone or cast stone blocks constructed in accordance with the relevant<br />
recommendations of Section 3 of BS5390: 1976 (1984) and to suit the degree of exposure to wind<br />
and rain as described in BS8104: 1992.<br />
d. Masonry cavity walls incorporating insulation material, either as a complete or partial cavity fill,<br />
where the insulating material is the subject of a current certificate issued under the relevant conditions<br />
of an independent testing body, the walls are constructed in accordance with the terms of<br />
the certificate and to suit the degree of exposure to wind and rain as described in BS8104: 1992<br />
and the relevant recommendations of the following British <strong>Standards</strong>.<br />
Materials or conditions British <strong>Standards</strong><br />
Urea formaldehyde (UF) foam BS5617: 1985 and BS5618: 1985<br />
Man-made mineral fibre (slabs) BS6676: Part 1: 1986 and Part 2: 1986<br />
Assessment of walls for filling BS8208: Part 1: 1985<br />
11G<br />
(G2.3 – G3.1)<br />
Amdt: December 1999<br />
G
G<br />
(G3.1)<br />
e. Walls or roofs incorporating cladding materials constructed in accordance with the recommendations<br />
of the following British <strong>Standards</strong> or Codes of Practice -<br />
Amdt: December 1999<br />
British <strong>Standards</strong> and<br />
Materials or conditions Element Codes of Practice<br />
Aluminium wall or roof CP 143: Part 15: 1973 (1986)<br />
Galvanised corrugated steel wall or roof CP 143: Part 10: 1973<br />
Lead wall or roof BS6915: 1988<br />
Copper wall or roof CP 143: Part 12: 1970 (1988)<br />
Slates and tiles wall or roof BS5534: Part 1: 1997<br />
Zinc wall or roof CP 143: Part 5: 1964<br />
Non-loadbearing walls wall or steep roof BS8200: 1985<br />
Precast concrete cladding wall BS8297: 1995<br />
Natural stone cladding wall BS8298: 1994<br />
Flat roofs roof BS6229: 1982<br />
Bitumen felt roof BS8217: 1994<br />
Mastic asphalt roof BS8218: 1998<br />
f. Roofs with copper, lead, zinc and other sheet metal roof coverings require provision for expansion<br />
and contraction of the sheet material. In ‘warm deck’ roofs, in order to reduce the risk of<br />
condensation and corrosion, it may be necessary to provide a ventilated air space on the cold<br />
side of the insulation and a high performance vapour control layer between the insulation and<br />
the roof structure. It may also be necessary to consult the relevant trade association.<br />
12G
Wall type 1: solid walls of masonry<br />
;25<br />
A. Solid wall, 200mm thick of bricks, blocks or<br />
slabs of clay, calcium silicate, concrete or cast<br />
stone.<br />
plasterboard<br />
Wall rendered or unrendered externally.<br />
insulation<br />
Insulation and plasterboard internally, with<br />
;<br />
a<br />
cavity<br />
cavity 25mm wide.<br />
A. Solid wall with internal insulation<br />
B. Solid wall as A. above.<br />
Insulation applied to the external surface of the<br />
wall; protected externally either by cladding<br />
(of sheets, tiles or boarding) with permanent<br />
ventilation, or by rendering.<br />
;insulation<br />
external protection<br />
Wall with or without an internal surface finish B. Solid wall with external insulation<br />
of plaster or plasterboard.<br />
Wall type 2: cavity walls of masonry<br />
A. Cavity wall of 2 leaves of masonry separated<br />
by a 50mm cavity; each leaf, 100mm thick, of<br />
either bricks or blocks of clay, calcium silicate<br />
or concrete.<br />
Wall rendered or unrendered externally.<br />
plasterboard<br />
;insulation<br />
Insulation applied as a lining to the internal<br />
cavity<br />
surface of the wall and plasterboard.<br />
A. Cavity wall with internal insulation<br />
B. Cavity wall as A. above.<br />
Wall rendered or unrendered externally.<br />
Insulation applied as a cavity fill.<br />
Wall with or without an internal surface finish<br />
of plaster or plasterboard.<br />
C. Cavity wall as A. above.<br />
Wall rendered or unrendered externally.<br />
Insulation applied to either leaf as a partial<br />
cavity fill so as to preserve a residual space of<br />
50mm wide.<br />
Wall with or without an internal surface finish<br />
of plaster or plasterboard.<br />
100 50 100<br />
100 50 100<br />
;<br />
13G<br />
insulation<br />
B. Cavity wall with cavity fill insulation<br />
(G3.1)<br />
;insulation<br />
50<br />
cavity<br />
C. Cavity wall with partial fill insulation<br />
Amdt: December 1999<br />
G
G<br />
(G3.1)<br />
Wall type 3: framed walls<br />
A. Framed wall of timber standards and rails, with<br />
a vapour permeable sheathing to the framing<br />
covered with a breather membrane.<br />
Masonry external cladding of 100mm thick<br />
clay brick or block, concrete or calcium silicate<br />
brick or block, dense in-situ concrete, lightweight<br />
concrete or autoclaved aerated<br />
concrete, with an externally ventilated cavity<br />
of 50mm but not more than 100mm wide<br />
between the cladding and the framing, the<br />
cavity ventilated to the outside by means of one<br />
open perpend joint for at least every 1.2<br />
;A. Masonry cladding<br />
metre<br />
run at the top and bottom of the wall.<br />
Masonry cladding rendered or unrendered<br />
externally.<br />
Insulation applied as an infill to the framing.<br />
The framing lined internally with a vapour<br />
control layer and plasterboard.<br />
B. Framed wall of timber standards and rails with<br />
a breather membrane.<br />
Cladding material, on battens and counter<br />
battens as required, of timber weatherboarding,<br />
tile or slate. ;insulation<br />
;B.<br />
sheathing<br />
breather<br />
Insulation and internal lining as A. above.<br />
membrane<br />
Weatherboarding, tile or slate cladding<br />
C. Framed wall of timber or metal standards and<br />
rails.<br />
lining<br />
vapour control<br />
layer<br />
Sheet or panel cladding material of ;insulation<br />
fibre<br />
cement, plastic, metal, GRP or GRC.<br />
C. Sheet or panel cladding<br />
Amdt: December 1999<br />
Insulation applied either to the internal face of<br />
the framing with permanent ventilation behind<br />
any impervious cladding, or as an infill to the<br />
framing; in either case the wall lined internally<br />
with a vapour control layer and a lining.<br />
14G<br />
50 to 100<br />
vapour control<br />
layer<br />
plasterboard<br />
insulation<br />
sheathing<br />
breather<br />
membrane<br />
vapour control<br />
layer<br />
plasterboard<br />
lining<br />
vapour control<br />
layer<br />
;insulation<br />
ventilated cavity<br />
C. Sheet or panel cladding (with ventilated cavity)
Roof type 1: flat roofs [Note 1]<br />
B. Flat roof structure as A. above.<br />
External protective covering; with low permeability<br />
insulation laid on a waterproof membrane<br />
between the roof structure and the<br />
external covering.<br />
C. Flat roof structure of timber or metal framed ;weatherproof covering<br />
construction with a board decking 19mm thick;<br />
insulation<br />
with or without a ceiling or soffit.<br />
vapour control layer<br />
External weatherproof covering, insulation and<br />
vapour control layer as A. above. [Note 1]<br />
Note:<br />
1. Roof types 1A. and 1C. are not suitable for<br />
sheet metal coverings that require joints to<br />
allow for thermal movement. See also<br />
‘General’, f. of the provision deemed to satisfy<br />
G3.1.<br />
15G<br />
(G3.1)<br />
A. Flat roof structure of in-situ or precast concrete<br />
with or without a screed; with or without ;weatherproof a<br />
covering<br />
ceiling or soffit.<br />
insulation<br />
vapour control layer<br />
External weatherproof covering; with insula-<br />
screed if required<br />
tion laid on a vapour control layer between the<br />
roof structure and the weatherproof covering.<br />
[Note 1]<br />
A. Concrete - warm roof<br />
;protective covering<br />
B. Concrete - inverted roof<br />
insulation<br />
waterproof membrane<br />
screed if required<br />
C. Timber or metal frame - warm roof<br />
Amdt: December 1999<br />
G
G<br />
(G3.1)<br />
D. Flat roof structure as C. above.<br />
External protective covering, insulation and<br />
protective covering<br />
waterproof membrane as B. above.<br />
insulation<br />
waterproof membrane<br />
E.<br />
;<br />
D. Timber or metal frame - inverted roof<br />
;<br />
weatherproof<br />
covering<br />
Flat roof structure of timber or metal framed<br />
insulation<br />
construction with a troughed metal decking;<br />
vapour control layer<br />
with or without a ceiling or soffit.<br />
External weatherproof covering and insulation<br />
and vapour control layer as A. above. [Note 1]<br />
E. Troughed metal decking - warm roof<br />
F. ;<br />
protective covering<br />
Flat roof structure as E. above.<br />
insulation<br />
waterproof<br />
External protective covering, insulation and<br />
membrane<br />
waterproof membrane as B. above.<br />
Note:<br />
1. Roof type 1E. is not suitable for sheet metal<br />
coverings that require joints to allow for<br />
thermal movement. See also ‘General’, f. of the<br />
provision deemed to satisfy G3.1.<br />
Amdt: December 1999<br />
16G<br />
F. Troughed metal decking - inverted roof
Roof type 2: pitched roofs [Note 1]<br />
A. Pitched roof structure of timber or metal<br />
framed construction.<br />
External weatherproof covering of slates or<br />
tiles on under stating felt with or without<br />
boards or battens.<br />
Insulation laid on a level ceiling with a ventilated<br />
space between the insulation and the roof<br />
structure.<br />
B. Pitched roof structure as A. above.<br />
External weatherproof covering as A. above.<br />
Insulation and vapour control layer laid on a<br />
sloping ceiling, with a ventilated air space<br />
50mm in depth between the insulation and the<br />
boards of the pitched roof covering.<br />
C. Pitched roof structure as A. above with a<br />
decking of low permeability insulation fitted to<br />
and between the roof framing.<br />
External weatherproof covering of slates or<br />
tiles, with tiling battens and counter battens<br />
(located over roof framing), and a breather<br />
membrane laid on the insulation decking; with<br />
a sloping ceiling.<br />
D. Pitched roof structure as A. above.<br />
External weatherproof covering of metal or<br />
fibre cement sheet sandwich construction laid<br />
on purlins; with insulation sandwiched<br />
between the external and soffit sheeting; and<br />
with or without a ceiling. [Note 1]<br />
Note:<br />
1. Roof type 2D. is not suitable for sheet metal<br />
coverings that require joints to allow for<br />
thermal movement. See also ‘General’ f. of the<br />
provisions deemed to satisfy G3.1.<br />
17G<br />
(G3.1)<br />
slates or tiles<br />
;underslating<br />
felt<br />
A. Slates or tiles - insulation on a level ceiling<br />
ventilated<br />
space<br />
insulation<br />
;underslating<br />
slates or tiles<br />
felt<br />
50mm<br />
ventilated<br />
space<br />
insulation<br />
vapour<br />
control layer<br />
B. Slates or tiles - insulation on a sloping ceiling<br />
;<br />
slates or<br />
tiles on<br />
battens<br />
counter battens<br />
breather<br />
membrane<br />
insulation<br />
C. Slates or tiles - insulation as decking<br />
(longitudinal section)<br />
;<br />
external<br />
sheet<br />
covering<br />
insulation<br />
sandwich<br />
D. Metal or fibre cement sheet - sandwich insulation<br />
;<br />
Amdt: December 1999<br />
G
G<br />
(G4.1), (G4.2)<br />
INTERSTITIAL CONDENSATION<br />
(G4.1) The requirements of G4.1 will be met where the walls, roofs and floors are assessed and/or constructed<br />
in accordance with Appendix D and Clauses 9.1 to 9.5.5.2 of BS5250: 1989.<br />
SURFACE CONDENSATION<br />
(G4.2) The requirements of G4.2 will be met where openings and junctions in or between the specified elements<br />
are constructed in accordance with Clauses 9.6.1 to 9.6.3 of BS5250: 1989 to a thermal transmittance<br />
(U-value) which does not exceed 1.2 W/m 2 K at any point.<br />
Amdt: December 1999<br />
18G
Appendix<br />
THIS APPENDIX IS NOT PART OF THE TECHNICAL STANDARDS OR THE DEEMED TO SATISFY PROVISIONS AND IS<br />
THEREFORE NON-MANDATORY. IT GIVES OUTLINE GUIDANCE ON THE PREPARATION OF A SITE WHERE HARMFUL<br />
OR DANGEROUS SUBSTANCES ARE SUSPECTED OR IDENTIFIED AND ON FLOOD DAMAGE TO BUILDINGS AND RADON<br />
PROTECTION MEASURES FOR NEW DWELLINGS.<br />
Preparation of a site<br />
1. Harmful or dangerous substances includes deposits of faecal or animal matter and any substance or<br />
mixture of substances which is, or could become, corrosive, explosive, flammable, radioactive or<br />
toxic or which produces, or could produce, any gas likely to have any such characteristic.<br />
2. Where records or local knowledge of previous use identifies land which may contain, or give rise to,<br />
harmful or dangerous substances, planning permission will normally be subject to conditions. These<br />
conditions will be imposed to ensure that the development proposed for the land will not expose<br />
future users or occupiers, or any building or services, to hazards associated with the contaminants.<br />
Examples of land likely to contain contaminants are given in Table 1.<br />
3. There may be occasions when land containing harmful or dangerous substances has not been identified<br />
at the planning stage, and the presence of contaminants is only suspected later. Some signs of<br />
the possible presence of contaminants are given in Table 2.<br />
4. If any signs of possible contaminants are present the Local Authority should be told at once. If the<br />
presence of any of the contaminants listed in Table 2 is confirmed, it is likely that some form of<br />
remedial action will be required. For guidance, the normal course of remedial action is listed against<br />
each contaminant noted in Table 2. In all cases these courses of action assume that the ground to be<br />
covered by the building will have at least 100mm of in-situ concrete cover. Expert advice may be<br />
required to provide an economical and safe solution to the hazards encountered, especially where<br />
contaminants are present in large amounts or where there is imminent danger to health or safety.<br />
5. With the increasing re-development of former industrial land in the UK, attention is also drawn to<br />
the British <strong>Standards</strong> Institution publication, first issued in April 1988 as a Draft for Development,<br />
DD 175: 1988 (1992), “Code of practice for the identification of potentially contaminated land and<br />
its investigation”. This is designed to provide guidance on the identification and investigation of land<br />
where contaminants may exist and where hazards from undesirable substances may occur.<br />
6. The subject is still relatively new and continues to develop, hence publication of DD 175 as a Draft<br />
for Development which is intended to complement both BS5930: 1981, “Code of practice for site<br />
investigations” and the guidance notes issued by the Department of the Environment’s Inter-Departmental<br />
Committee on the redevelopment of Contaminated Land.<br />
Flooding<br />
7. Serious river and coastal flooding which has occurred in a number of areas in Scotland is, unfortunately,<br />
not entirely preventable. Pressure for land development may mean that development proposals<br />
could be given planning approval on land subject to some risk of flooding. Paragraph 8 below refers<br />
to sources of information on measures to reduce the effects of flood damage to buildings.<br />
19G<br />
Amdt: December 1999<br />
G
G<br />
8. Where development is to take place on land assessed by the planning authority as having a flood<br />
risk, advice should be sought from sources such as the local planning authority, the <strong>Scottish</strong> Environmental<br />
Protection Agency (SEPA) and those responsible for coastal defences. Further information is<br />
in “National Planning Policy Guideline 7: “Planning and Flooding”, 1995”. Detailed guidance on the<br />
likely effects of flooding on building materials and fabric and on the precautionary measures that can<br />
be taken in the design of dwellings to reduce the effects of flood damage can be obtained from<br />
“Design Guidance on Flood Damage to Dwellings, 1996”. Both publications are available from the<br />
Stationery Office.<br />
Radon<br />
9. Radon is a naturally occurring, radioactive, colourless and odourless gas that is formed where<br />
uranium and radium are present. It can move through cracks and fissures in the subsoil, and so into<br />
buildings. Where this gas occurs under buildings, the external walls contain it and the containment of<br />
radon can build up inside the buildings over the long term posing a risk to health and increasing the<br />
risk of developing cancer.<br />
The precise areas where measures will require to be taken to reduce radon penetration into dwellings<br />
are regularly reviewed by the <strong>Scottish</strong> Executive in light of advice from the National Radiological<br />
Protection Board. These are listed the the Building Research Establishment’s document “Radon:<br />
guidance on protection measures for new dwellings in Scotland”.<br />
Table 1 to Part G Appendix: Examples of land likely to contain contaminants<br />
Examples of land likely to contain contaminants is land on which there has been -<br />
asbestos works;<br />
chemical works;<br />
gas works, coal carbonisation plants and ancillary by-products works;<br />
industries making or using wood preservatives;<br />
landfill and other waste disposal sites;<br />
metal mines, smelters, foundries, steel works and metal finishing works;<br />
munitions production and testing sites;<br />
nuclear installations;<br />
oil storage and distribution sites;<br />
paper and printing works;<br />
railway land, especially the larger sidings and depots;<br />
scrap yards;<br />
sewage works, sewage farms and sludge disposal sites; and<br />
tanneries<br />
Amdt: December 1999<br />
20G
Table 2 to Part G Appendix: Possible contaminants and actions<br />
Signs of possible Possible contaminant Probable remedial<br />
contamination action required<br />
a. Vegetation metals, metal compounds none<br />
(absence, poor or<br />
unnatural growth) organic compounds, gases removal<br />
b. Surface materials metals, metal compounds none<br />
(unusual colours and<br />
contours may indicate) oil and tarry wastes removal, filling or<br />
sealing<br />
asbestos (loose) removal, filling or<br />
sealing [Note 1]<br />
other fibres none<br />
organic compounds removal or filling<br />
including phenols<br />
potentially combustible removal or inert filling<br />
material including coal and<br />
coke dust<br />
refuse and waste removal<br />
c. Fumes and odours flammable, explosive, toxic removal<br />
(may indicate organic and asphyxiating gases<br />
chemicals at very low including methane and the construction is to<br />
concentrations) carbon dioxide be free from<br />
unventilated voids<br />
corrosive liquids removal, filling or<br />
sealing [Note 1]<br />
faecal, animal and vegetable removal or filling<br />
matter (biologically active)<br />
d. Drums and containers various removal with all<br />
(whether full or empty) contaminated ground<br />
[Note 1]<br />
Note:<br />
1. The local authority may require the removal to be done by specialists.<br />
2. In the table -<br />
REMOVAL means that the contaminant itself and any contaminated ground to be covered by the<br />
building should be taken out to a depth of 1m (or less if the Local Authority agrees) below the<br />
level of the lowest floor and taken away to a place to be named by the Local Authority;<br />
FILLING means that the ground to be covered by the building is to be covered to a depth of 1m<br />
(or less if the Local Authority agrees) with a material which will not react adversely with any<br />
contaminant remaining and will be suitable for making up levels. The type of filling and the<br />
design of the ground floor should be considered together;<br />
INERT FILLING means that the filling is wholly non-combustible and not easily changed by<br />
chemical reactions; and<br />
SEALING means that a suitable imperforate barrier is laid between the contaminant and the<br />
building and sealed at the joints, around the edges and at the service entries. Note that polyethylene<br />
may not be suitable if the contaminant is a liquid such as a tarry waste or organic solvent.<br />
21G<br />
Amdt: December 1999<br />
G
22G
RESISTANCE TO THE<br />
TRANSMISSION OF SOUNDH
Contents<br />
INTRODUCTION<br />
REGULATIONS 19, 20 & 21<br />
Resistance to transmission of sound<br />
THE STANDARDS<br />
H1 Application of Part H H1.1-H1.4<br />
H2 Walls and floors to resist sound transmission<br />
Airborne sound H2.1<br />
Impact sound H2.2-H2.3<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(H2.1) -<br />
(H2.3) Airborne sound and impact sound<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A, General.<br />
3H<br />
Amdt: December 1999<br />
H
5H<br />
Introduction<br />
1 The intention of this Part is to protect occupants of a<br />
dwelling from excessive noise transmitted from other parts<br />
of a building as this can damage health, particularly when it<br />
recurs over a period of time. It does not apply to a wholly<br />
detached dwelling nor does it deal with external sources such<br />
as road traffic or aircraft noise.<br />
2 The requirements therefore apply to walls and floors<br />
separating a dwelling from other parts of the same building<br />
in different occupation and from other adjoining buildings.<br />
External walls are controlled only to the extent necessary to<br />
reduce flanking transmission around the ends of separating<br />
walls and separating floors. They also apply to balconies and<br />
roofs which are accessible, other than for maintenance,<br />
where they are above a dwelling.<br />
3 In addition it is envisaged that other ways of satisfying<br />
the regulations could be acceptable. For example; if an identical<br />
block of dwellings has been built elsewhere, tested, and<br />
been shown to meet the performance standards, a building<br />
warrant can be given on that evidence. Care is necessary to<br />
ensure that results are equally applicable since, for example,<br />
a construction giving acceptable results in a stepped or staggered<br />
situation may not perform adequately in a straight<br />
terrace block of dwellings.<br />
4 It should be understood that meeting the requirements of<br />
this Part will not guarantee freedom from the transmission of<br />
disturbing noise. The intention is to achieve reasonable standards<br />
of sound insulation by common, economically viable,<br />
forms of construction. It is important to bear in mind that<br />
standards of workmanship are as important as constructional<br />
details as air paths, bridging, or incorrectly placed resilient<br />
layers can destroy the effectiveness of measures used.<br />
Amdt: December 1999<br />
H
H<br />
Regulations 19, 20 & 21<br />
Resistance to transmission of sound<br />
19 1. Subject to paragraph (2), every wall which<br />
separates a dwelling from another building<br />
and, in the case of a dwelling forming part of<br />
a building, every wall and floor which separates<br />
the dwelling from another part of the<br />
building shall provide adequate resistance to<br />
transmission of airborne sound.<br />
2. Paragraph (1) shall not apply to a wall<br />
between a dwelling and any area which is<br />
open to the external air.<br />
20 1. Every floor separating a dwelling from any<br />
other part of a building above the dwelling<br />
shall provide adequate resistance to transmission<br />
of sound caused by impact.<br />
2. Roofs or walkways which are situated directly<br />
above a dwelling and to which there is access<br />
other than for maintenance purposes shall<br />
provide adequate resistance to transmission of<br />
sound caused by impact.<br />
21 Regulations 19 and 20 shall not be subject to<br />
specification in a notice served under section 11<br />
of the Act.<br />
Amdt: December 1999<br />
6H
The standards<br />
H1 Application of Part H<br />
H1.1 This Part sets out the required standards for Regulations 19 to 21.<br />
H1.2 The standards apply to a dwelling other than a wholly detached dwelling.<br />
7H<br />
H1.1 – H2.3<br />
H1.3 The standards are for separating elements (walls and floors) in a new dwelling, in a dwelling created by<br />
conversion, and in a dwelling where the building warrant covers a change of use of an element invoking<br />
a more onerous requirement e.g. in a rehabilitated flat where an existing internal wall becomes a<br />
separating wall.<br />
H1.4 The term dwelling includes any part of a building, being a part intended for occupation as a separate<br />
dwelling, irrespective of the purpose group of the rest of the building. The elements separating such a<br />
dwelling from the rest of the building must comply. Roofs or walkways to which there is access for<br />
purposes other than for maintenance of the building, which lie directly above a dwelling, must also<br />
comply. Walls separating a dwelling from a common access corridor or stair, or waste chute, must also<br />
provide adequate sound insulation.<br />
H2 Walls and floors to resist sound transmission<br />
AIRBORNE SOUND<br />
H2.1* A wall or floor separating a dwelling from any part of a building must provide adequate resistance to<br />
airborne sound.<br />
IMPACT SOUND<br />
H2.2* A floor separating a dwelling from any part of a building above the dwelling must provide adequate<br />
resistance to impact sound.<br />
H2.3* A roof or walkway over a dwelling which is accessible for any purpose other than maintenance must<br />
provide adequate resistance to impact sound.<br />
Amdt: December 1999<br />
H
Provisions deemed to satisfy the standards<br />
AIRBORNE SOUND AND IMPACT SOUND<br />
(H2.1, The requirements of H2.1 for airborne sound and H2.2 and H2.3 for impact sound will be met where<br />
H2.2, walls, floors and roofs -<br />
H2.3)<br />
a. are constructed in accordance with the specified constructions given in points 1 to 17;<br />
or<br />
b. achieve the standards given in point 18 when tested in accordance with points 19 to 29.<br />
Specified constructions<br />
1 The requirements for sound insulation will be met where walls and floors are constructed as specified<br />
below (but note that the diagrams do not show all the structural bracing that may be required).<br />
2 The thicknesses, masses, and other dimensions specified are the minimum required unless otherwise<br />
stated; greater figures are therefore permissible. Timber sizes quoted are the minimum actual sizes<br />
required.<br />
3 Where a mass is specified for a wall it is expressed in kg/m 2 of wall face area. For a floor the mass is<br />
expressed in kg/m 2 on plan.<br />
4 To calculate the mass of a leaf of masonry the formulae in point 5 must be used. Densities of bricks or<br />
blocks (at 3% moisture content) may be taken from a current BBA Certificate or from the manufacturer’s<br />
literature, in which case the local authority may ask for confirmation e.g. that the measurement<br />
was done by an accredited test house. Note that the quoted density of bricks or blocks is normally the<br />
apparent density, i.e. the weight divided by the volume including perforations, voids or frogs. This is<br />
the density appropriate to the formulae. For co-ordinating course heights other than those given in<br />
point 5 use the formula for the nearest height. Include any finish of plaster, render or dry lining in<br />
calculating the mass unless otherwise stated.<br />
9H<br />
(H2.1), (H2.3)<br />
Amdt: December 1999<br />
H
H<br />
(H2.1), (H2.3)<br />
5 To calculate the mass of a masonry leaf use the following formulae.<br />
Co-ordinating height of Formulae to be used<br />
masonry course (mm)<br />
M-NP<br />
( –––– - 380)<br />
75 M = T (0.79D + 380) + NP or D = T<br />
–––––––––––––<br />
0.79<br />
M-NP<br />
( –––– - 255)<br />
100 M = T (0.86D + 255) + NP or D = T<br />
–––––––––––––<br />
0.86<br />
M-NP<br />
( –––– - 145)<br />
150 M = T (0.92D + 145) + NP or D = T<br />
–––––––––––––<br />
0.92<br />
M-NP<br />
( –––– - 125)<br />
200 M = T (0.93D + 125) + NP or D = T<br />
–––––––––––––<br />
0.93<br />
Where M = Mass of 1m 2 of leaf in kg/m 2<br />
T = Thickness of masonry in metres i.e unplastered thickness)<br />
D = Density of masonry units in kg/m 3 (at 3 % moisture content)<br />
N = Number of finished faces<br />
P = Mass of 1m 2 of wall finish in kg/m 2 (see below)<br />
Mass of plaster (assumed thickness 13 mm)<br />
Cement Render = 29 kg/m 2<br />
Gypsum = 17 kg/m 2<br />
Lightweight = 10 kg/m 2<br />
Plasterboard = 10 kg/m 2<br />
6 In point 5 a mortar joint of 10 mm and a dry, set mortar density of 1800 kg/m 3 are assumed.<br />
Values within 10% of these figures are acceptable.<br />
7 For in-situ concrete or screeds calculate the mass by multiplying the density (kg/m 3 ) by the thickness<br />
(in metres). For slabs or composite floor bases divide the total mass of the element (kg) by the plan<br />
area of the element (m 2 ).<br />
Conditions on the use of specified constructions<br />
8 In any separating wall being built to meet the specified construction standard, the following conditions<br />
must be met -<br />
a. no opening is permitted except a doorway between a dwelling and a stairway or passage where<br />
the doorway is protected by a fire door satisfying Part D;<br />
b. no service pipes or ducts may pass through except between a dwelling and a stairway, passage<br />
or duct where the pipes and ducts are protected to satisfy Part D;<br />
Amdt: December 1999<br />
10H
c. chases for services are allowed in wall type 1 or 2 provided the depth of any horizontal chase<br />
does not exceed one-sixth of the thickness of the leaf, and the depth of any vertical chase does<br />
not exceed one-third of the thickness; chases back to back in a single leaf are not permitted; in<br />
wall type 3 services may pierce the free-standing panels provided any gaps are sealed with tape<br />
or caulking; no services are permitted in wall type 4; and<br />
d. flues are only permitted in walls where the flues are of masonry construction (including precast<br />
concrete flue blocks); no flues are permitted in wall type 4.<br />
9 In any separating floor being built to meet the specified construction standard no openings are permitted<br />
except openings for service ducts, pipes or flues protected to satisfy Part D or Part F and which are<br />
also enclosed above and below the floor to satisfy this Part.<br />
11H<br />
(H2.1), (2.3)<br />
Amdt: December 1999<br />
H
H<br />
(H2.1), (H2.3)<br />
10 Wall type 1: solid masonry<br />
The resistance to airborne sound depends<br />
mainly on the mass of the wall.<br />
Points to watch<br />
Fill masonry joints with mortar (to achieve the<br />
mass and avoid air paths).<br />
Limit the pathways around the wall (to reduce<br />
flanking transmission).<br />
Construction<br />
Five wall constructions which give suitable<br />
resistance to direct transmission are specified.<br />
Details of how junctions must be made to limit<br />
flanking transmission follow.<br />
A. Brick, plastered both sides.<br />
Mass including plaster 375 kg/m2 .<br />
13 mm plaster each side.<br />
Lay bricks in a bond which includes<br />
headers.<br />
Example: 215 mm brick, lightweight<br />
plaster, 75 mm coursing; brick density of<br />
1610 kg/ m3 gives the required mass.<br />
B. Concrete block, plastered both sides. Mass<br />
including plaster 415 kg/m2 .<br />
13 mm plaster each side.<br />
Use blocks which extend to the full thickness<br />
of the wall.<br />
Example: 215 mm block, lightweight<br />
plaster, 110 mm coursing; block density of<br />
1840 kg/m3 gives the required mass.<br />
C. Brick, plasterboard both sides.<br />
Mass including plasterboard 375 kg/m2 .<br />
12.5 mm plasterboard each side, use any<br />
normal fixing method.<br />
Lay bricks in a bond which includes<br />
headers.<br />
Example: 215 mm brick, 75 mm coursing;<br />
brick density of 1610 kg/m3 gives the<br />
required mass.<br />
D. Concrete block, plasterboard both sides.<br />
Mass of masonry alone 415 kg/m2 .<br />
12.5 mm plasterboard each side, use any<br />
normal fixing method.<br />
Use blocks which extend to the full thickness<br />
of the wall.<br />
Example: 215 mm block, 150 mm coursing;<br />
block density of 1840 kg/m3 gives the<br />
required mass.<br />
E. Concrete (minimum density 1500 kg/m3 ),<br />
in-situ or large panel.<br />
Plaster optional.<br />
Mass (including plaster if used) 415 kg/m2 .<br />
Fill joints between panels with mortar.<br />
Example: an unplastered wall of density<br />
2200 kg/m3 ; 190mm thickness gives the<br />
required mass.<br />
Amdt: December 1999<br />
12H
10. Junctions for wall type 1<br />
(Cont’d)<br />
Roof<br />
Fire-stop the joint between wall and roof (see<br />
Part D).<br />
Ceiling and roof space<br />
Where there is a heavy ceiling with sealed joints<br />
(12.5 mm plasterboard or equivalent), the mass of<br />
the wall above the ceiling may be reduced to 150<br />
kg/m 2 . If lightweight aggregate blocks are used to<br />
reduce mass, seal one side with cement paint or<br />
plaster skim.<br />
Intermediate and ground floors<br />
With a timber floor do not build joists into the<br />
wall, use hangers. With a concrete floor either the<br />
wall or the floor may be carried through.<br />
External wall<br />
The outer leaf of a cavity wall may be of any construction.<br />
Where a cavity wall has an inner leaf of<br />
masonry; or where the external wall is of solid<br />
masonry -<br />
a. i. the masonry of the walls must be bonded<br />
together, or<br />
ii. the masonry of the external wall must<br />
abut the separating wall and be tied to it<br />
with ties at no more than 300 mm centres<br />
vertically,<br />
b.<br />
to create a homogeneous unit; and<br />
the masonry must have a mass of 120 kg/m2 unless the length of the external wall is<br />
limited by openings,<br />
i. of 1 metre high,<br />
ii. on both sides of the separating wall at<br />
every storey, and<br />
iii. not more than 700 mm from the face of<br />
the separating wall on both sides1 .<br />
Where a cavity wall has an inner leaf of<br />
timber construction it must -<br />
c. abut the separating wall;<br />
d. be tied to it with ties at no more than 300 mm<br />
centres vertically; and<br />
e. have the joints sealed with tape or caulking .<br />
1. a short length of wall will not vibrate excessively<br />
at low frequencies to give flanking<br />
transmissions.<br />
Partitions<br />
There are no restrictions on a partition wall<br />
meeting a type 1 separating wall.<br />
13H<br />
timber<br />
timber<br />
masonry<br />
;; Roof<br />
Section<br />
Plan<br />
(H2.1), (H2.3)<br />
Ceiling<br />
Intermediate<br />
floor<br />
concrete<br />
Ground<br />
floor<br />
concrete<br />
External wall<br />
timber<br />
caulking<br />
or tape<br />
Amdt: December 1999<br />
H
H<br />
(H2.1), (H2.3)<br />
11. Wall type 2: cavity masonry<br />
The resistance to airborne sound depends on<br />
the mass of the leaves and on the degree of isolation<br />
achieved.<br />
Points to watch<br />
Fill masonry joints with mortar (to achieve the<br />
mass and to avoid air paths).<br />
Maintain the cavity up to the underside of the<br />
roof.<br />
Connect the leaves only where necessary for<br />
structural reasons. Use only butterfly pattern<br />
ties, spaced no more than 900 mm apart horizontally<br />
and 450 mm apart vertically. (BS<br />
5628: Part 3: 1985 limits this tie type and<br />
spacing to cavities of 50 mm to 75 mm with a<br />
minimum masonry leaf thickness of 90 mm).<br />
If external walls are to be filled with an insulating<br />
material other than loose fibre the insulating<br />
material must be prevented from<br />
entering the cavity in the separating wall.<br />
Constructions<br />
Two wall constructions (A and B) which give<br />
suitable resistance to direct transmission are<br />
specified.<br />
Two other wall constructions (C and D) will be<br />
suitable between houses provided a step in elevation<br />
and/or a stagger in plan is incorporated<br />
at the separating wall.<br />
Details of how junctions must be made to limit<br />
flanking transmission follow.<br />
A. Two leaves of brick with 50 mm cavity,<br />
plastered on both room faces.<br />
Mass including plaster 415 kg/m2 . 13 mm<br />
plaster each face.<br />
Example: 102 mm leaves, lightweight<br />
plaster, 75 mm coursing; brick density of<br />
1970 kg/m3 gives the required mass.<br />
B. Two leaves of concrete block with 50 mm<br />
cavity, plastered on both room faces.<br />
Mass including plaster 415 kg/m2 . 13 mm<br />
plaster each face.<br />
Example: 100 mm leaves, lightweight<br />
plaster, 225 mm coursing; block density of<br />
1990 kg/m3 gives the required mass.<br />
Amdt: December 1999<br />
14H<br />
50
11. Additional constructions permitted only where a step and/or stagger of at least 300 mm is used<br />
(Cont’d)<br />
C. Two leaves of concrete block with 50 mm<br />
cavity, plasterboard on both room faces.<br />
Mass of masonry alone 415 kg/m2 .<br />
12.5 mm plasterboard each face, use any<br />
normal fixing method.<br />
Example: 100 mm leaves, 225 mm coursing;<br />
block density of 1990 kg/m3 gives the<br />
required mass.<br />
D. Two leaves of lightweight aggregate concrete<br />
block (maximum density 1500<br />
kg/m3 ) with 75 mm cavity, plastered on<br />
both room faces.<br />
Mass including plaster 250 kg/m2 . 13 mm<br />
plaster each face.<br />
Seal the face of the blockwork, with<br />
cement paint or plaster, through the full<br />
width and depth of any intermediate floor.<br />
Example: 100 mm leaves, lightweight<br />
plaster, 225 mm coursing; block density of<br />
1105 kg/m3 gives the required mass.<br />
15H<br />
50<br />
75<br />
(H2.1), (H2.3)<br />
Amdt: December 1999<br />
H
H<br />
(H2.1), (H2.3)<br />
11. Junctions for wall type 2<br />
(Cont’d)<br />
Roof<br />
Fire-stop the joint between wall and roof (see<br />
Part D).<br />
Ceiling and roof space<br />
Where there is a heavy ceiling with sealed<br />
joints (12.5 mm plasterboard or equivalent),<br />
the mass of the wall above the ceiling may be<br />
reduced to 150 kg/m 2 . The cavity must still be<br />
maintained. If lightweight aggregate blocks are<br />
used to reduce mass, one face of the wall must<br />
be sealed with cement paint or plaster skim.<br />
Intermediate and ground floors<br />
With a timber floor use joist hangers for any<br />
joists supported on the wall.<br />
With a concrete intermediate or suspended<br />
ground floor the floor may be carried through<br />
only to the cavity face of each leaf.<br />
A concrete slab on the ground may be<br />
continuous.<br />
External wall<br />
The outer leaf of a cavity wall may be of any<br />
construction.<br />
Where a cavity wall has an inner leaf of<br />
masonry -<br />
a. i. the masonry of the walls must be<br />
bonded together, or<br />
ii. the masonry of the external wall must<br />
abut the separating wall and be tied to<br />
it with ties at no more than 300 mm<br />
centres vertically,<br />
to create a homogeneous unit; and<br />
b. the masonry must have a mass of<br />
120 kg/m 2 except where separating wall<br />
type 2 is used when there is no minimum<br />
required mass.<br />
Where a cavity wall has an inner leaf of timber<br />
construction it must -<br />
c. abut the separating wall;<br />
d. be tied to it with ties at no more than<br />
300 mm centres vertically; and<br />
e. have the joints sealed with tape or<br />
caulking.<br />
The cavity in the separating wall must only be<br />
sealed in accordance with Part D.<br />
Partitions<br />
There are no restrictions on partition walls<br />
meeting a type 2 separating wall.<br />
Amdt: December 1999<br />
16H<br />
;; Roof<br />
;;<br />
timber<br />
timber<br />
masonry<br />
Section<br />
Plan<br />
Ceiling<br />
Intermediate<br />
floor<br />
concrete<br />
Ground floor<br />
concrete<br />
External wall<br />
timber<br />
caulking<br />
or tape
12. Wall type 3: solid masonry between isolated panels<br />
The resistance to airborne sound depends on<br />
the mass and type of core and on the isolation<br />
and mass of the panels.<br />
Points to watch<br />
Fill masonry joints with mortar (to achieve the<br />
mass and to avoid air paths).<br />
Support the panels only from floor and ceiling<br />
- do not fix or tie them to the masonry core (to<br />
maintain isolation).<br />
Constructions<br />
Four masonry cores and two panels are specified<br />
which in any combination of core plus<br />
panels give suitable resistance to direct transmission.<br />
Details of how junctions must be made to limit<br />
flanking transmission follow.<br />
Basic construction<br />
A masonry core, with an isolated panel on each<br />
side.<br />
Minimum air space between panels and core<br />
25 mm. Keep framing clear of core (at least<br />
5 mm).<br />
Masonry cores<br />
A. Brick<br />
Mass 300 kg/m 2 .<br />
Example: 215 mm core, 75 mm coursing;<br />
brick density of 1290 kg/m 3 gives the<br />
required mass.<br />
B. Concrete block<br />
Mass 300 kg/m 2.<br />
Example: 140 mm core, 110 mm coursing;<br />
block density of 2200 kg/m 3 gives the<br />
required mass.<br />
C. Lightweight aggregate concrete block<br />
(maximum density 1500 kg/m 3 ).<br />
Mass 200 kg/m 2 .<br />
Example: 140 mm core, 225 mm coursing;<br />
block density of 1405 kg/m 3 gives the<br />
required mass.<br />
Example: 215 mm core, 150 mm coursing;<br />
block density of 855 kg/m 3 gives the<br />
required mass.<br />
D. Autoclaved aerated concrete block. Mass<br />
160 kg/m 2.<br />
Example: 200 mm core, 225 mm coursing;<br />
block density of 730 kg/m 3 gives the<br />
required mass.<br />
17H<br />
25 25<br />
(H2.1), (H2.3)<br />
Any framing<br />
must be kept<br />
clear of the<br />
masonry<br />
core<br />
Amdt: December 1999<br />
H
H<br />
(H2.1), (H2.3)<br />
12. Panels<br />
(Cont’d)<br />
E. Two sheets of plasterboard joined by a cellular<br />
core.<br />
Mass (including plaster finish if used)<br />
18 kg/m 2<br />
Fix to ceiling and floor only. Tape joints<br />
between panels.<br />
F. Two sheets of plasterboard with joints<br />
staggered.<br />
Thickness of each sheet 12.5 mm if a supporting<br />
framework is used, or total thickness<br />
of 30 mm if no framework is used.<br />
Junctions for wall type 3<br />
Roof<br />
Fire-stop the joint between masonry core and<br />
roof (see Part D).<br />
Ceiling and roof space<br />
Where there is a heavy ceiling with sealed<br />
joints (12.5 mm plasterboard or equivalent),<br />
the free-standing panels may be omitted in the<br />
roof space and mass of the core above the<br />
ceiling may be reduced to 150 kg/m 2 . If lightweight<br />
aggregate blocks are used to reduce<br />
mass, seal one side with cement paint or plaster<br />
skim. Seal the junction between ceiling and<br />
free-standing panels with tape or caulking.<br />
Intermediate and ground floors<br />
With a timber intermediate floor use joist<br />
hangers for any joists supported on the wall<br />
and seal the spaces between joists with full<br />
depth timber battens.<br />
With a concrete intermediate floor the floor<br />
base may only be carried through where it has<br />
a mass of 365 kg/m 2 . Seal the junction between<br />
ceiling and panel with tape or<br />
caulking.<br />
The ground floor must be a solid slab, laid on<br />
the ground to prevent air paths.<br />
Amdt: December 1999<br />
18H<br />
Ceiling<br />
timber joists<br />
parallel<br />
Roof<br />
Ground floor<br />
;<br />
Section<br />
Caulking<br />
or tape<br />
concrete floor<br />
built in (only if<br />
greater than<br />
365kg/m 2 )<br />
timber joists at<br />
right angles<br />
ground floor<br />
must be solid<br />
and may pass<br />
through wall
12. External wall<br />
(Cont’d)<br />
The outer leaf of a cavity wall may be of any<br />
construction.<br />
The inner leaf of a cavity wall must have an<br />
internal finish of isolated panels as specified<br />
for the separating wall except where the<br />
separating wall has core A or B when plaster<br />
or dry-lining with joints sealed with tape or<br />
caulking may be used.<br />
A layer of insulation may be added to such<br />
internal finish provided the 25 mm and 10 mm<br />
gaps shown in the diagram are maintained.<br />
The inner leaf may be of any construction if it<br />
is lined with isolated panels.<br />
If the inner leaf is dry-lined it must be masonry<br />
with a mass of 120 kg/m 2 , butt jointed to the<br />
separating wall core with ties at no more than<br />
300 mm centres, vertically.<br />
Partitions<br />
Partitions abutting a type 3 separating wall<br />
must not be of masonry construction. ;Loadbearing<br />
partition<br />
Other loadbearing partitions should be fixed to<br />
the masonry core through a continuous pad of<br />
mineral fibre quilt.<br />
Non-loadbearing partitions should be tight<br />
butted to the isolated panels.<br />
All joints between partitions and panels must<br />
be sealed with tape or caulking.<br />
19H<br />
(H2.1), (H2.3)<br />
25 10<br />
free-standing<br />
panel lining<br />
Nonloadbearing<br />
partition<br />
External wall<br />
25 25<br />
Plan<br />
Plan<br />
dry-lining<br />
alternative<br />
for core types<br />
A&B only<br />
Amdt: December 1999<br />
H
H<br />
(H2.1), (H2.3)<br />
13. Wall type 4: timber frames with absorbent curtain<br />
The resistance to airborne sound depends on<br />
the isolation of the frames plus absorption in<br />
the air space between.<br />
Limitations<br />
Part D places limits on the storey height at<br />
which this type may be used. The special walls<br />
specified in Part D for common stairs are suitable<br />
to resist sound transmission provided isolation<br />
of the leaves is maintained.<br />
Points to watch<br />
Only connect frames if necessary for structural<br />
reasons, and then use as few ties as possible -<br />
not more than 14-16 gauge (40 mm x 3 mm)<br />
metal straps fixed at or just below ceiling level,<br />
1.2 m apart.<br />
Services must not be contained in the wall.<br />
This is a structural fire precaution (see Part D)<br />
but also prevents the creation of air paths<br />
through the lining. Where fire-stops are needed<br />
in the cavity between frames they must either<br />
be flexible or fixed to only one frame.<br />
Constructions<br />
Two constructions which, with appropriate<br />
cladding and absorbent curtain, give suitable<br />
resistance to direct transmission are specified.<br />
Details of how junctions must be made to limit<br />
flanking transmission follow.<br />
Basic construction<br />
A. Timber frames, 200 mm between<br />
claddings, plus absorbent curtain in cavity.<br />
Plywood sheathing may be used in the<br />
cavity as necessary for structural reasons.<br />
200<br />
between claddings<br />
plywood<br />
sheathing<br />
;absorbent<br />
if necessary<br />
curtain (position<br />
may vary - see<br />
specification E)<br />
200<br />
between claddings<br />
B. Timber frames, masonry core, plus<br />
absorbent curtain in a cavity. Claddings ;absorbent<br />
200 mm apart (ignore core).<br />
curtain<br />
Framing must be clear of core by 5 mm.<br />
(position may<br />
vary - see<br />
;<br />
specification E)<br />
5 5<br />
Amdt: December 1999<br />
20H
13. Masonry core<br />
(Cont’d)<br />
C. This does not normally improve sound<br />
resistance but may be useful for support<br />
and in stepped or staggered situations.<br />
There are no restrictions on type but the<br />
core may be connected to only one frame.<br />
Cladding<br />
D. On each side: two or more layers of plasterboard,<br />
combined thickness 30 mm,<br />
joints staggered to avoid air paths.<br />
Absorbent curtain<br />
E. Unfaced mineral fibre quilt (which may be<br />
wire reinforced), density 12-36 kg/m 3 ,<br />
thickness 25 mm if suspended in the<br />
cavity between frames, 50 mm if fixed to<br />
one frame, or 25 mm per quilt if one fixed<br />
to each frame.<br />
Junctions for wall type 4<br />
Roof<br />
Fire-stop the joint between wall and roof (see<br />
Part D).<br />
Ceiling and roof space<br />
Carry the complete construction through to the<br />
underside of the roof. Provision of a ceiling of<br />
any type is optional.<br />
Intermediate floor and ground floor<br />
Block the air path to the wall cavity either by<br />
carrying the cladding through the floor or by<br />
using a solid timber edge to the floor. Where<br />
the joists are at right angles to the wall, seal<br />
spaces between joists with full depth timber<br />
battens.<br />
External wall<br />
There are no restrictions on a traditional timber<br />
framed wall but if the wall is of cavity<br />
construction. the cavity must be sealed<br />
between the ends of the separating wall and the<br />
outer leaf to prevent air gaps.<br />
The internal finish must be 12.5 mm plasterboard<br />
or other equally heavy material (resilient<br />
layers for thermal insulation may be incorporated<br />
if desired).<br />
Partitions<br />
There are no restrictions on partitions meeting<br />
a type 4 separating wall.<br />
absorbent<br />
curtain<br />
(position may<br />
vary, see<br />
specification E)<br />
;;;; ;; ;;<br />
;<br />
; ;;;<br />
caulking<br />
or tape<br />
solid slab<br />
may extend<br />
into wall leaf<br />
Section<br />
External wall<br />
(H2.1), (H2.3)<br />
Roof<br />
Ceiling<br />
Intermediate<br />
floor<br />
Ground<br />
floor<br />
H<br />
caulking<br />
or tape<br />
;;<br />
Plan<br />
21H<br />
Amdt: December 1999
H<br />
(H2.1), (H2.3)<br />
14. Floor type 1: concrete base with soft covering<br />
The resistance to airborne sound depends on<br />
the mass of the concrete base and on eliminating<br />
air paths. The soft covering reduces impact<br />
sound at source.<br />
Limitations<br />
Where resistance to airborne sound only is<br />
required the soft covering may be omitted. No<br />
other part of the construction may be omitted<br />
as this would reduce airborne sound resistance.<br />
Points to watch<br />
Fill all joints between parts of the floor to avoid<br />
air paths.<br />
Limit pathways around the floor to reduce<br />
flanking transmission.<br />
Workmanship and detailing must be given<br />
special attention at the perimeter and wherever<br />
the floor is penetrated by a pipe or duct to reduce<br />
flanking transmission and to avoid air paths.<br />
Constructions<br />
Four floor bases which give suitable resistance<br />
to direct transmission of airborne sound are<br />
specified, followed by the soft covering which<br />
must be added to give suitable resistance to<br />
impact sound transmission.<br />
Details of how junctions must be made to limit<br />
flanking transmission follow.<br />
Floor bases<br />
A. Solid concrete slab (in-situ).<br />
Floor screed and/or ceiling finish optional.<br />
Mass (including any screed and/or ceiling<br />
finish) 365 kg/m 2 .<br />
B. Solid concrete slab with permanent shuttering.<br />
Floor screed and/or ceiling finish optional.<br />
Mass (including shuttering only if it is<br />
solid concrete or metal and including any<br />
screed and/or ceiling finish) 365 kg/m 2 .<br />
C. Concrete beams with infilling blocks.<br />
Floor screed and/or structural topping<br />
must be used.<br />
Ceiling finish optional.<br />
Mass of beams, blocks, any structural<br />
topping and screed (including any ceiling<br />
finish) 365 kg/m 2 .<br />
D. Concrete planks (solid or hollow).<br />
Floor screed and/or structural topping<br />
must be used.<br />
Ceiling finish optional.<br />
Mass of planks, any structural topping and<br />
screed (including any ceiling finish)<br />
365 kg/m 2 .<br />
Amdt: December 1999<br />
22H<br />
Sections
14. Soft covering<br />
(Cont’d)<br />
E. Any resilient material, or material with a<br />
resilient base, with an overall uncompressed<br />
thickness of 4.5 mm. (A material<br />
is resilient if it returns to its original thickness<br />
after it has been compressed). The<br />
soft covering must be bonded to the floor<br />
base.<br />
Junctions for floor type 1<br />
External wall or cavity separating wall<br />
The mass of the wall leaf adjoining the floor<br />
must be 120 kg/m 2 (including any plaster)<br />
except where the area of openings in the external<br />
wall exceeds 20% of its area there is no<br />
minimum mass requirement for such a wall.<br />
The floor base (excluding any screed, even in C<br />
and D) must pass through the leaf whether<br />
spanning parallel to, or at right angles to, the<br />
wall. The cavity must not be bridged.<br />
Internal wall or solid separating wall<br />
If the wall mass is less than 355 kg/m 2 including<br />
any plaster then the floor base excluding<br />
any screed must pass through.<br />
If the wall mass is more than 355 kg/m 2 including<br />
any plaster either the wall or the floor base<br />
excluding any screed may pass through. Where<br />
the wall does pass through, tie the floor base to<br />
the wall and grout the joint.<br />
Floor penetrations<br />
Ducts or pipes penetrating the floor must be in<br />
an enclosure, both above and below the floor.<br />
Either line the enclosure, or wrap the duct or<br />
pipe within the enclosure, with 25 mm unfaced<br />
mineral fibre.<br />
The material of the enclosure must have a mass<br />
of 15 kg/m 2 .<br />
Penetrations of a separating floor by ducts and<br />
pipes must have fire protection in accordance<br />
with Part D.<br />
Where permitted by Part F, a flue-pipe may<br />
penetrate the floor. Unless the flue-pipe discharges<br />
into a flue within a chimney carried by<br />
the floor, a non-combustible enclosing duct<br />
with mineral fibre absorbent must be provided.<br />
23H<br />
Sections<br />
(H2.1), (H2.3)<br />
unfaced<br />
mineral fibre<br />
enclosure<br />
caulking<br />
unfaced<br />
mineral fibre<br />
enclosure<br />
caulking<br />
Amdt: December 1999<br />
H
H<br />
(H2.1), (H2.3)<br />
15. Floor type 2: concrete base with floating layer<br />
The resistance to airborne sound depends<br />
mainly on the mass of the concrete base and<br />
partly on the mass of the floating layer. Resistance<br />
to impact sound depends on a resilient<br />
layer from the base and from the surrounding<br />
construction.<br />
Limitations<br />
Where resistance to airborne sound only is<br />
required the full construction must still be<br />
used.<br />
Points to watch<br />
Fill all joints between parts of the floor base to<br />
avoid air paths.<br />
Limit the pathways around the floor to reduce<br />
flanking transmission.<br />
Workmanship and detailing must be given<br />
special attention at the perimeter and wherever<br />
the floor is penetrated to reduce flanking transmission<br />
and to avoid air paths.<br />
Take care not to create a bridge between the<br />
floating layer and the base, surrounding walls,<br />
or adjacent screeds.<br />
With bases C and D a screed is recommended<br />
to accommodate surface irregularities and<br />
prevent reduced resistance at joints.<br />
Constructions<br />
Four floor bases, two floating layers and one<br />
resilient layer are specified. Any combination<br />
of base, resilient layer and floating layer give<br />
suitable resistance to direct transmission. Two<br />
additional resilient layers which may be used<br />
under screeds only are also specified (H and I).<br />
Details of how junctions must be made to limit<br />
flanking transmission follow.<br />
Floor bases<br />
A. Solid concrete slab (in-situ).<br />
Floor screed and/or ceiling finish optional.<br />
Mass (including any screed and/or ceiling<br />
finish) 300 kg/m 2 .<br />
B. Solid concrete slab with permanent shuttering.<br />
Floor screed and/or ceiling finish optional.<br />
Mass (including shuttering only if it is<br />
solid concrete or metal, and including any<br />
screed and/or ceiling finish) 300 kg/m 2 .<br />
Amdt: December 1999<br />
24H<br />
Sections
15. C. Concrete beams with infilling blocks.<br />
(Cont’d)<br />
Floor screed/structural topping/ceiling<br />
finish optional. (A levelling screed is<br />
required where the floating layer is a<br />
timber raft.) Mass of beams and blocks<br />
and any structural topping (including any<br />
screed and/or ceiling finish) 300 kg/m 2 .<br />
D. Concrete planks (solid or hollow).<br />
Floor screed/structural topping/ceiling<br />
finish optional.<br />
Mass of planks and any structural topping<br />
(including any screed and/or ceiling<br />
finish) 300 kg/m 2 .<br />
Floating layers<br />
E. Timber raft.<br />
Timber boarding or wood based board,<br />
18 mm thick with tongued and grooved<br />
edges, fixed to 45 x 45 mm battens. The raft<br />
must be laid loose on the resilient layer.<br />
F. Screed.<br />
65 mm cement sand screed with mesh<br />
underlay to protect the resilient layer<br />
while the screed is being laid.<br />
Resilient layer<br />
G. 25 mm mineral fibre, density 36 kg/m 3 .<br />
A 13 mm thickness may be used under a<br />
timber raft if the battens used have an integral<br />
closed cell resilient foam strip.<br />
Lay the fibre tightly butted and turned up<br />
at the edges of the floating layer.<br />
Under a timber raft, fibre may be paper<br />
faced on the underside.<br />
Under a screed, fibre must be paper faced<br />
on upper side to prevent screed entering<br />
the layer.<br />
Additional resilient layers for use under<br />
screeds only.<br />
H. 13 mm pre-compressed expanded polystyrene<br />
board (impact sound duty grade).<br />
Lay boards tightly butted, use on edge as a<br />
resilient strip at edges of floating screed.<br />
I. 5 mm extruded (closed cell) polyethylene<br />
foam, density 30-45 kg/m 3 . To protect the<br />
material from puncture it should be laid<br />
over a levelling screed. Lay with joints<br />
lapped.<br />
25H<br />
Sections<br />
(H2.1), (H2.3)<br />
Amdt: December 1999<br />
H
H<br />
(H2.1), (H2.3)<br />
15. Junctions for floor type 2<br />
(Cont’d)<br />
External wall or cavity separating wall.<br />
The mass of the leaf adjoining the floor must<br />
be 120 kg/m 2 (including any plaster) except<br />
where the area of openings in the external wall<br />
exceeds 20% of its area there is no minimum<br />
mass requirement.<br />
The floor base (excluding any screed) must<br />
pass through the wall whether spanning parallel<br />
to or at right angles to the wall.<br />
The cavity must not be bridged.<br />
Carry the resilient layer up at all edges to<br />
isolate the floating layer.<br />
Leave a 3 mm gap between skirting and floating<br />
layer or turn resilient layer under skirting.<br />
A seal is not necessary but if used must be flexible.<br />
Internal wall or solid separating wall<br />
If the wall mass is less than 355 kg/m2 including<br />
any plaster then the floor base excluding<br />
any screed must pass through.<br />
If the wall mass is more than 355 kg/m2 includ- ;<br />
ing any plaster either the wall or the floor base<br />
excluding any screed may pass through. Where<br />
the wall does pass through tie the floor base to<br />
the wall and grout the joint.<br />
mineral fibre<br />
enclosure<br />
Floor penetrations<br />
caulking<br />
Ducts or pipes penetrating the floor must be in<br />
an enclosure, both above and below the floor.<br />
Either line the enclosure, or wrap the duct or<br />
pipe within the enclosure, with 25 mm unfaced<br />
caulking<br />
mineral fibre.<br />
;;unfaced<br />
The material of the enclosure must have a mass<br />
of 15 kg/m 2 .<br />
Penetrations of a separating floor by ducts and<br />
pipes must have fire protection in accordance<br />
with Part D.<br />
Leave a 3 mm gap between enclosure and<br />
floating layer and seal with acrylic caulking or<br />
neoprene.<br />
Where permitted by Part F, a flue-pipe may<br />
penetrate the floor. Unless the flue-pipe discharges<br />
into a flue within a chimney carried by<br />
the floor a non-combustible enclosing duct<br />
with mineral fibre absorbent must be provided.<br />
Amdt: December 1999<br />
;<br />
;<br />
26H<br />
floating layer<br />
resilient layer<br />
screed<br />
floor<br />
;; ;<br />
;<br />
unfaced<br />
Sections<br />
mineral fibre<br />
enclosure<br />
caulking<br />
caulking
16. Floor type 3: timber base with floating layer<br />
The resistance to airborne sound depends<br />
partly on the structural floor plus absorbent<br />
blanket or deafening, and partly on the floating<br />
layer. Resistance to impact sound depends on a<br />
resilient layer isolating the floating layer from<br />
the base and the surrounding construction.<br />
Limitations<br />
Where resistance to airborne sound only is<br />
required the full construction must still be<br />
used.<br />
Part D places limits on the storey height at<br />
which this type may be used.<br />
This type can also be used as a specified construction<br />
for converted properties. Use is only<br />
permitted with appropriate adjoining walls (see<br />
“Junctions” below).<br />
Points to watch<br />
Limit the pathways around the floor (to reduce<br />
flanking transmission).<br />
Workmanship and detailing must be given<br />
special attention at the perimeter and wherever<br />
the floor is penetrated (to reduce flanking<br />
transmission and to avoid air paths).<br />
Use the correct density of resilient layer.<br />
Take care not to bridge between the floating<br />
layer and the base or surrounding walls (e.g.<br />
with services or fixings which penetrate the<br />
resilient layer). Allow for movement of materials<br />
e.g. expansion of chipboard after laying (to<br />
maintain isolation).<br />
Constructions<br />
Three complete constructions which give suitable<br />
resistance to direct sound transmission are<br />
specified. Note that there are some alternatives<br />
within each construction.<br />
Details of how junctions must be made to limit<br />
flanking transmission follow.<br />
27H<br />
(H2.1), (H2.3)<br />
Amdt: December 1999<br />
H
H<br />
(H2.1), (H2.3)<br />
16. Floors<br />
(Cont’d)<br />
A. Platform floor with absorbent blanket.<br />
Either a floating layer of timber or wood<br />
based board, 18 mm thick, with tongued<br />
and grooved edges and all joints glued,<br />
spot bonded to substrate of 19 mm plasterboard;<br />
or a floating layer of two thicknesses<br />
of cement bonded particleboard<br />
with joints staggered, glued and screwed<br />
together, total thickness 24 mm.<br />
Resilient layer of 25 mm mineral fibre,<br />
density 60-100 kg/m3 . Note that the low<br />
figure gives the best insulation but a “soft”<br />
floor.<br />
Floor base of 12 mm timber boarding or<br />
wood-based board nailed to timber joists<br />
(size to suit the structure).<br />
Ceiling of two layers of plasterboard with<br />
joints staggered, total thickness 30 mm,<br />
with an absorbent blanket of 100 mm<br />
unfaced mineral fibre, density 12-36<br />
kg/m3 B.<br />
, laid on the ceiling.<br />
Heavy ribbed floor with absorbent<br />
blanket.<br />
Floating layer of timber or wood based<br />
board, 18 mm thick with tongued and<br />
grooved edges and all joints glued, spot<br />
bonded to substrate of 19 mm plasterboard<br />
nailed to 45 mm x 45 mm timber battens<br />
placed on the joists.<br />
Resilient strips of 25 mm mineral fibre,<br />
density 80-140 kg/m3 , laid on joists.<br />
Floor base of 45 mm thick timber joists.<br />
Ceiling of two layers of plasterboard with<br />
joints staggered, total thickness 30 mm,<br />
with an absorbent blanket of 100 mm<br />
unfaced mineral fibre, density<br />
12-36 kg/m3 ;floating layer<br />
resilient layer<br />
floor base<br />
absorbent<br />
;<br />
blanket<br />
ceiling<br />
;floating layer<br />
batten<br />
resilient layer<br />
absorbent<br />
blanket<br />
ceiling<br />
;Sections<br />
, laid on the ceiling .<br />
Amdt: December 1999<br />
28H
16. C. Ribbed floor with heavy deafening †<br />
(Cont’d)<br />
Floating layer of timber or wood based<br />
board, 18 mm thick with tongued and<br />
grooved edges and all joints glued, nailed<br />
to 45 mm x 45 mm timber battens placed<br />
either on or between joists (for sheet materials,<br />
placing on joists is recommended).<br />
Resilient strips of 25 mm mineral fibre,<br />
density 80-140 kg/m 3 , laid on joists.<br />
Floor base of 45 mm thick timber joists.<br />
Ceiling of either 19 mm dense plaster on<br />
expanded metal lath or 6 mm plywood<br />
fixed under the joists plus two layers of<br />
plasterboard with joints staggered, total<br />
thickness 25 mm. Both types of ceiling to<br />
have deafening of mass 80 kg/m 2 laid on a<br />
polyethylene layer.<br />
† Deafening (pugging) may be of the following<br />
types:<br />
Traditional ash (75 mm), or<br />
2-10mm limestone chips (60 mm), or<br />
2-10 whin aggregate (60 mm), or<br />
Dry sand (50 mm).<br />
Figures in brackets show approximate<br />
thickness required to achieve 80 kg/m 2 .<br />
Do not use sand in kitchens, bathrooms,<br />
shower rooms or watercloset compartments.<br />
Junctions for floor type 3<br />
Timber frame wall<br />
Seal the gap between wall and floating layer<br />
with a resilient strip glued to the wall.<br />
Leave a 3 mm gap between skirting and floating<br />
layer. A seal is not necessary but if used<br />
must be flexible. Block air paths between the<br />
floor base and the wall, including the space<br />
between joists when joists are at right angles to<br />
the wall.<br />
Seal the junction of ceiling and wall with tape<br />
or caulking.<br />
29H<br />
(H2.1), (H2.3)<br />
;floating<br />
layer<br />
;<br />
batten<br />
resilient<br />
strip<br />
pugging<br />
liner<br />
plaster on<br />
lath<br />
floating<br />
layer<br />
batten<br />
pugging<br />
;<br />
;<br />
;resilient<br />
strip<br />
timber<br />
frame<br />
wall<br />
liner<br />
plywood<br />
ceiling<br />
Amdt: December 1999<br />
H<br />
;<br />
Sections<br />
caulking<br />
or tape<br />
floating layer<br />
resilient strip<br />
pugging<br />
liner<br />
plywood<br />
ceiling
H<br />
(H2.1), (H2.3)<br />
16. Heavy masonry leaf<br />
(Cont’d)<br />
Mass of leaf (including any plaster)<br />
355 kg/m2 , both above and below floor. ;resilient<br />
Seal the gap between wall and floating strip<br />
layer with a resilient strip glued to the wall.<br />
Leave a 3 mm gap between skirting and<br />
floating layer. A seal is not necessary but if<br />
used must be flexible. Use any normal<br />
method of connecting floor base to wall.<br />
Seal the junction of ceiling and wall lining<br />
with tape or caulking.<br />
Light masonry leaf<br />
If the mass (including any plaster) is less<br />
than 355 kg/m 2 a free-standing panel as<br />
specified in wall type 3 must be used.<br />
Seal the gap between wall and floating<br />
layer with a resilient strip glued to the freestanding<br />
panel.<br />
Leave a 3 mm gap between skirting and<br />
floating layer. A seal is not necessary but if<br />
used must be flexible. Use any normal<br />
method of connecting floor base to wall but<br />
block air paths between floor and wall cavities.<br />
Take ceiling through to masonry, seal junction<br />
with free-standing panel with tape or<br />
caulking.<br />
Floor penetrations<br />
Ducts or pipes penetrating the floor must be<br />
in an enclosure both above and below the<br />
floor.<br />
Either line the enclosure, or wrap the duct<br />
or pipe within the enclosure, with 25 mm<br />
unfaced mineral fibre.<br />
The material of the enclosure must have a<br />
mass of 15 kg/m 2 .<br />
Penetrations of a separating wall by ducts<br />
and pipes must have fire protection in<br />
accordance with Part D.<br />
Leave a 3 mm gap between enclosure and<br />
floating layer, seal with acrylic caulking or<br />
neoprene. Enclosure may go down to the<br />
floor base if specification A is used, but<br />
keep isolation of enclosure from floating<br />
layer.<br />
Where permitted by Part F, a flue-pipe may<br />
penetrate the floor. The flue-pipe must be in<br />
a non-combustible enclosing duct with<br />
mineral fibre absorbent.<br />
Seal the junction of ceiling and enclosure<br />
with tape or caulking.<br />
Amdt: December 1999<br />
30H<br />
resilient<br />
strip<br />
25<br />
Sections<br />
floating layer<br />
resilient strip<br />
;<br />
;<br />
25<br />
;<br />
resilient<br />
strip<br />
;;;<br />
pugging<br />
liner<br />
plywood<br />
ceiling<br />
caulking<br />
or tape<br />
floating layer<br />
resilient strip<br />
pugging<br />
liner<br />
plywood<br />
ceiling<br />
caulking<br />
or tape<br />
unfaced mineral fibre<br />
seal<br />
floating layer<br />
resilient layer<br />
floor base<br />
Floor penetration (type A floor shown)<br />
absorbent blanket<br />
ceiling<br />
seal<br />
enclosure<br />
seal<br />
floating layer<br />
resilient layer<br />
unfaced mineral<br />
fibre<br />
Floor penetration (type C floor shown)<br />
pugging<br />
liner<br />
plywood<br />
ceiling<br />
seal
17. Floor type 4: timber base with independent ceiling<br />
The resistance to airborne and impact sound<br />
depends mainly on the mass and isolation of<br />
the independent ceiling and partly on the mass<br />
of the floor base.<br />
Limitations<br />
Where resistance to airborne sound only is<br />
required the full construction must still be<br />
used.<br />
Part D places limits on the storey height at<br />
which this type may be used. It must only be<br />
used with heavy masonry walls.<br />
It is mainly for use as a specified construction<br />
for converted properties with suitable existing<br />
floors and walls.<br />
Points to watch<br />
Limit the pathways around the floor, especially<br />
at the edges of the independent ceiling (to<br />
reduce flanking transmission and to avoid air<br />
paths).<br />
Workmanship and detailing must be given<br />
special attention wherever the floor is penetrated.<br />
Take care not to create bridges between the<br />
floor base and the independent ceiling.<br />
Construction<br />
The floor and independent ceiling specified<br />
below, together give suitable resistance to<br />
direct sound transmission.<br />
Details of how junctions must be made to limit<br />
flanking transmission follow.<br />
Floor<br />
Timber boarding or wood based board, 18 mm<br />
thick with tongued and grooved edges (or 3.2<br />
mm hardboard over the whole floor to seal<br />
gaps).<br />
45 mm thick joists plus deafening of mass<br />
80 kg/m 2 and a ceiling of either 19 mm dense<br />
plaster on lath or two layers of plasterboard<br />
with joints staggered, total thickness 30 mm. In<br />
existing floors deafening may be on boards<br />
between joists, in new floors use 6 mm<br />
plywood fixed to underside of joists.<br />
A polyethylene liner may be used if desired.<br />
; ;150<br />
31H<br />
Section (through new floor)<br />
;; ;150<br />
(H2.1), (H2.3)<br />
boarding or<br />
board<br />
deafening<br />
liner (optional)<br />
false ceiling<br />
(plasterboard<br />
option)<br />
unfaced<br />
mineral<br />
fibre<br />
ceiling<br />
Section (through adapted existing floor)<br />
boarding or<br />
board<br />
deafening<br />
plywood<br />
false ceiling<br />
(plaster option)<br />
unfaced<br />
mineral<br />
fibre<br />
ceiling<br />
Amdt: December 1999<br />
H
H<br />
(H2.1), (H2.3)<br />
17. Independent ceiling<br />
(Cont’d)<br />
Absorbent blanket of 25 mm unfaced mineral<br />
fibre, density 12-36 kg/m 3 , draped over 45 mm<br />
thick joists supported independently of the<br />
floor. Ceiling of two layers of plasterboard<br />
with joints staggered, total thickness 30 mm.<br />
Keep ceiling 150 mm away from the underside<br />
of the floor base.<br />
Junctions for floor type 4<br />
External wall or separating wall<br />
Mass of leaf must be 355 kg/m 2 (including any<br />
plaster), both above and below the floor, on at<br />
least 3 sides. Leaf on fourth side must be at<br />
least 180 kg/m 2 .<br />
Use bearers on walls to support the edges of the<br />
ceiling and to block air paths.<br />
Seal the junction of ceiling and wall with tape<br />
or caulking.<br />
Internal wall<br />
If masonry, mass must be 180 kg/m 2 .<br />
No restriction if stud partition.<br />
Support and seal as for external walls.<br />
Floor penetrations<br />
Ducts or pipes penetrating the floor must be in<br />
an enclosure both above and below the floor.<br />
Either line the enclosure, or wrap the duct or<br />
pipe within the enclosure, with 25 mm unfaced<br />
mineral fibre.<br />
The material of the enclosure must have a mass<br />
of 15 kg/m 2 .<br />
Penetrations of a separating floor by ducts and<br />
pipes must have fire protection in accordance<br />
with Part D.<br />
Where permitted by Part F, a flue-pipe may<br />
penetrate the floor. The flue-pipe must be in a<br />
non-combustible enclosing duct with mineral<br />
fibre absorbent.<br />
Seal the junction of ceiling and enclosure with<br />
tape or caulking.<br />
Amdt: December 1999<br />
32H<br />
Sections<br />
boarding or<br />
board<br />
deafening<br />
plywood<br />
false ceiling<br />
(plaster option)<br />
unfaced mineral<br />
fibre<br />
ceiling<br />
seal<br />
unfaced mineral<br />
fibre<br />
enclosure<br />
boarding or board<br />
trimmer<br />
deafening<br />
plywood<br />
false ceiling<br />
(plaster<br />
option)<br />
unfaced<br />
mineral fibre<br />
ceiling<br />
seal<br />
enclosure
Performance standards and test procedures<br />
<strong>Standards</strong><br />
18. A wall or floor will meet the requirements for sound insulation if the following values are achieved when<br />
the performance is tested after construction under the procedures set out in 19 to 29.<br />
Airborne Sound<br />
Minimum values of weighted standardised level difference<br />
(DnT,w) as defined in BS EN ISO 717-1: 1997<br />
Mean Value (dB) Individual Value (dB)<br />
Walls 53 49<br />
Floors 52 48<br />
Impact Sound<br />
Maximum values of weighted standardised impact sound pressure level<br />
(L’nT,w) as defined in BS EN ISO 717-2: 1997<br />
Mean Value (dB) Individual Value (dB)<br />
Floors 61 65<br />
Test procedures<br />
19. For each wall or floor which requires to be tested take four sets of measurements, or as close to four as<br />
possible given the following restrictions -<br />
a. for each set of measurements use a pair of rooms if possible;<br />
b. use a pair consisting of a room and some other space only where necessary to make up the four sets;<br />
c. use a pair consisting of spaces other than rooms only where no other measurement is possible; and<br />
d. take only one set of measurements between each pair.<br />
20. When measuring between a pair of rooms of unequal area, the sound source must be in the larger room.<br />
21. When measuring between a room and some other space, the sound source must be in the other space.<br />
22. Carry out the tests for airborne sound in accordance with BS EN ISO 140-4: 1998 and for impact sound<br />
in accordance with BS EN ISO 140-7: 1998. The tests are to be done in completed but unfurnished<br />
dwellings. Doors and windows must be closed. The tests will determine the standardised level differences<br />
(DnT) for airborne sound transmission and the standardised impact sound pressure levels (L’nT)<br />
for impact sound transmission.<br />
23. For each set of measurements calculate the weighted standardised level difference (DnT,w) in accordance<br />
with BS EN ISO 717-1: 1997 or the weighted standardised impact sound pressure level (L’nT,w)<br />
in accordance with BS EN ISO 717-2: 1997.<br />
33H<br />
(H2.1), (H2.3)<br />
Amdt: December 1999<br />
H
H<br />
(H2.1), (H2.3)<br />
24. The calculated value from each set of measurements must be no worse than that stated in the “Individual<br />
Value” column in point 18.<br />
25. The mean of the four † calculated values must be no worse than that stated in the “Mean Value” column<br />
in point 18.<br />
† where only two or three sets of measurements have been possible the mean must still be reached, and<br />
where only one set is possible the value achieved must not be worse than the mean value.<br />
26. In a building every wall or floor, or part of a wall or floor, which requires sound resistance and is of nominally<br />
identical construction, may be regarded as forming part of a single wall or floor e.g. in a block<br />
of flats a wall rising through several storeys may be regarded as a single wall, and floors over a whole<br />
storey may be regarded as a single floor, wherever the flat plans are nominally identical.<br />
27. A wall which changes construction only in a roof space may be regarded as a single wall.<br />
28. In any group of dwellings covered by one building warrant, walls and floors of nominally identical<br />
dwelling types which are similarly situated in regard to adjoining buildings may all be regarded as<br />
meeting the performance standard if the ones selected for test meet the standard.<br />
29. Note that the test procedure described above is intended only to provide evidence that a particular wall<br />
or floor not built to a specified construction satisfies the performance standards set out in point 18.<br />
Amdt: December 1999<br />
34H
CONSERVATION OF<br />
FUEL AND POWERJ
Contents<br />
INTRODUCTION<br />
REGULATION 22<br />
Conservation of fuel and power<br />
THE STANDARDS<br />
J1 Application of Part J J1.1-J1.2<br />
J2 Rules for the use of Part J<br />
Thermal conductivity and transmittance J2.1-J2.4<br />
Calculation of areas J2.5<br />
BUILDINGS IN PURPOSE GROUP 1<br />
J3 Building fabric<br />
<strong>Standards</strong> for buildings in purpose group 1 J3.1<br />
Elemental method J3.2-J3.3<br />
Target U-value method J3.4-J3.10<br />
Carbon index method J3.11<br />
Maximum permissible U-values J3.12<br />
J4 Limiting thermal bridging at junctions and around J4.1<br />
openings<br />
J5 Limiting infiltration J5.1<br />
J6 Building services<br />
Space heating controls J6.1<br />
Hot water service system controls J6.2<br />
Insulation of pipes, ducts and vessels J6.3-J6.4<br />
Commissioning of heating and hot water<br />
service systems<br />
J6.5-J6.6<br />
J7 Conservatories J7.1<br />
BUILDINGS OTHER THAN DWELLINGS<br />
J8 Buildings in Purpose Groups 2 to 7<br />
<strong>Standards</strong> for buildings other than dwellings J8.1<br />
Elemental method J8.2-J8.4<br />
Heat loss method J8.5-J8.6<br />
Carbon emissions calculation method J8.7-J8.9<br />
J9 Limiting thermal bridging at junctions and around J9.1<br />
openings<br />
J10 Limiting infiltration J10.1<br />
J11 Building services (space heating and hot water)<br />
Heating system efficiency J11.1<br />
Space heating controls J11.2-J11.4<br />
Hot water service system controls J11.5<br />
Insulation of pipes, ducts and vessels J11.6-J11.7<br />
J12 Building services (artificial lighting)<br />
Artificial lighting J12.1<br />
Display lighting J12.2<br />
Controls for artificial lighting J12.3<br />
J13 Building services (air conditioning, mechanical<br />
ventilation)<br />
J13.1<br />
J14 Commissioning of the building services J14.1-J14.2<br />
3J<br />
Amdt: September 2001<br />
J
J<br />
Amdt: September 2001<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
Rules for the use of Part J<br />
(J2.1) Thermal conductivity and transmittance<br />
Buildings in Purpose Group 1<br />
(J4.1) Limiting thermal bridging at junctions and around openings<br />
(J5.1) Limiting infiltration<br />
(J6.1) Space heating controls<br />
(J6.2) Hot water service system controls<br />
(J6.3-J6.4) Insulation of pipes, ducts and vessels<br />
Buildings in purpose groups 2 to 7<br />
(J8.5) Heat loss method<br />
(J8.7) Carbon emissions calculation method<br />
(J9.1) Limiting thermal bridging at junctions and around openings<br />
(J10.1) Limiting infiltration<br />
(J11.1) Heating system efficiency<br />
(J11.3) Space heating controls<br />
(J11.5) Hot water service system controls<br />
(J11.6-J11.7) Insulation of pipes, ducts and vessels<br />
(J12.1) Artificial lighting<br />
(J12.2) Display lighting<br />
(J12.3) Controls for artificial lighting<br />
(J13.1) Air conditioning and mechanical ventilation<br />
(J14.1-J14.2) Commissioning of the building services<br />
PART J APPENDICES<br />
The appendices relevant to buildings in purpose group 1 and those to buildings in<br />
purpose groups 2 to 7 are listed separately below. Note that many of the appendices<br />
appear in both lists.<br />
For buildings in purpose group 1:<br />
A Tables of U-values<br />
B Worked examples of U-value calculations using the Combined Method.<br />
C U-values of ground floors and basements<br />
D Thermal bridging at the edges of openings<br />
E Determining U-values of windows, doors and rooflights in the Elemental<br />
Method<br />
F Examples illustrating the use of the Target U-value Method<br />
G Example SAP Energy Ratings and Carbon Indexes<br />
For buildings in purpose groups 2 to 7:<br />
A Tables of U-values<br />
B Worked examples of U-value calculations using the Combined Method.<br />
C U-values of ground floors and basements<br />
D Thermal bridging at the edges of openings<br />
E Determining U-values of windows, doors and rooflights in the Elemental<br />
Method<br />
H Examples illustrating the use of the Heat Loss Method<br />
J Example lighting calculations<br />
K Performance assessment methods for building services<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes either that a provision is deemed to satisfy the<br />
standard or that some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in Italics is a defined term. The definition is listed in Part A, General.<br />
4J
Introduction<br />
1. The construction industry has a major role to play in the conservation<br />
of fuel and power. Energy use in buildings is a major source of carbon<br />
dioxide emissions which contribute to climate change. The intention of<br />
this Part is to ensure that effective measures for the conservation of fuel<br />
and power are incorporated in a building. It contains energy conservation<br />
provisions for the building fabric and the building services.<br />
2. All buildings not exempted by Part A are required to conform to specific<br />
standards for the overall performance of the fabric. There are a<br />
variety of ways of demonstrating compliance, ranging from the simple calculation<br />
of the heat losses through each building element, to more sophisticated<br />
methods that provide greater flexibility for designers.<br />
3. For buildings in purpose group 1, there are 3 alternative methods for<br />
showing compliance with this Part, the Elemental Method, the Target Uvalue<br />
Method and the Carbon Index Method. The different methods allow<br />
some design flexibility, for example, the benefits of solar heat gain or a<br />
more efficient heating system may be taken into account.<br />
4. The Building (Procedure) (Scotland) Regulations 1981, as amended in<br />
1997, continue to require all applications for building warrant for buildings<br />
in purpose group 1 to include an energy rating calculated in accordance<br />
with the Standard Assessment Procedure (SAP). Achievement of a particular<br />
level of SAP energy rating is no longer required to show compliance<br />
with this Part. However, the SAP worksheet and computer software is able<br />
to calculate CO2 emissions, expressed as the Carbon Index. Achievement<br />
of a given minimum Carbon Index figure is one of the ways for a dwelling<br />
to show compliance with this Part.<br />
5. Conservatories with a floor area more than 8 square metres are no<br />
longer exempt from the requirements of the <strong>Technical</strong> <strong>Standards</strong>.<br />
However, where the floor area is not more than 30 square metres a less<br />
onerous standard applies to the glazed elements than for glazing elsewhere<br />
in the dwelling and the average U-value of the dwelling may be calculated<br />
independently of the conservatory.<br />
6. Buildings other than buildings in purpose group 1 also require to<br />
conform to any one of 3 methods: the Elemental Method, the Heat Loss<br />
Method and the Carbon Emissions Calculation Method.<br />
7. In addition to requirements for insulation of the fabric there are<br />
requirements for building services, including in the case of non-domestic<br />
buildings, requirements for artificial lighting, air conditioning and<br />
mechanical ventilation.<br />
8. This Part must be read in conjunction with Part G (which deals with<br />
condensation), Part H (sound insulation) and Part K (ventilation). Reference<br />
should also be made to BS 5250: 1989, (note 2001 edition being prepared):<br />
“Code of practice for control of condensation in buildings”,<br />
Building Research Establishment (BRE) Report, BR 262: “Thermal insulation,<br />
Avoiding risks”, Second Edition, 1994, (note Third edition being<br />
prepared), and BRE report, BR 265: “Minimising air infiltration in office<br />
buildings”.<br />
5J<br />
Amdt: September 2001<br />
J
J<br />
Regulation 22<br />
Conservation of fuel and power<br />
22. (1) In a building to which this regulation applies,<br />
reasonable provision shall be made for the<br />
conservation of fuel and power.<br />
(2) This regulation shall apply to all buildings,<br />
other than -<br />
(a) a building which is unheated or which has<br />
a space heating system for protection<br />
against frost designed to give a maximum<br />
output not exceeding 25 watts per square<br />
metre of floor area; or<br />
(b) unheated parts of a building of purpose<br />
sub-group 1A that do not form part of a<br />
dwelling.<br />
Amdt: September 2001<br />
6J
The standards<br />
J1 Application of Part J<br />
J1.1 This Part sets out the required standards for Regulation 22.<br />
J1.2 The standards apply as follows -<br />
Buildings in purpose group 1: J2 to J7<br />
Purpose in purpose groups 2 to 7: J2 and J7 to J14<br />
except -<br />
the standards do not apply to a building or part of a building specified in Regulation 22(2).<br />
7J<br />
J1.1 – J2.3<br />
Note:<br />
Regulation 22 applies in full where the intended level of provision of heating cannot be established<br />
because the use of the building is not known at the construction stage, e.g. speculative development.<br />
J2 Rules for the use of Part J<br />
THERMAL CONDUCTIVITY AND TRANSMITTANCE<br />
J.2.1* Individual U-values of building elements must be established -<br />
a. by providing insulation to a thickness derived from manufacturers’ data relating to thermal conductivities<br />
(W/m·K) and thermal transmittances (U-values: W/m 2 K) certified by a notified body; or<br />
b. in the absence of certified manufacturers’ data, by suitable alternative means.<br />
Notes:<br />
1. The thermal conductivity (the k-value) of a material is a measure of the rate at which that material<br />
will pass heat and is expressed in units of Watts per metre per degree of temperature difference<br />
(W/m·K).<br />
2. Thermal transmittance (the U-value) is a measure of how much heat will pass through one square<br />
metre of a structure when the air temperatures on either side differ by one degree, and is<br />
expressed in units of Watts per square metre per degree of temperature difference (W/m 2 K).<br />
J2.2 For the purposes of Part J, any part of a floor that serves as a roof (e.g. an open deck) is to be treated as<br />
a roof.<br />
J2.3 The U-value of a floor above, or a wall adjoining, a garage, unheated stairwell, atrium, underground car<br />
park or other unheated space must be calculated -<br />
a. in the case of a dwelling, using the method given in SAP 2001, Clause 3.3, to take into account<br />
the thermal resistance of the unheated space; or<br />
b. in any other case, by either of the following two methods:<br />
• disregarding so that the element is considered as directly exposed to the outside, or<br />
• by using the procedure in BS EN ISO 13789: 1999 to take account of the effect of the unheated space<br />
Amdt: September 2001<br />
J
J<br />
J2.4, J2.5<br />
J2.4 Separating walls or separating floors between 2 buildings in purpose group 1 or between other buildings<br />
or parts of a building intended to be heated to the same temperature may be ignored.<br />
CALCULATION OF AREAS<br />
J2.5 In calculating areas:<br />
a. all areas are to be measured in m 2 unless otherwise stated; and<br />
b. the area of a floor, wall or roof is to be measured between finished internal faces of the external<br />
building elements of the building, including any projecting bays and, in the case of a roof, in the<br />
plane of the insulation; and<br />
c. floor areas are to include stair wells within the heated envelope and non-useable space such as<br />
service ducts; and<br />
d. in calculating the maximum permitted area of glazing for an extension to a dwelling, the floor<br />
area of the whole dwelling may be used; and<br />
e. the area of an opening is to be measured internally from reveal to reveal and from head to sill.<br />
Amdt: September 2001<br />
8J
J3 BUILDINGS IN PURPOSE GROUP 1<br />
BUILDING FABRIC<br />
STANDARDS FOR BUILDINGS IN PURPOSE GROUP 1<br />
J3.1 A building in purpose group 1 must have provision for conservation of fuel and power in accordance<br />
with either:<br />
a. the Elemental Method; or<br />
b. the Target U-value Method; or<br />
c. the Carbon Index Method.<br />
The following table illustrates the routes through the alternative methods of showing that buildings in<br />
purpose group 1 comply with Part J -<br />
Table to 3.1: Routes to compliance with Part J for buildings in purpose group 1.<br />
START: Choose method of compliance-<br />
Elemental Method go to 1.<br />
Target U-value Method go to 6.<br />
Carbon Index Method go to 13.<br />
COMPLIANCE BY ELEMENTAL METHOD<br />
1 Is the heating by mains gas, LPG<br />
or oil?<br />
YES go to 3.<br />
NO go to 2.<br />
2 Are all U-values of the proposed<br />
dwelling not more than the<br />
corresponding values from Column B<br />
of Table 1 to J3.2?<br />
YES go to 5.<br />
NO FAIL by Elemental Method - revise U-values<br />
and repeat 2 or go to START.<br />
3 Is the SEDBUK [Note 1] of the<br />
proposed heating system not less<br />
YES go to 4.<br />
than the SEDBUK from Table 2 to J3.2?<br />
NO go to 2.<br />
4 Are all U-values of the proposed<br />
dwelling not more than the<br />
corresponding values from Column A<br />
of Table 1 to J3.2?<br />
YES go to 5.<br />
NO FAIL by Elemental Method - revise U-values<br />
and repeat 4 or go to START.<br />
5 Is the area of windows, doors and<br />
rooflights not more than 25% of<br />
total floor area?<br />
YES PASS by Elemental Method.<br />
NO FAIL by Elemental Method - reduce area of<br />
openings and repeat 5 or go to START.<br />
9J<br />
J3.1<br />
Amdt: September 2001<br />
J
J<br />
J3.1, J3.2<br />
COMPLIANCE BY TARGET U-value METHOD<br />
6 Calculate the Target U-value from the equation in J3.5.<br />
7 Are the windows metal framed ? YES Multiply the Target U-value by 1.03 and go to 8.<br />
NO Go to 8.<br />
8 Is the heating by electricity, solid<br />
fuel or is it undecided?<br />
YES Divide the Target U-value by 1.15 and go to 10.<br />
NO go to 9.<br />
9 Is the SEDBUK for the proposed YES Multiply the Target U-value by;<br />
heating system less than the<br />
corresponding SEDBUK from the<br />
table to J3.6?<br />
The proposed boiler SEDBUK (%)<br />
divided by Referenced boiler SEDBUK<br />
(%) from Table to J3.6 and go to 10.<br />
NO go to 10.<br />
10 Is there a greater area of glazing YES Subtract the north facing glazing area from the<br />
facing south than is facing north? south facing, divide the result by the total<br />
area of glazing, multiply by 0.04 and add the<br />
result to the Target U-value; then go to 11.<br />
NO go to 11.<br />
11 Calculate the average U-value (U) by multiplying the area of each building element by its Uvalue,<br />
adding the results and dividing the total by the total area of all exposed elements.<br />
12 Is U not more than the Target<br />
U-value, and is the U-value of each<br />
building element not more than the<br />
corresponding value from the<br />
Table to J3.12?<br />
YES PASS by Target U-value Method.<br />
NO FAIL by Target U-value Method - revise and go<br />
to 6 or go to START.<br />
COMPLIANCE BY CARBON INDEX METHOD<br />
13 Calculate the Carbon Index (CI) as defined in SAP 2001.<br />
14 Is the Carbon Index (CI) at least 8.0,<br />
and is the U-value of each building<br />
element not more than the<br />
corresponding value from the<br />
Table to J3.12?<br />
YES PASS by Carbon Index Method.<br />
Note:<br />
NO FAIL by Carbon Index Method - revise and go<br />
to 13 or go to START.<br />
1. SEDBUK is the Seasonal Efficiency of a Domestic Boiler in the UK, defined in “The <strong>Government</strong>’s<br />
Standard Assessment Procedure for the Energy Rating of Dwellings 2001 Edition” (SAP<br />
2001). For boilers for which the SEDBUK is not available the appropriate value from Table 4b<br />
of SAP 2001 may be used.<br />
ELEMENTAL METHOD<br />
J3.2 Individual building elements of a building in purpose group 1 must have U-values in accordance with<br />
those given in Table 1(as read with Table 2) and diagram A. to this standard<br />
Amdt: September 2001<br />
10J
Table 1 to J3.2: Maximum U-values for exposed building elements when using the Elemental Method<br />
11J<br />
J3.2<br />
Type of heating system<br />
Exposed building element Column A Column B<br />
Gas or oil central heating with Other gas or oil central heating,<br />
boiler SEDBUK not less than or any electric heating system or<br />
the relevant entry in Table 2 to J3.2 solid fuel central heating or undecided<br />
Maximum U-values (W/m2K) Pitched roof -<br />
With insulation between rafters<br />
Pitched roof -<br />
0.20 0.18<br />
With insulation between joists 0.16 0.16<br />
Flat roof 0.25 0.22<br />
External wall [Note 1] 0.30 0.27<br />
Floor 0.25 0.22<br />
Windows, doors and rooflights (areaweighted<br />
average), glazing in metal<br />
frames [Notes 2, 3, 4]<br />
2.2 2.0<br />
Windows, doors and rooflights (areaweighted<br />
average), glazing in wood<br />
or PVC frames [Notes 2, 3, 4]<br />
2.0 1.8<br />
Notes:<br />
1. Solid area of element only (i.e. excluding windows, doors and rooflights).<br />
2. U-values for windows, doors and rooflights may vary provided that the average U-value for all<br />
windows, doors and rooflights is not more than the figure shown. For method of calculation see<br />
Appendix E.<br />
3. Metal framed windows have slimmer frames and therefore provide a passive solar benefit, justifying<br />
a less onerous U-value standard.<br />
4. The area of windows, doors and rooflights must comply with J3.3.<br />
Table 2 to J3.2: Minimum boiler SEDBUK to enable adoption of U-values in Column A of Table 1 to<br />
J3.2<br />
Central heating system fuel Minimum SEDBUK (%)<br />
Mains natural gas 78<br />
LPG 80<br />
Oil (Note ) 85<br />
Note:<br />
For oil combination boilers the minimum SEDBUK (%) is 82%<br />
Amdt: September 2001<br />
J
J<br />
J3.2 – J3.5<br />
Diagram to J3.2 Maximum U-values using the Elemental Method<br />
2.0<br />
0.30<br />
2.0<br />
0.20<br />
2.0<br />
window<br />
door<br />
(a) Gas or oil central heating with boiler SEDBUK (b) Other gas or oil central heating, or any<br />
not less than the relevant entry in Table 2 to J3.2 electric heating system or solid fuel central<br />
heating or undecided<br />
Note:<br />
The U-value of a floor above, or a wall adjoining, an unheated space must be calculated in accordance<br />
with the procedure in SAP 2001 (see J2.3).<br />
J3.3 The area of windows, doors and rooflights (including frames) as a percentage of the total floor area of<br />
all storeys of the dwelling must not be more than 25%.<br />
TARGET U-VALUE METHOD<br />
J3.4 The average U-value of the exposed elements of a building in purpose group 1 must not exceed the<br />
Target U-value, corrected as necessary for the proposed method of heating and any solar gains.<br />
Note:<br />
This method allows greater flexibility than the Elemental Method. The aim is to achieve a level of<br />
performance broadly equivalent to that obtained through the Elemental Method by comparing the<br />
average fabric U-value of the proposed building in purpose group 1 with a Target U-value obtained from<br />
the formula in J3.5. For examples of the use of this method, see Appendix F.<br />
J3.5 The base Target U-value for the building in purpose group 1 must be determined as follows:<br />
where -<br />
Amdt: September 2001<br />
roof<br />
space<br />
rooflight<br />
0.25<br />
0.30<br />
U T = [0.30 – 0.14(A R/A T) – 0.05(A GF/A T) + 0.425(A F/A T)]<br />
U T<br />
0.16<br />
AR AGF AF AT 0.25<br />
unheated space<br />
0.25<br />
0.25<br />
0.30<br />
is the base Target U-value prior to adjustment for heating system performance or<br />
solar gain;<br />
is the exposed roof area;<br />
is the ground floor area;<br />
is the total floor area (all storeys);<br />
is the total area of exposed building elements of the building in purpose group 1<br />
(including the ground floor).<br />
Note:<br />
The base Target U-value equation assumes a boiler SEDBUK that is equal to the tabulated value and<br />
equal distribution of glazed openings on north and south elevations.<br />
12J<br />
0.18<br />
1.8<br />
0.27<br />
1.8<br />
1.8<br />
window<br />
door<br />
roof<br />
space<br />
rooflight<br />
0.22<br />
0.27<br />
0.16<br />
0.22<br />
unheated space<br />
0.22<br />
0.22<br />
0.27
13J<br />
J3.6 – J3.11<br />
J3.6 Where the proposed boiler has a SEDBUK that is less than the value in the table to this standard, the<br />
Target U-value must be improved by multiplying it by the factor ƒ e<br />
where -<br />
ƒ e=<br />
Proposed boiler SEDBUK (%)<br />
Reference Boiler SEDBUK (%)<br />
Table to J3.6: Minimum boiler SEDBUK using the Target U-value Method<br />
Central heating system fuel Minimum SEDBUK (%)<br />
Mains natural gas 78<br />
LPG 80<br />
Oil (Note) 85<br />
Note :<br />
For oil combination boilers the minimum SEDBUK (%) is 82%<br />
J3.7 Where the dwelling is heated by electricity or solid fuel, or where the proposed method of heating is not<br />
known, the base Target U-value must be divided by 1.15 to compensate partially for the higher CO 2<br />
emission rate associated with these fuels.<br />
J3.8 Where the dwelling has metal framed windows (including any rooflights and including thermally-broken<br />
frames), the base Target U-value may be increased by multiplying by 1.03, to take account of the additional<br />
solar gain due to the greater glazed proportion.<br />
J3.9 The Target U-value equation assumes equal distribution of glazed openings on north and south elevations.<br />
Where the area of glazed openings, including frames, on the south elevations is greater than that<br />
on the north, the benefit of solar heat gains can be taken into account by adding:<br />
0.04 × [(A S-A N) ÷ A TG] to the Target U-value.<br />
where AS is the total area of glazed openings facing south;<br />
AN is the total area of glazed openings facing north;<br />
ATG is the total area of glazed openings;<br />
North facing is defined as North plus or minus 30 degrees; and<br />
South facing is defined as South plus or minus 30 degrees.<br />
J3.10 Where adjustments to the Target U-value are being made for heating system or window frame type as<br />
well as for solar gain, the adjustment for solar gain must be applied last.<br />
CARBON INDEX METHOD<br />
J3.11 The Carbon Index for the dwelling must not be less than 8.0.<br />
Note:<br />
This method allows much greater flexibility than either the Elemental Method or the Target U-value<br />
Method while still achieving an overall performance not less than that obtained through the Elemental<br />
Method. The Carbon Index adopted in this Method is that defined in SAP 2001 and is calculated using<br />
the SAP worksheet or by using BRE-approved computer software. Examples of dwellings with Carbon<br />
Index of 8.0 or more are given in Appendix G.<br />
Amdt: September 2001<br />
J
J<br />
J3.12 – J6.1<br />
MAXIMUM PERMISSIBLE U-VALUES<br />
J3.12 When using the Target U-value and Carbon Index Methods, the U-value of any building element must<br />
comply with the table to this standard -<br />
Table to J3.12: Maximum permissible U-values for parts of building elements when using the<br />
Target U-value and Carbon Index Methods<br />
Exposed building element Maximum permissible U-value<br />
Parts of roof 0.35<br />
Parts of external wall or floor 0.70<br />
J4 Limiting thermal bridging at junctions and around openings<br />
J4.1* The dwelling’s fabric must be constructed to limit thermal bridges and gaps in the insulation layer(s) -<br />
a. within the various building elements; and<br />
b. at the junctions between building elements; and<br />
c. at the edges of building elements (e.g. around window and door openings).<br />
J5 Limiting infiltration<br />
J5.1* The infiltration of air through extraneous air paths must be limited as far as is reasonably practical.<br />
J6 Building services<br />
SPACE HEATING CONTROLS<br />
J6.1* In a building in purpose group 1 the output of a space heating system must be controlled by -<br />
a. room thermostats or thermostatic radiator valves for each part of the heating system designed to<br />
be separately controlled (e.g. separate living and sleeping areas); and<br />
b. a manually adjustable 7-day automatic timing device or devices to control the periods of operation;<br />
and<br />
c. in a system using a boiler,<br />
Amdt: September 2001<br />
i. an automatic control which shuts the boiler off when heat is not required (after an over-run<br />
time if this is specified by the manufacturer) or, if it is a solid fuel boiler, reduces the<br />
firing to the minimum burning rate, and<br />
ii. where the system is fitted solely with thermostatic radiator valves, a thermostat, flow<br />
control or similar device to prevent boiler cycling,<br />
except -<br />
this standard shall not apply to individual solid fuel open fires, gas or electric fires, or controlled room<br />
heaters including electric storage heaters.<br />
14J
HOT WATER SERVICE SYSTEM CONTROLS<br />
15J<br />
J6.2 – J7.1<br />
J6.2* A hot water service system must have controls that will switch off the heat when the required water<br />
temperature has been achieved and during periods when hot water is not required,<br />
except -<br />
this standard shall not apply to instantaneous combination boilers or storage combination boilers where<br />
the storage capacity in each case is not more than 15 litres.<br />
INSULATION OF PIPES, DUCTS AND VESSELS<br />
J6.3* Heating pipes, pipes used for the supply of hot water, and warm air ducts must be suitably insulated<br />
against heat loss,<br />
except -<br />
heating pipes and warm air ducts need not be insulated where the heat loss will always contribute to the<br />
heating requirements of a room or space.<br />
J6.4* A hot water storage vessel must be adequately insulated against heat loss.<br />
COMMISSIONING OF HEATING AND HOT WATER SERVICE SYSTEMS<br />
J6.5 A heating and hot water service system must be inspected, commissioned and tested in accordance with<br />
manufacturer’s instructions to ensure optimum efficiency in the conservation of fuel and power.<br />
J6.6 Written information must be provided for the use of the occupier on the operation and maintenance of<br />
any heating and hot water service system to encourage optimum efficiency in the conservation of fuel<br />
and power.<br />
J7 Conservatories<br />
J7.1 a conservatory must comply with the requirements of J2-J6,<br />
except -<br />
where the floor area is not more than 30 square metres -<br />
a. glazing, including frames, may have a U-value not more than 3.3 W/m 2 K; and<br />
b. in calculating the average U-value of the dwelling, the conservatory may be ignored.<br />
Amdt: September 2001<br />
J
J<br />
J8.1 – J8.3<br />
BUILDINGS OTHER THAN DWELLINGS<br />
J8 Buildings in Purpose Groups 2 to 7<br />
J8.1 A building other than a building in purpose groups 2 to 7 must have provision for conservation of fuel<br />
and power in accordance with one of the three following methods:<br />
a. the Elemental Method; or<br />
b. the Heat Loss Method; or<br />
c. the Carbon Emissions Calculation Method.<br />
ELEMENTAL METHOD<br />
J8.2 To comply with this method the building envelope must provide minimum levels of thermal insulation as<br />
set out in J8.3 and areas of windows, doors and rooflights as set out in J8.4.<br />
J8.3 The individual specified building elements must have U-values in accordance with the table to this<br />
standard -<br />
Table to J8.3: Maximum U-values of exposed building elements when using the Elemental Method<br />
[Note 1]<br />
Exposed building element Maximum U-value (W/m2K) Pitched roof - with insulation between rafters 0.20<br />
Pitched roof - with insulation between joists 0.16<br />
Flat roof 0.25<br />
External wall [Note 2] 0.30<br />
Floor 0.25<br />
Windows, personnel doors and rooflights (area weighted average for the<br />
whole building) [Note 3], glazing in metal frames [Note 4]<br />
2.2<br />
Windows, personnel doors and rooflights (area weighted average for the<br />
whole building) [Note 3], glazing in wood or PVC frames<br />
2.0<br />
Vehicle access and similar large doors [Note 5] 0.7<br />
Notes:<br />
1. When an element is exposed to the outside via an unheated space, the unheated space may be<br />
disregarded or the U-value of the element calculated using BS EN ISO 13789: 1999 - see J2.3.<br />
2. Solid area of element only (i.e. excluding windows, doors and rooflights).<br />
3. For method of calculation, see Appendix E.<br />
4. Metal framed windows have slimmer frames and therefore provide a passive solar benefit, justifying<br />
a less onerous U-value standard.<br />
5. No requirement where for operational reasons doors have to be left open when building is in use.<br />
Amdt: September 2001<br />
16J
17J<br />
J8.4 – J8.6<br />
J8.4 The specified building elements must have areas of windows, doors and rooflights not more than those<br />
prescribed in the table to this standard -<br />
Table to J8.4: Maximum percentage areas of windows, doors and rooflights<br />
Purpose group Windows and doors as % of<br />
exposed wall area [Note 1]<br />
Rooflights as % of roof area<br />
2 30 20<br />
3, 4, 5 40 20<br />
6, 7 15 20<br />
Note:<br />
1. Excluding vehicle access and other similar large doors, shop entrances and shop display windows<br />
at an access level, for which there is no limit.<br />
HEAT LOSS METHOD<br />
J8.5* When using this method -<br />
a. the total rate of heat loss through the envelope of the proposed building must not be more than<br />
that from a notional building of the same size and shape designed to comply with the Elemental<br />
Method; and<br />
b. the U-value of any building element must not be more than that shown in the table to this standard.<br />
Note:<br />
This method allows greater flexibility than the Elemental Method since the U-values of some building<br />
elements, and the areas of windows, doors and rooflights, may be more than those required by J8.3 and<br />
J8.4, provided that these are “traded-off” against other elements having lower U-values than required by<br />
J8.3 and J8.4.<br />
Table to J8.5: Maximum permissible U-values when trading off between building elements<br />
Exposed building element Maximum permissible U-value (W/m2K) Roof 0.45<br />
Wall or floor 0.70<br />
Windows, doors and rooflights No limit<br />
J8.6 When comparing the proposed building with the notional building -<br />
a. if the U-value of a floor next to the ground in the proposed building is less than that required by<br />
J8. 3, with no added insulation, then that lower value must be used in the notional building; and<br />
b. if the total area of windows, doors and rooflights in the proposed building is less than the total<br />
area required by J8.4, then the average U-value of the roof, wall or floor cannot exceed the<br />
appropriate value given in the Table to J8.3 by more than 0.02 W/m 2 K; and<br />
c. a maximum of half of the permitted rooflight area can be converted into an increased area of<br />
window and doors.<br />
Amdt: September 2001<br />
J
J<br />
J8.7 – J10.1<br />
THE CARBON EMISSIONS CALCULATION METHOD<br />
J8.7* To comply with this method the thermal insulation of the fabric and the efficiency of the building services<br />
systems must be such that the annual carbon emissions from the building are not more than from<br />
an equivalent notional building designed to comply with the Elemental Method.<br />
except –<br />
When using this method the standards for building services systems in J11, J12 and J13 may be ignored.<br />
Note:<br />
This method allows much greater flexibility than either the Elemental Method or the Heat Loss Method.<br />
It is a calculation method that allows completely free design of the building using any energy conservation<br />
measure.<br />
J8.8 When using this method the U-value of any building element must be in accordance with the table to<br />
this standard -<br />
Table to J8.8: Maximum permissible U-values when using the Carbon Emissions Calculation Method<br />
Element Maximum permissible U-value<br />
Roofs 0.45<br />
Exposed walls and floors 0.70<br />
Windows, doors and rooflights No limit<br />
J8.9 In using this method -<br />
if the U-value of a floor next to the ground without added insulation in the proposed building is less than<br />
0.25 then that lower value must be used in the notional building.<br />
J9 Limiting thermal bridging at junctions and around openings<br />
J9.1* The building’s fabric must be constructed to minimise thermal bridges and gaps in the insulation layer(s) -<br />
a. within the various building elements; and<br />
b. at the junctions between building elements; and<br />
c. at the edges of building elements (e.g. around window and door openings).<br />
J10 Limiting infiltration<br />
J10.1*The infiltration of air into a building through extraneous air paths must be limited as far as is reasonably<br />
practical.<br />
Amdt: September 2001<br />
18J
J11Building services (space heating and hot water)<br />
HEATING SYSTEM EFFICIENCY<br />
19J<br />
J11.1– J11.3<br />
J11.1*The heating system of a building must be designed and installed to make efficient use of energy for the<br />
conservation of fuel and power.<br />
SPACE HEATING CONTROLS<br />
J11.2 Boiler cycling must be limited by -<br />
a. an automatic control which shuts the boiler off when heat is not required (after an over-run time<br />
if this is specified by the manufacturer) or, if it is a solid fuel boiler, reduces the firing to the<br />
minimum burning rate; and<br />
b. where the system is fitted solely with thermostatic radiator valves, a thermostat, flow control or<br />
similar device to prevent boiler cycling,<br />
except -<br />
this standard does not apply to a ducted warm air system or to fanned output electric storage heaters.<br />
J11.3*A space heating system must incorporate -<br />
a. room thermostats or thermostatic radiator valves for each part of the heating system designed to<br />
be separately controlled; and<br />
b. where the system is other than off-peak electricity and operates intermittently, controls to ensure<br />
that the system operates only when the building is normally occupied, comprising -<br />
i. for a space heating system with an output of more than 100 kW, a control arrangement<br />
which will give start and stop times appropriate to the rate at which the building will<br />
respond (optimising control) ; or<br />
ii. for a space heating system with an output of not more than 100 kW, a manually adjustable<br />
7-day automatic timing device or devices to control the periods of operation; and<br />
c. controls to allow sufficient heating to prevent damage to the building structure, services or contents<br />
by frost, excessive humidity or condensation; and<br />
d. where the system uses hot water, an external temperature sensing device (weather compensating<br />
control) to regulate the temperature of the water flowing in the heating circuit; and<br />
e. where the system has two or more gas or oil fired boilers which can work together to supply the<br />
heat demand, boiler controls which can detect variations in the need for heat in the building and<br />
start, stop, or modulate the boilers as required (sequence control), and hydraulic design to ensure<br />
stable control.<br />
except -<br />
this standard does not apply to a ducted warm air system or to flap controlled electric storage heaters.<br />
Amdt: September 2001<br />
J
J<br />
J11.4 – J12.1<br />
J11.4 Thermostats and time controls must be fitted to -<br />
a. ducted warm air systems; and<br />
b. flap controlled electric storage heaters.<br />
HOT WATER SERVICE SYSTEM CONTROLS<br />
J11.5*A hot water service system must be designed to make efficient use of energy by providing controls that<br />
will switch off the heat when the required water temperature has been achieved.<br />
INSULATION OF PIPES, DUCTS AND VESSELS<br />
J11.6*Pipes and ducts for the provision of space heating, space cooling (including chilled water and refrigerants),<br />
and hot water supply must be adequately insulated against heat loss,<br />
except -<br />
pipes or ducts for space heating or space cooling need not be insulated where -<br />
a. the heat loss will always contribute to the heating or cooling requirements of the room or space<br />
and the pipes are situated not more than 3 m above the floor; or<br />
b. where pipes and/or ducts are installed solely as part of an industrial or commercial process.<br />
J11.7*A hot water storage vessel must be -<br />
a. adequately insulated against heat loss; and<br />
b. constructed so that insulation to safety fittings on an unvented system does not impede safe<br />
operation or visibility of warning discharges,<br />
except -<br />
a vessel used to store hot water solely for an industrial process.<br />
J12Building services (artificial lighting)<br />
ARTIFICIAL LIGHTING<br />
J12.1*A building provided with artificial lighting must have general purpose artificial lighting systems<br />
designed to make efficient use of power,<br />
except -<br />
a. emergency lighting; and<br />
b. specialist process lighting; and<br />
c. buildings with a floor area not more than 100 m 2 .<br />
Note:<br />
Specialist process lighting means lighting intended to illuminate specialist tasks within a space, rather<br />
than the space itself.<br />
Amdt: September 2001<br />
20J
DISPLAY LIGHTING<br />
21J<br />
J12.2 – J14.2<br />
J12.2*Every display lighting system provided in a building must be designed to make efficient use of power.<br />
Note:<br />
Display lighting means artificial lighting intended to highlight displays of exhibits or merchandise, or<br />
lighting used in spaces for public entertainment in a building of purpose sub-group 5A.<br />
CONTROLS FOR ARTIFICIAL LIGHTING<br />
J12.3*Every artificial lighting system in a building must have controls which encourage the maximum use of<br />
daylight and minimise the use of artificial lighting during the times when rooms or spaces are unoccupied,<br />
except -<br />
controls for lighting systems described in the exceptions to J12.1.<br />
J13Building services (air conditioning, mechanical ventilation)<br />
J13.1*A building incorporating air conditioning or mechanical ventilation must be designed and constructed so<br />
that -<br />
a. the form and fabric of the building do not result in a requirement for excessive installed capacity<br />
of cooling equipment; and<br />
b. fans, pumps, refrigeration equipment and other components are reasonably efficient and appropriately<br />
sized to have no more capacity for demand and standby than is necessary; and<br />
c. there are appropriate means of managing, controlling and monitoring the operation of equipment<br />
and systems.<br />
J14Commissioning of the building services<br />
J14.1*The building services installation required to comply with this Part must -<br />
a. be capable of operating at the manufacturer’s specified efficiency; and<br />
b. incorporate adequate provisions for testing and commissioning to be carried out satisfactorily.<br />
J14.2*Written information must be provided for the building’s occupier on the installed building services plant<br />
and controls required to comply with this Part, their method of operation, maintenance requirements,<br />
and details forecasting annual energy consumption for the building.<br />
Amdt: September 2001<br />
J
J<br />
(J2.1) – (J5.1)<br />
Provisions deemed to satisfy the standards<br />
Rules for the use of Part J<br />
THERMAL CONDUCTIVITY AND TRANSMITTANCE<br />
(J2.1) The requirements of J2.1b. will be met -<br />
a. by providing insulation to a thickness derived from the tables in Appendix A; or<br />
b. by calculation taking into account thermal bridging effects of, e.g. timber joists, structural and<br />
other framing, normal bedding mortar and window frames, by using the Combined Method set<br />
out in BS EN ISO 6946 or CIBSE Guide Section A3, 1999 Edition (for worked examples see<br />
Appendix B) [Note 1]; or<br />
c. for basement storeys, by using the method outlined in Appendix C and set out fully in BS EN<br />
ISO 13370 or CIBSE Guide Section A3, 1999 Edition; or<br />
d. for glazing, by using BS EN ISO 10077-1 or BS EN ISO 10077-2.<br />
Notes:<br />
1 Thermal bridging may be disregarded where the difference in thermal resistance between bridging<br />
and bridged material is less than 0.1 m 2 K/W. For example, normal mortar joints need not be<br />
taken into account in calculations for brickwork but must be taken into account for lightweight<br />
insulating blockwork.<br />
2 Measurements of thermal conductivity should be made in accordance with BS EN 12664 or BS<br />
EN 12667, and of thermal transmittance in accordance with BS EN 8990.<br />
Buildings in purpose group 1<br />
LIMITING THERMAL BRIDGING AT JUNCTIONS AND AROUND OPENINGS<br />
(J4.1) The requirements of J4.1, as regards minimising thermal bridges and gaps in the insulation, will be met<br />
by -<br />
a. constructing the dwelling in accordance with Building Research Establishment (BRE) Report,<br />
BR 262: “Thermal insulation, Avoiding risks”, Second Edition, 1994 ; or<br />
b. demonstrating by calculation that equivalent performance to sub-clause a. has been achieved.<br />
LIMITING INFILTRATION<br />
(J5.1) The requirements of J5.1, as regards minimising extraneous air leakage paths in the dwelling’s fabric,<br />
will be met by constructing the dwelling in accordance with BRE Report BR Building Research Establishment<br />
(BRE) Report, BR 262: “Thermal insulation, Avoiding risks”, Second Edition, 1994 [Note 1],<br />
including -<br />
a. sealing the gaps between dry linings and masonry walls at the edges of window, door and roof<br />
space openings, and at the junctions between walls, floors and ceilings; and<br />
b. sealing vapour control membranes in timber framed and other framed panel constructions; and<br />
Amdt: September 2001<br />
22J
c. sealing at service penetrations of the fabric or around boxing for services; and<br />
d. fitting draught seals to the openable parts of windows, doors and rooflights; and<br />
e. sealing around joist ends built into the inner leaf of external cavity walls.<br />
23J<br />
(J5.1) – (J6.4)<br />
Note:<br />
1. This document provides examples of acceptable design details and construction practice, but<br />
alternative details may be used if equivalent performance can be demonstrated.<br />
SPACE HEATING CONTROLS<br />
(J6.1) The requirements of J6.1 will be met for a building in purpose group 1 with a heating system with an<br />
output not greater than 100 kW by having space heating controls in accordance with BRECSU Good<br />
Practice Guide GPG 143: “Wet Central Heating Systems”.<br />
HOT WATER SERVICE CONTROLS<br />
(J6.2) The requirements of J6.2 will be met by complying with sub-clauses a. or b. below -<br />
a. for a system other than one heated by a solid fuel boiler -<br />
i. the heat exchanger in the storage vessel should have sufficient heating capacity, such as<br />
one complying with BS 1566: Part 2: 1984 (1990) or BS 3198: 1981, and in particular it<br />
should comply with the requirements in these standards for the surface area of heat<br />
exchangers (i.e. pipe diameter and number of coils), and<br />
ii. a thermostat should be provided which switches off the heat when the required storage<br />
temperature has been achieved, and which in the case of hot water central heating systems<br />
is interconnected with the room thermostat(s) to switch off the boiler when no heat is<br />
required, and<br />
iii. a manually adjustable 7-day automatic timing device should be provided either as part of<br />
the central heating system or as a local device to control the periods of operation; or<br />
b. for a solid fuel fired system where the cylinder is not providing the slumber load, a thermostatically<br />
controlled valve should be provided.<br />
INSULATION OF PIPES, DUCTS AND VESSELS<br />
(J6.3) The requirements of J6.3 and J6.4 will be met by providing insulation in accordance with BS 5422:<br />
(J6.4) 1990 to all pipes, ducts and storage vessels. The requirement for storage vessels will be met by applying<br />
insulation in accordance with the provisions of BS 5422 for flat surfaces.<br />
Amdt: September 2001<br />
J
J<br />
(J8.5) – (J8.7)<br />
BUILDINGS OTHER THAN DWELLINGS<br />
HEAT LOSS METHOD<br />
(J8.5) The requirements of J8.5, for showing by calculation compliance with the Heat Loss Method, will be<br />
met by following the procedure set out below -<br />
a. calculate the total rate of heat loss for the proposed building in accordance with the table to this<br />
standard;<br />
b. repeat the calculation for a notional building in accordance with the table to this standard but<br />
using the values given in the Tables to J8.3 and J8.4 and applying the rules in J8.7;<br />
c. the proposed building will comply with Part J if the total rate of heat loss is no greater than that<br />
for the notional building.<br />
Table to (J8.5): Calculated total rate of heat loss through the enclosing fabric<br />
Element Gross Area Openings Net Area U-value Area x<br />
(m2 ) (m2 ) (m2 ) (W/m2K) U-value<br />
exposed walls ________ - ________ = ________ x ________ = ________<br />
exposed floors ________ - ________ = ________ x ________ = ________<br />
roofs ________ - ________ = ________ x ________ = ________<br />
Amdt: September 2001<br />
24J<br />
TOTAL A = ________<br />
windows ________ x ________ = ________<br />
personnel doors ________ x ________ = ________<br />
vehicle and similar large access doors ________ x ________ = ________<br />
Note:<br />
For example calculations see Appendix H.<br />
CARBON EMISSIONS CALCULATION METHOD<br />
TOTAL B = ________<br />
TOTAL RATE OF HEAT LOSS (TOTAL A + TOTAL B) =<br />
(J8.7) The requirements of J8.7 will be met by using a calculation procedure that -<br />
a. has been tested satisfactorily against available benchmark tests as described in CIBSE Application<br />
Manual “Building Energy and Environmental Modelling”, AM11, 1998; and<br />
b. has been accepted by the submitting organisation as having satisfied their in-house quality assurance<br />
procedures, for example by submitting with the calculations a completed and signed copy of<br />
Appendix B to AM11: “Checklist for choosing BEEM software”, showing that the software used<br />
is appropriate for the purpose to which it has been applied.
LIMITING THERMAL BRIDGING AT JUNCTIONS AND AROUND OPENINGS<br />
25J<br />
(J9.1) – (J11.1)<br />
(J9.1) The requirements of J9.1, as regards minimising thermal bridges and gaps in the insulation, will be met<br />
by -<br />
a. constructing the building in accordance with Building Research Establishment (BRE) Report, BR<br />
262: “Thermal insulation, Avoiding risks”, Second Edition, 1994 or<br />
b. demonstrating by calculation that equivalent performance to (J9.1)a. has been achieved,.<br />
LIMITING INFILTRATION<br />
(J10.1)The requirements of J10.1 will be met by constructing the building in accordance with BRE Report BR<br />
265 [Note 1].<br />
Note 1:<br />
This document provides examples of acceptable design details and construction practice, but alternative<br />
details may be used if equivalent performance can be demonstrated.<br />
HEATING SYSTEM EFFICIENCY<br />
(J11.1)The requirements of J11.1, as regards the efficiency of the boiler or other primary heat source, will be<br />
met -<br />
a. where the rating-weighted average carbon intensity of the boiler or other primary heat source is<br />
in accordance with Table 1 to this standard; or<br />
b. in the case of a liquid or gaseous fuelled boiler only, by compliance with the Boiler Efficiency<br />
Regulations 1993 and 1994.<br />
Table 1 to (J11.1): Maximum carbon intensities of heating systems<br />
Fuel Maximum carbon intensities (kgC/kWh) [Notes 1-3]<br />
at design capacity at 30% of design capacity<br />
Mains natural gas 0.068 0.064<br />
Other fuels 0.088 0.088<br />
Notes :<br />
1. The carbon intensity of the heating plant is based on the carbon emitted per useful kWh of heat<br />
output and applies to boilers, heat pump systems and electrical heating, and is given by-<br />
A = B ÷ C (Equation 1)<br />
where A is the carbon intensity of the heating system (kgC/kWh of useful heat);<br />
B is the carbon emission factor of the fuel (kgC/kWh of delivered fuel) obtained from<br />
Table 2 to this specification;<br />
C is the gross thermal efficiency of the heating system (kWh of heat divided by kWh<br />
of delivered fuel).<br />
Amdt: September 2001<br />
J
J<br />
(J11.1) – (J11.5)<br />
Table 2 to (J11.1): Carbon emission factors<br />
Fuel type Carbon emission factor (kgC/kWh)<br />
Mains natural gas 0.053<br />
LPG 0.068<br />
Biogas 0.0<br />
Oil (all grades of fuel oil) 0.074<br />
Coal 0.086<br />
Biomass 0.0<br />
Electricity (grid-supplied) 0.113<br />
2. Where a combined heat and power system (CHP) is proposed, the carbon intensity of the CHP<br />
can take account of the benefit of the on-site generation in reducing emissions from power stations<br />
feeding the national grid by using the following equation;<br />
Amdt: September 2001<br />
A = (B ÷ D) - (F ÷ E) (Equation 2)<br />
where A is the carbon intensity of the heating system (kgC/kWh of useful heat);<br />
B is the carbon emission factor of the fuel (kgC/kWh of delivered fuel) obtained from<br />
Table 2 to this specification;<br />
D is the heat output ratio of the CHP engine (kWh of heat per kWh of delivered fuel);<br />
E is the electrical output ratio of the engine (kWh of electricity per kWh of delivered<br />
fuel);<br />
F is the carbon emission factor for grid supplied electricity (kgC/kWh). This should<br />
be taken as the factor for new generating capacity that might otherwise be built if<br />
the CHP had not been provided, i.e. the intensity of a new generation gas-fired<br />
station at 0.123 kg/kWh<br />
This adjusted carbon intensity can then be used in equation 1 to determine the carbon intensity of the<br />
overall heating system at 100% and 30% of heating system output.<br />
3. Where the CHP has no facility for heat dumping, the gross thermal efficiency is the CHP heat<br />
output divided by the energy content of the fuel burned. Where the CHP includes facilities for<br />
heat dumping, the gross thermal efficiency should be based on an estimate of the useful heat<br />
supplied to the building, i.e. the heat output from the CHP minus the heat dumped.<br />
SPACE HEATING CONTROLS<br />
(J11.3)The requirements of J11.3 will be met for small buildings (i.e. those with heating systems with an output<br />
not greater than 100 kW), where the space heating controls are in accordance with BRECSU Good<br />
Practice Guide GPG 132.<br />
HOT WATER SERVICE SYSTEM CONTROLS<br />
(J11.5)The requirements of J11.5 will be met by complying with sub-clauses a. or b. below -<br />
a. for a system other than one heated by a solid fuel boiler -<br />
i. the heat exchanger in the storage vessel should have sufficient heating capacity, such as<br />
one complying with BS 1566: Part 2: 1984 (1990) or BS 3198: 1981, and in particular it<br />
should comply with the requirements in these standards for the surface area of heat<br />
exchangers (i.e. pipe diameter and number of coils), and<br />
26J
27J<br />
(J11.5) – (J12.1)<br />
ii. a thermostat should be provided which switches off the heat when the required storage<br />
temperature has been achieved, and which in the case of hot water central heating systems<br />
is interconnected with the room thermostat(s) to switch off the boiler when no heat is<br />
required, and<br />
iii. a manually adjustable 7-day automatic timing device or devices should be provided either<br />
as part of the central heating system or as a local device to control the periods of operation;<br />
or<br />
b. for a solid fuel fired system where the cylinder is not providing the slumber load, a thermostatically<br />
controlled valve should be provided.<br />
INSULATION OF PIPES, DUCTS AND VESSELS<br />
(J11.6)The requirements of J11.6, for insulation of pipes and ducts, will be met by providing insulation in<br />
accordance with BS 5422: 1990.<br />
(J11.7)The requirements of J11.7 for insulation of hot water storage vessels will be met by applying insulation<br />
in accordance with the provisions of BS 5422: 1990 for flat surfaces.<br />
ARTIFICIAL LIGHTING<br />
(J12.1)The requirements of J12.1 will be met where the artificial lighting complies with a., b., or c. below -<br />
a. 95% of the artificial lighting capacity in circuit Watts (i.e. the power consumed by lamps, their<br />
associated control gear and power factor correction equipment) is provided by lighting fittings<br />
using lamps with luminous efficacies not less than those of the types listed in the table to this<br />
specification -<br />
Table to (J12.1)a. Artificial lighting<br />
Light Source Types<br />
High pressure sodium All types and sizes.<br />
Metal halide All types and sizes.<br />
Induction lighting All types and sizes.<br />
Triphosphor tubular fluorescent All 26mm diameter (T8) lamps, and 16mm diameter (T5)<br />
lamps rated above 11 W, provided with low-loss or high<br />
frequency control gear; 38mm diameter (T12) linear fluorescent<br />
lamps 2400 mm long.<br />
Compact fluorescent All ratings above 11 W.<br />
Other Any type and rating with an efficiency greater than 65 lumens<br />
per circuit Watt.<br />
b. the installed lighting capacity comprises lighting fittings with lamps having an average initial<br />
(100 hour) efficacy of not less than 65 lumens per circuit Watt.<br />
c. the lighting is in accordance with Part 4 of the CIBSE publication “Code for Interior Lighting”,<br />
1994.<br />
Amdt: September 2001<br />
J
J<br />
(J12.2) – (J12.3)<br />
DISPLAY LIGHTING<br />
(J12.2)The requirements of J12.2 will be met by display lighting -<br />
a. whose installed capacity comprises lighting fittings incorporating lamps with an average initial<br />
(100 hour) efficacy of not less than 15 lumens per circuit Watt; or<br />
b. at least 95% of whose installed capacity in circuit Watts (i.e. the power consumed by lamps, their<br />
associated control gear and power factor correction equipment) is provided by lighting fittings<br />
using lamps with luminous efficacies not less than those of the types listed in the table to this<br />
specification -<br />
Table to (J12.2)b. Display lighting<br />
Light Source Types and ratings<br />
High pressure sodium All types and ratings.<br />
Metal halide All types and ratings.<br />
Tungsten halogen All types and ratings.<br />
Compact and tubular fluorescent All types and ratings.<br />
Other Any type and rating with an efficacy greater than 15 lumens<br />
per circuit Watt.<br />
CONTROLS FOR ARTIFICIAL LIGHTING<br />
(J12.3)The requirements of J12.3 will be met by an artificial lighting system having -<br />
a. local manually operated switches where the distance measured directly on plan from a switch to<br />
the furthest light fitting it controls is not more than 8 metres or 3 times the height of the light<br />
fitting above the finished floor level, whichever is the greater; or<br />
b. lighting rows adjacent to windows controlled by photocells to monitor daylight and adjust the<br />
artificial lighting accordingly, either by switching or dimming; or<br />
c. switches operated by ultrasonic, infra-red or other remote control handsets; or<br />
d. automatic switching which turns the lighting off when it senses the absence of occupants; or<br />
e. in buildings of purpose groups 4 to 6, in areas where continuous lighting is required during hours<br />
of operation, time switching or daylight-linked photo-electric switching; or<br />
f. switching in accordance with Section 4.4.4 of the CIBSE publication “Code for Interior Lighting”,<br />
1994; or<br />
g. for display lighting, dedicated circuits that can be switched off at times when people will not be<br />
inspecting exhibits or merchandise or being entertained [Note 1].<br />
Note:<br />
1. In a retail store, for example, (J12.3)g. could be achieved by timers to switch off the display<br />
lighting outwith opening hours, other than for displays intended to be viewed from outside the<br />
building).<br />
Amdt: September 2001<br />
28J
AIR CONDITIONING AND MECHANICAL VENTILATION<br />
29J<br />
(J13.1) – (J14.2)<br />
(J13.1)The requirements of J13.1, for energy efficiency of air conditioning and mechanical ventilation, will be<br />
met -<br />
a. for buildings of purpose group 3, by achieving a Carbon Performance Index [Note 1] of at least<br />
100, or in the case of a conversion, at least 90; or<br />
b. for buildings of purpose groups 2 and 4 to 7, by providing air conditioning or mechanical ventilation<br />
with a total specific fan power (i.e. the design power of all fans in the distribution system<br />
divided by the design ventilation rate through the building) not greater than 1.5 W/ls -1 .<br />
Notes:<br />
1. The Carbon Performance Index (CPI) relates the performance of the proposed building to a<br />
benchmark based on the measured consumption data contained in ECON 19 [“Energy use in<br />
offices - Energy Consumption Guide 19”, DETR, 1998].<br />
2. The CPI calculation procedure is described in Appendix K.<br />
COMMISSIONING OF THE BUILDING SERVICES<br />
(J14.1)The requirements of J14.1, as regards the commissioning of the building services, will be met by certifying<br />
that commissioning of the installation has been done in accordance with CIBSE Commissioning<br />
Codes and BSRIA Commissioning Guides.<br />
(J14.2)The requirements of J14.2, as regards the provision of information for energy efficient operation, will be<br />
met by a self-contained building log-book containing the following details -<br />
a. a schedule of the floor areas of each of the building zones categorised by environmental servicing<br />
type (e.g. air-conditioned, naturally ventilated); and<br />
b. the purpose of the individual building services systems; and<br />
c. the location of the relevant plant and equipment; and<br />
d. the installed capacities (input power and output rating) of the services plant; and<br />
e. simple descriptions of the operational and control strategies of the energy consuming services in<br />
the building; and<br />
f. operating and maintenance instructions that include provisions enabling the specified performance<br />
to be sustained during occupation.<br />
Amdt: September 2001<br />
J
J Appendix A<br />
Appendix A: Tables of U–values<br />
Contents<br />
TABLES Page<br />
Windows, rooflights and doors<br />
Table A1 U-values for windows (and rooflights) with wooden frames and doors 4JA<br />
Table A2 U-values for windows with metal frames (4 mm thermal break) 5JA<br />
Table A3 Adjustments to Table A2 for various thermal breaks and/or rooflights 5JA<br />
Roofs<br />
Table A4 Base thickness of insulation between ceiling joists or rafters 6JA<br />
Table A5 Base thickness of insulation between and over joists or rafters 6JA<br />
Table A6 Base thickness for continuous insulation 6JA<br />
Table A7 Allowable reductions in thickness for common roof components 7JA<br />
Walls<br />
Table A8 Base thickness of insulation layer 9JA<br />
Table A9 Allowable reductions in base thickness for common components 10JA<br />
Table A10 Allowable reductions in base thickness for concrete components 10JA<br />
Table A11 Allowable reductions in base thickness for timber frame walls 11JA<br />
Ground floors<br />
Table A12 Insulation thickness for solid floors in contact with the ground 16JA<br />
Table A13 Insulation thickness for suspended timber ground floors 17JA<br />
Table A14 Insulation thickness for suspended concrete beam and block ground floors 18JA<br />
Upper floors<br />
Table A15 Upper floors of timber construction 20JA<br />
Table A16 Upper floors of concrete construction 20JA<br />
Table A17 Upper floors - allowable reductions in base thickness for common components 20JA<br />
Building materials<br />
Table A18 Thermal conductivity of some common building materials 21JA<br />
Notes:<br />
1. The values in these tables have been derived using the Combined Method, taking into account the effects<br />
of thermal bridging where appropriate.<br />
2. Intermediate values can be obtained from the tables by linear interpolation.<br />
3. As an alternative to using these tables, the procedures in Appendices B and C can be used to obtain a<br />
more accurate calculation of the thickness of insulation required.<br />
Amdt: September 2001<br />
1JA
2JA<br />
Appendix A<br />
EXAMPLE CALCULATIONS Page<br />
Roofs<br />
Example 1 Pitched roof with insulation between ceiling joists or between rafters 8JA<br />
Example 2 Pitched roof with insulation between and over ceiling joists 9JA<br />
Example 3 Concrete deck roof 9JA<br />
Walls<br />
Example 4 Masonry cavity wall with internal insulation 12JA<br />
Example 5 Masonry cavity wall filled with insulation 13JA<br />
Example 6 Masonry wall with partial cavity fill 14JA<br />
Example 7 Timber frame wall 15JA<br />
Ground floors<br />
Example 8 Solid floor in contact with the ground 19JA<br />
Example 9 Suspended timber floor 19JA<br />
Amdt: September 2001<br />
J
J<br />
Appendix A<br />
Windows, rooflights and doors<br />
A1 Full details about calculating the U-value of a window or door are given in BS EN ISO 10077–1. This<br />
Appendix provides indicative U-values for windows, rooflights and doors. Table A1 applies to windows<br />
(and rooflights) with wood or PVC-U frames. Table A2 applies to windows with metal frames, for<br />
which the adjustments (for thermal breaks and/or rooflights) in Table A3 should be applied.<br />
A2 The U-value of a window or rooflight containing low-E glazing is influenced by the emissivity, εn, of<br />
the low-E coating. Low-E coatings are of two principal types, known as ‘hard’ and ‘soft’. Hard coatings<br />
generally have emissivities in the range 0.15 to 0.2, and the data for εn = 0.2 should be used for hard<br />
coatings, or if the glazing is stated to be low-E but the type of coating is not specified. Soft coatings<br />
generally have emissivities in the range 0.05 to 0.1. The data for εn = 0.1 should be used for a soft<br />
coating if the emissivity is not specified.<br />
A3 When available, manufacturers’ U-values, certified by a notified body, for windows, or rooflights or<br />
doors must be used in preference to the data given in these tables.<br />
Amdt: September 2001<br />
3JA
4JA<br />
Appendix A<br />
Table A1: Indicative U-values (W/m 2 K) for windows, rooflights and doors with wood or PVC-U frames<br />
[Note 1]<br />
Gap between panes Adjustment for<br />
6 mm 12 mm 16 mm rooflights in<br />
or more dwellings [Note 4]<br />
Single glazing 4.8 + 0.3<br />
Double glazing (air filled) 3.1 2.8 2.7<br />
Double glazing (low-E, εn = 0.2) [Note 2] 2.7 2.3 2.1<br />
Double glazing ((low-E, εn = 0.15) 2.7 2.2 2.0<br />
Double glazing (low-E, εn = 0.1) 2.6 2.1 1.9<br />
Double glazing (low-E, εn = 0.05) 2.6 2.0 1.8<br />
Double glazing (argon filled) [Note 3] 2.9 2.7 2.6<br />
Double glazing (low-E, εn = 0.2, argon filled) 2.5 2.1 2.0<br />
Double glazing (low-E, εn = 0.1, argon filled) 2.3 1.9 1.8<br />
Double glazing (low-E, εn = 0.05, argon filled) 2.3 1.8 1.7<br />
Triple glazing 2.4 2.1 2.0 + 0.2<br />
Triple glazing (low-E, εn = 0.2) 2.1 1.7 1.6<br />
Triple glazing (low-E, εn = 0.1) 2.0 1.6 1.5<br />
Triple glazing (low-E, εn = 0.05) 2.0 1.5 1.4<br />
Triple glazing (argon filled) 2.2 2.0 1.9<br />
Triple glazing (low-E, εn = 0.2, argon filled) 1.9 1.6 1.5<br />
Triple glazing (low-E, εn = 0.1, argon filled) 1.8 1.4 1.3<br />
Triple glazing (low-E, εn = 0.05, argon filled) 1.7 1.4 1.3<br />
Solid wooden door [Note 5] 3.0 N/A<br />
Notes:<br />
1. The U-values in this table are based on the frame comprising 30% of the total window area.<br />
2. The emissivities quoted are normal emissivities. (Corrected emissivity is used in the calculation<br />
of glazing U-values.) Uncoated glass is assumed to have a normal emissivity of 0.89.<br />
3. The gas mixture is assumed to consist of 90% argon and 10% air.<br />
4. No adjustment need be applied to rooflights in buildings other than dwellings.<br />
5. For doors which are half-glazed the U-value of the door is the average of the appropriate window<br />
U-value and that of the non-glazed part of the door (e.g. 3.0 W/m 2 K for a wooden door).<br />
Amdt: September 2001<br />
J
J<br />
Appendix A<br />
Table A2: Indicative U-values (W/m2K) for windows with metal frames (4 mm thermal break)<br />
gap between panes<br />
6 mm 12 mm 16 mm or<br />
more<br />
Single glazing 5.7<br />
Double glazing (air filled) 3.7 3.4 3.3<br />
Double glazing (low-E, εn = 0.2) 3.3 2.8 2.6<br />
Double glazing (low-E, εn = 0.1) 3.2 2.6 2.5<br />
Double glazing (low-E, εn = 0.05) 3.1 2.5 2.3<br />
Double glazing (argon filled) 3.5 3.3 3.2<br />
Double glazing (low-E, εn = 0.2,argon filled) 3.1 2.6 2.5<br />
Double glazing (low-E, εn = 0.1, argon filled) 2.9 2.4 2.3<br />
Double glazing (low-E, εn = 0.05, argon filled) 2.8 2.3 2.1<br />
Triple glazing 2.9 2.6 2.5<br />
Triple glazing (low-E, εn = 0.2) 2.6 2.2 2.0<br />
Triple glazing (low-E, εn = 0.1) 2.5 2.0 1.9<br />
Triple glazing (low-E, εn = 0.05) 2.4 1.9 1.8<br />
Triple glazing (argon-filled) 2.8 2.5 2.4<br />
Triple glazing (low-E, εn = 0.2, argon filled) 2.4 2.0 1.9<br />
Triple glazing (low-E, εn = 0.1, argon filled) 2.2 1.9 1.8<br />
Triple glazing (low-E, εn = 0.05, argon filled) 2.2 1.8 1.7<br />
Note:<br />
The U-values in this table are based on the frame comprising 20% of the total window area.<br />
A4 For windows (or rooflights) with metal frames incorporating a thermal break other than 4 mm, the<br />
adjustments given in Table 3 should be made to the U-values given in Table A2.<br />
Table A3: Adjustments to U–values in Table A2 for frames with thermal breaks<br />
Thermal break (mm) Adjustment to U-value (W/m2K) Window, or rooflight in a Roof window<br />
building other than a in a dwelling<br />
dwelling [Note 1]<br />
0 (no break) + 0.3 + 0.7<br />
4 + 0.0 + 0.3<br />
8 - 0.1 + 0.2<br />
12 - 0.2 + 0.1<br />
16 - 0.2 + 0.1<br />
Notes:<br />
1. Where applicable, adjustments for both thermal break and rooflight should be made. For intermediate<br />
thicknesses of thermal breaks, linear interpolation may be used.<br />
Amdt: September 2001<br />
5JA
ROOFS<br />
6JA<br />
Appendix A<br />
Table A4: Base thickness of insulation between ceiling joists or rafters<br />
Thermal conductivity of insulant (W/m·K)<br />
Design U-value 0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
(W/m 2 K) Base thickness of insulating material (mm)<br />
A B C D E F G H<br />
1 0.15 371 464 557 649 742 835 928<br />
2 0.20 180 224 269 314 359 404 449<br />
3 0.25 118 148 178 207 237 266 296<br />
4 0.30 92 110 132 154 176 198 220<br />
5 0.35 77 91 105 122 140 157 175<br />
6 0.40 67 78 90 101 116 130 145<br />
Table A5: Base thickness of insulation between and over joists or rafters<br />
Thermal conductivity of insulant (W/m·K)<br />
Design U-value 0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
(W/m 2 K) Base thickness of insulating material (mm)<br />
A B C D E F G H<br />
1 0.15 161 188 217 247 277 307 338<br />
2 0.20 128 147 167 188 210 232 255<br />
3 0.25 108 122 137 153 170 187 205<br />
4 0.30 92 105 117 130 143 157 172<br />
5 0.35 77 91 103 113 124 136 148<br />
6<br />
Note:<br />
0.40 67 78 90 101 110 120 130<br />
Tables A4 and A5 are derived for roofs with the proportion of timber at 8%, corresponding to 48 mm<br />
wide timbers at 600 mm centres, excluding noggings. For other proportions of timber the U-value can<br />
be calculated using the procedure in Appendix B.<br />
Table A6: Base thickness for continuous insulation<br />
Thermal conductivity of insulant (W/m·K)<br />
Design U-value 0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
(W/m 2 K) Base thickness of insulating material (mm)<br />
A B C D E F G H<br />
1 0.15 131 163 196 228 261 294 326<br />
2 0.20 97 122 146 170 194 219 243<br />
3 0.25 77 97 116 135 154 174 193<br />
4 0.30 64 80 96 112 128 144 160<br />
5 0.35 54 68 82 95 109 122 136<br />
6 0.40 47 59 71 83 94 106 118<br />
Amdt: September 2001<br />
J
J<br />
Appendix A<br />
Table A7 Allowable reductions in thickness for common roof components<br />
Thermal conductivity of insulant (W/m·K)<br />
0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
Amdt: September 2001<br />
Concrete slab Reduction in base thickness of insulating material (mm) for<br />
density (Kg/m 2 ) each 100 mm of concrete slab<br />
A B C D E F G H<br />
1 600 10 13 15 18 20 23 25<br />
2 800 7 9 11 13 14 16 18<br />
3 1100 5 6 8 9 10 11 13<br />
4 1300 4 5 6 7 8 9 10<br />
5 1700 2 2 3 3 4 4 5<br />
6 2100 1 2 2 2 3 3 3<br />
Other materials<br />
and components<br />
Reduction in base thickness of insulating material (mm)<br />
A B C D E F G H<br />
7 10 mm plasterboard 1 2 2 2 3 3 3<br />
8 13 mm plasterboard 2 2 2 3 3 4 4<br />
9 13 mm sarking board 2 2 3 3 4 4 5<br />
10 12 mm calcium<br />
silicate liner board<br />
1 2 2 2 3 3 4<br />
11 Roof space (pitched) 4 5 6 7 8 9 10<br />
12 Roof space (flat) 3 4 5 6 6 7 8<br />
13 19 mm roof tiles 0 1 1 1 1 1 1<br />
14 19 mm asphalt<br />
(or 3 layers of felt)<br />
1 1 1 1 2 2 2<br />
15 50 mm screed 2 3 4 4 5 5 6<br />
Example 1 - Pitched roof with insulation between ceiling joists or between rafters<br />
Determine the thickness of the insulation layer required to achieve a U-value of 0.20 W/m 2 K if insulation is<br />
between the joists, and 0.25 W/m 2 K if insulation is between the rafters.<br />
For insulation placed between ceiling joists (U-value 0.20 W/m 2 K)<br />
Using Table A4:<br />
joist<br />
insulation<br />
(thermal conductivity<br />
0.030 W/mK)<br />
From column D, row 2 of the table, the base thickness of insulation required is 269 mm.<br />
The base thickness may be reduced by taking account of the other materials as follows:<br />
From Table A7:<br />
7JA<br />
10mm plasterboard
19 mm roof tiles column D, row 13= 1 mm<br />
Roof space (pitched) column D, row 11= 6 mm<br />
10 mm plasterboard column D, row 7 = 2 mm<br />
Total reduction = 9 mm<br />
8JA<br />
Appendix A<br />
The minimum thickness of the insulation layer between the ceiling joists required to achieve a U-value of<br />
0.20 W/m 2 K is therefore:<br />
Base thickness less total reduction i.e. 269 – 9 = 260 mm.<br />
For insulation placed between rafters (U-value 0.25 W/m 2 K)<br />
Using Table A4:<br />
rafter<br />
10mm plasterboard<br />
From column D, row 3 in the table, the base thickness of insulation required is 178 mm.<br />
The reductions in the base thickness are obtained as follows:<br />
From Table A7:<br />
19 mm roof tiles column D, row 13= 1 mm<br />
10 mm plasterboard column D, row 7 = 2 mm<br />
Total reduction = 3 mm<br />
The minimum thickness of the insulation layer between the rafters required to achieve a U-value of<br />
0.25 W/m 2 K is therefore:<br />
Base thickness less total reduction i.e.178 - 3 = 175 mm.<br />
Example 2 - Pitched roof with insulation between and over ceiling joists<br />
Determine the thickness of the insulation layer above the joists required to achieve a U-value of 0.20 W/m 2 K<br />
for the roof construction shown below:<br />
insulation over joists<br />
100mm deep joist ;;;;<br />
insulation between joists<br />
;;;;;;;<br />
; ;;;;;;; ;;<br />
; ;;;; ;;<br />
10mm plasterboard<br />
insulation<br />
thermal conductivity 0.030 W/mK<br />
It is proposed to use mineral fibre insulation between and over the joists with a thermal conductivity of<br />
0.04 W/m·K. Using Table A5:<br />
From column F, row 2 of the table, the base thickness of insulation layer is 210 mm.<br />
Amdt: September 2001<br />
J
J<br />
Appendix A<br />
The base thickness may be reduced by taking account of the other materials as follows:<br />
From Table A7:<br />
19 mm roof tiles column F, row 13 = 1 mm<br />
Roof space (pitched) column F, row 11 = 8 mm<br />
10 mm plasterboard column F, row 7 = 3 mm<br />
Total reduction = 12 mm<br />
The minimum thickness of the insulation layer over the joists, required in addition to the 100 mm insulation<br />
between the joists, to achieve a U-value of 0.20 W/m 2 K is therefore:<br />
Base thickness less total reduction i.e. 210 - 1OO - 12 = 98 mm.<br />
Example 3- Concrete deck roof<br />
Determine the thickness of the insulation layer required to achieve a U-value of 0.25 W/m 2 K for the roof construction<br />
shown below.<br />
Using Table A6:<br />
From column D, row 3 of the table, the base thickness of the insulation layer is 116 mm.<br />
The base thickness may be reduced by taking account of the other materials as follows:<br />
From Table A7:<br />
3 layers of felt column D, row 14= 1 mm<br />
150 mm concrete deck column D, row 3<br />
adjusted for 150 mm thickness (1.5 × 8) = 12 mm<br />
Total reduction = 13 mm<br />
The minimum thickness of the insulation layer required to achieve a U-value of 0.25 W/m 2 K is therefore:<br />
Base thickness less total reduction i.e. 116 - 13 = 103 mm.<br />
Walls<br />
three layers of roofing felt<br />
insulation (thermal conductivity 0.03 W/m.K)<br />
150mm concrete (density 1100kg/m 3 )<br />
Table A8 Base thickness of insulation layer<br />
Thermal conductivity of insulant (W/m·K)<br />
Design U-value 0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
(W/m 2 K) Base thickness of insulating material (mm)<br />
A B C D E F G H<br />
1 0.20 97 121 145 169 193 217 242<br />
2 0.25 77 96 115 134 153 172 192<br />
3 0.30 63 79 95 111 127 142 158<br />
4 0.35 54 67 81 94 107 121 134<br />
5 0.40 47 58 70 82 93 105 117<br />
6 0.45 41 51 62 72 82 92 103<br />
Amdt: September 2001<br />
9JA
10JA<br />
Appendix A<br />
Table A9 Allowable reductions in base thickness for common components<br />
Thermal conductivity of insulant (W/m·K)<br />
0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
Component Reduction in base thickness of insulating material (mm)<br />
A B C D E F G H<br />
1 Cavity (25 mm or more) 4 5 5 6 7 8 9<br />
2 Outer leaf brick 3 3 4 5 5 6 6<br />
3 13 mm plaster 1 1 1 1 1 1 1<br />
4 13 mm lightweight<br />
plaster<br />
2 2 2 3 3 4 4<br />
5 9.5 mm plasterboard 1 2 2 2 3 3 3<br />
6 12.5 mm plasterboard 2 2 2 3 3 4 4<br />
7 Air space behind<br />
plasterboard dry lining<br />
2 3 4 4 5 5 6<br />
8 9 mm sheathing ply 1 2 2 2 3 3 3<br />
9 20 mm cement render 1 1 1 1 2 2 2<br />
10 13 mm tile hanging 0 0 0 1 1 1 1<br />
Table A10 Allowable reductions in base thickness for concrete components<br />
Thermal conductivity of insulant (W/m·K)<br />
0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
Density Reduction in base thickness of insulation (mm)<br />
(Kg/m2 ) for each 100 mm of concrete<br />
A<br />
Concrete inner leaf<br />
B C D E F G H<br />
1 600 9 11 13 15 17 20 22<br />
2 800 7 9 10 12 14 16 17<br />
3 1000 5 6 8 9 10 11 13<br />
4 1200 4 5 6 7 8 9 10<br />
5 1400 3 4 5 6 7 8 8<br />
6 1600 3 3 4 5 6 6 7<br />
7 1800 2 2 3 3 4 4 4<br />
8 2000 2 2 2 3 3 3 4<br />
9 2400 1 1 2 2 2 2 3<br />
Continued overleaf<br />
Amdt: September 2001<br />
J
J<br />
Appendix A<br />
Table A10 continued<br />
Amdt: September 2001<br />
Thermal conductivity of insulant (W/m·K)<br />
0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
Density Reduction in base thickness of insulation (mm)<br />
(Kg/m2 ) for each 100 mm of concrete<br />
A B C D E F G H<br />
Concrete outer leaf or single leaf wall<br />
10 600 8 11 13 15 17 19 21<br />
11 800 7 9 10 12 14 15 17<br />
12 1000 5 6 7 8 10 11 12<br />
13 1200 4 5 6 7 8 9 10<br />
14 1400 3 4 5 6 6 7 8<br />
15 1600 3 3 4 5 5 6 7<br />
16 1800 2 2 3 3 3 4 4<br />
17 2000 1 2 2 3 3 3 4<br />
18 2400 1 1 2 2 2 2 3<br />
Table A11 Allowable reductions in base thickness for insulated timber framed walls<br />
Thermal conductivity of insulant (W/m·K)<br />
0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
Thermal conductivity of Reduction in base thickness of insulation (mm)<br />
insulation within frame (W/m·K) for each 100 mm of frame(mm)<br />
A B C D E F G H<br />
1 0.035 42 53 63 74 84 95 105<br />
2 0.040 38 48 58 67 77 87 96<br />
Note:<br />
The table is derived for walls for which the proportion of timber is 12%, which corresponds to 48 mm<br />
wide studs at 400 mm centres. For other proportions of timber the U-value can be calculated using the<br />
procedure in Appendix B.<br />
11JA
Example 4 - Masonry cavity wall with internal insulation<br />
12JA<br />
Appendix A<br />
(For buildings other than detached buildings, this construction might not provide adequate resistance to flanking<br />
sound transmission)<br />
Determine the thickness of the insulation layer required to achieve a U-value of 0.35 W/m2K for the wall construction<br />
shown below.<br />
Using Table A8:<br />
From column C, row 4 of the table, the base thickness of the insulation layer is 67 mm.<br />
The base thickness may be reduced by taking account of the other materials as follows:<br />
From Table A9:<br />
Brick outer leaf column C, row 2 = 3 mm<br />
Cavity column C, row 1 = 5 mm<br />
Plasterboard column C, row 6 = 2 mm<br />
And from table A10<br />
;;<br />
;;<br />
;;<br />
;;<br />
;;<br />
;;<br />
;;<br />
102mm brick outer leaf<br />
50mm cavity<br />
;;<br />
;; ;<br />
;; ;; ;<br />
;; ;<br />
;; ;<br />
Concrete block column C, row 1<br />
adjusted for 150 mm block<br />
thickness (1.5 × 11) = 17 mm<br />
Total reduction = 27 mm<br />
The minimum thickness of the insulation layer required to achieve a U-value of 0.35 W/m 2 K is therefore:<br />
Base thickness less total reduction i.e. 67 – 27 = 40 mm<br />
150mm concrete block (density 600 kg/m 3 )<br />
thermal insulation (thermal conductivity 0.025 W/mK)<br />
13mm plasterboard<br />
heat flow<br />
Amdt: September 2001<br />
J
J<br />
Appendix A<br />
Example 5 - Masonry cavity wall filled with insulation with plasterboard on dabs<br />
Determine the thickness of the insulation layer required to achieve a U-value of 0.35 W/m 2 K for the wall construction<br />
shown below. (This calculation assumes the effect of wall ties to be negligible).<br />
Using Table A8:<br />
From column F, row 4 of the table, the base thickness of the insulation layer is 107 mm.<br />
The base thickness may be reduced by taking account of the other materials as follows:<br />
From Table A9:<br />
Brick outer leaf column F, row 2 = 5 mm<br />
Plasterboard column F, row 6 = 3 mm<br />
Air space behind plasterboard<br />
column F, row 7 = 5 mm<br />
And from Table A10:<br />
Amdt: September 2001<br />
102mm brick outer leaf<br />
Concrete block column F, row 8 = 3 mm<br />
Total reduction = 16 mm<br />
The minimum thickness of the insulation layer required to achieve a U-value of 0.35 W/m 2 K is therefore:<br />
Base thickness less total reduction i.e. 107 – 16 = 91 mm<br />
cavity filled with insulation (thermal conductivity 0.040 W/mK)<br />
100mm concrete block (density 2000 kg/m 3 )<br />
airspace between dabs<br />
12.5mm plasterboard on dabs<br />
13JA<br />
heat flow
Example 6 - Masonry wall with partial cavity-fill<br />
14JA<br />
Appendix A<br />
Determine the thickness of the insulation layer required to achieve a U-value of 0.30 W/m 2 K for the wall construction<br />
shown below.<br />
Using Table A8:<br />
From column C, row 3 of the table, the base thickness of the insulation layer is 79 mm.<br />
The base thickness may be reduced by taking account of the other materials as follows:<br />
From Table A9:<br />
Brick outer leaf column C, row 2 = 3 mm<br />
Cavity column C, row 1 = 5 mm<br />
Lightweight plaster column C, row 4 = 2 mm<br />
And from Table A10:<br />
102mm brick outer leaf<br />
50mm residual cavity<br />
Concrete block column C, row 5 = 4 mm<br />
Total reduction = 14 mm<br />
The minimum thickness of the insulation layer required to achieve a U-value of 0.30 W/m 2 K is therefore:<br />
Base thickness less total reduction i.e. 79 – 14 = 65 mm<br />
partial fill cavity insulation (thermal conductivity 0.025 W/mK)<br />
100mm lightweight aggregate block (density 1400 kg/m 3 )<br />
13mm lightweight plaster<br />
heat flow<br />
Amdt: September 2001<br />
J
J<br />
Appendix A<br />
Example 7 - Timber-frame wall<br />
Determine the thickness of the insulation layer required to achieve a U-value of 0.30 W/m 2 K for the wall construction<br />
shown below.<br />
Using Table A8:<br />
From column D, row 3 of the table, the base thickness of the insulation layer is 95 mm.<br />
The base thickness may be reduced by taking account of the other materials as follows:<br />
From Table A9:<br />
Brick outer leaf column D, row 2 = 4 mm<br />
Cavity column D, row 1 = 5 mm<br />
Sheathing ply column D, row 8 = 2 mm<br />
Plasterboard column D, row 6 = 2 mm<br />
Plasterboard column D, row 6 = 2 mm<br />
And from Table A11:<br />
Timber frame column D, row 1<br />
adjusted for shallower<br />
member (0.9 × 63 mm) = 57 mm<br />
Total reduction = 72 mm<br />
The minimum thickness of the insulation layer required to achieve a U-value of 0.30 W/m 2 K is therefore:<br />
Base thickness less total reduction i.e. 95 – 72 = 23 mm<br />
Amdt: September 2001<br />
102mm brick outer leaf<br />
50 mm cavity<br />
9 mm sheathing ply<br />
Insulation (thermal conductivity 0.03W/m K)<br />
90mm timber frame filled with insulation<br />
(thermal conductivity 0.035 W/m K)<br />
two sheets of 12.5mm plasterboard<br />
15JA<br />
heat flow
16JA<br />
Appendix A<br />
GROUND FLOORS<br />
Note:<br />
In using the tables for floors it is first necessary to calculate the ratio P/A, where P is the floor perimeter<br />
length in metres; and A is the floor area in square metres.<br />
Table A12 Insulation thickness for solid floors in contact with the ground<br />
Thermal conductivity of insulant (W/m·K)<br />
P/A 0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
A B C D E F G H<br />
Insulation thickness (mm) for U-value of 0.20 W/m2K 1 1.00 81 101 121 142 162 182 202<br />
2 0.90 80 100 120 140 160 180 200<br />
3 0.80 78 98 118 137 157 177 196<br />
4 0.70 77 96 115 134 153 173 192<br />
5 0.60 74 93 112 130 149 167 186<br />
6 0.50 71 89 107 125 143 160 178<br />
7 0.40 67 84 100 117 134 150 167<br />
8 0.30 60 74 89 104 119 134 149<br />
9 0.20 46 57 69 80 92 103 115<br />
U-value of 0.25 W/m2K 10 1.00 61 76 91 107 122 137 152<br />
11 0.90 60 75 90 105 120 135 150<br />
12 0.80 58 73 88 102 117 132 146<br />
13 0.70 57 71 85 99 113 128 142<br />
14 0.60 54 68 82 95 109 122 136<br />
15 0.50 51 64 77 90 103 115 128<br />
16 0.40 47 59 70 82 94 105 117<br />
17 0.30 40 49 59 69 79 89 99<br />
18 0.20 26 32 39 45 52 58 65<br />
U-value of 0.30 W/m2K 19 1.00 48 60 71 83 95 107 119<br />
20 0.90 47 58 70 81 93 105 116<br />
21 0.80 45 56 68 79 90 102 113<br />
22 0.70 43 54 65 76 87 98 108<br />
23 0.60 41 51 62 72 82 92 103<br />
24 0.50 38 47 57 66 76 85 95<br />
25 0.40 33 42 50 59 67 75 84<br />
26 0.30 26 33 39 46 53 59 66<br />
27 0.20 13 16 19 22 25 28 32<br />
Note:<br />
P/A is the ratio of floor perimeter (m) to floor area (m 2 ).<br />
Amdt: September 2001<br />
J
J<br />
Appendix A<br />
Table A13 Insulation thickness for timber ground floors<br />
Amdt: September 2001<br />
Thermal conductivity of insulant (W/m·K)<br />
P/A 0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
A B C D E F G H<br />
Insulation thickness (mm) for U-value of 0.20 W/m2K 1 1.00 127 145 164 182 200 218 236<br />
2 0.90 125 144 162 180 198 216 234<br />
3 0.80 123 142 160 178 195 213 230<br />
4 0.70 121 139 157 175 192 209 226<br />
5 0.60 118 136 153 171 188 204 221<br />
6 0.50 114 131 148 165 181 198 214<br />
7 0.40 109 125 141 157 173 188 204<br />
8 0.30 99 115 129 144 159 173 187<br />
9 0.20 82 95 107 120 132 144 156<br />
U-value of 0.25 W/m2K 10 1.00 93 107 121 135 149 162 176<br />
11 0.90 92 106 119 133 146 160 173<br />
12 0.80 90 104 117 131 144 157 170<br />
13 0.70 88 101 114 127 140 153 166<br />
14 0.60 85 98 111 123 136 148 161<br />
15 0.50 81 93 106 118 130 142 154<br />
16 0.40 75 87 99 110 121 132 143<br />
17 0.30 66 77 87 97 107 117 127<br />
18 0.20 49 57 65 73 81 88 96<br />
U-value of 0.30 W/m2K 19 1.00 71 82 93 104 114 125 135<br />
20 0.90 70 80 91 102 112 122 133<br />
21 0.80 68 78 89 99 109 119 129<br />
22 0.70 66 76 86 96 106 116 126<br />
23 0.60 63 73 82 92 102 111 120<br />
24 0.50 59 68 78 87 96 104 113<br />
25 0.40 53 62 70 79 87 95 103<br />
26 0.30 45 52 59 66 73 80 87<br />
27 0.20 28 33 38 42 47 51 56<br />
Notes:<br />
1. P/A is the ratio of floor perimeter (m) to floor area (m 2 ). The table is derived for suspended<br />
timber floors for which the proportion of timber is 12%, which corresponds to 48 mm wide<br />
timbers at 400 mm centres.<br />
2. For other proportions of timber the U-value can be calculated using the procedure in Appendix B.<br />
17JA
Table A14:Insulation thickness for suspended concrete beam and block ground floors<br />
Thermal conductivity of insulant (W/m·K)<br />
18JA<br />
Appendix A<br />
P/A 0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
A B C D E F G H<br />
Insulation thickness (mm) for U-value of 0.20 W/m2K 1 1.00 82 103 123 144 164 185 205<br />
2 0.90 81 101 122 142 162 183 203<br />
3 0.80 80 100 120 140 160 180 200<br />
4 0.70 79 99 118 138 158 177 197<br />
5 0.60 77 96 116 135 154 173 193<br />
6 0.50 75 93 112 131 150 168 187<br />
7 0.40 71 89 107 125 143 161 178<br />
8 0.30 66 82 99 115 132 148 165<br />
9 0.20 56 69 83 97 111 125 139<br />
U-value of 0.25 W/m2K 10 1.00 62 78 93 109 124 140 155<br />
11 0.90 61 76 92 107 122 138 153<br />
12 0.80 60 75 90 105 120 135 150<br />
13 0.70 59 74 88 103 118 132 147<br />
14 0.60 57 71 86 100 114 128 143<br />
15 0.50 55 68 82 96 110 123 137<br />
16 0.40 51 64 77 90 103 116 128<br />
17 0.30 46 57 69 80 92 103 115<br />
18 0.20 36 45 54 62 71 80 89<br />
U-value of 0.30 W/m2K 19 1.00 49 61 73 85 97 110 122<br />
20 0.90 48 60 72 84 96 108 120<br />
21 0.80 47 59 70 82 94 105 117<br />
22 0.70 45 57 68 80 91 102 114<br />
23 0.60 44 55 66 77 88 98 109<br />
24 0.50 41 52 62 72 83 93 104<br />
25 0.40 38 48 57 67 76 86 95<br />
26 0.30 33 41 49 57 65 73 81<br />
27 0.20 22 28 33 39 44 50 56<br />
Note:<br />
P/A is the ratio of floor perimeter (m) to floor area (m 2 ).<br />
Amdt: September 2001<br />
J
J<br />
Appendix A<br />
Example 8 – Solid floor in contact with the ground<br />
Determine the thickness of the insulation layer required to achieve a U-value of 0.3 W/m2K for the ground floor<br />
slab shown below.<br />
10<br />
It is proposed to use insulation with a thermal conductivity of 0.025 W/m·K.<br />
The overall perimeter length of the slab is: (10 + 4 + 4 + 2 + 6 + 6) = 32 m.<br />
The floor area of the slab is : (6 × 6) + (4 × 4) = 52 m 2 .<br />
The ratio: perimeter length = 32 = 0.6<br />
floor area 52<br />
Using Table A12, column C, row 23 indicates that 51 mm of insulation is required.<br />
Example 9 - Suspended timber floor<br />
If the floor shown above was of suspended timber construction, the perimeter length and floor area would be<br />
the same, yielding the same ratio of:<br />
Amdt: September 2001<br />
6<br />
perimeter length = 32 = 0.6<br />
floor area 52<br />
6<br />
To achieve a U-value of 0.30 W/m 2 ·K, using insulation with a thermal conductivity of 0.04 W/m·K, Table A13<br />
column F, row 23 indicates that the insulation thickness between the joists should be not less than 102 mm.<br />
19JA<br />
4<br />
4<br />
2
UPPER FLOORS<br />
Table A15 Upper floors of timber construction<br />
Design U-value Thermal conductivity of insulant (W/m·K)<br />
20JA<br />
Appendix A<br />
(W/m 2 K) 0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
Base thickness of insulation between joists to achieve design U-values<br />
A B C D E F G H<br />
1 0.20 167 211 256 298 341 383 426<br />
2 0.25 109 136 163 193 225 253 281<br />
3<br />
Note:<br />
0.30 80 100 120 140 160 184 208<br />
Table A15 is derived for floors with the proportion of timber at 12% which corresponds to 48 mm wide<br />
timbers at 400 mm centres. For other proportions of timber the U-value can be calculated using the<br />
procedure in Appendix E.<br />
Table A16 Upper floors of concrete construction<br />
Design U-value Thermal conductivity of insulant (W/m·K)<br />
(W/m 2 K) 0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
Base thickness of insulation to achieve design U-value<br />
A B C D E F G H<br />
1 0.20 95 119 142 166 190 214 237<br />
2 0.25 75 94 112 131 150 169 187<br />
3 0.30 62 77 92 108 123 139 154<br />
Table A17 Upper floors: allowable reductions in base thickness for common components<br />
Thermal conductivity of insulant (W/m·K)<br />
0.020 0.025 0.030 0.035 0.040 0.045 0.050<br />
Component Reduction in base thickness of insulation material (mm)<br />
A B C D E F G H<br />
1 10 mm plasterboard 1 2 2 2 3 3 3<br />
2 19 mm timber flooring 3 3 4 5 5 6 7<br />
3 50 mm screed 2 3 4 4 5 5 6<br />
Amdt: September 2001<br />
J
J<br />
Appendix A<br />
Table A18:Thermal conductivity of some common construction materials<br />
Density Conductivity<br />
(kg/m3 ) (W/m·K)<br />
Walls<br />
Brickwork (outer leaf) 1700 0.77<br />
Brickwork (inner leaf) 1700 0.56<br />
Lightweight aggregate concrete block 1400 0.57<br />
Autoclaved aerated concrete block 600 0.18<br />
Concrete (medium density) 1800 1.13<br />
2000 1.33<br />
2200 1.59<br />
Concrete (high density): 2400 1.93<br />
Reinforced concrete (1% steel) 2300 2.3<br />
Reinforced concrete (2% steel) 2400 2.5<br />
Mortar (protected) 1750 0.88<br />
Mortar (exposed) 1750 0.94<br />
Gypsum 600 0.18<br />
900 0.30<br />
1200 0.43<br />
Gypsum plasterboard 900 0.25<br />
Sandstone 2600 2.3<br />
Limestone, soft 1800 1.1<br />
Limestone, hard 2200 1.7<br />
Fibreboard 400 0.1<br />
Plasterboard 900 0.25<br />
Tiles ceramic 2300 1.3<br />
Timber 500 0.14<br />
700 0.18<br />
Surface finishes<br />
External rendering 1300 0.57<br />
Plaster (dense) 1300 0.57<br />
Plaster (lightweight) 600 0.18<br />
Roofs<br />
Aerated concrete slab 500 0.16<br />
Asphalt 2100 0.70<br />
Felt/bitumen layers 1100 0.23<br />
Screed 1200 0.41<br />
Stone chippings 2000 2.0<br />
Tiles (clay) 2000 1.0<br />
Tiles (concrete) 2100 1.5<br />
Wood wool slab 500 0.10<br />
Amdt: September 2001<br />
21JA
Table A18 (continued)<br />
22JA<br />
Density Conductivity<br />
(kg/m 3 ) (W/m·K)<br />
Floors<br />
Cast concrete 2000 1.35<br />
Metal tray (steel) 7800 50.0<br />
Screed 1200 0.41<br />
Hardwood timber 700 0.18<br />
Softwood timber, plywood, chipboard 500 0.13<br />
Insulation<br />
Expanded polystyrene (EPS) slab 15 0.040<br />
Mineral wool quilt 12 0.042<br />
Mineral wool batt 25 0.038<br />
Phenolic foam board 30 0.025<br />
Polyurethane board 30 0.025<br />
Note:<br />
If available, certified test values must be used in preference to those in the table.<br />
Appendix A<br />
Amdt: September 2001<br />
J
J<br />
Appendix B<br />
Appendix B: Worked examples of U-value calculations using<br />
the Combined Method<br />
Introduction<br />
B1 For building elements which contain repeating thermal bridges, such as timber joists between insulation<br />
in a roof or floor, timber studs in a wall, or mortar joints in lightweight blockwork, the effect of thermal<br />
bridges should be taken into account when calculating the U-value. The calculation method, known as<br />
the Combined Method, is set out in BS EN ISO 6946 and the following examples illustrate the use of<br />
the method for typical wall, roof and floor designs.<br />
B2 In cases where the joists in roof, wall or floor constructions project beyond the surface of the insulation,<br />
the depths of the joists should be taken to be the same as the thickness of insulation for the purposes of<br />
the U-value calculation (as specified in BS EN ISO 6946).<br />
B3 Conductivity values for common building materials can be obtained from the CIBSE Guide Section A3<br />
or from prEN ISO 12524. For specific insulation products, however, data must be obtained from manufacturers.<br />
Table A18 (Appendix A) gives typical thermal conductivities for some common construction<br />
materials.<br />
B4 The procedure in this Appendix does not address elements containing metal connecting paths. For builtup<br />
sheet metal walls and roofs, BRE IP 5/98 may be used. For curtain walling, the reader is directed to<br />
the CAB publication (Guide for assessment of the thermal performance of aluminium curtain wall<br />
framing” (September 1996). For ground floors and basements the reader is directed to Appendix C.<br />
The procedure<br />
B5 The U-value is calculated by applying the following steps:<br />
a. Calculate the upper resistance limit (R upper) by combining in parallel the total resistances of all<br />
possible heat-flow paths (i.e. sections) through the plane building element.<br />
b. Calculate the lower resistance limit (R lower) by combining in parallel the resistances of the heat<br />
flow paths of each layer separately and then summing the resistances of all layers of the plane<br />
building element.<br />
c. Calculate the U-value of the element from U = 1 / R T,<br />
Amdt: September 2001<br />
where R T = R upper + R lower<br />
2<br />
d. Where appropriate, add a correction for air gaps and mechanical fasteners (including wall ties) as<br />
described in BS EN ISO 6946 Appendix D.<br />
1JB
Example 1 - Timber framed wall<br />
2JB<br />
Appendix B<br />
In this example there is a single bridged layer in the wall, involving insulation bridged by timber studs. The<br />
construction consists of outer leaf brickwork, a clear ventilated cavity, 19 mm plywood, 38 × 140 mm timber<br />
framing with 140 mm of mineral wool quilt insulation between the timber studs and 2 sheets of plasterboard<br />
each 12.5 mm thick.<br />
Figure B1: Timber framed wall construction<br />
(Total thickness: 336 mm; U-value: 0.29 W/m2K)<br />
102 mm brick outer leaf (conductivity 0.77 W/m K)<br />
50 mm ventilated cavity (resistance 0.09 W/m K)<br />
19 mm plywood (conductivity 0.13 W/m K)<br />
mineral wool quilt (conductivity 0.042 W/m K)<br />
between 38 x 140 mm timber studs<br />
(conductivity 0.13 W/m K)<br />
at 400 mm centres<br />
2 x 12.5mm plasterboard (conductivty 0.25 W/m K)<br />
heat flow<br />
The thicknesses of each layer, together with the thermal conductivities of the materials in each layer, are shown<br />
below. The internal and external surface resistances are those appropriate for wall constructions. Layer 4 is<br />
thermally bridged and two thermal conductivities are given for this layer, one for the unbridged part and one for<br />
the bridging part of the layer. For each homogeneous layer and for each section through a bridged layer, the<br />
thermal resistance is calculated by dividing the thickness (in metres) by the thermal conductivity.<br />
Table B1 Calculation of thermal resistance (timber frame)<br />
Layer Material Thickness (mm) Thermal conductivity Thermal resistance<br />
(W/m·K) (m2K/W) external surface - - 0.040<br />
1 outer leaf brick 102 0.77 0.132<br />
2 ventilated air cavity 50 - 0.090<br />
3 plywood 19 0.13 0.146<br />
4(a) mineral wool quilt<br />
between timber studs<br />
140 0.042 3.333<br />
4(b) 48 mm × 140 mm timber<br />
studs at 400 mm centres<br />
140 0.13 1.077<br />
5 plasterboard 25 0.25 0.100<br />
internal surface - - 0.130<br />
Amdt: September 2001<br />
J
J<br />
Appendix B<br />
Both the upper and the lower limits of thermal resistance are calculated by combining the alternative resistances<br />
of the bridged layer in proportion to their respective areas, as illustrated below. The method of combining<br />
differs in the two cases.<br />
Upper resistance limit<br />
When calculating the upper limit of thermal resistance, the building element is considered to consist of two<br />
thermal paths (or sections). The upper limit of resistance is calculated from:<br />
R UPPER = 1<br />
F 1 + F 2<br />
R 1 + R 2<br />
where F 1 and F 2 are the fractional areas of the two sections (paths) and R 1 and R 2 are the total resistances of the<br />
two sections. The method of calculating the upper resistance limit is illustrated conceptually below:<br />
Figure B2 Conceptual illustration of how to calculate the upper limit of thermal resistance<br />
Amdt: September 2001<br />
F 1<br />
F 2<br />
external<br />
surface<br />
Resistance through the section containing insulation<br />
External surface resistance = 0.040<br />
Resistance of bricks = 0.132<br />
Resistance of air cavity = 0.090<br />
Resistance of plywood = 0.146<br />
Resistance of mineral wool (90.5%) = 3.333<br />
Resistance of plasterboard = 0.100<br />
Internal surface resistance = 0.130<br />
Total (R 1) = 3.971 m 2 K/W<br />
Fractional area F 1 = 0.905 (90.5%)<br />
1 2 3 4(a) 5<br />
1 2 3 4(b) 5<br />
3JB<br />
internal<br />
surface
Resistance through the section containing timber stud<br />
External surface resistance = 0.040<br />
Resistance of bricks = 0.132<br />
Resistance of air cavity = 0.090<br />
Resistance of plywood = 0.146<br />
Resistance of timber studs (9.5%) = 1.077<br />
Resistance of plasterboard = 0.100<br />
Internal surface resistance = 0.130<br />
Total (R 2) = 1.715 m 2 K/W<br />
Fractional area F 2 = 0.095 (9.5%)<br />
The upper limit of resistance is then:<br />
R upper<br />
=<br />
Lower resistance limit<br />
1 = 1 = 3.530 m 2 K/W<br />
———— ———————<br />
F 1 + F 2 0.905 + 0.095<br />
— — ——— ———<br />
R 1 R 2 3.971 1.715<br />
4JB<br />
Appendix B<br />
When calculating the lower limit of thermal resistance, the resistance of a bridged layer is determined by combining<br />
in parallel the resistances of the unbridged part and the bridged part of the layer. The resistances of all<br />
the layers in the element are then added together to give the lower limit of resistance.<br />
The resistance of the bridged layer is calculated using:<br />
1<br />
R = —————————<br />
Finsul + Ftimber —— ———<br />
Rinsul + Rtimber The method of calculating the lower limit of resistance is illustrated conceptually below.<br />
Figure B3 Conceptual illustration of how to calculate the lower limit of thermal resistance<br />
external<br />
surface<br />
The lower limit of resistance is then obtained by adding up the resistances of all the layers:<br />
External surface resistance = 0.040<br />
Resistance of bricks = 0.132<br />
F 1<br />
4(a)<br />
1 2 3 5 internal<br />
F2 4(b)<br />
surface<br />
Amdt: September 2001<br />
J
J<br />
Appendix B<br />
Resistance of air cavity = 0.090<br />
Resistance of plywood = 0.146<br />
Resistance of bridged layer = 1 = 2.780<br />
0.905 + 0.095<br />
3.333 1.077<br />
Resistance of plasterboard = 0.100<br />
Internal surface resistance = 0.130<br />
Total (R lower) = 3.418 m 2 K/W<br />
Total resistance of wall (not allowing for air gaps around the insulation)<br />
The total resistance of the wall is the average of the upper and lower resistance limits:<br />
R T<br />
= R upper + R lower = 3.530 + 3.418 = 3.474m 2 K/W<br />
2 2<br />
Correction for air gaps<br />
If there are small air gaps penetrating the insulating layer a correction should be applied to the U-value to<br />
account for this. The correction for air gaps is ∆U g where<br />
∆U g = ∆U" × (R I / R T) 2<br />
and where R I is the thermal resistance of the layer containing gaps, R T is the total resistance of the element and<br />
∆U" is a factor which depends upon the way in which the insulation is installed. In this example R I is 2.780<br />
m 2 K/W, R T is 3.474 m 2 K/W and ∆U" is 0.01 (i.e. correction level 1). The value of ∆U g is then:<br />
∆U g = 0.01 × (2.780 / 3.474) 2 = 0.006 W/m 2 K<br />
U-value of the wall<br />
The effect of air gaps or mechanical fixings should be included in the U-value unless they lead to an adjustment<br />
in the U-value of less than 3%.<br />
U = 1 / R T + ∆U g<br />
U = 1 / R T<br />
Amdt: September 2001<br />
(if ∆U g is not less than 3% of 1 / R T)<br />
(if ∆U g is less than 3% of 1 / R T)<br />
In this case ∆U g = 0.006 W/m 2 K and 1 / R T = 0.288 W/m 2 K. Since ∆U g is less than 3% of (1 / R T),<br />
U = 1 / R T = 1 / 3.474 = 0.29 W/m 2 K.<br />
5JB
6JB<br />
Appendix B<br />
Notes:<br />
1. In the above calculation it is assumed that the noggings (or dwangs) do not penetrate the whole of the<br />
insulation. If, however, the noggings (or dwangs) penetrate the whole of the insulation thickness they<br />
should be included within the timber percentage used in the calculation.<br />
2. In this example correction level 1 is appropriate. This is because air gaps are likely to exist, in some<br />
cases, between the insulation and the timber framing.<br />
3. The additional timbers at the junctions of plane elements, for example wall/wall, wall/floor, and wall<br />
ceiling junctions, and the additional timbers surrounding openings are taken account of in the treatment<br />
of such details and so are not taken into account in the calculation of the U-value of the wall.<br />
4. BS EN ISO 6946 states that if the insulation is installed in such a way that no air circulation is possible<br />
the warm side of the insulation the ∆U" is set to 0.01 W/m 2 K. If, on the other hand, air circulation is<br />
possible on the warm side then it should be set to 0.04 W/m 2 K. The possible correction levels and<br />
correction factors are summarised as follows:<br />
Table B2 Correction for air gaps<br />
Description of air gap Correction level ∆U" W/m2K Insulation installed in such a way that no air<br />
circulation is possible on the warm side of the<br />
insulation. No air gaps penetrating the<br />
entire insulation layer.<br />
0 0.00<br />
Insulation installed in such a way that no air<br />
circulation is possible on the warm side of the<br />
insulation. Air gaps may penetrate the<br />
insulation layer.<br />
1 0.01<br />
Air circulation possible on the warm side<br />
of the insulation. Air gaps may penetrate<br />
the insulation.<br />
2 0.04<br />
Amdt: September 2001<br />
J
J<br />
Appendix B<br />
Example 2 Cavity wall with lightweight masonry leaf and insulated dry-lining<br />
In this example there are two bridged layers - insulation bridged by timber and lightweight blockwork bridged<br />
by mortar. The construction consists of outer leaf brickwork, a clear cavity, 125 mm AAC blockwork,<br />
38 × 89 mm timber studs (400 mm centre-to-centre spacing) with insulation between the studs and one sheet of<br />
12.5 mm plasterboard.<br />
Figure B4 Wall construction with two bridged layers<br />
(Total thickness: 378.5 mm; U-value: 0.29 W/m 2 K)<br />
The thicknesses of each layer, together with the thermal conductivities of the materials, are shown below, with<br />
appropriate internal and external surface resistances, these being, for a wall, 0.13 m 2 K/W and 0.04 m 2 K/W.<br />
Layers 3 and 4 are both thermally bridged and two thermal conductivities are given for each layer to reflect the<br />
bridged part and the bridging part in each case. For each homogeneous layer and for each section through a<br />
bridged layer the thermal resistance is calculated by dividing the thickness (expressed in metres) by the thermal<br />
conductivity.<br />
Table B3: Calculation of thermal resistance (cavity wall)<br />
Layer Material Thickness (mm) Thermal conductivity Thermal resistance<br />
(W/m·K) (m2K/W) external surface - - 0.040<br />
1 outer leaf brick 102 0.77 0.132<br />
2 air cavity 50 - 0.180<br />
3(a) AAC blocks (93.4%) 15 0.11 1.136<br />
3(b) mortar (6.6%) (125) 0.88 0.142<br />
4(a) mineral wool (90.5%) 89 0.038 2.342<br />
4(b) timber studs (9.5%) (89) 0.13 0.685<br />
5 plasterboard 12.5 0.25 0.050<br />
internal surface - - 0.130<br />
Amdt: September 2001<br />
102 mm brick outer leaf (conductivity 0.77 W/m K)<br />
50 mm unvented air cavity ( thermal resistance 0.018 m 2 W/m K)<br />
125 mm AA C blocks (conductivity 0.11 W/m K)<br />
bridged by mortar (conductivity 0.88 W/m K)<br />
mineral wool (conductivity 0.038 W/m K)<br />
between 38 x 89 mm timber studs<br />
(conductivity 0.13 W/m K) at 400 mm centres<br />
12.5mm plasterboard<br />
(conductivty 0.25 W/m K)<br />
7JB<br />
heat flow
8JB<br />
Appendix B<br />
Both the upper and lower limits of thermal resistance are calculated by combining the alternative resistances of<br />
the bridged layer in proportion to their respective areas, as illustrated below. The method of combining differs<br />
in the two cases.<br />
Upper resistance limit<br />
When calculating the upper limit of thermal resistance, the building element is considered to consist of a<br />
number of thermal paths (or sections). In this example there are four sections (or paths) through which heat<br />
can pass. The upper limit of resistance, R upper, is given by<br />
R upper = 1<br />
F 1 + F 2 + F 3 + F 4<br />
— — — —<br />
R 1 R 2 R 3 R 4<br />
where F 1, F 2, F 3 and F 4 are the fractional areas of sections 1, 2, 3 and 4 respectively and R 1, R 2, R 3 and R 4 are<br />
the corresponding total thermal resistances of the sections. A conceptual illustration of the method of calculating<br />
the upper limit of resistance is shown in Figure B5 below:<br />
Figure B5 Conceptual illustration of how to calculate the upper limit of thermal resistance<br />
Resistance through section containing AAC blocks and mineral wool<br />
External surface resistance = 0.040<br />
Resistance of bricks = 0.132<br />
Resistance of air cavity = 0.180<br />
Resistance of AAC blocks (93.4%) = 1.136<br />
Resistance of mineral wool (90.5%) = 2.342<br />
Resistance of plasterboard = 0.050<br />
Internal surface resistance = 0.130<br />
Total thermal resistance (R 1) = 4.010 m 2 K/W<br />
Fractional area F 1 = 0.845 (93.4% × 90.5%)<br />
Resistance through the section containing mortar and mineral wool<br />
External surface resistance = 0.040<br />
Resistance of bricks = 0.132<br />
Resistance of air cavity = 0.180<br />
Resistance of mortar (6.6%) = 0.142<br />
Resistance of mineral wool (90.5%) = 2.342<br />
Resistance of plasterboard = 0.050<br />
Internal surface resistance = 0.130<br />
Total thermal resistance (R 2) = 3.016 m 2 K/W<br />
Fractional area F 2 = 0.060 (6.6% × 90.5%)<br />
F 1<br />
F 2<br />
F 3<br />
F 4<br />
external<br />
surface<br />
1 2 3(a) 4(a) 5<br />
1 2 3(b) 4(a) 5<br />
1 2 3(a) 4(b) 5<br />
1 2 3(b) 4(b) 5<br />
internal<br />
surface<br />
Amdt: September 2001<br />
J
J<br />
Appendix B<br />
Resistance through section containing AAC blocks and timber<br />
External surface resistance = 0.040<br />
Resistance of bricks = 0.132<br />
Resistance of air cavity = 0.180<br />
Resistance of AAC blocks (93.4%) = 1.136<br />
Resistance of timber (9.5%) = 0.685<br />
Resistance of plasterboard = 0.050<br />
Internal surface resistance = 0.130<br />
Total thermal resistance (R 3) = 2.353 m 2 K/W<br />
Fractional area F 3 = 0.089 (93.4% × 9.5%)<br />
Resistance through section containing mortar and timber<br />
External surface resistance = 0.040<br />
Resistance of bricks = 0.132<br />
Resistance of air cavity = 0.180<br />
Resistance of mortar (6.6%) = 0.142<br />
Resistance of timber (9.5%) = 0.685<br />
Resistance of plasterboard = 0.050<br />
Internal surface resistance = 0.130<br />
Total thermal resistance (R 4) = 1.359 m 2 K/W<br />
Fractional area F 4 = 0.006 (6.6% × 9.5%)<br />
Combining these resistances we obtain:<br />
R upper =<br />
Amdt: September 2001<br />
1 1 3.665 m<br />
=<br />
= 2K/W ————————— ——————————————<br />
F1 F2 F3 F4 0.845 0.060 0.089 0.006<br />
— + — + — + — ——— + ——— + ——— + ———<br />
R1 R2 R3 R4 4.010 3.016 2.353 1.359<br />
9JB
Lower resistance limit<br />
10JB<br />
Appendix B<br />
When calculating the lower limit of thermal resistance, the resistance of a bridged layer is determined by combining<br />
in parallel the resistances of the unbridged part and the bridged part of the layer. The resistances of all<br />
the layers in the element are then added together to give the lower limit of resistance. A conceptual illustration<br />
of the method of calculating the lower limit of resistance is shown below:<br />
Figure B6 Conceptual illustration of how to calculate the lower limit of thermal resistance<br />
The resistances of the layers are added together to give the lower limit of resistance. The resistance of the<br />
bridged layer consisting of AAC blocks and mortar is calculated using:<br />
R first =<br />
1<br />
—————————<br />
Fblocks + Fmortar —— ———<br />
Rblocks + Rmortar and the resistance of the bridged layer consisting of insulation and timber is calculated using:<br />
R second =<br />
1<br />
—————————<br />
Finsul + Ftimber —— ———<br />
Rinsul + Rtimber The lower limit of resistance is then obtained by adding together the resistances of all the layers:<br />
External surface resistance = 0.040<br />
Resistance of bricks = 0.132<br />
Resistance of air cavity = 0.180<br />
Resistance of polystyrene insulation = 0.500<br />
Resistance of first bridged layer<br />
R first<br />
= 1<br />
———————<br />
0.934 0.066<br />
——— + ———<br />
1.136 0.142 = 0.777<br />
Resistance of second bridged layer<br />
external<br />
surface<br />
3(a)<br />
Rsecond = 1<br />
———————<br />
0.905 0.095<br />
——— + ———<br />
2.342 0.685 = 1.904<br />
4(a)<br />
1 2 5 internal<br />
surface<br />
3(b) 4(b)<br />
Resistance of plasterboard = 0.050<br />
Internal surface resistance = 0.130<br />
Total (R lower) = 3.213 m 2 K/W<br />
Amdt: September 2001<br />
J
J<br />
Appendix B<br />
Total resistance of wall<br />
The total resistance of the wall is the average of the upper and lower resistance limits:<br />
RT = Rupper + Rlower 3.665 + 3.213 2 ——————— = ——————— = 3.439m K/W<br />
2 2<br />
Correction for air gaps between the timber studs<br />
Since the insulation is entirely between studs (i.e. there is no continuous layer of insulation) a correction should<br />
be applied to the U-value in order to account for air gaps. The overall U-value of the wall should include a<br />
term ∆U g, where<br />
∆Ug = ∆U’’ × (R I / R T) 2<br />
and where ∆U’’ = 0.01 (referred to in BS EN ISO 6946 as correction level 1), R I is the thermal resistance of<br />
the layer containing the gaps and R T is the total resistance of the element. ∆U g is therefore:<br />
∆U g = 0.01 × (1.904 / 3.439) 2 = 0.003 W/m 2 K<br />
U-value of the wall<br />
The effect of air gaps or mechanical fixings should be included in the U-value unless they lead to an adjustment<br />
in the U-value of less than 3%.<br />
U = 1 / R T + ∆Ug (if ∆Ug is not less than 3% of 1 / R T)<br />
U = 1 / R T<br />
Amdt: September 2001<br />
(if ∆Ug is less than 3% of 1 / R T)<br />
In this case ∆U g = 0.003 W/m 2 K and 1 / R T = 0.291 W/m 2 K. Since ∆U g is less than 3% of (1 / R T),<br />
U = 1 / 3.439 = 0.29 W/m 2 K.<br />
Notes:<br />
1. Since the cavity wall ties do not penetrate any insulation no correction need be applied to the U–value to<br />
take account of them.<br />
2. In the above calculation it is assumed that the dwangs (or noggings) do not penetrate the whole of the<br />
insulation. If the dwangs (or noggings) do penetrate the whole of the insulation thickness they should<br />
be included as part of the timber percentage used in the calculation.<br />
11JB
Appendix C: U-values of ground floors and basements<br />
1JC<br />
Appendix C<br />
C1 A ground floor must not have a U-value exceeding 0.25 W/m 2 K, or 0.22 W/m 2 K for dwellings depending<br />
on the heating system, if the Elemental Method of compliance is to be used. This can normally be<br />
achieved without the need for insulation if the perimeter to area ratio is less than 0.15 m -1 for solid<br />
ground floors or less than 0.13 m -1 for suspended floors. For most buildings, however, some ground<br />
floor insulation will be necessary. For basement floors the standard Elemental U-value is also<br />
0.25 W/m 2 K (or 0.22 W/m 2 K) but for basement walls it is 0.30 W/m 2 K (or 0.27 W/m 2 K). For exposed<br />
floors and for floors over unheated spaces the reader is referred to Appendix B.<br />
C2 Full details about how to calculate the U-value of a ground floor, a basement floor or a basement wall<br />
are given in BS EN ISO 13370 and in CIBSE Guide Section A3 (1999 edition). This Appendix provides<br />
a summary of how to determine the U-value which will suffice for most common constructions.<br />
C3 For ground floors and basements the U-value depends upon the type of soil beneath the building.<br />
Where the soil type is unknown, clay soil should be assumed as this is the most typical soil type in the<br />
UK. The tables which follow refer to this soil type. Where the soil is not clay or silt, the U-value<br />
should be calculated using the procedure in BS EN ISO 13370.<br />
C4 Floor dimensions should be measured in accordance with J2. In the case of semi-detached or terraced<br />
premises, blocks of flats and similar, the floor dimensions can either be taken as those of the premises<br />
themselves, or of the whole building. When considering extensions to existing buildings the floor<br />
dimensions may be taken as those of the complete building including the extension.<br />
C5 Care should be taken to avoid thermal bridging at the floor edge. See BRE Report BR262 “Thermal<br />
insulation: avoiding risks”.<br />
C6 Unheated spaces outside the insulated fabric, such as attached garages or porches, should be excluded<br />
when determining the perimeter and area but the length of the wall between the heated building and the<br />
unheated space should be included when determining the perimeter.<br />
C7 The following tables have been derived from BS EN ISO 13370. For the purposes of Part J it will be<br />
sufficient to derive the U-values from the tables using linear interpolation where necessary.<br />
Amdt: September 2001<br />
J
J<br />
Appendix C<br />
Example of how to obtain U-values from the tables<br />
The following example serves as an illustration of how to use the tables supplied in this appendix, interpolating<br />
between appropriate rows or columns.<br />
Example of the use of Table C.1 for a solid ground floor<br />
A proposed dwelling has a perimeter of 38.4 m and a ground floor area of 74.25 m 2 . The floor construction<br />
consists of a 150 mm concrete slab, 75 mm of rigid insulation (thermal conductivity 0.04 W/mK) and a 65 mm<br />
screed. Only the insulation layer is included in the calculation of the thermal resistance.<br />
Figure C1<br />
The perimeter to area ratio is equal to 38.4 ÷ 74.25 = 0.517 m -1 . Table C.1 provides values for perimeter/area<br />
ratios of 0.50 and 0.55 but not for any values between 0.50 and 0.55. In this case, the U-value corresponding to<br />
a perimeter to area ratio of 0.50 should be used since 0.517 is closer to 0.50 than to 0.55.<br />
The thermal resistance of the insulation is obtained by dividing the thickness (in metres) by the conductivity.<br />
The resistance is then 0.075 ÷ 0.04 = 1.875 m 2 K/W.<br />
The relevant part of Table C1 is shown below:<br />
Thermal resistance (m2K/W) Perimeter/Area 1.5 2.0<br />
0.50 0.33 0.28<br />
The U-value corresponding to a thermal resistance of 1.875 m 2 K/W is obtained by linear interpolation as<br />
below:<br />
U = 0.33 × 2.0 – 1.875 1.875 – 1.5<br />
—————— + 0.28 × ——————<br />
2.0 – 1.5 2.0 – 1.5<br />
= 0.33 × 0.25 + 0.28 × 0.75<br />
= 0.29 W/m2K The U-value of this ground floor is therefore 0.29 W/m 2 K.<br />
Note:<br />
Amdt: September 2001<br />
9.0<br />
3.7<br />
10.2<br />
2.7<br />
In the example for Table C.1 the appropriate row was chosen and interpolation was carried out between<br />
the appropriate columns. For all of the other tables, however, the appropriate column in the table should<br />
be selected and interpolation should be carried out between the appropriate rows.<br />
2JC<br />
6.5<br />
6.3
Solid ground floors<br />
3JC<br />
Appendix C<br />
Solid ground floors are taken to mean ground floors in which there is no significant air layer separating the<br />
building from the ground. Listed in the table below are U-values for solid ground floors. U-values are given in<br />
the following table for various perimeter-to-area ratios for a range of insulation levels. Where the floor is<br />
uninsulated the column corresponding to a thermal resistance of 0 should be used.<br />
Table C1: U-values for solid ground floors (W/m2K) Thermal resistance of all-over insulation (m2K/W) Perimeter/Area 0 0.5 1 1.5 2<br />
0.05 0.13 0.11 0.10 0.09 0.08<br />
0.10 0.22 0.18 0.16 0.14 0.13<br />
0.15 0.30 0.24 0.21 0.18 0.17<br />
0.20 0.37 0.29 0.25 0.22 0.19<br />
0.25 0.44 0.34 0.28 0.24 0.22<br />
0.30 0.49 0.38 0.31 0.27 0.23<br />
0.35 0.55 0.41 0.34 0.29 0.25<br />
0.40 0.60 0.44 0.36 0.30 0.26<br />
0.45 0.65 0.47 0.38 0.32 0.27<br />
0.50 0.70 0.50 0.40 0.33 0.28<br />
0.55 0.74 0.52 0.41 0.34 0.28<br />
0.60 0.78 0.55 0.43 0.35 0.29<br />
0.65 0.82 0.57 0.44 0.35 0.30<br />
0.70 0.86 0.59 0.45 0.36 0.30<br />
0.75 0.89 0.61 0.46 0.37 0.31<br />
0.80 0.93 0.62 0.47 0.37 0.32<br />
0.85 0.96 0.64 0.47 0.38 0.32<br />
0.90 0.99 0.65 0.48 0.39 0.32<br />
0.95 1.02 0.66 0.49 0.39 0.33<br />
1.00 1.05 0.68 0.50 0.40 0.33<br />
Note:<br />
As an alternative to the above table, the methods described in BS EN ISO 13370 may be used.<br />
Amdt: September 2001<br />
J
J<br />
Appendix C<br />
Ground floors with edge insulation<br />
Where horizontal or vertical edge insulation is used instead of all-over floor insulation, the U-value of the floor<br />
is adjusted by Ψ×P/A to account for the effects of edge insulation, where P/A is the perimeter (m) to area (m 2 )<br />
ratio and Ψ is the edge insulation factor obtained from one of the following two tables:<br />
Table C2: Edge insulation factor (Ψ) for horizontal edge insulation<br />
Insulation width (m) Thermal resistance of insulation (m 2 K/W)<br />
Amdt: September 2001<br />
0.5 1.0 1.5 2.0<br />
0.5 -0.13 -0.18 -0.21 -0.22<br />
1.0 -0.20 -0.27 -0.32 -0.34<br />
1.5 -0.23 -0.33 -0.39 -0.42<br />
Table C3: Edge insulation factor (Ψ) for vertical edge insulation<br />
Insulation depth (m) Thermal resistance of insulation (m 2 K/W)<br />
0.5 1.0 1.5 2.0<br />
0.25 -0.13 -0.18 -0.21 -0.22<br />
0.50 -0.20 -0.27 -0.32 -0.34<br />
0.75 -0.23 -0.33 -0.39 -0.42<br />
1.00 -0.26 -0.37 -0.43 -0.48<br />
Note:<br />
As an alternative to the above table, the methods described in BS EN ISO 13370 may be used.<br />
Uninsulated suspended ground floors<br />
The following table gives U-values of uninsulated suspended floors for various perimeter to area ratios and for<br />
two levels of ventilation (expressed in m 2 /m) below the floor deck. The data apply for the floor deck at a height<br />
not more than 0.5 m above the external ground level where the wall surrounding the underfloor space is uninsulated.<br />
4JC
5JC<br />
Appendix C<br />
Table C4 U-values of uninsulated suspended floors<br />
Height of floor deck above ground level and ventilation<br />
opening area per unit perimeter of underfloor space (m2 /m)<br />
Perimeter to area ratio 0.0015 m2 /m 0.0030 m2 /m<br />
0.05 0.15 0.15<br />
0.10 0.25 0.26<br />
0.15 0.33 0.35<br />
0.20 0.40 0.42<br />
0.25 0.46 0.48<br />
0.30 0.51 0.53<br />
0.35 0.55 0.58<br />
0.40 0.59 0.62<br />
0.45 0.63 0.66<br />
0.50 0.66 0.70<br />
0.55 0.69 0.73<br />
0.60 0.72 0.76<br />
0.65 0.75 0.79<br />
0.70 0.77 0.81<br />
0.75 0.80 0.84<br />
0.80 0.82 0.86<br />
0.85 0.84 0.88<br />
0.90 0.86 0.90<br />
0.95 0.88 0.92<br />
1.00<br />
Note:<br />
0.89 0.93<br />
As an alternative to the above table, the methods described in BS EN ISO 13370 may be used.<br />
Insulated suspended floors<br />
The U-value of an insulated suspended floor should be calculated using:<br />
U = 1 / [(1/U 0 ) – 0.2 + R f]<br />
where U 0 is the U-value of an uninsulated suspended floor obtained using the above table or another approved<br />
method. R f, the thermal resistance of the floor deck, is determined from U f, the U-value of the floor deck,<br />
where<br />
Rf = 1 — – 0.17 – 0.17<br />
Uf and where U f is calculated using the Combined Method, as described in BS EN ISO 6946, assuming thermal<br />
resistances of 0.17 m 2 K/W for both the upper and lower surfaces of the floor deck.<br />
Amdt: September 2001<br />
J
J<br />
Appendix C<br />
Uninsulated basement floors<br />
The U-value of an uninsulated basement floor must be calculated by using Table C5 below, or the methods<br />
described in BS EN ISO 13370.<br />
Table C5 U-values of uninsulated basement floors<br />
Perimeter to area ratio Basement depth (m)<br />
0.5 1 1.5 2 2.5<br />
0.1 0.20 0.19 0.18 0.17 0.16<br />
0.2 0.34 0.31 0.29 0.27 0.26<br />
0.3 0.44 0.41 0.38 0.35 0.33<br />
0.4 0.53 0.48 0.44 0.41 0.38<br />
0.5 0.61 0.55 0.50 0.46 0.43<br />
Amdt: September 2001<br />
0.6 0.68 0.61 0.55 0.50 0.46<br />
0.7 0.74 0.65 0.59 0.53 0.49<br />
0.8 0.79 0.70 0.62 0.56 0.51<br />
0.9 0.84 0.73 0.65 0.58 0.53<br />
1.0 0.89 0.77 0.68 0.60 0.54<br />
Insulated basement floors<br />
Determine the U-value of an insulated basement floor from<br />
U = 1 / [(1/U 0) + R ins]<br />
where U 0 is the U-value determined from Table C5 (or other approved method) for uninsulated basements and<br />
R ins is the thermal resistance of the insulation in m 2 K/W. The value of R ins may be calculated from the thickness<br />
of the insulation divided by its conductivity.<br />
Basement walls<br />
Table C6 below provides the U-value of a basement wall for a given basement depth and basement wall resistance.<br />
Table C6: U-values of basement walls<br />
Basement wall Basement depth (m)<br />
resistance (m2K/W) 0.5 1 1.5 2 2.5<br />
0.2 1.55 1.16 0.95 0.81 0.71<br />
0.5 0.98 0.78 0.66 0.58 0.52<br />
1.0 0.61 0.51 0.45 0.40 0.37<br />
2.0 0.35 0.30 0.27 0.25 0.24<br />
2.5 0.28 0.25 0.23 0.21 0.20<br />
6JC
Appendix D: Thermal bridging at the edges of openings<br />
Summary<br />
D1 This Appendix gives a procedure for establishing whether:<br />
a. there is an unacceptable risk of condensation at the edges of openings; and/or<br />
b. the heat losses at the edges of openings are significant.<br />
1JD<br />
Appendix D<br />
D2 The procedure involves the assessment of the minimum thermal resistance between inside and outside<br />
surfaces at the edges of openings. This requires identification of minimum thermal resistance paths, and<br />
calculation of their thermal resistance, taking into account the effect of thin layers such as metal lintels.<br />
D3 These minimum thermal resistances are then compared with satisfactory performance criteria to see<br />
whether corrective action is indicated.<br />
Minimum thermal resistance path<br />
D4 The minimum thermal resistance path through a thermal bridge is that path from internal surface to<br />
external surface which has the smallest thermal resistance, R min. Diagram D1 illustrates this for a<br />
section through a window jamb.<br />
Diagram D1: Minimum thermal resistance path<br />
external<br />
internal<br />
The minimum resistance path in this case is from the internal surface at A to the external surface at B.<br />
R min is equal to the total length from inside to outside (AB) divided by the thermal conductivity of the<br />
material of the jamb. An example calculation is given on the following page.<br />
Additional calculation for thin layers such as metal lintels<br />
D5 For details containing thin layers of thickness not exceeding 4 mm (such as metal lintels), a second<br />
modified calculation of minimum thermal resistance (R mod) is made wherein the effective thermal conductivity<br />
of the thin layer is taken as the largest of 0.1 W/mK or the thermal conductivities of the materials<br />
immediately on either side of it. An example of this more complex calculation is given in<br />
BRE IP 12/94: “Assessing condensation risk and heat loss at thermal bridges around openings”.<br />
B<br />
A<br />
window<br />
Amdt: September 2001<br />
J
J<br />
Appendix D<br />
Risk of surface condensation<br />
D6 The risk of surface condensation and mould growth at the edges of openings can be assumed to be<br />
negligible if:<br />
a. for edges containing thin layers of thickness not exceeding 4 mm:<br />
R min (rounded to two decimal places) is at least 0.10 m 2 K/W, and<br />
R mod (rounded to two decimal places) is at least 0.45 m 2 K/W; or<br />
b. for other edge designs:<br />
R min (rounded to two decimal places) is at least 0.20 m 2 K/W.<br />
Note:<br />
These criteria do not apply to cases where internal surface projections are used to avoid surface condensation,<br />
e.g. curtain walling.<br />
D7 In the event of an unacceptable risk being identified, marginal cases could be more rigorously analysed<br />
using numerical calculation methods, but in any case modification to improve the design should be<br />
considered.<br />
Additional heat loss<br />
D8 For the purposes of Part J, the additional heat losses at the edges of openings may be ignored if:<br />
a. for edges containing thin layers of thickness not exceeding 4 mm,<br />
R mod (rounded to two decimal places) is at least 0.45 m 2 K/W, or<br />
b. for other edge designs:<br />
R min (rounded to two decimal places) is at least 0.45 m 2 K/W.<br />
Compensating for additional heat loss<br />
D9 Where the additional heat losses around the edges of openings cannot be ignored they can be taken into<br />
account in calculations as follows:<br />
a. for dwellings the Target U-value method could be used with the average U-value increased by the<br />
following amount:<br />
Amdt: September 2001<br />
0.3 × total length of relevant opening surrounds (W/m 2 K)<br />
———————————————————<br />
total exposed surface area<br />
b. for other buildings the calculation procedure could be used with the rate of heat loss from the<br />
proposed building increased by the following amount:<br />
0.3 × total length of relevant opening surrounds (W)<br />
c. compensating measures, such as reducing the U-value of one of the building elements, should<br />
then be incorporated so that:<br />
i. for dwellings, the average U-value does not exceed the Target U-value, or<br />
ii. for other buildings, the rate of heat loss from the proposed building does not exceed that<br />
of the notional building.<br />
2JD
Example<br />
3JD<br />
Appendix D<br />
Diagram D2 shows a window jamb in a masonry cavity wall with the blockwork returned towards the outer leaf<br />
at the reveal. By inspection it can be seen that ABCD is the minimum resistance path.<br />
Diagram D2 70mm cavity wall showing window jamb with blockwork returned at the reveal<br />
Note: Numbers denote regions in Table D1 below.<br />
Table Dl: Thermal conductivity of materials in Diagram D2<br />
Region Material Conductivity (W/m·K)<br />
1 Brick outer leaf 0.77<br />
2 Insulation 0.035<br />
3 Medium weight concrete block inner leaf 0.61<br />
4 Lightweight plaster 0.16<br />
Calculation of R min<br />
Using the thermal conductivities from Table Dl, Table D2 gives the resistance R for each segment of the path<br />
ABCD. R for each segment is obtained by dividing the length of the path segment in metres by its thermal<br />
conductivity in W/mK. R min is the sum of the resistances of each path segment.<br />
Avoidance of the risk of surface condensation and mould growth<br />
Referring to paragraph D6, R min in this example is greater than 0.20 m 2 K/W and so the risk of surface condensation<br />
and mould growth is acceptably low.<br />
Table D2: Thermal resistance path in Diagram D2<br />
Path segments Length (m) Conductivity (W/m·K) R (m2K/W) AB 0.015 0.16 0.094<br />
BC 0.070 0.61 0.115<br />
CD 0.023 0.77 0.177<br />
Additional heat loss at the edge detail<br />
1<br />
2<br />
3<br />
4<br />
window<br />
Minimum Resistance R min = 0.386<br />
Referring to paragraph D8, R min in this example is less than 0.45 m 2 K/W, and so the additional heat loss at this<br />
edge should not be ignored.<br />
B<br />
C<br />
A<br />
D<br />
Amdt: September 2001<br />
J
J<br />
Appendix D<br />
Improving the edge design<br />
Instead of returning the blockwork at the reveal the cavity could be closed using an insulated cavity closer, as<br />
in Diagram D3.<br />
Diagram D3 Window jamb showing cavity closed with an insulated cavity closer<br />
The revised calculation of the minimum resistance is shown in Table D3. R min is now greater than 0.45 m 2 K/W<br />
and so the additional heat loss can be ignored.<br />
Table D3 Minimum resistance path with insulated cavity closer<br />
Path segments Length (m) Conductivity (W/m·K) R (m2K/W) AB 0.015 0.16 0.094<br />
BC 0.070 0.04 1.750<br />
Minimum resistance Rmin = 1.844<br />
Alternative method<br />
D10 A heat loss factor for a particular detail could be obtained by a numerical method and used to modify<br />
the calculation of the average U-value or the total rate of heat loss. A calculation procedure for deriving<br />
such loss factors is given in BRE IP 12/94: “Assessing condensation risk and heat loss at thermal bridges<br />
around openings”.<br />
Amdt: September 2001<br />
Insulated cavity<br />
closer<br />
C<br />
;;<br />
4JD<br />
;;<br />
B A<br />
window
1JE<br />
Appendix E<br />
Appendix E: Determining U-values of windows, doors and roof<br />
windows in the Elemental Method<br />
Within the Elemental Method of compliance it is permissible to have windows, doors or roof windows with<br />
U-values that exceed the standard Elemental U-values provided that the average U–value of all of the windows,<br />
doors and roof windows taken together does not exceed 2.0 (or 1.8 W/m 2 K in the case of dwellings, depending<br />
on the heating system). The following example illustrates how this can be done.<br />
Example<br />
A semi-detached house is to have a total window area of 16.9 m 2 (including frames) and a total door area of<br />
3.8 m 2 . It is proposed to use solid wooden doors with a U-value of 3.0 W/m 2 K. In order to use the Elemental<br />
Method, the additional heat loss due to the use of solid timber doors must be compensated for by lower<br />
U-values in the windows and/or roof windows so that the average U-value of openings does not exceed<br />
2.0 W/m 2 K.<br />
Windows with a U-value of 1.7 W/m 2 K can achieve this requirement, as shown in the following table and<br />
subsequent calculation:<br />
Table to Part J Appendix E: Average U-value calculation<br />
Element Area (m2 ) U-value (W/m2K) Rate of heat loss per degree (W/K)<br />
Windows 16.9 1.7 [Note 1] 28.73<br />
Doors 3.8 3.0 11.4<br />
Roof windows 0.9 1.9 [Note 1] 1.71<br />
Total<br />
Note:<br />
21.6 41.84<br />
1. These U-values correspond to double glazed windows or roof windows with a wood or PVC-U<br />
frame, with a 16 mm argon-filled space between the panes and a soft low-emissivity coating on<br />
the glass. Note that although the windows and roof windows have the same design the roof<br />
window U-value is 0.2 W/m2K higher than the window U-value.<br />
This gives an average U-value of 41.84 ÷ 21.6, or 1.94 W/m 2 K, which is below 2.0 W/m 2 K. The windows,<br />
doors and roof windows therefore satisfy the requirements of the Elemental Method.<br />
Amdt: September 2001<br />
J
J<br />
Appendix F: Examples illustrating the use of the Target U-value Method<br />
F1 For a building in purpose group 1 with a heating system based on a gas or oil boiler, the Target U-value<br />
is given by<br />
U T = [0.30 – 0.14(A R/A T) – 0.05(A GF/A T) + 0.425(A F/A T)]<br />
where U T is the target U-value prior to any adjustment for heating system performance or solar gain, A R<br />
is the exposed roof area, A GF is the ground floor area, A F is the total floor area (all storeys) and A T is<br />
the total area of exposed elements (including the ground floor).<br />
F2 A dwelling can comply by the Target U-value Method if the Target U-value is not less than the average<br />
U-value, where the average U-value is defined as the area-weighted average U-value of all exposed<br />
building elements of the dwelling. Exposed elements here include walls, roofs, floors, windows and<br />
doors, including elements adjacent to unheated spaces.<br />
Example 1 – A semi-detached dwelling<br />
F3 The following table gives the proposed surface areas and U-values. It is proposed to adopt the Target Uvalue<br />
method with the U-value of the walls a little higher (i.e. poorer) than would be required in the<br />
Elemental method. The walls are to have a U-value of 0.35 W/m 2 K. The area of windows and doors is<br />
equal to 25% of the total internal floor area and the efficiency of the gas boiler is 85%. The total area of<br />
North-facing glazed openings is 6.82 m 2 and the total area of South-facing glazed openings is 8.88 m 2 .<br />
The windows are wood-framed.<br />
Figure F.1: Plans of the semi-detached house<br />
Table F1: Data for the semi-detached house<br />
Exposed element Exposed surface area U-value Rate of heat loss per degree<br />
wall 80.3 0.35 28.10<br />
roof 44.4 0.20 8.88<br />
ground floor 44.4 0.25 11.10<br />
windows 18.4 2.2 40.48<br />
doors 3.8 2.2 8.36<br />
Total 191.3 - 96.92<br />
F4 The Target U-value is<br />
Amdt: September 2001<br />
First floor Ground floor<br />
U T = [0.30 – 0.14(44.4/191.3) – 0.05(44.4/191.3) + 0.425(88.8/191.3)] = 0.453<br />
Since the proposed boiler SEDBUK is greater than the reference boiler SEDBUK the Target U-value is<br />
not adjusted for boiler efficiency.<br />
1JF<br />
height to eaves-5m
2JF<br />
Appendix F<br />
F5 Since the area of glazed openings on the South elevations exceeds that on the North, the benefit of solar<br />
heat gains can be taken into account to ease the target U-value by adding ∆S to the target U-value,<br />
where: -<br />
∆S = 0.04 x [(A S – A N) / A TG]<br />
and A S = Area of glazed openings facing south; A N = Area of glazed openings facing north;<br />
A TG = Total area of all glazed openings in the building;<br />
So 0.04 x [(8.88 - 6.82) / 18.4], or 0.004, is added to the Target U-value, giving a Target U-value of<br />
0.457 W/m 2 K.<br />
F6 The average U-value is given by:<br />
Total rate of heat loss per degree<br />
Uavg = ——————————————<br />
Total external surface area<br />
These values are calculated in the above table, and in this case the average U-value is:<br />
Uavg = 96.92 = 0.507 W/m2 ———<br />
K<br />
191.3<br />
Since the average U-value is greater than the target U-value the proposed design does not meet the<br />
requirements and modifications must be made to the design. The Target U-value method may still be<br />
used, however, if the average U-value is reduced.<br />
F7 A number of ways of modifying the proposed design in order to comply with the Target U-value Method<br />
are described below:<br />
a) Reducing the total area of the windows and doors<br />
If the total area of windows and doors is reduced from 25% of the floor area to 19% of the floor area the<br />
average U-value will be reduced by (6% of 88.8) × (2.2 – 0.35) / 191.3, or 0.052 W/m 2 K, which is<br />
sufficient to reduce the average U-value to below the Target U-value.<br />
Average U-value = 0.507 – 0.052 = 0.455 W/m 2 K<br />
Since the final average U-value is less than the final Target U-value, compliance with the Target U-value<br />
Method is achieved.<br />
b) Specifying windows and doors with lower U-values.<br />
Using windows and doors with a U-value of 1.7 W/m 2 K instead of 2.2 W/m 2 K will reduce the average<br />
U-value by [(2.2 – 1.7) × (18.4 + 3.8) / 191.3], or 0.058 W/m 2 K. This is sufficient to reduce the average<br />
U-value to below the Target U-value. Reducing the window U-value to 1.71 W/m 2 K is therefore sufficient<br />
to achieve compliance.<br />
Average U-value = 0.507 – 0.058 = 0.449 W/m 2 K<br />
Since the final average U-value is less than the final Target U-value, compliance with the Target U-value<br />
Method is achieved.<br />
Example 2 – A detached house<br />
F8 Consider the example in Figure F.2 which has details as given in the following table. It is proposed to<br />
adopt the Target U-value approach with the walls having a U-value of 0.35W/m 2 K. To compensate for<br />
this the floor U-value is reduced to 0.15 W/m 2 K, the roof U-value is reduced to 0.16 W/m 2 K and the<br />
window U-value is reduced to 1.7 W/m 2 K. The SEDBUK efficiency of the boiler is not less than the<br />
reference SEDBUK efficiency.<br />
Amdt: September 2001<br />
J
J<br />
Appendix F<br />
Figure F.2: Plans of the detached house<br />
Table F2: Data for the detached house<br />
Exposed element Exposed surface area U-value Rate of heat loss per degree<br />
wall 123.0 0.35 43.05<br />
roof 52.0 0.16 8.32<br />
ground floor 52.0 0.15 7.80<br />
windows & glazed doors* 24.1 1.7 40.97<br />
solid doors 1.9 3.0 5.7<br />
Total 253.0 105.84<br />
*this includes 7.0 m2 of North facing glazing and 8.9 m2 of South facing glazing<br />
F9 The Target U-value is where:<br />
U T = [0.30 – 0.14(A R/A T) – 0.05(A GF/A T) + 0.425(A F/A T)]<br />
Then in this example<br />
U T = [0.30 – 0.14(52/253) – 0.05(52/253) + 0.425(104/253)] = 0.436 W/m 2 K.<br />
No adjustment to the Target U-value for efficiency is applied since the heating system efficiency is not<br />
less than the base SEDBUK efficiency.<br />
F10 Since the area of glazed openings on the South elevations exceeds that on the North, the benefit of solar<br />
heat gains can be taken into account to ease the target U-value by adding ∆S to the target U-value,<br />
where: -<br />
∆S = 0.04 x [(A S – A N) / A TG]<br />
and A S = Area of glazed openings facing south; A N = Area of glazed openings facing north;<br />
A TG = Total area of all glazed openings in the building;<br />
F11 The adjustment to the Target U-value for solar gains is:<br />
0.04 × [(8.9 - 7.0) / 24.1] = 0.003 W/m 2 K<br />
This gives a final Target U-value of 0.436 W/m 2 K + 0.003 W/m 2 K, or 0.439 W/m 2 K.<br />
F12 The average U-value is given by the following ratio:<br />
U avg =<br />
Amdt: September 2001<br />
Total rate of heat loss per degree<br />
——————————————<br />
Total external surface area<br />
For this example, therefore, the average U-value is<br />
Uavg = 105.8 = 0.418 W/m2 ———<br />
K<br />
253.0<br />
Ground floor<br />
Since the average U-value is less than the Target U-value , the proposed design meets the requirements<br />
3JF<br />
First floor
1JG<br />
Appendix G<br />
Appendix G: Example SAP Energy Ratings and Carbon Indexes<br />
THE SAP ENERGY RATING AND THE CARBON INDEX<br />
The SAP energy rating method is the <strong>Government</strong>’s chosen method for producing an energy cost rating for a<br />
dwelling, based on calculated annual energy cost for space and water heating, assuming a standard occupancy<br />
pattern, derived from the measured floor area of the dwelling, and a standard heating pattern. The Carbon<br />
Index is derived from the SAP procedure, but measures the annual carbon output of the heating system and fuel<br />
selected. Both the SAP rating and the Carbon Index (CI) are adjusted for floor area so that the size of the<br />
dwelling does not affect the results, which are expressed on a scale of SAP rating 1 to 120 and CI 0.0 to 10.0:<br />
the higher the number the better the standard.<br />
The full procedure is described in “The <strong>Government</strong>’s Standard Assessment Procedure for energy rating of<br />
dwellings - 2001 edition” (SAP 2001), published by the Building Research Establishment (BRE). This sets out<br />
the method of calculating the SAP rating and the CI in the form of a worksheet, accompanied by a series of<br />
tables. A calculation may be carried out by completing, in sequence, the numbered boxes in the worksheet,<br />
using the data in the tables as indicated. Alternatively, and more usually, a computer program approved for<br />
SAP/CI calculations by BRE may be used.<br />
THE SAP ENERGY RATING, THE CARBON INDEX AND THE BUILDING REGULATIONS<br />
The Building (Procedure) (Scotland) Regulations 1981, as amended in 1997, require all new dwellings to have<br />
an energy rating calculated in accordance with the <strong>Government</strong>’s Standard Assessment Procedure (SAP).<br />
There is no requirement to achieve a particular level of SAP rating but the rating must be notified to the local<br />
authority. SAP ratings no longer form part of the <strong>Technical</strong> <strong>Standards</strong> for compliance with the Building <strong>Standards</strong><br />
Regulations, but instead achievement of a specified CI is one of the ways of complying with Part J.<br />
The following apply when calculating SAP ratings for Building Procedure Regulations purposes and the CI for<br />
Building <strong>Standards</strong> Regulations purposes -<br />
1. The data used in calculations should be obtained from the tables in SAP 2001. The fuel cost data (for<br />
the SAP rating) will be revised in future editions.<br />
2. When the final heating system is unknown, the SAP energy rating notified to the building control body<br />
must be calculated assuming a main system of electric room heaters and a secondary system of electric<br />
heaters, both systems using on-peak electricity.<br />
3. When undertaking SAP energy rating calculations for designs not intended for specific construction sites<br />
(e.g. type designs) the following assumptions should be made -<br />
a. two sides of the dwelling will be sheltered; and<br />
b. the windows, doors and roof windows are all on the east and west elevations; and<br />
c. the solar access factor is 1.0 (average).<br />
4. The rules in 1-3 above apply also when calculating the carbon index.<br />
5. Where a housing development involves large numbers of dwellings it is acceptable for the worst case in<br />
that development to be identified and for a SAP energy rating to be calculated for that dwelling only.<br />
Amdt: September 2001<br />
J
J<br />
Appendix G<br />
Example 1 – Two bedroom mid-terrace house<br />
Diagram G1 Plans of the two bedroom mid-terraced house<br />
6.5m<br />
Table G1 Data for the two bedroom mid-terrace house with conventional gas boiler<br />
Construction element Description Area U-value<br />
Wall Brick/cavity/dense block with 130 mm<br />
blown fibre cavity insulation<br />
30.3 0.30<br />
Roof Pitched roof, 100 mm insulation<br />
between joists, 160 mm on top<br />
27.3 0.16<br />
Ground floor Suspended timber, 115 mm insulation 27.3 0.25<br />
Windows and doors Double glazed low-E, wooden frame 13.7 2.0<br />
Heating Central heating with conventional<br />
gas boiler (efficiency 78%)<br />
Amdt: September 2001<br />
4.2m<br />
2JG<br />
Height to eaves 5m<br />
Ground Floor First Floor<br />
SAP energy rating = 91<br />
CI = 8.2
Example 2 – Three bedroom semi-detached house<br />
Diagram G2 Plans of the three bedroom semi-detached house<br />
7.7m<br />
5.2m<br />
Table G2 Data for the three bedroom semi-detached house with gas condensing boiler<br />
Construction element Description Area U-value<br />
Wall Brick/cavity/dense block with 130 mm<br />
blown fibre cavity insulation<br />
72.5 0.30<br />
Roof Pitched roof, 100 mm insulation between<br />
joists, 160 mm on top<br />
40 0.16<br />
Ground floor Solid concrete, 60 mm insulation 40 0.25<br />
Windows and doors Double glazed, low-E, PVC-U frame 20.0 2.0<br />
Heating Central heating with gas condensing<br />
boiler (efficiency 85%)<br />
3JG<br />
Height to eaves 5m<br />
Ground Floor First Floor<br />
SAP energy rating = 99<br />
CI = 8.3<br />
Appendix G<br />
Amdt: September 2001<br />
J
J<br />
Appendix G<br />
Example 3 – Three bedroom semi-detached house<br />
Diagram G3 Plans of three bedroom semi-detached house<br />
7.7m<br />
Table G3 Data for three bedroom semi-detached house with gas condensing boiler<br />
Construction element Description Area U-value<br />
Wall Brick/cavity/dense block with 130 mm<br />
blown fibre cavity insulation<br />
72.5 0.30<br />
Roof Pitched roof, 100 mm insulation between<br />
joists, 160 mm on top<br />
40 0.16<br />
Ground floor Solid concrete, 60 mm insulation 40 0.25<br />
Windows and doors Double glazed, low-E, PVC-U frame 20.0 2.0<br />
Heating Central heating with gas condensing boiler<br />
(efficiency 85%)<br />
Amdt: September 2001<br />
5.2m<br />
4JG<br />
Height to eaves 5m<br />
Ground Floor First Floor<br />
LPG Gas<br />
SAP energy rating = 72 99<br />
CI = 7.4 8.3
Example 4 – Four bedroom detached house<br />
Diagram G4 Plans of four bedroom detached house<br />
7.3m<br />
8.9m<br />
Table G4 Data for the four bedroom detached house with gas condensing boiler<br />
Construction element Description Area U-value<br />
Wall Brick/partial cavity fill/medium density<br />
block with insulated plasterboard<br />
116.5 0.30<br />
Roof Pitched roof, 100 mm insulation between<br />
joists, 160 mm on top<br />
50 0.16<br />
Ground floor Suspended timber, 150 mm insulation 50 0.25<br />
Windows and doors Double glazed low-E, wood frame 25 2.0<br />
Heating Central heating with gas condensing boiler<br />
(efficiency 89%)<br />
5JG<br />
Height to eaves 5m<br />
Ground Floor First Floor<br />
SAP energy rating = 100<br />
CI = 8.2<br />
Appendix G<br />
Amdt: September 2001<br />
J
J<br />
Appendix G<br />
Example 5 – Two bedroom bungalow<br />
Diagram G5 Plan of the two bedroom bungalow<br />
Table G5 Data for the two bedroom bungalow with gas condensing boiler<br />
Construction element Description Area U-value<br />
Wall Brick/cavity/aerated concrete block<br />
with insulated plasterboard<br />
64.2 0.30<br />
Roof Pitched roof, 100 mm insulation between<br />
joists, 160 mm on top<br />
56.7 0.16<br />
Ground floor Concrete suspended beam and<br />
medium density, 70 mm insulation<br />
56.7 0.25<br />
Windows and doors Double glazed, low-E, PVC-U frame 14.2 2.0<br />
Heating Central heating with gas condensing boiler<br />
(efficiency 87%)<br />
Amdt: September 2001<br />
8.5m<br />
7.0m<br />
6JG<br />
Height to eaves 2.4m<br />
SAP energy rating = 92<br />
CI = 8.2
1JH<br />
Appendix H<br />
Appendix H: Examples illustrating the use of the Heat Loss Method<br />
A detached, four storey office building 45 metres × 13 metres in plan and height 15 metres is to be constructed<br />
with glazing occupying 48% of the external wall area, using windows with a measured U–value of 2.0 W/m 2 K.<br />
No rooflight glazing is proposed. The remaining exposed walls and the roof are to have U-values of<br />
0.30 W/m 2 K and 0.20 W/m 2 K respectively, with the ground floor being insulated with 65 mm expanded polystyrene<br />
with thermal resistance of all-over floor insulation 1.76 m 2 KW, giving a U-value of 0.20 W/m 2 K<br />
(Appendix C).<br />
Proposed building<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
QQQQQQ<br />
¢¢¢¢¢¢<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
QQQQQQ<br />
¢¢¢¢¢¢<br />
;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; QQ ¢¢ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; QQ ¢¢ ;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
QQQQQQ<br />
¢¢¢¢¢¢<br />
;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; QQQQ ¢¢¢¢<br />
;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; QQ ¢¢ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; QQ ¢¢ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; QQ ¢¢ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; QQ ¢¢ ;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
QQQQQQ<br />
¢¢¢¢¢¢<br />
;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; QQQQ ¢¢¢¢<br />
;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; QQ ¢¢ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; QQ ¢¢ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; QQQQ ¢¢¢¢<br />
;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; QQ ¢¢<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
QQQQQQ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; QQ ¢¢<br />
;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; QQQQ ¢¢¢¢;;<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
QQQQQQ<br />
¢¢¢¢¢¢ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; QQ ¢¢ @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; QQ ¢¢<br />
;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; QQQQ ¢¢¢¢ ;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
QQQQQQ<br />
¢¢¢¢¢¢ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; @@ ÀÀ ;; QQ ¢¢<br />
;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; QQQQ ¢¢¢¢ ;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
@@@@@@<br />
ÀÀÀÀÀÀ<br />
;;;;;;<br />
QQQQQQ<br />
¢¢¢¢¢¢<br />
;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; @@@@ ÀÀÀÀ ;;;; QQQQ ¢¢¢¢<br />
13m<br />
¢¢¢¢¢¢15m<br />
Step 1 Calculate the areas of each building element:<br />
area of roof (45 × 13) = 585 m2 area of elevations (45 + 45 + 13 + 13) × 15 = 1740 m 2<br />
area of windows (48% of 1740 m 2 ) = 835 m 2<br />
area of personnel doors = 14 m 2<br />
area of vehicle unloading bay doors = 27 m 2<br />
area of exposed wall (1740 - 835 - 14 - 27) = 864 m 2<br />
area of floor (45 × 13) = 585 m 2<br />
45m<br />
unloading<br />
bay doors<br />
Amdt: September 2001<br />
J
J<br />
Appendix H<br />
Step 2 Calculate the rate of heat loss from the proposed building as follows:<br />
Building element Area (m2 ) U-value (W/m2K) Rate of heat loss (W/K)<br />
Roof 585 0.20 117.0<br />
Exposed walls 864 0.30 259.2<br />
Windows 835 2.0 1670.0<br />
Personnel doors 14 2.0 28.0<br />
Vehicle loading bay doors 27 0.70 18.9<br />
Ground floor 585 0.20 117.0<br />
Total rate of heat loss 2210.1<br />
Notional building<br />
The area of openings in the proposed building is more than the basic allowance in the table to J7.4. So the<br />
basic area allowance of 40% of exposed wall area for windows and 20% of roof area for roof windows should<br />
be assumed for the notional building.<br />
Step 1 Calculate the areas of each building element:<br />
area of rooflights (20% of 585 m2 ) = 117 m2 area of roof (45 × 13) -117 = 468 m2 area of elevations (45 + 45 + 13 + 13) × 15 = 1740 m 2<br />
area of windows and personnel doors (40% of 1740 m 2 ) = 696 m 2<br />
area of vehicle unloading bay doors = 27 m 2<br />
area of exposed wall (1740 - 696 - 27) = 1017 m 2<br />
area of floor (45 × 13) = 585 m 2<br />
Step 2 Calculate the rate of heat loss from the notional building as follows:<br />
Building element Area (m2 ) U-value (w/m2k) Rate of heat loss (w/k)<br />
Rooflights 117 2.0 234.0<br />
Roof 468 0.25 117.0<br />
Exposed walls 1017 0.30 305.1<br />
Windows and personnel doors 696 2.0 1392.0<br />
Vehicle loading bay doors 27 0.7 18.9<br />
Ground floor 585 0.25 146.25<br />
Total rate of heat loss 2213.25<br />
The rate of heat loss from the proposed building is less than that from the notional building and therefore the<br />
requirements of Part J are met.<br />
Amdt: September 2001<br />
2JH
Appendix J: Example lighting calculations<br />
1JJ<br />
Appendix J<br />
J1 Lighting calculation procedure to show that 95% of installed circuit power is comprised of lamps<br />
listed in the table to (J12.1)a.<br />
A new hall and changing rooms are to be added to an existing community centre. The proposed lighting<br />
scheme incorporates lamps that are listed in the table to (J12.1)a. except for some low voltage tungsten halogen<br />
downlighters which are to be installed in the entrance area with local controls. A check therefore has to be<br />
made to show that the low voltage tungsten halogen lamps comprise less than 5% of the overall installed capacity<br />
of the lighting installation.<br />
Main hall<br />
Twenty wall mounted uplighters with 250 W high pressure Sodium lamps are to provide general lighting needs.<br />
The uplighters are to be mounted 7 metres above the floor. On plan, the furthest light is 20.5 metres from its<br />
switch, which is less than three times the height of the light above the floor.<br />
It is also proposed to provide twenty 18 W compact fluorescent lights as an additional system enabling instant<br />
background lighting whenever needed.<br />
Changing rooms, corridors and entrance<br />
Ten 58 W, high frequency fluorescent light fittings are to be provided in the changing rooms and controlled by<br />
occupancy detectors. Six more 58 W fluorescent light fittings are to be located in the corridors and the<br />
entrance areas and switched locally. Additionally, in the entrance area there are to be the six 50 W tungsten<br />
halogen downlighters noted above.<br />
Calculation<br />
A schedule of light fittings is prepared as follows:<br />
Table J1 Schedule of light fittings<br />
Position Number Description of Circuit Watts Total circuit<br />
light source per lamp Watts (W)<br />
Main hall 20 250 W SON 286 W 5720<br />
Main hall 20 18 W compact fluorescent 23 W 460<br />
Entrance, changing<br />
rooms and corridors<br />
16 58 W HF fluorescent 64 W 1024<br />
Entrance 6 50 W low voltage tungsten halogen 55 W 330<br />
Total = 7534 W<br />
The percentage of circuit Watts consumed by lamps not listed in the table to (J12.1)a.:<br />
= 330 × 100 = 4.4%<br />
—————<br />
7534<br />
Therefore, more than 95% of the installed lighting capacity, in circuit Watts, is from light sources listed in the<br />
table to (J12.1)a. The switching arrangements comply with J12.3. The proposed lighting scheme therefore<br />
meets the requirements of Part J.<br />
Amdt: September 2001<br />
J
J<br />
Appendix J<br />
J2 Lighting calculation procedure to show average circuit efficacy complies with (J12.1)b.<br />
A lighting scheme is proposed for a new public house comprising a mixture of concealed perimeter lighting<br />
using high frequency fluorescent fittings and supplementary compact fluorescent lamps in the dining area.<br />
Lights in the dining and lounge areas are to be switched locally from behind the bar. Lighting to kitchens and<br />
toilets is to be switched locally.<br />
Table J2 shows a schedule of the light sources proposed together with the calculation of the overall average<br />
circuit efficacy.<br />
Table J2 Schedule of light fittings<br />
Position Number Description Circuit Lumen Total Total<br />
Watts (W) output (lm) circuit lamp lumen<br />
per lamp per lamp Watts (W) output (lm)<br />
Over tables 20 11 W compact fluorescent 16 900 320 18,000<br />
Concealed perimeter 24 32 W T8 fluorescent high 36 3300 864 79,200<br />
and bar lighting frequency ballast<br />
Toilets and 6 18 W compact fluorescent 23 1200 138 7,200<br />
circulation with mains frequency ballast<br />
Kitchens 6 50 W, 1500 T8 fluorescent<br />
with high frequency ballast<br />
56 5200 336 31,200<br />
From Table J2, the total lumen output of the lamps in the installation is 135,600 lumens.<br />
The total circuit Watts of the installation is 1658 Watts.<br />
Therefore, the average circuit efficacy is:<br />
= 135,600 ———— = 81.8 lumens/Watt<br />
1658<br />
The proposed lighting scheme therefore meets the requirements of Part J.<br />
Amdt: September 2001<br />
2JJ<br />
Totals 1658 135,600<br />
Note: If 60 W tungsten lamps were used in the dining area instead of the 11 W compact fluorescent lamps<br />
actually proposed, the average circuit efficacy would drop to 51.9 lumens/W, which would not be sufficient<br />
to comply with Part J.
1JK<br />
Appendix K<br />
Appendix K: Performance assessment methods for office buildings<br />
K1. Assessing the contribution to carbon emissions due to building services design and operation<br />
The efficiencies of buildings, and of the services systems that produce the indoor conditions required by occupants,<br />
can be compared provided that a consistent system is used to describe the buildings and their energy use.<br />
Applying such a consistent approach to buildings of purpose group 3 has allowed energy consumption benchmarks<br />
to be developed with which the performance of existing buildings, or the likely performance of new<br />
designs, can be compared. The benchmarks result from information obtained from surveys of operational<br />
buildings, and are included in DETR’s Energy Consumption Guide 19 “Energy use in offices” (ECON 19),<br />
available from BRECSU tel. 01923 664258.<br />
K1.1 Performance benchmarks<br />
The information contained in ECON 19 provides benchmarks for the energy consumed by air conditioning and<br />
mechanical ventilation (ACMV), heating and lighting services, together with benchmark information describing<br />
the hours of use of the equipment. Benchmarks also describe the energy consumed by the additional equipment<br />
necessary to support use of the building for typical office activities. The benchmarks refer to buildings of<br />
purpose group 3 described as representing ‘typical’ and ‘good practice’ for the sector.<br />
K1.2 Design assessment<br />
The annual energy likely to be consumed by a particular service can be estimated as the product of the total<br />
installed input power rating of the plant installed to provide the service and the annual hours of use of that plant<br />
at the equivalent of full load. The annual hours of use can be considered to be the result of combining a benchmark<br />
value for the ‘typical’ hours of use of the service with a management factor that acts to reduce or increase<br />
this value. The management factor is a number related to the provisions that the design incorporates that have<br />
the potential to help the occupier control and manage the use of the plant.<br />
The Carbon Performance Index (CPI) referred to in Section K2 is a technique for assessing the likely performance<br />
of building services systems using this design information. It uses benchmarks consistent with ECON19<br />
and is intended to estimate the potential for efficient operation of building services systems using information<br />
available at the design or construction stage.<br />
Amdt: September 2001<br />
J
J<br />
Appendix K<br />
K1.3 Performance assessment<br />
The inclusion of meters improves the confidence with which occupiers may assess their buildings’ performance<br />
by estimating the energy consumed by servicing plant and the additional equipment required for the full operation<br />
of the building.<br />
K1.3.1A technique of estimating and measuring operational energy consumption, and comparing the achieved<br />
performance of buildings with the ECON19 benchmarks, has been developed to assess the achieved<br />
performance of buildings of purpose group 3. This method is described in CIBSE <strong>Technical</strong> Memoranda<br />
TM22 “Energy Assessment and Reporting Methodology: Office Assessment Method”.<br />
K1.3.2A means of comparing the design of services with benchmarks of installed load and energy use is<br />
described in CIBSE Guide “Energy Efficiency in Buildings”, 1998.<br />
K1.3.3The results of ongoing performance assessment could be used to provide valuable information from<br />
which to maintain and improve performance benchmarks, and hence the CPI method, and to inform the<br />
design process.<br />
K2 The carbon performance index (CPI)<br />
K2.1 The CPI for mechanical ventilation - CPI (MV)<br />
The assessment is based on the calculation of a Carbon Performance Index using the following relationship:<br />
CPI (MV) =<br />
Amdt: September 2001<br />
MV<br />
——————————<br />
(PD × HD × CD × FD)<br />
Where the value of the factor MV = 800 has been set so that the design is considered to represent acceptable<br />
practice where the result of the calculation is 100 or greater.<br />
For the system installed to provide mechanical ventilation, the factors PD, HD, CD and FD are as defined below:<br />
PD is the total installed capacity (sum of the input kW ratings) of the fans installed to provide<br />
mechanical ventilation divided by the relevant treated area (square metres);<br />
HD is the typical annual equivalent hours of full load operation, and is taken as 3 700 hours per year;<br />
CD is the conversion factor relating the emissions of carbon to the fuel used, here electricity, in<br />
kgC/kWh. (Table K 0);<br />
FD is a factor which depends on the provisions that are made to control and manage the installed<br />
plant and which could act to improve the annual efficiency of the plant above that of the typical<br />
installation, or to reduce the effective annual hours of use. (See Table K1)<br />
2JK
K2.2 The CPI for air conditioning - CPI (ACMV)<br />
3JK<br />
Appendix K<br />
The assessment is based on the calculation of a Carbon Performance Index using the following relationship:<br />
CPI (ACMV)<br />
=<br />
ACMV<br />
————————————————————<br />
(PD × HD × CD × FD) + (PR × HR × CR × FR)<br />
The value of the factor ACMV = 1200 has been set so that the design is considered to represent acceptable<br />
practice where the result of the calculation is 100 or greater.<br />
For the distribution system transferring cooled medium to the conditioned spaces, the factors PD, HD, CD and FD<br />
are as defined below:<br />
PD is the total installed capacity (sum of the input kW ratings) of the fans and pumps installed to<br />
distribute air and/or cooled media around the building divided by the relevant treated area (square<br />
metres);<br />
HD is the typical annual equivalent hours of full load operation, and is taken as 3 700 hours per year;<br />
CD is the conversion factor relating the emissions of carbon to the fuel used, here electricity, in<br />
kgC/kWh. (Table K 0);<br />
FD is a factor which depends on the provisions that are made to control and manage the installed<br />
plant and which could act to improve the annual efficiency of the plant above that of the typical<br />
installation, or to reduce the effective annual hours of use. (See Table K2).<br />
For the refrigeration system, the factors PR, HR, CR and FR are as defined below:<br />
PR is the total installed capacity (sum of the input kW ratings) of the plant installed to provide the<br />
cooling or refrigeration function divided by the relevant treated area (square metres);<br />
HR is the typical annual equivalent hours of full load operation of the refrigeration plant, and is taken<br />
as 1 000 hours per year;<br />
CR is the conversion factor relating the emissions of Carbon to the fuel used, here most frequently<br />
electricity, sometimes gas, in kgC/kWh, from Table K 0 below;<br />
FR is a factor which depends on the provisions that are made to control and manage the installed<br />
plant and which could act to improve the annual efficiency of the plant above that of the typical<br />
installation, or to reduce the effective annual hours of use. (See Table K3).<br />
Amdt: September 2001<br />
J
J<br />
Appendix K<br />
Table K 0: Carbon emission factors<br />
Delivered energy Carbon emission factor (kgC/kWh)<br />
Gas 0.053<br />
Oil 0.074<br />
Coal 0.086<br />
Electricity (average) 0.139<br />
K2.3 Plant control and management factors<br />
Tables K1, K2 and K3 below itemise a number of control and management features which could act to improve<br />
the annual efficiency of the relevant plant above that of the typical installation, or to reduce the effective annual<br />
hours of use. Values to be associated with each feature are obtained from column A, B or C as appropriate and<br />
the resultant factor is obtained by multiplying together all of the individual values obtained. Values are selected<br />
from columns A, B and C of the table depending on the extent to which facilities for monitoring and reporting<br />
are provided, as follows:<br />
Column C No monitoring provided.<br />
Column B Provision of energy metering of plant and/or metering of plant hours run, and/or monitoring<br />
of internal temperatures in zones.<br />
Column A Provision as B above, plus the ability to draw attention to ‘out of range’ values.<br />
Table K1: To obtain factor (FD) for the air distribution system<br />
Plant management features Values<br />
A B C<br />
i. Operation in mixed mode with natural ventilation 0.85 0.9 0.95<br />
ii. Controls which restrict the hours of operation<br />
of distribution system<br />
0.9 0.93 0.95<br />
iii. Efficient means of controlling air flow rate 0.75 0.85 0.95<br />
Amdt: September 2001<br />
Column product (FD)<br />
The plant management features for Table K1 are more fully described below:<br />
i. Mixed mode operation available as a result of including sufficient openable windows to provide the<br />
required internal environment from natural ventilation when outdoor conditions permit. This may only<br />
apply where the perimeter zone is greater than 80% of the treated floor area.<br />
ii. Control capable of limiting plant operation to occupancy hours with the exceptions noted below in<br />
which operation outside the hours of occupancy forms a necessary part of the efficient use of the system:<br />
for control of condensation,<br />
for optimum start/stop control, or<br />
as part of a ‘night cooling’ strategy.<br />
iii. Air flow rate controlled by a variable motor speed control which efficiently reduces input power at<br />
reduced output; variable pitch fan blades. (damper, throttle or inlet guide vane controls do not attract<br />
this factor).<br />
4JK
Table K2: To obtain factor (FD) for the cooling distribution system<br />
5JK<br />
Appendix K<br />
Plant management features Values<br />
A B C<br />
i. Operation in mixed mode with natural ventilation 0.85 0.9 0.95<br />
ii. Controls which restrict the hours of operation<br />
of distribution system<br />
0.9 0.93 0.95<br />
iii. Efficient means of controlling air flow rate 0.75 0.85 0.95<br />
Column product (FD)<br />
The plant management features for Table K2 are more fully described below:<br />
i. Mixed mode operation available as a result of including sufficient openable windows to provide the<br />
required internal environment from natural ventilation when outdoor conditions permit. This may only<br />
apply where the perimeter zone is greater than 80% of the treated floor area. This factor is credited only<br />
where interlocks are provided to inhibit the air conditioning supply in zones with opened windows.<br />
ii., iii. are as described in Table K1 above for mechanical ventilation.<br />
Amdt: September 2001<br />
J
J<br />
Appendix K<br />
Table K3: To obtain factor (FR) for the refrigeration plant<br />
Plant management features Values<br />
A B C<br />
i. Free cooling from cooling tower 0.9 0.93 0.95<br />
ii. Variation of fresh air using economy<br />
cycle or mixed mode operation<br />
0.85 0.9 0.95<br />
iii. Controls to restrict hours of operation 0.85 0.9 0.95<br />
iv. Controls to prevent simultaneous heating and<br />
cooling in the same zone<br />
0.9 0.93 0.95<br />
v. Efficient control of plant capacity, including modular plant 0.9 0.93 0.95<br />
vi. Partial ice thermal storage 1.8 1.86 1.9<br />
vii. Full ice thermal storage 0.9 0.93 0.95<br />
Amdt: September 2001<br />
Column product (FR)<br />
The plant management features for Table K3 are more fully described below:<br />
i. Systems that permit cooling to be obtained without the operation of refrigeration equipment when conditions<br />
allow. (e.g., ‘strainer cycle’; ‘thermosyphon’.)<br />
ii. Systems that incorporate an economy cycle in which the fresh air and recirculated air mix is controlled<br />
by dampers, or where mixed mode operation is available as defined below Table K2.<br />
iii. Controls that are capable of limiting plant operation to the hours of occupancy of the building, with the<br />
exceptions noted below in which operation outside the hours of occupancy forms a necessary part of the<br />
efficient use of the system:<br />
for control of condensation,<br />
for optimum start/stop control, or<br />
as part of a strategy to pre-cool the building overnight using outside air.<br />
iv. Controls that include an interlock or dead band capable of precluding simultaneous heating and cooling<br />
in the same zone.<br />
v. Refrigeration plant capacity controlled on-line by means that reduce input power in proportion to<br />
cooling demand and maintain good part load efficiencies (e.g. modular plant with sequence controls;<br />
variable speed compressor). (Hot gas bypass control does not attract this factor).<br />
vi. Partial ice storage in which the chiller is intended to operate continuously, charging the store overnight<br />
and supplementing its output during occupancy.<br />
vii. Full ice storage in which the chiller operates only to recharge the thermal store overnight and outside<br />
occupancy hours.<br />
6JK
K2.4 Example CPI calculation for an office proposal including air conditioning<br />
7JK<br />
Appendix K<br />
In this example it is intended to include an air conditioning system in a new office building. The relevant<br />
details from the proposal are that:<br />
The total area to be treated by the system is 3 000 m 2 .<br />
Cooling will be provided by two speed-controlled electrically powered compressors, with a total rated<br />
input power of 150 kW.<br />
The refrigeration compressor energy consumption will be metered.<br />
The fans used to distribute cooled air to treated spaces have a total rated input power of 35 kW.<br />
The fan energy consumption will be metered.<br />
A time clock control is to be provided so that the operation of the cooling system (refrigeration and air<br />
distribution) may be restricted to occupancy hours.<br />
Windows in treated areas will be openable so that natural ventilation may be used, and the cooling<br />
system turned off, when required.<br />
The CPI calculation for air conditioning is:<br />
CPI (ACMV)<br />
=<br />
1200<br />
————————————————————<br />
(PD × HD × CD × FD) + (PR × HR × CR × FR)<br />
In this proposal, for the cooling distribution system:<br />
PD is the total installed capacity (sum of the input kW ratings) of the fans divided by the relevant treated<br />
area (square metres)<br />
= 0.0117 (35/3000)<br />
HD = 3 700 hours per year<br />
CD is the carbon conversion factor for electricity, in kgC/kWh. (Table K 0)<br />
= 0.139<br />
FD = 0.84, determined from Table K2 as follows:<br />
As the major plant will be metered, factors from Column B of the table are used. Then:<br />
Factor for including the opportunity for natural ventilation (mixed mode operation) = 0.9;<br />
Factor for including provision to restrict the hours of use of the system (time control) = 0.93;<br />
Column product (FD) = 0.84. (0.9 × 0.93)<br />
And, for the refrigeration system:<br />
PR = the total installed capacity (sum of the input kW ratings) of the refrigeration plant divided by the<br />
treated area (square metres),<br />
= 0.05 (150/3000).<br />
HR = 1 000 hours per year.<br />
CR = the carbon conversion factor for electricity, in kgC/kWh. (Table K 0),<br />
= 0.139.<br />
FR = 0.75, determined from Table K3 as follows:<br />
As the major plant will be metered, factors from Column B of the table are used. Then:<br />
Factor for including the opportunity for natural ventilation (mixed mode operation) = 0.9;<br />
Factor for including provision to restrict the hours of use of the system (time control) = 0.9;<br />
Factor for providing efficient means of controlling plant capacity = 0.93;<br />
Column product (FR) = 0.75. (0.9 × 0.9 × 0.93)<br />
Amdt: September 2001<br />
J
J<br />
Appendix K<br />
The CPI calculation is then:<br />
1200<br />
CPI (ACMV) = —————————————————————————— = 114<br />
(0.0117 × 3700 × 0.139 × 0.84) + (0.05 × 1000 × 0.139 × 0.75)<br />
The proposal therefore achieves a calculated index of 114, which is better than the required target CPI of 100<br />
and would therefore be acceptable on this basis.<br />
[The index of 114 indicates that, under similar patterns of occupancy and use, the system proposed would be<br />
likely to cause about 10% less carbon emission than would be caused by the use of air conditioning in the<br />
typical air conditioned building defined in ECON 19].<br />
Amdt: September 2001<br />
8JK
VENTILATION OF<br />
BUILDINGSK
Contents<br />
INTRODUCTION<br />
REGULATION 23<br />
Ventilation of buildings<br />
THE STANDARDS<br />
K1 Application of Part K K1.1- K1.4<br />
K2 Ventilation of buildings other than garages<br />
K3<br />
Ventilation of buildings other than garages K2.1<br />
Ventilation of garages<br />
Large garages K3.1<br />
Small garages K3.2<br />
K4 General ventilation requirements<br />
Natural ventilation K4.1- K4.5<br />
Mechanical ventilation K4.6- K4.10<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(K2.1) Ventilation of buildings other than garages<br />
(K3.1) Large garages<br />
(K3.2) Small garages<br />
(K4.1,<br />
K4.3)<br />
Natural ventilation<br />
(K4.9,<br />
K4.10)<br />
Mechanical ventilation<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A, General.<br />
3K<br />
Amdt: December 1999<br />
K
5K<br />
Introduction<br />
1. The intention of this Part is to ensure reasonable provision<br />
for an adequate supply of air for human occupation of a<br />
building. Ventilation can be provided by natural means,<br />
natural with mechanical assistance or wholly mechanical.<br />
2. The standards apply to all buildings covered by the Regulations<br />
except to a building, or part of a building, to which<br />
the Factories Act applies. Buildings subject to the Factories<br />
Act have very diverse ventilation requirements which will be<br />
determined by the Factories Inspectorate of the Health and<br />
Safety Executive. Those involved in the provision of such a<br />
building are advised to consult the Inspectorate at an early<br />
stage.<br />
3. The ventilation of a building can have a significant affect<br />
on energy consumption and a thorough assessment of natural<br />
as against mechanical ventilation should be made as the<br />
decision could significantly affect the energy efficiency of a<br />
building.<br />
4. Increased standards of insulation and “tighter” construction<br />
of buildings, which reduces the number of natural air<br />
changes, increase the risk of condensation particularly in<br />
dwellings. The standards of ventilation given for moisture<br />
producing areas are the minimum necessary to provide<br />
means of combating condensation. The effect of these standards<br />
will be determined by design and workmanship both of<br />
the ventilation arrangements and the building as a whole.<br />
5. There are other requirements for ventilation which will<br />
have to be taken into account in certain cases. Part E for<br />
example, has requirements for smoke ventilation of escape<br />
routes in case of fire. Where these would meet the requirements<br />
of this Part the provision need not be duplicated. Part<br />
F has requirements related to combustion appliances, in particular,<br />
where an open-flued appliance takes combustion air<br />
from within a dwelling. These are in addition to, and must be<br />
kept separate from, any openings required by this Part. It is<br />
therefore particularly important that, as in common with all<br />
work requiring building warrant, this Part is read in conjunction<br />
with all other Parts and particularly Part F.<br />
Amdt: December 1999<br />
K
K<br />
Regulation 23<br />
Ventilation of buildings<br />
23.(1) A building to which this regulation applies<br />
shall have means of providing an adequate<br />
supply of air for users of the building.<br />
(2) This regulation shall apply to all buildings<br />
except buildings or any part of a building to<br />
which the Factories Act 1961 (a) applies.<br />
(a) 1961 c.34<br />
Amdt: December 1999<br />
6K
The standards<br />
K1 Application of Part K<br />
K1.1 This Part sets out the required standards for Regulation 23.<br />
K1.1 – K2.1<br />
K1.2 The standards apply to all buildings except to a building, or part of a building, specified in Regulation<br />
23(2).<br />
K1.3 The volume of any space for ventilation purposes is the internal cubic capacity of the space,<br />
except -<br />
a. where the space is for vehicle parking, any volume more than 3 metres above any floor level in<br />
that space is to be disregarded; and<br />
b. in any other space, any volume more than 6 metres above any floor level in that space is to be<br />
disregarded.<br />
K1.4 Any requirement for an area of opening may be met by a combination of areas.<br />
K2 Ventilation of buildings other than garages<br />
VENTILATION OF BUILDINGS OTHER THAN GARAGES<br />
K2.1* A building other than a garage must have adequate provision for ventilation by natural means, mechanical<br />
means, or a combination of natural and mechanical means,<br />
except -<br />
a. there is no requirement to ventilate a storage room used only for storage requiring a controlled<br />
temperature; and<br />
b. there is no requirement to ventilate a room with a floor area of not more than 4 square metres; and<br />
c. a passive stack ventilation system is only permissible in a building of purpose group 1 with no<br />
storey at a height of more than 7.5 metres; and<br />
d. a room where the cubic space per occupant is not more than 3 cubic metres must have mechanical<br />
ventilation.<br />
7K<br />
Amdt: September 2001<br />
K
K<br />
K3.1– K4.5<br />
K3 Ventilation of garages<br />
LARGE GARAGES<br />
K3.1* A garage with a floor area greater than 60 square metres for the parking of motor vehicles must have<br />
adequate provision for natural or mechanical ventilation on every storey.<br />
SMALL GARAGES<br />
K3.2* A garage with a floor area of at least 30 square metres but not more than 60 square metres used for the<br />
parking of motor vehicles must have adequate provision for natural or mechanical ventilation.<br />
K4 General ventilation requirements<br />
NATURAL VENTILATION<br />
K4.1* Ventilation must be to the outside air,<br />
except -<br />
a. a ventilator serving a room in a dwelling may open into a conservatory provided that the ventilation<br />
of the conservatory is to the outside air and is calculated on the basis of the total floor area<br />
of the room and the conservatory; and<br />
b. a trickle ventilator serving a bathroom or shower-room may open into a bedroom from which it<br />
has direct access, provided the bedroom is fitted with a suitable trickle ventilator.<br />
K4.2 Some part of the opening part of a ventilator, including a trickle ventilator, must be at least 1.75 metres<br />
above floor level.<br />
K4.3* A passive stack ventilation system must be suitably constructed and installed.<br />
K4.4 Each passive stack ventilation system must -<br />
a. incorporate an automatic humidity sensitive ventilation inlet grille; and<br />
b. where it passes through a roof space or other unheated space or where it extends above roof level,<br />
be insulated with at least 25mm thick material having a thermal conductivity of 0.04 W/mK.<br />
K4.5 The duct or casing forming a passive stack ventilation system serving a kitchen must be non-combustible<br />
except -<br />
where it passes through a roof space,<br />
Amdt: December 1999<br />
8K
MECHANICAL VENTILATION<br />
K4.6 Where a mechanical ventilation system serves more than one dwelling it must have a duplicate motor<br />
and be separate from any other ventilation system installed for any other purpose.<br />
K4.7 Where a mechanical ventilation system gathers extracts into a common duct for discharge to an outlet,<br />
no connection to the system is permitted between any exhaust fan and the outlet.<br />
K4.8 Mechanical ventilation must be to the outside air. It may be via a duct or heat exchanger.<br />
K4.9* An inlet to, and an outlet from, a mechanical ventilation system must be suitably installed so as to<br />
avoid contamination of the air supply to the system.<br />
K4.10* A mechanical ventilation system must be constructed to ensure, as far as is reasonably practicable, the<br />
avoidance of contamination by legionella.<br />
9K<br />
K4.6 – K4.10<br />
Amdt: December 1999<br />
K
10K
Provisions deemed to satisfy the standards<br />
VENTILATION OF BUILDINGS OTHER THAN GARAGES<br />
(K2.1) The requirements of K2.1 will be met -<br />
a. for a room in a building other than a dwelling, by the provision of a ventilator with an opening<br />
area of at least 1/30th of the floor area of the room it serves; and where the area of the room is<br />
i. not more than 10 square metres, a trickle ventilator with an opening area of at least<br />
4000 mm 2; or<br />
ii. more than 10 square metres, a trickle ventilator with an opening area of at least 400 mm 2<br />
for each square metre of room area; or<br />
b. for any building with natural ventilation by -<br />
i. compliance with Section 3 of BS5925: 1991 (1995); or<br />
ii. CIBSE Guide A: 1986, Design data, Section A4, Air infiltration and natural ventilation; or<br />
c. for any building with mechanical ventilation (there are additional provisions in Part E for<br />
mechanical ventilation systems), by -<br />
i. compliance with BS5720: 1979; or<br />
ii. CIBSE Guide B: 1986, Section B2; or<br />
d. for dwellings only, by -<br />
i. compliance with the requirements of BRE Digest 398; or<br />
ii. the table to this specification -<br />
11K<br />
(K2.1)<br />
Amdt: December 1999<br />
K
K<br />
(K2.1) – (K3.1)<br />
LARGE GARAGES<br />
Table to (K2.1): Ventilation of a dwelling<br />
Space Minimum Ventilation Requirements Trickle<br />
Ventilation<br />
(minimum)<br />
[Note 1]<br />
Apartment a ventilator with an opening area of 1/30th of 8000 mm 2<br />
the floor area it serves.<br />
Kitchen either - 4000 mm 2<br />
a. mechanical extraction capable of 30 litres/sec<br />
(intermittent) above a hob [Note 2];<br />
b. mechanical extraction capable of 60 litres/sec<br />
(intermittent) if elsewhere [Note 2]; or<br />
c. a passive stack ventilation system [Notes 3 & 4].<br />
Utility room either - 4000 mm 2<br />
a. mechanical extraction capable of 30 litres/sec<br />
(intermittent) [Note 2]; or<br />
b. a passive stack ventilation system [Notes 3 & 4].<br />
Bathroom or either - 4000 mm 2<br />
shower-room a. mechanical extraction capable of 15 litres/sec<br />
(with or without (intermittent); or<br />
a WC). b. a passive stack ventilation system [Note 3].<br />
Toilet either - 4000 mm 2<br />
a. a ventilator with an opening area of 1/30th<br />
of the floor area it serves; or<br />
b. mechanical extraction capable of 3 air changes per hour.<br />
Notes:<br />
1. The overall provision of trickle ventilation in a dwelling may be provided at an<br />
average of 6000 mm 2 per room, with a minimum provision of 4000 mm 2 in each<br />
apartment.<br />
2. Refer to Part F where an extract fan is fitted in a building containing an open-flued<br />
combustion appliance.<br />
3. Refer to Part D where a passive stack ventilation system is installed in a building<br />
of purpose sub-group 1A.<br />
4. The flue of an open-flued combustion appliance may serve as a passive stack<br />
ventilation system provided that either -<br />
a. the appliance is a solid fuel appliance and is the primary source of heating,<br />
cooking or hot water production; or<br />
b. the flue has an unobstructed area equivalent to a 125mm diameter duct and<br />
the appliance’s combustion air inlet and dilution air inlet are permanently<br />
open, i.e. there is a path with no control dampers which could block the flow,<br />
or the ventilation path can be left open when the appliance is not in use.<br />
(K3.1) The requirements of K3.1 will be met by a parking garage constructed -<br />
Amdt: September 2001<br />
a. in accordance with Section B2 of the CIBSE Guide: 1986, -<br />
i. to give carbon monoxide concentrations of not more than 50 parts per million averaged<br />
over an eight hour period; and<br />
ii. to restrict peak concentrations of carbon monoxide at areas of traffic concentration such as<br />
ramps and exits to not more than 100 parts per million for periods not exceeding 15 minutes;<br />
12K
. in accordance with Section 4 of the Association for Petroleum and Explosive Administration’s<br />
“Code of practice for ground floor, multi-storey and underground car parks”, and Section B2 of<br />
the CIBSE Guide B: 1986;<br />
SMALL GARAGES<br />
c. where the garage is naturally ventilated, by providing openings in the walls on every storey of at<br />
least 1/20th of the floor area of that storey with at least half of such area in opposite walls;<br />
d. where the garage is mechanically ventilated, by providing a system capable of at least 6 air<br />
changes per hour and at least 10 air changes per hour where traffic concentrations occur; or<br />
e. where there is a combined natural/mechanical ventilation system, by providing -<br />
i. openings in the walls on every storey of at least 1/40th of the floor area of that storey<br />
with at least half of such area in opposite walls; and<br />
ii. a mechanical system capable of at least 3 air changes per hour.<br />
(K3.2) The requirements of K3.2 will be met -<br />
a. where the garage is naturally ventilated, by providing at least 2 permanent ventilators, each with<br />
an open area of at least 1/3000th of the floor area they serve, positioned to encourage through<br />
ventilation with one of the permanent ventilators being not more than 600mm above floor level; or<br />
b. where the garage is mechanically ventilated, by providing a ventilation system -<br />
NATURAL VENTILATION<br />
i. capable of continuous operation, designed to provide at least 2 air changes per hour;<br />
ii. independent of any other ventilation system; and<br />
iii. constructed so that two-thirds of the exhaust air is extracted from outlets not more than<br />
600mm above floor level.<br />
(K4.1) The requirements of K4.1b will be met where the trickle ventilator fitted in the bedroom complies with<br />
the table to (K2.1).<br />
(K4.3) The requirements of K4.3 will be met by a passive stack ventilation system constructed and installed<br />
fully in accordance with Information Paper BRE IP 13/94.<br />
MECHANICAL VENTILATION<br />
(K4.9) The requirements of K4.9 will be met where the inlet to, and outlet from, the mechanical ventilation<br />
system are installed in accordance with Clause 2.3.3 of BS5720: 1979.<br />
(K4.10) The requirements of K4.10 will be met where the ventilation system is constructed in accordance with<br />
the requirements of paragraphs 70 to 84 of “The control of legionellosis including legionnaires’<br />
disease”.<br />
13K<br />
(K3.1) – (K4.10)<br />
Amdt: December 1999<br />
K
14K
DRAINAGE AND<br />
SANITARY FACILITIESM
Contents<br />
INTRODUCTION<br />
REGULATION 24<br />
Drainage<br />
REGULATION 25<br />
Sanitary facilities<br />
THE STANDARDS<br />
M1 Application of Part M M1.1-M1.4<br />
M2 Drainage<br />
Wastewater and surface water drainage M2.1-M2.5<br />
Discharges into a drainage system M2.6-M2.7<br />
Discharges from a drainage system M2.8-M2.9<br />
M3 Private wastewater treatment systems<br />
Private wastewater treatment plants or septic tanks M3.1-M3.4<br />
Infiltration systems M3.5-M3.7<br />
M4 Sanitary facilities<br />
Sanitary facilities in a dwelling M4.1-M4.3<br />
Sanitary facilities in a building other than a dwelling M4.4-M4.9<br />
General requirements for a toilet M4.10<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(M2.1-M2.5) Wastewater and surface water drainage<br />
(M2.6-M2.7) Discharges into a drainage system<br />
(M2.9) Discharges from a drainage system<br />
(M3.1-M3.4) Private wastewater treatment plants or septic tanks<br />
(M3.5-M3.7) Infiltration systems<br />
(M4.1-M4.2) Sanitary facilities in a dwelling<br />
(M4.4-M4.8) Sanitary facilities in a building other than a dwelling<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A, (General).<br />
3M<br />
Amdt: September 2001<br />
M
Introduction<br />
1. The intention of this Part is to ensure safe and adequate drainage from a building and from paved surfaces<br />
within the curtilage of a building. It is also intended that there should be suitable and sufficient provision of<br />
sanitary facilities for buildings, other than schools which are covered by their own legislation. Suitable facilities<br />
for disabled people in schools will however require to be provided.<br />
2. The standards in relation to Regulation 24 are intended to ensure that wastewater and surface water from<br />
a building are carried to a suitable point of disposal. Also any pipework and fittings by which wastewater and<br />
surface water are carried should be of suitable size and constructed to minimise the likelihood of leakage or<br />
blockage. It is also intended that the drainage system is sealed and vented in such a way as to prevent the<br />
escape of foul air into the building. In a dwelling, where it is not reasonably practicable to connect a wastewater<br />
drainage system to a public sewerage system, it will now be acceptable to install waterless closets.<br />
Installation of a waterless closet in a building other than a dwelling is not permitted except by a relaxation<br />
which may be granted by the local authority dependant upon local circumstances. There is also the option now<br />
to discharge greywater (from baths, showers, washbasins, sinks and washing machines) separately to ground.<br />
3. Conventional piped surface water drainage systems can cause flooding and pollution and disrupt the water<br />
cycle to the detriment of water resources and the natural environment. An alternative approach is needed to<br />
reach a more sustainable solution. Sustainable urban drainage is a concept that focuses decisions about<br />
drainage on the environment and people. The concept takes account of the quantity and quality of surface<br />
water run-off and the amenity value of surface water in the urban environment. Sustainable Urban Drainage<br />
Systems (SUDS) are physical structures that are designed to store, treat and control surface water run-off<br />
making provision for the concept for sustainable urban drainage. Drainage methods inspired by natural<br />
processes therefore have now been introduced for surface water drainage. The approach to the disposal of<br />
surface water from within the curtilage of a building clearly needs to be considered at the earliest stage in the<br />
design development of a project. (See also the <strong>Scottish</strong> Executive Development Department’s Planning<br />
Advice Note No. PAN 61 - Planning and Sustainable Urban Drainage Systems)<br />
4. A developer should be aware that, where mains drainage is not available, the <strong>Scottish</strong> Environment Protection<br />
Agency (SEPA) may, in some instances, issue a Prohibition Notice (a method whereby discharges are<br />
controlled). The local authority may wish to establish whether such a notice has been issued or whether SEPA<br />
intends to do so. A consent from SEPA is not automatically required for discharge to a soakaway but is always<br />
required before discharge of wastewater to controlled waters is permitted.<br />
5. The standards in relation to Regulation 25 are intended to ensure the minimum provision of sanitary facilities<br />
considered necessary on grounds of health and convenience. To establish an adequate provision, an estimate<br />
of the number of persons likely to use the building must be submitted in writing to the local authority.<br />
In most cases a precise number can be provided or a realistic estimate made. Where the end use of the building<br />
is unknown at initial design stage, or an estimate cannot be made, it will be necessary to confirm the<br />
numbers later in the contract, perhaps through a staged building warrant application. The table of sanitary<br />
facilities for staff is based on tables in the Approved Code of Practice to the Workplace (health, safety and<br />
welfare) Regulations 1992 and the cost implications of non-conformity should prevent submission of inappropriate<br />
figures.<br />
6. It is the intention that, where reasonably practicable, all dwellings shall be provided with accessible sanitary<br />
facilities for disabled people but it is recognised however that not all accessible sanitary facilities will be<br />
fully accessible to all disabled people. In all other buildings, where sanitary facilities are provided, facilities<br />
for disabled people will normally be required.<br />
7. Unless stated to the contrary, the term disabled people always includes wheelchair users.<br />
5M<br />
Amdt: September 2001<br />
M
M<br />
Regulations 24, 25<br />
Drainage<br />
24. A building shall be provided with adequate<br />
drainage to ensure the safe and hygienic<br />
disposal of wastewater from the building, and<br />
of surface water from the building and paved<br />
surfaces within the curtilage of the building.<br />
Sanitary facilities<br />
25.(1) A building, to which this Regulation applies,<br />
shall be provided with adequate and suitable<br />
sanitary facilities.<br />
(2) This Regulation shall apply to all buildings<br />
other than a building or any part of a building<br />
to which the School Premises (General<br />
Requirements and <strong>Standards</strong>) (Scotland)<br />
Regulations 1967 to 1979(a) apply in relation<br />
to numbers of sanitary facilities only.<br />
(3) This Regulation shall not be subject to specification<br />
in a notice served under section 11 of<br />
the Act.<br />
(a) SI 1967/1199, 1973/322 and 1979/1186.<br />
Amdt: September 2001<br />
6M
The <strong>Standards</strong><br />
M1 Application of Part M<br />
M1.1 This Part sets out the required standards for Regulations 24 and 25.<br />
7M<br />
M1.1 – M2.4<br />
M1.2 The standards in M2 apply to methods of draining wastewater and surface water (above and below<br />
ground) from all buildings to the point at which the discharge is made to a public sewer or to a wastewater<br />
treatment system or, in the case of surface water, to ground by Sustainable Urban Drainage<br />
Systems (SUDS).<br />
M1.3 The standards in M3 apply to underground wastewater drainage systems from, and including, the<br />
treatment plant to the point at which the discharge is made to ground or receiving waters.<br />
M1.4 The standards in M4 apply to buildings as follows -<br />
a. M4.1 to M4.3 apply to dwellings only;<br />
b. M4.4 to M4.9 apply to buildings other than dwellings;<br />
except -<br />
M4.4 to M4.6 do not apply to a building or part of a building specified in Regulation 25(2)<br />
other than for the provision of sanitary facilities for disabled people;<br />
c. M4.10 applies to all buildings.<br />
M2 Drainage<br />
WASTEWATER AND SURFACE WATER DRAINAGE<br />
M2.1* A building must be provided with a drainage system suitable for the safe and hygienic removal of<br />
wastewater from the building.<br />
M2.2* To ensure the safe and hygienic removal of surface water from a building and from a paved surface<br />
within the curtilage of a building, there must be provided -<br />
a. drainage using suitable SUDS techniques; or<br />
b a surface water drainage system complying with M2.4 to M2.7 and M2.9.<br />
Note: PAVED SURFACE means any constructed hard surface more than 200 m 2 (including car<br />
parking), access to a dwelling required by Q2.1, and access to a building, other than a dwelling,<br />
required by S2.3.<br />
M2.3* A wastewater drainage system of a building must be adequately ventilated to limit pressure fluctuations<br />
within the system and minimise the possibility of foul air entering the building.<br />
M2.4* A drainage system must be suitably designed and constructed to minimise the risk of blockage and<br />
flooding.<br />
Amdt: September 2001<br />
M
M<br />
M2.5 – M3.1<br />
M2.5* A drainage system must be suitably tested to ensure satisfactory installation,<br />
except -<br />
there is no requirement to test the drain leading from a private wastewater treatment plant or septic<br />
tank.<br />
DISCHARGES INTO A DRAINAGE SYSTEM<br />
M2.6* Where a discharge into a drainage system serving a dwelling contains silt or grit there must be suitable<br />
facilities for the adequate separation and removal of such substances.<br />
M2.7* Where a discharge into a drainage system serving a building, other than a dwelling, contains oil, fat,<br />
grease, volatile substances, silt or grit there must be suitable facilities for the adequate separation and<br />
removal of such substances.<br />
DISCHARGES FROM A DRAINAGE SYSTEM<br />
M2.8 A drainage system must be capable of discharging wastewater -<br />
Amdt: September 2001<br />
a. where it is reasonably practicable to do so, to a public sewer or public wastewater treatment<br />
plant provided under the Sewerage (Scotland) Act 1968, or<br />
b. where it is not reasonably practicable to do so -<br />
i. to a private wastewater treatment plant or septic tank, or<br />
ii. where it is greywater, to ground via a readily accessible washable filter and thereafter an<br />
infiltration system, or<br />
iii. in the case of waste products from a waterless closet serving a dwelling, to a holding<br />
tank for safe disposal.<br />
M2.9* A drainage system must be capable of discharging surface water -<br />
a. by suitable SUDS techniques, including a soakaway; or<br />
b. to a public sewer provided under the Sewerage (Scotland) Act 1968; or<br />
c. to a suitable outfall that will minimise the risk of environmental pollution; or<br />
d. where it is rainwater from a building, to a storage container with an overflow discharging in<br />
accordance with sub-clause a, b or c.<br />
M3 Private wastewater treatment systems<br />
PRIVATE WASTEWATER TREATMENT PLANT OR SEPTIC TANKS<br />
M3.1* A private wastewater treatment plant or septic tank must -<br />
a. be suitable for its purpose; and<br />
b. be provided with a suitably sealed, secure cover; and<br />
8M
c. incorporate facilities that will provide suitable access for inspection and sampling of the treated<br />
wastewater discharged; and<br />
d. be located at a suitable distance from a building to prevent possible damage to its foundations;<br />
and<br />
e. be located at a suitable distance from a boundary.<br />
M3.2* A private wastewater treatment plant or septic tank must be provided with a suitable outlet to minimise<br />
the risk of environmental pollution.<br />
M3.3* A private wastewater treatment plant or septic tank must have suitable access for desludging.<br />
M3.4* Every building with a drainage system discharging to a private wastewater treatment plant or septic<br />
tank must have a suitably located label alerting the occupier to this.<br />
INFILTRATION SYSTEMS<br />
M3.5* An infiltration system serving a private wastewater treatment plant, septic tank or for greywater must<br />
be constructed in ground suitable for the treatment and dispersion of the wastewater discharged.<br />
M3.6* An infiltration system serving a private wastewater treatment plant, septic tank or for greywater must<br />
be suitably designed and constructed as determined by the ground conditions into which the treated<br />
wastewater is discharged.<br />
M3.7* An infiltration system serving a private wastewater treatment plant or septic tank must be suitably<br />
located to minimise the risk of pollution.<br />
M4 Sanitary facilities<br />
SANITARY FACILITIES IN A DWELLING<br />
M4.1* Every dwelling must be provided with an adequate number of sanitary facilities.<br />
M4.2* A waterless closet must be suitably designed and installed.<br />
M4.3 Every dwelling must have at least 1 of the waterclosets, or waterless closets, (required by M4.1) on the<br />
accessible entrance storey as required by Q2.11 together with an activity space clear of any door swing,<br />
of at least 750 mm long x 800 mm wide in front of the watercloset, or waterless closet, in accordance<br />
with the diagram to this standard,<br />
except -<br />
where level or ramped access suitable for disabled people is not required by Q2.1, such facilities must<br />
be provided -<br />
a. on the storey accessible to disabled people; or<br />
b. where there are no apartments on the storey accessible to disabled people, on the first storey<br />
above or below this storey containing an apartment.<br />
9M<br />
M3.1 – M4.3<br />
Amdt: September 2001<br />
M
M<br />
M4.3 – M4.10<br />
Diagram to M4.3: Plan view of activity space<br />
Note:<br />
1. A wall hung washbasin may project into the activity space. (see Diagram 2 to (M4.4))<br />
SANITARY FACILITIES IN A BUILDING OTHER THAN A DWELLING<br />
M4.4* A building, other than a dwelling, must be provided with an adequate number of suitable sanitary<br />
facilities for staff.<br />
M4.5* A building of purpose groups 2, 4 and 5 must be provided with an adequate number of suitable sanitary<br />
facilities for people other than staff.<br />
M4.6* A building, other than a dwelling, must be provided with an adequate number of watercloset cubicles<br />
designed to allow greater ease of movement within the cubicle.<br />
M4.7* Where changing cubicles are provided in a building, at least 1 cubicle in 20, or part thereof, must be<br />
designed to allow greater ease of movement within the cubicle.<br />
M4.8* In a building of purpose sub-group 2B containing bedrooms, other than in a place of lawful detention,<br />
at least 1 bedroom in 20, or part thereof, must be provided with sanitary accommodation accessible to,<br />
and suitable for, wheelchair users, either -<br />
a. where serving 1 bedroom, en-suite with that bedroom; or<br />
b. where serving more than 1 bedroom, accessible from a circulation area which is exclusive to the<br />
bedrooms.<br />
M4.9 Where sanitary accommodation, accessible to and suitable for disabled people, is required, the total<br />
horizontal distance to be travelled from any accessible point to the sanitary accommodation must be<br />
not more than 45 m.<br />
GENERAL REQUIREMENTS FOR A TOILET<br />
M4.10 Every toilet must -<br />
Amdt: September 2001<br />
a. have a washbasin within -<br />
i. the toilet itself, or<br />
ii. an adjacent space providing the sole means of access to the toilet; and<br />
b. be arranged so that the watercloset, or waterless closet, and washbasin are separated by a door<br />
from any room or space used wholly or partly for the preparation or consumption of food,<br />
except -<br />
in a place of lawful detention.<br />
800mm<br />
10M<br />
750mm
Provisions deemed to satisfy the standards<br />
WASTEWATER AND SURFACE WATER DRAINAGE<br />
(M2.1) The requirements of M2.1 will be met where the drainage system is constructed and installed in accordance<br />
with -<br />
a. for sanitary pipework, BS EN 12056-2: 2000;<br />
b. for a drainage system outside a building, BS EN 752-3: 1997 (amendment 2), BS EN 752-4:<br />
1998 and BS EN 1610: 1998;<br />
c. for a sewer that is intended for vesting in the Water Authority, ‘Sewers for Scotland’;<br />
d. for rainwater pipes and gutters, BS EN 12056-3: 2000.<br />
(M2.2) The requirements of M2.2a will be met where suitable SUDS techniques are provided in accordance<br />
with ‘Sustainable urban drainage systems: design manual for Scotland and Northern Ireland’.<br />
(M2.3) The requirements of M2.3 will be met where the wastewater drainage system is ventilated -<br />
a. in accordance with Sections 4, 5, 6 and national annex ND of BS EN 12056-2: 2000; or<br />
b. where provided, by an air admittance valve(s) installed in compliance with the conditions of<br />
certification by a notified body.<br />
(M2.4) The requirements of M2.4 will be met where -<br />
a. in the case of a paved surface, drainage is provided -<br />
i. in accordance with national annex NE of BS EN 752-4: 1998, or<br />
ii. where the paved surface provides access to a dwelling as required by Q2.1, or to a building<br />
as required by S2.3, by laying the surface to a fall of at least 1 in 60 to achieve<br />
natural run-off;<br />
b. the bore of a pipe or drain does not diminish in the direction of flow,<br />
except -<br />
the bore of sanitary pipework may be reduced where connected to a pump installed in compliance<br />
with the conditions of certification by a notified body;<br />
c. in the case of a sanitary appliance installed below the flood level of the drainage system with<br />
the possibility of surcharging, the drainage system is constructed in accordance with BS EN<br />
12056-4: 2000;<br />
11M<br />
(M2.1), (M2.4)<br />
Amdt: September 2001<br />
M
M<br />
(M2.4), (M2.9)<br />
Diagram to (M2.4)c: Flood level of a drainage system<br />
Amdt: September 2001<br />
sanitary appliance<br />
Diagrammatic section through a typical basement area<br />
d. in the case of a drainage system discharging to a public sewer or to a sewer that is intended for<br />
vesting in the Water Authority, access to the drainage system is provided in accordance with the<br />
requirements of the relevant Water Authority.<br />
(M2.5) The requirements of M2.5 will be met where the drainage system is tested in accordance with -<br />
a. for sanitary pipework, national annex NG of BS EN 12056-2: 2000;<br />
b. for a drainage system under and around a building, BS EN 1610: 1998.<br />
DISCHARGES INTO A DRAINAGE SYSTEM<br />
(M2.6) The requirements of M2.6 will be met for the separation and removal of silt or grit by incorporating<br />
removable grit interceptors within surface water gully pots.<br />
(M2.7) The requirements of M2.7 will be met where separation and removal of oil, fat, grease and volatile<br />
substances is provided in accordance with -<br />
a. for light liquids such as oil and petrol, prEN 858-1 & 2: 1999;<br />
b. for fat or grease, prEN 1825-1 & 2: 1999.<br />
The requirements of M2.7 will be met for the separation and removal of silt or grit by incorporating<br />
removable grit interceptors within surface water gully pots.<br />
DISCHARGES FROM A DRAINAGE SYSTEM<br />
(M2.9) The requirements of M2.9a will be met -<br />
a. where suitable SUDS techniques are constructed in accordance with ‘Sustainable urban<br />
drainage systems: design manual for Scotland and Northern Ireland’; or<br />
b. by a soakaway designed and constructed in accordance with -<br />
i. BRE Digest 365 ‘Soakaway Design’, or<br />
ii. National annex NG.2 of BS EN 752-4: 1998.<br />
The requirements of M2.9c will be met where the outfall is to a watercourse, and complies with any<br />
notice and/or consent issued by SEPA.<br />
12M<br />
lifting pump<br />
flood level (m.h. cover)<br />
manhole<br />
sewer
PRIVATE WASTEWATER TREATMENT PLANT OR SEPTIC TANKS<br />
13M<br />
(M3.1) – (M3.3)<br />
(M3.1) The requirements of M3.1a will be met by a private wastewater treatment plant or septic tank<br />
designed, constructed and installed -<br />
a. for a prefabricated septic tank, in accordance with BS EN 12566-1: 2000; or<br />
b. in accordance with the recommendations of BS 6297: 1983; or<br />
c. in compliance with the conditions of certification by a notified body.<br />
The requirements of M3.1b will be met by a solid cover over the settlement tank capable of being<br />
removed by 1 person with the use of standard operating keys.<br />
The requirements of M3.1c will be met where access for inspection and sampling of the final treated<br />
wastewater is provided in accordance with the diagram to this specification -<br />
Diagram to (M3.1)c: Access for inspection and sampling treated wastewater<br />
secure lid<br />
direction of flow<br />
at least 150 mm<br />
Diagrammatic section through chamber<br />
at least 300 mm<br />
no sump in chamber<br />
The requirements of M3.1d will be met where every part of the private treatment plant or septic tank is<br />
located at least 5 m from the building.<br />
The requirements of M3.1e will be met where every part of the private treatment plant or septic tank is<br />
located at least 5 m from the boundary.<br />
(M3.2) The requirements of M3.2 will be met where the outlet -<br />
a. when discharging from 5 or more dwellings or more than 15 population equivalent (based on<br />
BOD (biochemical oxygen demand) levels), is constructed in accordance with the requirements<br />
of a notice and/or a consent issued by SEPA. This may include an infiltration system described<br />
in (M3.6);<br />
b. when discharging from less than 5 dwellings or not more than 15 population equivalent (based<br />
on BOD levels) and based on a ground assessment report taking account of the criteria listed in<br />
(M3.5)a and a percolation test, is -<br />
i. constructed in accordance with the conditions of a notice and/or a consent issued by<br />
SEPA, or<br />
ii. to ground, via an infiltration system.<br />
chamber wall<br />
inlet pipe overhang by at least 75 mm<br />
(M3.3) The requirements of M3.3 will be met where access for a desludging tanker is provided to a working<br />
area -<br />
a. that will provide a clear route for the suction hose from the tanker to the tank; and<br />
Amdt: September 2001<br />
M
M<br />
(M3.3) – (M3.5)<br />
b. that is not more than 25 m from the tank where it is not more than 4 m higher than the invert<br />
level of the tank; and<br />
c. that is sufficient to support a vehicle axle load of 14 tonnes.<br />
(M3.4) The requirements of M3.4 will be met where the label states -<br />
‘The drainage system from this property discharges to a wastewater treatment plant (or septic tank, as<br />
appropriate). The owner is legally responsible for routine maintenance and to ensure that the system<br />
complies with any discharge consent issued by SEPA and that it does not present a health hazard or a<br />
nuisance’.<br />
A suitable location for the label would be adjacent to the kitchen sink, gas or electricity consumer unit<br />
or the water stop cock.<br />
INFILTRATION SYSTEMS<br />
(M3.5) The requirements of M3.5 will be met where the suitability of the ground is demonstrated by a ground<br />
assessment and percolation test carried out in accordance with the following procedures -<br />
a. Carry out a preliminary ground assessment. The following check list indicates the actions that<br />
should be taken and the type of information that should be collected -<br />
amendment: September 2001<br />
i. consult SEPA, Local Authority Building Control Officer and the Environmental Health<br />
Officer as required,<br />
ii. SEPAs groundwater protection policy,<br />
iii. underlying geology,<br />
iv. whether the ground is liable to flooding,<br />
v. nature of the sub-soil,<br />
vi. implication of plot size,<br />
vii. proximity of underground services,<br />
viii. site topography and local drainage patterns,<br />
ix. whether water is abstracted for drinking, used in food processing or farm dairies,<br />
x. implication for and of trees and other vegetation.<br />
The preliminary assessment may indicate that the ground is unsuitable for the installation of an infiltration<br />
system in which case an alternative disposal method should be considered.<br />
b. A trial hole should be dug to determine the position of the water table and soil conditions. This<br />
trial hole will enable the sub-soil type to be determined. The trial hole shall be a minimum of<br />
2 m deep, or a minimum of 1.5 m below the invert of the proposed distribution pipes. The trial<br />
hole should be left covered for a period of 48 hours before measuring any water table level. For<br />
safe and effective dispersal of the wastewater, the groundwater below the infiltration system<br />
must be at least 1 m below the bottom of the distribution pipes. It should also be noted that it is<br />
the seasonally highest level of the water table that should be determined for the infiltration area.<br />
14M
15M<br />
(M3.5), (M3.6)<br />
c. To determine the area of ground required, a percolation test is required to be carried out within,<br />
and to be representative of, the proposed infiltration area. The percolation test should be carried<br />
out using either of the following methods -<br />
i. expert examination of the soil distribution analysis, using the method described in<br />
BS 1377: Part 2: 1990, or<br />
ii. excavation of a percolation hole 300 mm square to a depth 300 mm below the proposed<br />
invert level of the effluent distribution pipe. Where deep drains are necessary, the hole<br />
should conform to this shape at the bottom but may be enlarged above the 300 mm level<br />
to enable safe excavation to be carried out. Fill the 300 mm square section of the hole to<br />
a depth of at least 300 mm with water and allow it to seep away overnight. It is important<br />
to saturate the soil surrounding the test hole to simulate day to day conditions in an<br />
operational drainage field. Next day, refill the test section with water to a depth of at<br />
least 300 mm and observe the time (t) in seconds, for the water to seep away from 75%<br />
to 25% full level.<br />
Divide this time by 150 mm. The answer gives the average time in seconds (Vp)<br />
required for the water to drop 1 mm. Take care when making the test to avoid unusual<br />
weather conditions such as heavy rain, severe frost or drought. Carry out the test at least<br />
3 times and take the average figure. At least 2 percolation holes, not less than 5 m apart,<br />
should be dug and tested 3 times each to obtain consistent results.<br />
The floor area of a sub-surface drainage trench required to disperse effluent from septic<br />
tanks may be calculated from -<br />
A = p x Vp x 0.25<br />
where A is the area of the sub-surface drainage trench, in m 2 ;<br />
p is the number of persons served by the tank; and<br />
Vp is the percolation value obtained, as described above, in seconds/mm.<br />
For wastewater that has received secondary treatment followed by settlement or for<br />
greywater, this area may be reduced by 20%, i.e.<br />
A = p x Vp x 0.2<br />
(M3.6) The requirements of M3.6 will be met by an infiltration system constructed -<br />
a. where the percolation value (as demonstrated by the percolation test) is not more than<br />
15 secs/mm, in accordance with the requirements of SEPA;<br />
b. where the percolation value (as demonstrated by the percolation test) is more than 15 secs/mm<br />
and not more than 100 secs/mm, as -<br />
i. a piped infiltration trench system in accordance with national annex NG.3 of<br />
BS EN 752-4: 1998, using perforated, rigid pipes with a smooth internal surface, or<br />
ii. a piped infiltration bed system in accordance with the diagram to this specification, or<br />
iii. any system described in (M3.6)c and d;<br />
amendment: September 2001<br />
M
M<br />
(M3.6)<br />
Diagram to (M3.6)b.ii: Typical piped infiltration bed system<br />
Amdt: September 2001<br />
c. where the percolation value (as demonstrated by the percolation test) is more than 100 secs/mm<br />
and not more than 140 secs/mm, as -<br />
i. a reed bed complying with the requirements of the BRE, Good Building Guide, GBG 42,<br />
Parts 1 and 2 together with a piped infiltration system described in (M3.6)b.i, (M3.6)b.ii,<br />
or a suitable outfall, or<br />
ii. a constructed wetland, other than a reed bed, to a professionally prepared design and<br />
constructed by specialist contractor(s), or<br />
iii. a proprietary filtration system designed, constructed and installed in accordance with the<br />
conditions of a notified body, or<br />
Diagram to (M3.6)c.iii: Typical proprietary filter module<br />
wastewater is pumped<br />
out through holes in<br />
distribution grid and<br />
filters down through the<br />
biofibrous media<br />
at least 1 m.<br />
distribution box<br />
wastewater<br />
distribution grid<br />
biofibrous media<br />
broken stone at base<br />
of module<br />
barrier material<br />
water table or<br />
creviced bedrock<br />
iv. any other equivalent filtration system designed by a specialist in this subject and constructed<br />
by specialist contractor(s);<br />
16M<br />
150 - 300 mm of 20 - 50 mm<br />
clean gravel or broken stone<br />
2 m.<br />
treated wastewater discharges through<br />
drain holes at base of module<br />
inlet pipe
17M<br />
(M3.6), (M3.7)<br />
d. where the percolation value (as demonstrated by the percolation test) is more than 140 secs/mm -<br />
i. as a system described in (M3.6)c. that does not use an infiltration system for the final<br />
treated wastewater, or<br />
ii. where the piped infiltration system connects to a private wastewater treatment plant or<br />
septic tank serving not more than 1 dwelling, by designing and constructing the infiltration<br />
system using a specialist contractor, within a mound filter system in accordance with<br />
the diagram to this specification -<br />
Diagram to (M3.6)d.ii: Cross-section through a typical soil covered mound filter system serving a single<br />
dwelling<br />
distribution pipes<br />
250 mm grassed<br />
top soil<br />
Note 3<br />
soil cap<br />
washed gravel (10-20mm)<br />
filter sand<br />
drained constructed filter gravel or permeable soil<br />
high water table or impervious ground<br />
Notes:<br />
1. Notional percolation times should be determined for filter sand (e.g. in accordance with sand<br />
test in BRE, Good Building Guide 42, Part 2) and the area of washed gravel calculated from the<br />
formula given in (M3.5).<br />
2. To provide venting of the filter, the upstream ends of the distribution pipes may be extended<br />
vertically above mound level and capped with a cowl or grille.<br />
3. Surface water run-off and uncontaminated seepage from the surrounding soil may be cut off by<br />
shallow interceptor drains and diverted away from the mound. There must be no seepage of<br />
wastewater to such an interceptor drain.<br />
4. Where the permeable soil is slow draining and overlaid on an impervious layer, the mound filter<br />
system should be constructed on a gently sloping site.<br />
(M3.7) The requirements of M3.7 will be met by locating the infiltration system -<br />
a. at least 50 m from any spring, well or borehole used as a drinking water supply; and<br />
b. at least 10 m horizontally from any watercourse (including any inland or coastal waters), permeable<br />
drain, road or railway; and<br />
c. at least 5 m from a building or a boundary.<br />
geotextile<br />
at least 100 mm<br />
at least 200 mm<br />
at least 700 mm<br />
at least 250 mm<br />
amendment: September 2001<br />
M
M<br />
(M4.1), (M4.2)<br />
SANITARY FACILITIES IN A DWELLING<br />
(M4.1) The requirements of M4.1 will be met by providing sanitary facilities in accordance with the table to<br />
this specification -<br />
Table to (M4.1): Minimum number of sanitary facilities in a dwelling<br />
Appliance Number of appliances<br />
watercloset, or waterless closet 1 where the dwelling is not more than 80 m2 total floor area<br />
2 where the dwelling is more than 80 m2 total floor area<br />
bath or shower 1<br />
washbasin 1 per watercloset, or waterless closet<br />
sink 1<br />
Notes:<br />
1. Where en-suite facilities are provided, access to at least 1 watercloset, or waterless closet, must<br />
be available other than through a bedroom.<br />
(M4.2) The requirements of M4.2 will be met where the waterless closet is designed and installed in compliance<br />
with -<br />
a. a National Sanitation Federation Certification to standard NSF 41; ‘Wastewater recycling/reuse<br />
and water conservation devices’; or<br />
b. NSF International standard ANSI/NSF 41-1999; ‘Non-liquid saturated treatment systems’; or<br />
c. the conditions of a certification by a notified body.<br />
amendment: September 2001<br />
18M
SANITARY FACILITIES IN A BUILDING OTHER THAN A DWELLING<br />
19M<br />
(M4.4)<br />
(M4.4) The requirements of M4.4 with regards to number of sanitary facilities, will be met by providing sanitary<br />
facilities for staff in accordance with the table to this specification -<br />
Table to (M4.4): Minimum number of sanitary facilities for staff [1]<br />
Number of Number of Number of Number of Sanitary facilities for<br />
staff waterclosets washbasins urinals disabled people<br />
Male 1 to 15 [2] 1 1 1 Where access for disabled people<br />
16 to 30 2 2 1 is required by S2.6, sanitary<br />
31 to 45 2 2 2 facilities for disabled people<br />
46 to 60 3 3 2 should be provided within the<br />
61 to 75 3 3 3 overall number of facilities<br />
76 to 90 4 4 3 required, as follows -<br />
91 to 100 4 4 4<br />
Over 100 1 additional watercloset, urinal and washbasin 1-20 staff -<br />
for every additional 50 males or part thereof at least 1 watercloset in accordance<br />
with Diagram 1 to (M4.4).<br />
Female 1 to 5 [2] 1 1<br />
(or male) 6 to 25 2 2 Over 20 staff, either -<br />
Over 25 1 additional watercloset and washbasin a. at least 1 unit (wc and<br />
for every additional 25 females (or males), washbasin) of unisex sanitary<br />
or part thereof accommodation in accordance<br />
with Diagram 2 to (M4.4), and<br />
accessed independently of any<br />
other sanitary accommodation; or<br />
b. where provided integrally<br />
within separate sanitary<br />
accommodation for males and<br />
females, at least 1 unit (wc and<br />
washbasin) of unisex sanitary<br />
accommodation for each sex<br />
in accordance with<br />
Diagram 2 to (M4.4).<br />
A greater provision may be<br />
required dependent upon the<br />
distance between facilities.<br />
(see M4.9)<br />
Notes:<br />
1. Adequate sanitary facilities for males and females should be calculated from the number of staff<br />
likely to be employed in the building at any specific time. A written statement of the numbers<br />
should be submitted to the relevant Building Control Authority who may wish to verify the figures.<br />
2. Separate sanitary facilities for staff are not required where fewer than 6 people are employed.<br />
3. In a restaurant, café or similar food outlet, sanitary facilities provided for the staff should be<br />
reserved for their sole use, except in small premises where the total number of persons (staff and<br />
non staff) using the building is not more than 20, only 1 unit (watercloset and washbasin) of unisex<br />
sanitary accommodation need be provided.<br />
Amdt: September 2001<br />
M
M<br />
(M4.4), (M4.5)<br />
The requirements of M4.4 with regard to suitable sanitary facilities, will be met by providing sanitary<br />
facilities for disabled people (as required by Table to (M4.4)) in accordance with Diagrams 1 and 2 to<br />
this specification -<br />
Diagram 1 to (M4.4): Plan of accessible sanitary facilities in a small building<br />
Notes:<br />
1. The activity space must be clear of any door swing.<br />
2. A wall hung washbasin may project into the activity space. (see Diagram 2 to (M4.4).<br />
3. Two rails should be provided on either side of the watercloset and at least 1 should be of the<br />
wall-fixed, grab rail type.<br />
Diagram 2 to (M4.4): Fully accessible sanitary facilities<br />
1.5m<br />
400mm<br />
Amdt: September 2001<br />
2m<br />
250mm<br />
Hinged<br />
support<br />
rail<br />
grab rail<br />
(wall-fixed)<br />
200mm<br />
activity space<br />
400mm<br />
800mm<br />
Plan of fully accessible watercloset with washbasin Section through fully accessible watercloset with washbasin<br />
Notes:<br />
1. Door width is clear opening width.<br />
2. A sliding door is an acceptable option.<br />
(M4.5) The requirements of M4.5 with regard to number of sanitary facilities, will be met by providing sanitary<br />
facilities in accordance with -<br />
a. for a building of purpose group 2, Table 2 to BS 6465: Part 1: 1994;<br />
b. for a building of purpose group 4, Table 1 to this specification -<br />
20M<br />
hinged support rail<br />
750mm<br />
800mm 650mm<br />
300mm<br />
450mm<br />
hinged support rail<br />
750mm
21M<br />
(M4.5)<br />
Table 1 to (M4.5): Minimum number of sanitary facilities for people, other than staff, in a building of<br />
purpose group 4<br />
Building type Sales area Number of Number of Sanitary facilities for<br />
of shop waterclosets [1] urinals disabled people<br />
Shops (Class 1) Unisex over 500m2 1 Where access for<br />
and shopping [6] disabled people is<br />
malls [2-5] required by S2.6,<br />
male 1000m2-2000m2 1 1 sanitary facilities for<br />
2001m2-4000m2 1 2 disabled people<br />
over 4000m2 plus 1 wc for each plus 1 urinal for should be provided<br />
additional 2000 m2 each additional within the overall<br />
of sales area, or 2000 m2 of number of facilities<br />
part thereof sales area, or<br />
part thereof<br />
required, as follows -<br />
at least 1 unit (wc<br />
female 1000m2-2000m2 2 and washbasin) of<br />
2001m2-4000m2 5 unisex sanitary<br />
over 4000m2 plus 2 wc for each accommodation in<br />
additional 2000 m2 accordance with<br />
of sales area, or Diagram 2 to (M4.4),<br />
part thereof and accessed<br />
independently of<br />
Shops (Class 2) Unisex over 1000m2 1 any other sanitary<br />
and shopping<br />
malls [2-5]<br />
[6] accommodation.<br />
male 1000m2-4000m2 1 1 A greater provision<br />
over 4000m2 plus 1 wc for each plus 1 urinal for may be required<br />
additional 3000 m2 each additional dependant upon<br />
of sales area, 3000 m2 of the distance between<br />
or part thereof sales area, or<br />
part thereof<br />
facilities. (see M4.9)<br />
female 1000m2-2000m2 1<br />
2001m2-4000m2 3<br />
over 4000m2 plus 1 wc for each<br />
additional 3000 m2 of sales area, or<br />
part thereof<br />
Notes:<br />
1. 1 washbasin should be provided for each watercloset, plus 1 washbasin per 5 urinals, or part<br />
thereof.<br />
2. The definition of Class 1 and 2 shops is listed in Schedule 4 in Part A, General.<br />
3. It has been assumed that the customers will be 50% male and 50% female. For different proportions<br />
the accommodation levels will have to be adjusted.<br />
4. For shopping malls, the sum of the sales areas of all the shops in the mall should be calculated<br />
and used with this table. Sanitary facilities provided within a shop may be included in the overall<br />
calculation.<br />
5. For shops with restaurants, additional sanitary facilities should be provided in accordance with<br />
Table 2 to (M4.5).<br />
6. Should include baby-changing facilities.<br />
7. Sanitary accommodation should be easily accessible and situated on the entrance floor and in<br />
large shops, on alternate floors.<br />
Amdt: September 2001<br />
M
M<br />
(M4.5)<br />
c. for a building of purpose group 5, other than a building listed in sub-clauses d, e and f, Table 2 to<br />
this specification;<br />
d. for sports stadia, as recommended in ‘Toilet Facilities at Stadia’;<br />
e. for a school not covered by the Schools Premises (General Requirements and <strong>Standards</strong>) (Scotland)<br />
Regulations 1967 and 1979, Table 6 to BS 6465: Part 1: 1994;<br />
f. for a place of higher education, the provision for a secondary school in Table 6 to BS 6465: Part 1:<br />
1994.<br />
Table 2 to (M4.5): Minimum number of sanitary facilities for people, other than staff, in a building<br />
of purpose group 5 [1]<br />
Building type [3-7] Number of Number of Number of Sanitary facilities<br />
people waterclosets [2] urinals for disabled people<br />
Buildings used male 1-100 1 2 Where access for<br />
for public [8] 101-200 1 plus 1 for each disabled people is<br />
entertainment 201-250 1 additional 80 required by S2.6,<br />
(e.g. single-screen over 250 plus 1 for each males, or part sanitary facilities for<br />
cinemas, theatres, additional 500 thereof, over disabled people should<br />
concert halls and males, or part 100 be provided within the<br />
other premises thereof overall number of<br />
without licensed facilities required,<br />
bars) as follows -<br />
female 1-40 3 1-20 people -<br />
[8] 41-70 4 at least 1 watercloset<br />
71-100 5 in accordance with<br />
over 100 plus 1 for each Diagram 1 to (M4.4)<br />
additional<br />
35 females, or Over 20 people -<br />
part thereof at least 1 unit (wc and<br />
washbasin) of unisex<br />
Restaurants,cafés, male 1-400 [9 10] 1 for every 100, 1 per 50 males, sanitary<br />
canteens and or part thereof, or part thereof accommodation in<br />
fast food outlets over 400 plus 1 for each accordance with<br />
(where seating additional 250 Diagram 2 to (M4.4)<br />
is provided) males, or part and accessed<br />
thereof independently of any<br />
other sanitary<br />
female 1-20 [9 10] 2 accommodation.<br />
21-50 3<br />
51-100 4 A greater provision<br />
101-150 5 may be required<br />
151-200 6 dependant upon the<br />
over 200 plus 1 for each distance between<br />
additional 100 facilities. (see M4.9)<br />
females, or part<br />
thereof<br />
Public houses male 1-75 1 2<br />
and licensed [11] 76-150 1 3<br />
bars [12 13] over 150 plus 1 for each plus 1 for each<br />
additional 150 additional 75<br />
males, or part males, or part<br />
thereof thereof<br />
Amdt: September 2001<br />
22M
23M<br />
(M4.5)<br />
Table 2 to (M4.5): Minimum number of sanitary facilities for people, other than staff, in a building<br />
of purpose group 5 [1] (continued)<br />
Building type [3-7] Number of Number of Number of Sanitary facilities<br />
people waterclosets [2] urinals for disabled people<br />
female 1-10 1<br />
[10] 11-25 2<br />
over 25 plus 1 for each<br />
additional 20<br />
females, or part<br />
thereof<br />
Swimming pools male 1-100 2 1 per 20 males<br />
(bathers only) over 100 plus 1 for each<br />
[14] additional 100<br />
males, or part<br />
thereof<br />
female 1-25 2<br />
plus 1 for each<br />
additional 25<br />
females, or part<br />
thereof<br />
Notes:<br />
1. Adequate sanitary facilities for males and females should be calculated from the number of persons the<br />
building is likely to accommodate in use. A written statement of the numbers should be submitted to<br />
the relevant Building Control Authority who may wish to verify the figures.<br />
2. 1 washbasin should be provided for each watercloset, plus 1 washbasin per 5 urinals, or part thereof.<br />
3. It has been assumed that the customers will be 50% male and 50% female. For different proportions<br />
the accommodation levels will have to be adjusted.<br />
4. In multi-use buildings each function should be treated separately for calculating overall provision.<br />
5. Where members of the public are permitted to use sanitary facilities provided for staff, a separate<br />
calculation should be made for each group and the total number of sanitary facilities provided accordingly.<br />
6. There is no requirement to provide sanitary facilities in a building of purpose group 3, 6 or 7 for<br />
people other than staff, but where they are, they should be readily accessible to the public, e.g. off<br />
entrance hall or foyer.<br />
7. Baby-changing facilities should be provided in buildings used for public entertainment, restaurants,<br />
cafés and fast food outlets where seating is provided.<br />
8. In cinema-multiplexes and similar premises where the use of sanitary facilities will be spread through<br />
the opening hours, the level of sanitary facilities should normally be based upon 75% of total capacity.<br />
For single-screen cinemas 100% occupancy is assumed.<br />
9. Only 1 unit (watercloset and washbasin) of unisex sanitary accommodation for both staff and customers<br />
need be provided where the total number of persons using the premises is not more than 20.<br />
10. In the case of works and office canteens, the scale of provision may be reduced proportionally where<br />
there are readily accessible workplace sanitary facilities close to the canteen.<br />
11. Number of customers should be calculated at the rate of 4 persons per 3 m 2 of effective drinking area<br />
(i.e. the total space of those parts of those rooms to which the public has access).<br />
12. Public houses with restaurants should be provided with sanitary facilities as for licensed bars.<br />
13. Public houses with public music, singing and dancing licenses should be as for licensed bars. The<br />
licensed area for public music, singing and dancing should be separated for calculation of occupancy<br />
and the provision of sanitary facilities should be in accordance with buildings used for public entertainment.<br />
14. Sanitary facilities for spectators should be provided in accordance with buildings used for public<br />
entertainment.<br />
Amdt: September 2001<br />
M
M<br />
(M4.5) – (M4.8)<br />
The requirements of M4.5 with regard to suitable sanitary facilities, will be met by providing sanitary<br />
facilities for disabled people (as required by Tables 1 and 2 to (M4.5)) in accordance with Diagrams 1<br />
and 2 to (M4.4).<br />
(M4.6) The requirements of M4.6 will be met, where there are 4 or more watercloset cubicles in a group, by<br />
providing at least 1 cubicle in the group with an activity space in front of the watercloset in accordance<br />
with the diagram to this specification -<br />
Diagram to (M4.6): Plan view of activity space<br />
Notes:<br />
1. The activity space must be clear of any door swing.<br />
2. A wall hung washbasin may project into the activity space. (see Diagram 2 to (M4.4).<br />
(M4.7) The requirements of M4.7 will be met where the changing cubicle is provided in accordance with the<br />
diagram to this specification -<br />
Diagram to (M4.7): Changing cubicle<br />
(M4.8) The requirements of M4.8 will be met where sanitary accommodation accessible from the bedroom, is<br />
provided, which -<br />
Amdt: September 2001<br />
800mm<br />
hinged<br />
support rail<br />
1.2m 1.5m<br />
grab rail<br />
curtain<br />
1.6m<br />
a. has plan dimensions of at least 2.4 m x 2.0 m; and<br />
b. has an outward opening or sliding door providing a clear opening width of at least 800 mm; and<br />
c. contains a bath or a shower accessible to wheelchair users; and<br />
d. contains a watercloset, washbasin and support rails arranged as shown in the Diagram 2 to<br />
(M4.4).<br />
24M<br />
750mm<br />
tip-up<br />
seat
ELECTRICAL<br />
INSTALLATIONSN
Contents<br />
INTRODUCTION<br />
REGULATIONS 26 & 26A<br />
Electrical installations<br />
THE STANDARDS<br />
N1 Application of Part N N1.1-N1.2<br />
N2 Electrical installations<br />
Electrical installations N2.1<br />
Aids to communication N2.2<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(N2.1) Electrical installations<br />
(N2.2) Aids to communication<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A, General.<br />
3N<br />
Amdt: December 1999<br />
N
5N<br />
Introduction<br />
1. The intention of this Part is to ensure that electrical<br />
installations are safe in terms of the hazards likely to arise<br />
from defective installations, namely fire, electric shock and<br />
burns or other personal injury and that other than in buildings<br />
of purpose group 1, aids to assist the hard of hearing are<br />
provided.<br />
2. It should be noted that relevant material from the now<br />
deleted Part T has been incorporated in this Part.<br />
3. The regulation applies to installations in, or serving,<br />
buildings. An installation consists of the electrical wiring<br />
and associated components and fittings, including permanently<br />
secured and large stationary equipment, but excluding<br />
portable equipment and appliances. Exceptions are made for<br />
mine and quarry buildings and factories (as they have particular<br />
hazards and are subject to other legislation), statutory<br />
supply undertakers’ works and extra-low voltage installations<br />
which are not supplied from a higher voltage (eg<br />
240 V) circuit.<br />
4. The requirements of the regulations are deemed to be<br />
satisfied by complying with British Standard 7671: 1992<br />
“The Requirements for Electrical Installations”. This British<br />
Standard is identical to the “Regulations for Electrical Installations”,<br />
Sixteenth Edition 1991 published by the Institute of<br />
Electrical Engineers (lEE). It should be noted that some of<br />
the provisions of the British <strong>Standards</strong>, such as the safeguards<br />
for livestock, the requirements for caravans, the provision<br />
of British <strong>Standards</strong>, lEE completion and inspection<br />
certificates and the recommendations for periodic inspection<br />
and testing, are outwith the scope of the Building <strong>Standards</strong><br />
Regulations.<br />
Amdt: December 1999<br />
N
N<br />
Regulations 26 & 26A<br />
Electrical installations<br />
26 (1) Every electrical installation to which this<br />
regulation applies and every item of stationary<br />
electrical equipment connected to such an<br />
installation shall provide adequate protection<br />
against its being a source of fire or a cause of<br />
personal injury.<br />
(2) This regulation shall not apply to an installation<br />
-<br />
(a) serving a building or any part of a building<br />
to which the Mines and Quarries Act<br />
1954(a) or the Factories Act 1961 applies;<br />
(b) forming part of the works of an undertaker<br />
to which regulations for the supply and<br />
distribution of electricity made under the<br />
Electricity (Supply) Acts 1882 to 1936 or<br />
section 16 of the Energy Act 1983(b)<br />
apply; or<br />
(c) consisting of a circuit (including a circuit<br />
for telecommunication or for transmission<br />
of sound, vision or data, or for alarm<br />
purposes) which operates at a voltage not<br />
normally exceeding 50 volts alternating<br />
current or 120 volts direct current, measured<br />
between any two conductors or<br />
between any conductor and earth, and<br />
which is not connected directly or indirectly<br />
to an electricity supply which operates<br />
at a voltage higher than those<br />
mentioned in this sub-paragraph.<br />
(3) In paragraph (1) “stationary electrical equipment”<br />
means electrical equipment which is<br />
fixed, or which has a mass exceeding 18kg<br />
and is not provided with a carrying handle.<br />
26A. Every building other than a building in<br />
purpose group 1 shall be provided with suitable<br />
aids to assist the hard of hearing.<br />
(a) 1954c.70<br />
(b) 1983c.25<br />
Amdt: December 1999<br />
6N
The standards<br />
N1 Application of Part N<br />
N1.1 This Part sets out the required standards for Regulations 26 and 26A.<br />
N1.2 The standards apply to electrical installations in, or serving, all buildings,<br />
except -<br />
installations specified in Regulations 26(2) and 26A<br />
N2 Electrical Installations<br />
Electrical Installations<br />
7N<br />
N1.1 – N2.2<br />
N2.1* An electrical installation must be constructed, installed and protected to minimise the risk of fire in the<br />
building or elsewhere.<br />
In normal operation, taking into account the surroundings, it must not create the risk of burns, shock or<br />
other injury to people.<br />
It must -<br />
a. safely accommodate any likely maximum demand;<br />
b. incorporate suitable automatic devices for protection against overcurrent or leakage; and<br />
c. have switches, or other means of isolating parts of the installation or equipment connected to it,<br />
as are necessary for safe working and maintenance.<br />
AIDS TO COMMUNICATION<br />
N2.2* Suitable aids for people with a hearing impairment must be provided in -<br />
a. auditoria and conference halls with a floor area more than 100 square metres; and<br />
b. situations where the public is separated from a vendor or service provider by a glazed screen.<br />
Amdt: December 1999<br />
N
Provisions deemed to satisfy the standards<br />
ELECTRICAL INSTALLATIONS<br />
(N2.1) The requirements of N2.1 will be met where an installation complies with the relevant requirements of<br />
BS7671: 1992.<br />
AIDS TO COMMUNICATION<br />
(N2.2) The requirements of N2.2 will be met by the installation of an aid to hearing system that will provide a<br />
sound signal to a hearing aid enhanced by 20dB and suppress any reverberation, audience or other<br />
environmental noise.<br />
9N<br />
(N2.1, N2.2)<br />
Amdt: December 1999<br />
N
10N
MISCELLANEOUS<br />
HAZARDSP
Contents<br />
Introduction<br />
REGULATIONS 27 & 28<br />
Miscellaneous hazards<br />
THE STANDARDS<br />
P1 Application of Part P P1.1-P1.3<br />
P2 Danger from accident<br />
Collision with projections P2.1<br />
Collision with glazing P2.2<br />
Cleaning of windows and rooflights P2.3-P2.4<br />
Emergency stopping of escalators and<br />
passenger conveyors<br />
P2.5<br />
Discharge of steam or hot water P2.6<br />
Access to manual controls P2.7<br />
Roof access P2.8<br />
P3 Danger from malfunction of an unvented hot<br />
water storage system<br />
Unvented hot water storage system P3.1<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(P2.2) Collision with glazing<br />
(P2.3-<br />
P2.4)<br />
Cleaning of windows and rooflights<br />
(P2.5) Emergency stopping of escalators and passenger conveyors<br />
(P2.8) Roof access<br />
(P3.1) Unvented hot water storage system<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A, General.<br />
3P<br />
Amdt: December 1999<br />
P
5P<br />
Introduction<br />
1 The intention of this Part is to reduce the risk of<br />
accidents which could otherwise arise from built-in hazards<br />
or from the malfunction of mechanical equipment in and<br />
around a building. The Part brings together safety controls<br />
which do not lend themselves to inclusion in other Parts of<br />
the <strong>Technical</strong> <strong>Standards</strong>.<br />
2 The requirements are intended to prevent the creation of<br />
dangerous obstructions, such as windows opening on to<br />
pedestrian routes at body height, and to prevent the<br />
construction and location of windows which cannot be<br />
cleaned and operated safely. They are intended to reduce<br />
injury caused by collision with glass and caused by unsafe<br />
access to and on roofs, to safely locate hot water and steam<br />
vent pipe outlets, and to reduce the risk of explosion through<br />
the malfunction of an unvented hot water storage system<br />
where a minimum range of safety devices is required and<br />
installation is controlled.<br />
3 Escalators and passenger conveyors are required to have<br />
safe stopping mechanisms which can be operated by the user<br />
in the event of an accident.<br />
Amdt: December 1999<br />
P
P<br />
Regulations 27 & 28<br />
Miscellaneous hazards<br />
27 (1) Subject to paragraph (2), every building shall<br />
be so constructed as to provide adequate<br />
protection for users of the building and<br />
persons in its vicinity from danger from<br />
accidents arising from -<br />
(a) collision with projections on the exterior of<br />
the building and in circulation areas within<br />
the building;<br />
(b) collision with glazing;<br />
(c) cleaning of windows and rooflights;<br />
(d) use of escalators or passenger conveyors;<br />
(e) discharge of steam or hot water;<br />
(f) the positioning of manual controls for<br />
operation of windows and rooflights;<br />
(g) the means of access to a roof.<br />
(2) Paragraph (1)(e) shall apply only, and<br />
paragraphs (1)(f) and (g) shall not apply, to<br />
buildings of purpose group 1.<br />
(3) In paragraph (1)(b) “glazing” means any<br />
permanently secured sheet of glass or plastics.<br />
28 (1) Subject to paragraph (2), every system in<br />
which heated water is stored in a building<br />
(irrespective of whether the water is heated in<br />
the system) and which does not incorporate a<br />
ventilating pipe open to the atmosphere shall<br />
be so constructed as to provide adequate<br />
protection from malfunctions of the system.<br />
(2) This regulation shall not apply to -<br />
(a) any system in which the storage capacity<br />
for heated water does not exceed 15 litres;<br />
(b) any parts of a system which are used solely<br />
for space heating;<br />
(c) any system used for an industrial or commercial<br />
process.<br />
Amdt: December 1999<br />
6P
The standards<br />
P1 Application of Part P<br />
P1.1 This Part sets out the required standards for Regulations 27 and 28.<br />
P1.2 The standards in P2 apply to all buildings,<br />
except -<br />
P2.6 applies only to a building of purpose group 1; and<br />
P2.7 and P2.8 apply to all buildings other than a building of purpose group 1.<br />
P1.3 The standards in P3 apply to an unvented hot water storage system in all buildings.<br />
P2 Danger from accident<br />
COLLISION WITH PROJECTIONS<br />
7P<br />
P1.1 – P2.3<br />
P2.1 Any projection on a building, and any part of a building capable of being projected, must be positioned<br />
and secured so that it does not cause a dangerous obstruction to people outside, or inside, the building in<br />
circulation spaces and a door which swings both ways across a route of passage must be glazed or have<br />
a vision panel.<br />
COLLISION WITH GLAZING<br />
P2.2* Glazing in a building positioned where accidental collision with it is likely, must be constructed and<br />
installed, or protected, to minimise the danger of collision and injury to people.<br />
CLEANING OF WINDOWS AND ROOFLIGHTS<br />
P2.3* In a building of purpose group 1, any window or part of a window more than 4 m above the adjacent<br />
ground must be constructed so that its external and internal glazed surfaces can be safely cleaned<br />
from -<br />
a. inside the building; or<br />
b. from a loadbearing surface; or<br />
c. a window access system mounted on the building,<br />
except -<br />
a window in any part of a building in common occupation which complies with the standard in<br />
P2.4b.<br />
Amdt: December 1999<br />
P
P<br />
P2.4 – P3.1<br />
P2.4* In a building of purpose groups 2 to 7 and in that part of a building of purpose group 1 which is in<br />
common occupation every window and rooflight, except for a rooflight within a roof access hatch must -<br />
a. be constructed to comply with P2.3, or<br />
b. have provision for cleaning from a portable ladder where no part of any external or internal<br />
glazed surface is more than 9 m above -<br />
Amdt: December 1999<br />
i. the adjacent ground; or<br />
ii. an adjacent loadbearing surface<br />
which has suitable unobstructed space for the use of such a ladder.<br />
EMERGENCY STOPPING OF ESCALATORS AND PASSENGER CONVEYORS<br />
P2.5* Escalators and passenger conveyors must be provided with devices capable of being readily operated<br />
which, when activated, can bring the equipment to a controlled halt in such a way that passengers will<br />
be able to maintain their balance.<br />
DISCHARGE OF STEAM OR HOT WATER<br />
P2.6 Any vent pipe of a hot water system in a building of purpose group 1 must be positioned so that any<br />
discharge will not endanger anyone inside or outside the building.<br />
ACCESS TO MANUAL CONTROLS<br />
P2.7 A manual control for operating a window or rooflight forming part of a building of purpose groups 2 to<br />
7 must be positioned so that the device can be operated without endangering the user of the control.<br />
ROOF ACCESS<br />
P2.8* A roof forming part of a building of purpose groups 2 to 7 must be provided with a safe and suitable<br />
access thereto including provision thereon of a suitable warning visibly identifying any part of the roof<br />
which is not capable of bearing a concentrated load of 0.9 kN per 130 millimetres square,<br />
except -<br />
a roof having eaves which at any part is at a height of less than 4.5 m above the adjacent ground need be<br />
provided only with a suitable warning.<br />
P3 Danger from malfunction of an unvented hot water storage system<br />
UNVENTED HOT WATER STORAGE SYSTEM<br />
P3.1* An unvented hot water storage system must be so constructed as to prevent the temperature of the stored<br />
water at any time exceeding 100°C and to provide adequate protection from malfunctions of the system.<br />
8P
Provisions deemed to satisfy the standards<br />
COLLISION WITH GLAZING<br />
9P<br />
(P2.2) – (P3.1)<br />
(P2.2) The requirements of P2.2 will be met where glazing is in accordance with BS 6262: Part 4: 1994.<br />
CLEANING OF WINDOWS AND ROOFLIGHTS<br />
(P2.3) The requirements of P2.3 will be met where external and internal glazed surfaces can be cleaned safely<br />
from -<br />
a. inside the building in accordance with the requirements of Clauses 10.2, 10.3 and 10.4 of BS<br />
8213: Part 1: 1991; or<br />
b. a loadbearing surface, eg balcony, catwalk, roof surface etc to which safe access can be<br />
obtained; and<br />
i. which has a protective barrier not less than 1.1 m high, where any edge of the surface or<br />
access is likely to be dangerous; and<br />
ii. where no part of the glazing is more than 4 m above the surface.<br />
c. a window access system mounted on the building in accordance with Clause 9 of BS 8213:<br />
Part 1: 1991.<br />
(P2.4) The requirements of P2.4b.ii. will be met by -<br />
a. a loadbearing surface, eg balcony, catwalk, roof surface etc to which safe access can be<br />
obtained; and<br />
i. the access is suitable for carrying a portable ladder; and<br />
ii. which has a protective barrier not less than 1.1 m high, where any edge of the surface or<br />
access is likely to be dangerous.<br />
EMERGENCY STOPPING OF ESCALATORS AND PASSENGER CONVEYORS<br />
(P2.5) The requirements of P2.5 will be met where the location of the devices and the stopping of the equipment<br />
complies with the requirements of BS EN 115: 1995.<br />
ROOF ACCESS<br />
(P2.8) The requirements for access will be met by stairs, ladders and walkways complying with BS 5395:<br />
Part 3: 1985 and the requirements for the visible warning will be met by sign A2.4 of BS 5378:<br />
Part 3:1982.<br />
UNVENTED HOT WATER STORAGE SYSTEM<br />
(P3.1) The requirements of P3.1 will be met where the storage vessel of an unvented hot water storage system<br />
meets the following requirements.<br />
Amdt: December 1999<br />
P
P<br />
(P3.1)<br />
1 Hot water storage system having a storage vessel of not more than 500 litres capacity having a power<br />
input not more than 45 kW.<br />
In this specification -<br />
UNIT means a vessel for heating water or storing hot water, factory fitted with the safety devices<br />
described in 1b below and incorporating other operating devices to stop primary flow, prevent backflow,<br />
control working pressure, relieve excess pressure and accommodate expansion all fitted on the<br />
unit by the manufacturer; and<br />
PACKAGE means a vessel for heating water or storing hot water, factory fitted with the safety devices<br />
described in 1b below and supplied by the manufacturer with a kit containing other operating devices<br />
to stop primary flow, prevent backflow, control working pressure, relieve excess pressure and accommodate<br />
expansion, to be fitted to the system by the installer.<br />
a. An unvented hot water storage system must be in the form of a proprietary unit or package<br />
which is:<br />
SAFETY DEVICES<br />
Amdt: December 1999<br />
i. the subject of a BBA Certificate; or<br />
ii. Kitemarked to BS 7206: 1990.<br />
b. A unit or package must have, subject to the requirements of 1c below, a minimum of 2 temperature<br />
activated devices operating in sequence comprising -<br />
i. a non self-resetting thermal cut-out; and<br />
ii. a temperature relief valve.<br />
The 2 devices are additional to any thermostatic control which is fitted to maintain the temperature<br />
of the stored water.<br />
c. In indirectly heated units and packages the non self-resetting thermal cut-out should be wired up<br />
to a motorised valve, or some other device specified in the BBA Certificate or British Standard,<br />
to shut off the flow to the primary heater. If the unit incorporates a boiler the thermal cut-out<br />
may be on the boiler.<br />
d. Where an indirect unit or package has any alternative direct method of water heating fitted a<br />
non self-resetting thermal cut-out device will also be needed on the direct source(s).<br />
e. In both directly and indirectly heated units and packages, the temperature relief valve referred to<br />
in 1b above should be located directly on the storage vessel. The valve should be sized to give a<br />
discharge rating at least equal to the power input to the water. The valve should not be disconnected<br />
other than for replacement or relocated in any other position nor the connecting boss<br />
used to connect any other device or fitting. Each valve should discharge via a short length of<br />
metal pipe of a size not less than the nominal outlet size of the temperature relief valve either<br />
directly or by way of a manifold sized to accept the total discharge from the discharge pipes<br />
connected to it, through an air break over a tundish located vertically as near as possible to the<br />
valve.<br />
f. The discharge pipe from the tundish should be of suitable metal and be at least one pipe size<br />
larger than the outlet pipe on the safety device. The pipe should be laid to a continuous fall and<br />
be no longer than the equivalent in hydraulic resistance of a pipe 9 m long unless the bore is<br />
increased. The pipe should terminate in a visible but safe place such as a gully, where there is<br />
no risk of contact with the discharge by persons.<br />
10P
11P<br />
(P3.1)<br />
2 A hot water storage system having a storage vessel of over 500 litres capacity or having a power input<br />
more than 45 kW.<br />
REQUIREMENTS<br />
a. These systems will generally be for projects specified to unique designs.<br />
SAFETY DEVICES<br />
INSTALLATION<br />
b. An unvented hot water storage system with a storage vessel of more than 500 litres capacity and<br />
a power input not more than 45 kW should have safety devices in accordance with the recommendations<br />
of Section 2 Clause 2.4 in BS 6700: 1997.<br />
c. Any unvented hot water storage vessel with a power input of more than 45 kW should have the<br />
appropriate number of temperature relief valves either to BS 6283: Part 2: 1991 or Part 3: 1991<br />
to give a combined discharge rating at least equal to the power input or equally suitable temperature<br />
relief valves marked with the set temperature in °C, and the discharge rating marked in<br />
kW, measured in accordance with Appendix F of BS 6283: Part 2: 1991 or Appendix G of BS<br />
6283: Part 3: 1991, at least equal to the power input. The valves should be factory fitted to the<br />
storage vessel and the sensing element located as described in 1e.<br />
d. Non self-resetting thermal cut-outs appropriate to the heat source should be incorporated in the<br />
system and installed as described in 1d.<br />
e. Discharge pipes to convey any discharges from safety devices should be installed as described<br />
in 1f.<br />
Amdt: December 1999<br />
P
12P
ACCESS AND<br />
FACILITIES FOR<br />
DWELLINGSQ
Contents<br />
INTRODUCTION<br />
REGULATION 29<br />
Access and facilities for dwellings<br />
THE STANDARDS<br />
Q1 Application of Part Q Q1.1-Q1.2<br />
Q2 Access<br />
Access to dwellings Q2.1-Q2.4<br />
Accessible entrance Q2.5-Q2.7<br />
Buildings of purpose sub-group 1A Q2.8-Q2.10<br />
Access within dwellings Q2.11-Q2.12<br />
Access between storeys Q2.13<br />
Q3 Facilities<br />
Accommodation Q3.1-Q3.2<br />
Kitchens Q3.3-Q3.4<br />
Windows Q3.5<br />
Space heating Q3.6<br />
Lighting points Q3.7-Q3.8<br />
Socket outlets Q3.9<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(Q2.1,<br />
Q2.4)<br />
Access to dwellings<br />
(Q2.7) Accessible entrance<br />
(Q2.10) Buildings of purpose sub-group 1A<br />
(Q2.11) Access within dwellings<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A, General.<br />
3Q<br />
Amdt: December 1999<br />
Q
5Q<br />
Introduction<br />
1. The intention of this Part is to ensure that every dwelling<br />
will be provided with suitable access from a road, basic<br />
accommodation and necessary facilities.<br />
2. In addition, the intention is to permit occupiers to invite<br />
disabled people to visit them in their homes with minimum<br />
inconvenience, although it is not intended to create dwellings<br />
that, from the outset, will permit independent living for all<br />
disabled people.<br />
3. Access for disabled people is normally required to at<br />
least one entrance of a house or other dwelling entered<br />
directly from outside, except where the steepness of the site<br />
makes this impracticable. However, such access is always<br />
required to the common entrance of a building of purpose<br />
sub-group 1A.<br />
4. Within a dwelling access for disabled people is normally<br />
required throughout the accessible entrance storey, or<br />
throughout the principal entrance storey of a dwelling to an<br />
entrance of which wheelchair access is not required.<br />
5. Sanitary facilities are required by Part M to be provided<br />
on a storey containing an accessible apartment.<br />
6. In this Part the term disabled people always includes<br />
wheelchair users.<br />
7. It should be noted that relevant material from the now<br />
deleted Part T has been incorporated in this Part.<br />
8. This Part is limited to the provision of access into and<br />
within buildings; it does not cover means of escape from fire<br />
or provision of means of warning of fire, for which reference<br />
should be made to Part E.<br />
Amdt: December 1999<br />
Q
Q<br />
Regulation 29<br />
Access and facilities for dwellings<br />
29 (1) A building of purpose group 1 shall be<br />
provided with -<br />
(a) safe and convenient access from a suitable<br />
road;<br />
(b) adequate access within and between its<br />
storeys;<br />
(c) adequate sleeping accommodation;<br />
(d) adequate kitchen facilities;<br />
(e) adequate windows; and<br />
(f) adequate space heating.<br />
(2) Every building of purpose group 1 to which it<br />
is reasonably practicable to make available a<br />
public supply of electricity shall be provided<br />
with sufficient electricity lighting points and<br />
socket outlets.<br />
(3) This regulation shall not be subject to specification<br />
in a notice served under section 11 of<br />
the Act.<br />
Amdt: December 1999<br />
6Q
The standards<br />
Q1 Application of Part Q<br />
Q1.1 This Part sets out the required standards for Regulation 29.<br />
Q1.2 The standards apply to every building, or part of a building, of purpose group 1 which is intended to be<br />
occupied as a single dwelling.<br />
except -<br />
Q2.8 to Q2.10 apply only to the common parts of buildings of purpose sub-group 1A.<br />
Q2 Access<br />
ACCESS TO DWELLINGS<br />
Q2.1* There must be access to at least one entrance of a dwelling, and to the common entrance of a building<br />
of purpose sub-group 1A, from a suitable road and from any car parking within land in the same<br />
occupation by an access route which is level or ramped and suitable for disabled people,<br />
except -<br />
wheelchair access is not required and steps are permitted on the access route -<br />
a. to a house where -<br />
i. there are no apartments on an accessible entrance storey, or<br />
ii. it is not reasonably practicable to construct an access route complying with this Part,<br />
and the requirements of Part S for ramps, between the point of access to, or from any car<br />
parking within, land in the same occupation and any entrance to the dwelling; or<br />
b. in the case of a building of purpose sub-group 1A not served by a lift, to -<br />
i. a common entrance where it does not serve a ground storey flat or maisonette, and<br />
ii. a flat or maisonette on an upper storey.<br />
Q2.2 The length of the access must not exceed 45 metres.<br />
Q2.3 The width of the access must be at least -<br />
a. where it serves 1 or 2 dwellings, 900mm; or<br />
b. where it serves more than 2 dwellings, 1200mm.<br />
Q2.4* The access must comprise a level or ramped firm surface suitable for pedestrian and wheelchair traffic.<br />
ACCESSIBLE ENTRANCE<br />
Q2.5 The accessible entrance to a dwelling, and the common entrance to a building of purpose sub-group<br />
1A, must comply with Q2.6 and Q2.7,<br />
except -<br />
where exceptions a. or b. to Q2.1 apply.<br />
7Q<br />
Q1.1 – Q2.5<br />
Amdt: September 2001<br />
Q
Q<br />
Q2.6 – Q2.13<br />
Q2.6 There must be a platt, level except for any necessary slope for drainage, at least 1.2 x 1.2 metres -<br />
a. at the entrance to the dwelling; or<br />
b. in a building of purpose sub-group 1A, at the common entrance to the building,<br />
except -<br />
where approach is head-on, the platt may be reduced to at least 900mm wide.<br />
Q2.7* The threshold must permit unassisted wheelchair access and the clear opening width of the entrance<br />
door must be at least 775 mm.<br />
except -<br />
in a building of purpose sub-group 1A, the clear opening width of the common entrance door to the<br />
building must be at least 800mm.<br />
BUILDINGS OF PURPOSE SUB-GROUP 1A<br />
Q2.8 Where in a building of purpose sub-group 1A access from the common entrance to the building to the<br />
entrance storey of the dwelling is by way of a common access corridor, the corridor must have an<br />
unobstructed width of at least 1.2 metres.<br />
Q2.9 Where the entrance door to a dwelling is more than 10 metres above the common entrance to the building,<br />
a lift in accordance with (S2.6)a must be provided from a point not more than 1 metre above that<br />
entrance to the building to a point not more than 3 metres above or below the entrance to the dwelling.<br />
Q2.10* In a building of purpose sub-group 1A -<br />
a. an entryphone system, where fitted, must be accessible to and operable by disabled people; and<br />
b. any light switch in a common access corridor or stair or other communal area must be accessible<br />
to, and operable by, disabled people.<br />
ACCESS WITHIN DWELLINGS<br />
Q2.11* The means of access throughout the accessible entrance storey of a dwelling or where there are no<br />
apartments on this storey, on the first storey above or below the accessible entrance storey containing<br />
an apartment, must be level or ramped and suitable for disabled people,<br />
except -<br />
a stair within a storey is permitted, provided that there is level or ramped access suitable for disabled<br />
people to and within at least one apartment and to sanitary accommodation provided in accordance<br />
with M4.3.<br />
Q2.12 Where level or ramped access suitable for disabled people is not required by Q2.1 the means of access<br />
throughout the principal entrance storey, or where there are no apartments on this storey, on the first<br />
storey above or below the principal entrance storey containing an apartment, must be in accordance<br />
with the requirements of Q2.11.<br />
ACCESS BETWEEN STOREYS<br />
Q2.13 Where a dwelling has accommodation, other than storage, on more than one storey the storeys containing<br />
accommodation must be connected by a stair or ramp in accordance with the requirements of Part S.<br />
Amdt: September 2001<br />
8Q
Q3 Facilities<br />
ACCOMMODATION<br />
Q3.1 Every apartment must be capable of accommodating at least -<br />
Notes:<br />
1. An activity space is measured at floor level.<br />
2. The shaded area of an activity space may overlap only the shaded area of another activity space.<br />
Q3.2 Every bedroom must be located so that it is not necessary to pass through another bedroom in order to<br />
reach a bathroom, toilet, or circulation space.<br />
KITCHENS<br />
a. a bed; and<br />
b. a wardrobe; and<br />
c. a chest of drawers,<br />
Q3.3 A dwelling must have a kitchen, provided with -<br />
a. a solid fuel cooker designed for continuous burning; or<br />
b. a space, plus such piping, cables or other apparatus as will enable a gas, electric or oil cooker to<br />
be used,<br />
together with the associated activity space of the dimensions shown in the diagram to this standard -<br />
9Q<br />
Q3.1 – Q3.3<br />
together with their associated activity spaces of the dimensions shown in the diagram to this standard,<br />
except -<br />
a wardrobe space is not required where a built-in wardrobe of equal size is provided.<br />
Diagram to Q3.1: Activity spaces<br />
900<br />
400<br />
2000<br />
250<br />
600<br />
Bed Space Wardrobe Space Chest of Drawers Space<br />
600<br />
1000<br />
(700)<br />
Notes:<br />
1. An activity space is measured at floor level.<br />
2. The shaded area of one activity space may overlap only the<br />
shaded area of another activity space.<br />
( )<br />
750<br />
450<br />
1000<br />
(700)<br />
KEY<br />
Activity space<br />
Dimension in millimetres<br />
Reduced dimension when<br />
measured to a bed<br />
Amdt: September 2001<br />
Q
Q<br />
Q3.3 – Q3.9<br />
Diagram to Q3.3: Activity spaces<br />
Z<br />
Cooker Space<br />
Amdt: September 2001<br />
Z<br />
1000<br />
Note:<br />
An activity space is measured at floor level<br />
Z<br />
10Q<br />
KEY<br />
Activity space<br />
Not less than the dimensions of the appliance<br />
Dimension in millimetres<br />
Q3.4 Kitchen storage of at least 1 cubic metre must be provided either within or adjacent to the kitchen.<br />
WINDOWS AND GLAZED DOORS<br />
Q3.5 Every apartment must have a window or windows of an aggregate glazed area equal to at least 1/15th<br />
of the floor area of the apartment and situated in an external wall or roof, or in a wall between the<br />
apartment and a conservatory.<br />
SPACE HEATING<br />
Q3.6 A dwelling must have a fixed space heating appliance or a central heating system, which may include<br />
any system of warm air or underfloor heating, capable of either -<br />
a. maintaining a temperature of 18 degrees Centigrade in at least one apartment when the outside<br />
temperature is minus 1 degree Centigrade ; or<br />
b. making available at least 3 kilowatts of heating in at least one apartment.<br />
LIGHTING POINTS<br />
Q3.7 A dwelling to which it is reasonably practicable to make available a public supply of electricity must<br />
have an electric lighting system providing at least one lighting point to every circulation space, kitchen,<br />
bathroom, toilet and other space having a floor area of 2 square metres or more.<br />
Q3.8 Any lighting point serving a stair must have controlling switches at each storey.<br />
SOCKET OUTLETS<br />
Q3.9 A dwelling to which it is reasonably practicable to make available a public supply of electricity must<br />
have at least -<br />
a. in the kitchen, 6 socket outlets;<br />
b. in each apartment, 4 socket outlets; and<br />
c. anywhere in the dwelling, 4 additional socket outlets.
Provisions deemed to satisfy the standards<br />
ACCESS TO DWELLINGS<br />
(Q2.1) The requirements of Q2.1, as regards a suitable road, will be met by -<br />
a. a public road; or<br />
b. a road, at least 3 metres wide capable of carrying a vehicle axle load of 5 tonnes.<br />
(Q2.4) The requirements of Q2.4 for the surface of paths or ramps will be met by -<br />
a. 50mm concrete slabs bedded on granular material; or<br />
b. 30mm tarmacadam to BS4987: Parts 1 and 2: 1993 laid on 100mm of consolidated hardcore<br />
bottoming; or<br />
c. 50mm clay or calcium silicate pavers to BS6677: Part 1: 1986, laid in accordance with<br />
BS6677: Part 2: 1986; or<br />
d. 60mm concrete paving blocks to BS6717: Part 1: 1993, laid in accordance with BS6677:<br />
Part 2: 1986.<br />
ACCESSIBLE ENTRANCE<br />
(Q2.7) The requirements of Q2.7 for an accessible threshold will be met by a threshold designed as follows:<br />
a. The surface of the platt should be no more than 10mm below the leading edge of the sill, as<br />
shown in Diagram A to this specification.<br />
b. No single vertical increment associated with the sill or the threshold should be more than 15<br />
mm, and any sloping element should have a slope not more than 15 degrees to the horizontal.<br />
Any vertical increment of more than 5mm should be rounded or chamfered.<br />
Diagram A to (Q2.7): Sill and threshold constraints<br />
10mm max<br />
platt<br />
sill<br />
15mm max<br />
15˚max<br />
threshold<br />
c. Where the floor covering (or finished structural floor where no covering is intended) is designed<br />
to be more than 15mm below the top of the threshold an internal transition unit should be provided<br />
as shown in Diagram B to this specification.<br />
11Q<br />
5mm max<br />
floor finish<br />
structural floor<br />
(Q2.1) – (Q2.7)<br />
Amdt: December 1999<br />
Q
Q<br />
(Q2.7) – (Q2.11)<br />
d. The transition unit should have a gradient not more than 15 degrees to the horizontal, a slip<br />
resistant surface, and should start not less than 5mm and not more than 10mm from the top of<br />
the threshold, and finish not more than 5mm above the floor covering, or finished structural<br />
floor where no covering is intended.<br />
Diagram B to (Q2.7): Internal transition unit<br />
sill<br />
BUILDINGS OF PURPOSE SUB-GROUP 1A<br />
(Q2.10) The requirements of Q2.10a. will be met where the entryphone control panel is situated 900mm -<br />
1.2 metres above the entrance platt<br />
The requirements of Q2.10c. will be met where light switches are situated 900mm - 1.2 metres above<br />
the floor.<br />
ACCESS WITHIN DWELLINGS<br />
(Q2.11) The requirements of Q2.11 will be met where -<br />
a. every accessible corridor is level or ramped and is at least 900mm wide,<br />
except -<br />
at a radiator the width may reduce to at least 750mm for a length not more than 2 metres; and<br />
b. access to each apartment and kitchen and to sanitary accommodation is provided through a<br />
doorway with a clear opening width at least that shown in the table to this specification.<br />
Table to (Q2.11): Width of internal doors<br />
threshold<br />
5mm max<br />
transition floor<br />
structural floor<br />
clear opening width (mm) Minimum corridor width at door (mm)<br />
750 1 200 (900 when approached head-on)<br />
775 1 050 (900 when approached head-on)<br />
800 900<br />
Amdt: December 1999<br />
12Q<br />
15˚max<br />
5mm max
STORAGE OF WASTE R
Contents<br />
INTRODUCTION<br />
REGULATIONS 30 & 31<br />
Storage of waste<br />
THE STANDARDS<br />
R1 Application of Part R R1.1-R1.3<br />
R2 Solid waste storage<br />
Buildings of purpose group 1 R2.1-R2.3<br />
R3 Dungsteads and farm effluent tanks<br />
Construction and location R3.1<br />
Safety R3.2<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(R2.3) Buildings of purpose group 1<br />
(R3.1) Construction and location<br />
(R3.2) Safety<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A, General.<br />
3R<br />
Amdt: September 2001<br />
R
5R<br />
Introduction<br />
1. The intention of this Part is to ensure that -<br />
a. there are facilities for the storage and removal of<br />
solid waste from buildings of purpose group 1; and<br />
b. any dungsteads or farm effluent tanks do not endanger<br />
health and safety.<br />
2. Since 1990, there has been a change in waste management<br />
initiatives. The <strong>Government</strong>’s White Paper on the<br />
Environment sets out a strategy for achieving more sustainable<br />
waste management. Included in the strategy are local<br />
authority targets for the recovery of 40% of municipal waste<br />
(this includes household waste) by 2005 and the composting<br />
of 1 million tonnes of organic household waste by 2001.<br />
Waste collection authorities are now required to produce<br />
recycling plans and, in order to implement efficient recycling<br />
schemes, a change in the means of storage of solid household<br />
waste may be necessary. The Environmental Protection<br />
Act, 1990 gives powers to the waste collection authority to<br />
stipulate the type and number of containers to be used and<br />
two or more containers may therefore be needed to store different<br />
types of waste. This could increase the spatial requirements<br />
for the storage area inside and outside the dwelling.<br />
The Act also empowers the waste collection authority to designate<br />
a collection point for removal of the waste and this is<br />
normally at the curtilage of the dwelling. House designers<br />
and developers should consult local authorities on local<br />
waste management strategies and make suitable provisions.<br />
3. There are other requirements that will have to be taken<br />
into account in certain cases. Parts D and E (Structural Fire<br />
Precautions and Means of Escape from Fire) for example<br />
have requirements for the construction of, and access to,<br />
solid waste storage accommodation in a dwelling.<br />
4. It should be noted that special arrangements may have to<br />
be made to arrange storage to take account of special waste<br />
from buildings other than dwellings, e.g. the Health and<br />
Safety Executive should be consulted about factory waste.<br />
Health Boards should consult the DOE Waste Management<br />
Paper No 25, “Clinical Wastes”.<br />
Amdt: September 2001<br />
R
R<br />
Regulations 30 & 31<br />
SOLID WASTE STORAGE<br />
30. (1) A building of purpose group 1 shall be<br />
provided with adequate accommodation<br />
for solid waste storage.<br />
(2) Such accommodation shall be so constructed<br />
as to -<br />
(a) facilitate access for storage and for<br />
removal of its contents;<br />
(b) minimise risks to health and safety;<br />
and<br />
(c) prevent contamination of any water<br />
supply or watercourse.<br />
(3) This regulation shall not be subject to<br />
specification in a notice served under<br />
section 11 of the Act.<br />
31. A dungstead or farm effluent tank shall be so<br />
constructed, positioned and protected as to<br />
minimise risks to health and safety and<br />
prevent contamination of any water supply or<br />
watercourse.<br />
Amdt: September 2001<br />
6R
The standards<br />
R1 Application of Part R<br />
R1.1 This Part sets out the required standards for Regulations 30 and 31.<br />
R1.2 The standards in R2 apply to buildings of purpose group 1.<br />
R1.3 The standards in R3 apply to dungsteads and farm effluent tanks.<br />
R2 Solid waste storage<br />
BUILDINGS OF PURPOSE GROUP 1<br />
R2.1 In order to minimise the risk to health and safety and to prevent environmental contamination, a building<br />
of purpose group 1 must be provided with a solid, washable hard-standing sufficiently large to accommodate,<br />
and provide access to, a waste container, or containers (as specified by the waste collection<br />
authority) from where -<br />
a. if it is at a collection point designated by the waste collection authority, the container(s) can be<br />
emptied or removed by the waste collection authority; or<br />
b. the container(s) can be readily presented at a collection point for emptying or removal by the<br />
waste collection authority.<br />
R2.2 Where the provision for communal solid waste storage is located within a building, there must be provision<br />
for washing down and draining the floor into a wastewater drainage system.<br />
R2.3* Solid waste storage must be secured against access by vermin, as far as is reasonably practicable, until<br />
the waste is presented for removal by the collection authority.<br />
7R<br />
R1.1 – R2.3<br />
Amdt: September 2001<br />
R
R<br />
R3.1 – R3.2<br />
R3 Dungsteads and farm effluent tanks<br />
CONSTRUCTION AND LOCATION<br />
R3.1* A dungstead or farm effluent tank (including a slurry or silage effluent tank) must be constructed -<br />
SAFETY<br />
a. in such a manner so as to prevent the escape of effluent through the structure that could cause<br />
ground contamination or environmental pollution; and<br />
b. in such a manner so as to avoid endangering any water supply or watercourse caused by the<br />
seepage or overflow of effluent; and<br />
c. at sufficient distance from a dwelling or premises used wholly or partly for the preparation or<br />
consumption of food so as not to be prejudicial to the health and safety of people in the dwelling<br />
or food premises.<br />
R3.2* Where there is the possibility of injury from falls, a dungstead or farm effluent tank must be suitably<br />
covered or fenced.<br />
Amdt: September 2001<br />
8R
Provisions deemed to satisfy the standards<br />
BUILDINGS OF PURPOSE GROUP 1<br />
(R2.3) The requirements of R2.3 will be met where the waste storage is -<br />
a. a container of solid, rigid material with a tight fitting lid; or<br />
b. a ventilated structure -<br />
CONSTRUCTION AND LOCATION<br />
i. with secure door or lid providing ready access; and<br />
9R<br />
(R2.3) – (R3.2)<br />
ii. constructed such that no part will permit a sphere of 15 mm diameter to pass through.<br />
(R3.1) The requirements of R3.1c will be met where the dungstead or farm effluent tank is located at least<br />
15 m from the dwelling or food premises.<br />
SAFETY<br />
(R3.2) The requirements of R3.2 will be met where the covers or fences for the dungstead or the farm effluent<br />
tank are in accordance with the relevant recommendations of Section 8 of BS 5502: Part 50: 1993.<br />
Amdt: September 2001<br />
R
10R
ACCESS TO AND MOVEMENT<br />
WITHIN BUILDINGS, AND<br />
PROTECTIVE BARRIERSS
Contents<br />
INTRODUCTION<br />
REGULATION 32<br />
Access to and movement within buildings, and protective barriers<br />
THE STANDARDS<br />
S1 Application of Part S S1.1-S1.3<br />
S2 Access to and movement within buildings<br />
Car parking S2.1-S2.2<br />
Access to buildings S2.3<br />
Principal entrance S2.4-S2.5<br />
Movement within buildings S2.6-S2.7<br />
Internal doors and lobbies S2.8-S2.9<br />
Areas of audience and spectator fixed seating S2.10<br />
S3 Stairs and ramps<br />
General standards for all stairs S3.1<br />
Rules of measurement S3.2<br />
Rise, going and pitch of a flights in stairs S3.3-S3.9<br />
Length of flights S3.10<br />
Risers and nosings S3.11<br />
Flights consisting partly of straight and partly of<br />
tapered treads<br />
S3.12-S3.14<br />
Flights consisting wholly of tapered treads S3.15<br />
Pedestrian ramps S3.16-S3.17<br />
Landings S3.18-S3.19<br />
Handrails S3.20-S3.24<br />
Headroom S3.25<br />
Industrial stairs and fixed ladders S3.26<br />
Stairs and fixed ladders in agricultural buildings S3.27<br />
Steps in sloping gangways S3.28<br />
S4 Protective barriers<br />
Pedestrian protective barriers S4.1-S4.3<br />
Vehicle protective barriers S4.4-S4.5<br />
PROVISIONS DEEMED TO SATISFY THE STANDARDS<br />
(S2.3) Access to buildings<br />
(S2.5) Principal entrance<br />
(S2.6- Movement within buildings<br />
S2.7)<br />
(S3.10) Rise, going and pitch of stairs<br />
(S3.11) Risers and nosings<br />
(S3.12) Flights consisting partly of straight and partly of tapered treads<br />
(S3.15) Flights consisting wholly of tapered treads<br />
(S3.26) Industrial stairs and fixed ladders<br />
(S3.27) Stairs and fixed ladders in agricultural buildings<br />
(S4.3) Pedestrian protective barriers<br />
(S4.5) Vehicle protective barriers<br />
ASTERISKS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> an asterisk against a standard denotes that a provision deemed to satisfy the standard<br />
or some aspect of the standard is specified at the end of the relevant Part.<br />
ITALICS<br />
Throughout the <strong>Technical</strong> <strong>Standards</strong> a term in italics is a defined term. The definition is listed in Part A, General.<br />
3S<br />
Amdt: December 1999<br />
S
Introduction<br />
1. The intention of this Part is to ensure, as far as is reasonably practicable,<br />
that buildings are accessible to all users including disabled people who<br />
should be able to gain access to and within buildings without assistance.<br />
There are provisions to ensure that those who have impaired sight can<br />
enter and move within buildings.<br />
2. It should be noted that relevant material from the now deleted Part T<br />
has been incorporated in this Part.<br />
3. All stairs, ramps and protective barriers forming part of a building<br />
must incorporate the basic criteria of safety, which are -<br />
a. that stair and ramp design must be within limits recognised as<br />
offering safe passage; and<br />
b. that protective barriers are designed to reduce the risk of injury<br />
from falling to a lower level and to protect people from vehicles,<br />
where vehicles have access to a building.<br />
4. The use of an industrial stair or fixed ladder is permitted in certain circumstances.<br />
5. A number of issues relating to good practice have not been included as<br />
being inappropriate to a document concerned with minimum standards.<br />
Designers may nevertheless find it helpful to refer to the “Access Guide”,<br />
published by Disability Scotland, and the “Guidance on the Use of Tactile<br />
Paving Surfaces”, published jointly by The <strong>Scottish</strong> Office and the Department<br />
for the Environment, Transport and the Regions.<br />
6. The “Guide to Safety at Sports Grounds” provides further guidance on<br />
steps or ramps associated with gangways of shallow pitch in assembly<br />
buildings (purpose sub-group 5B) such as sports stadia, arenas, theatres<br />
and cinemas.<br />
7. Where there is a storey accessible to disabled people with fixed seating<br />
for spectators or an audience, spectators in wheelchairs should be able to<br />
sit next to able-bodied or disabled companions.<br />
8. In this Part the term disabled people always includes wheelchair users.<br />
9. This Part is limited to the provision of access into and within buildings.<br />
It does not cover means of escape in the event of fire, for which reference<br />
should be made to Part E.<br />
10. Other legislation has a bearing on access, and in particular due regard<br />
should be taken of the provisions and supporting guidance of the Disability<br />
Discrimination Act 1995 and the Workplace (Health, Safety and<br />
Welfare) Regulations 1992.<br />
5S<br />
Amdt: December 1999<br />
S
S<br />
Regulation 32<br />
Access to and movement within buildings, and protective<br />
barriers<br />
32.(1) All users of a building shall be provided with<br />
adequate means of access, and adequate<br />
means of movement within the building both<br />
horizontally and vertically.<br />
(2) A building which contains fixed seating<br />
accommodation for an audience or spectators<br />
shall be provided with adequate level spaces<br />
for wheelchairs.<br />
(3) Except where -<br />
(a) the provision of protective barriers would<br />
obstruct the use of such areas; or<br />
(b) in terms of the <strong>Technical</strong> <strong>Standards</strong>, such<br />
provision is not necessary,<br />
every stair, ramp, raised floor or other raised<br />
accessible area which forms part of a building<br />
or which is provided to meet a requirement of<br />
this regulation shall have a suitable protective<br />
barrier.<br />
(4) Paragraphs (1) and (2) shall not be subject to<br />
specification in a notice served under section<br />
11 of the Act.<br />
Amdt: December 1999<br />
6S
The standards<br />
S1 Application of Part S<br />
S1.1 This Part sets out the required standards for Regulation 32.<br />
S1.2 The standards apply to all buildings,<br />
except -<br />
the standards in S2 do not apply to buildings of purpose group 1.<br />
S1.3 <strong>Standards</strong> S3.26 to S3.28 do not apply to access for disabled people.<br />
S2 Access to and movement within buildings other than dwellings<br />
CAR PARKING<br />
S2.1 Where car parking is provided within land in the same occupation as a building to which this standard<br />
applies, parking spaces in accordance with S2.2 must be -<br />
a. provided at a ratio at least one car parking space per 20 parking spaces or part thereof; and<br />
b. not more than 45 metres from the principal entrance of the building; and<br />
c. clearly marked for use by disabled people.<br />
S2.2 A car parking space or spaces must each be at least 4.8 x 2.4 metres with a clear space at least 1 metre<br />
wide along one long side. The clear space may be shared between 2 car parking spaces.<br />
ACCESS TO BUILDINGS<br />
S2.3* The approach to the principal entrance of a building from a point of access to, and from any car parking<br />
within, land in the same occupation, must have -<br />
a. a level or ramped firm surface suitable for disabled people; and<br />
b. an unobstructed width of at least 1.2 metres, unless a handrail is required by this Part, in which<br />
case the width at handrail level may reduce to at least 1 metre; and<br />
c. a dropped kerb between any road, or car parking provided for disabled people, and the access<br />
route to the building.<br />
PRINCIPAL ENTRANCE<br />
S2.4 The principal entrance door must -<br />
a. contain a leaf which provides a clear opening width of at least 800 mm in accordance with the<br />
diagram to this standard; and<br />
7S<br />
S1.1 – S2.4<br />
Amdt: December 1999<br />
S
S<br />
S2.4 – S2.6<br />
b. have an unobstructed space on the side next to the leading edge of at least 300mm, in accordance<br />
with the diagram to this standard,<br />
except -<br />
where the door is opened by automatic control; and<br />
c. have a clear glazed panel or panels giving a zone of visibility from a height of not more than<br />
900mm to at least 1.5 metres above finished floor level; and<br />
d. where it comprises a revolving door, be provided with an adjacent side hinged or automatic door<br />
complying with a. to c.<br />
Diagram to S2.4: Principal entrance<br />
S2.5* Where an entrance lobby is provided it must be sized to -<br />
a. permit a wheelchair user to move clear of one door before using the next; and<br />
b. allow for someone assisting the wheelchair user; and<br />
c. permit an able-bodied person to pass.<br />
MOVEMENT WITHIN BUILDINGS<br />
800mm<br />
S2.6* Access for disabled people must be provided to and throughout each storey of a building,<br />
except -<br />
a. to a storey containing only fixed plant or machinery the only normal visits to which are intermittent<br />
to inspect or maintain the fixed plant or machinery; or<br />
b. to any catwalk, racking or openwork floor; or<br />
300mm<br />
c. to a storey, other than the principal entrance storey, or gallery in a building of not more than 2<br />
storeys where the storey or gallery is not more than 280 square metres in area excluding vertical<br />
circulation, sanitary accommodation and plant rooms; or<br />
d. to a storey, other than the principal entrance storey, or gallery in a building of more than 2 storeys<br />
where the storey or gallery is not more than 200 square metres in area excluding vertical circulation,<br />
sanitary accommodation and plant rooms; or<br />
e. to a bedroom not having access to sanitary facilities suitable for disabled people in accordance<br />
with Part M, in a building of purpose sub-group 2B not provided with a lift; or<br />
Amdt: December 1999<br />
8S
f. within an area having fixed seating where wheelchair spaces and associated access are provided<br />
in accordance with S2.10; or<br />
g. in a car park and parking garage of purpose sub-group 7B or 7C, storeys where car parking for<br />
disabled people is not provided; or<br />
h. to more than half the public area of a restaurant or bar, provided there is access to the counter in<br />
a bar and to any self-service counter in a restaurant.<br />
S2.7* A change of level within a storey to which access for disabled people is required by S2.6 must be<br />
accomplished by a -<br />
a. ramp; or<br />
b. stair, together with a means of providing unassisted movement between levels for wheelchair<br />
users.<br />
INTERNAL DOORS AND LOBBIES<br />
S2.8 An internal door accessible to disabled people must -<br />
a. contain a leaf which provides a clear opening width of at least 750mm; and<br />
b. have an unobstructed space on the side next to the leading edge of at least 300mm in accordance<br />
with the diagram to this standard,<br />
except -<br />
where the door is opened by automatic control; and<br />
c. where the door is across a corridor or passageway, have a clear glazed panel or panels giving a<br />
zone of visibility from a height of no more than 900mm to at least 1.5 metres above finished<br />
floor level.<br />
Diagram to S2.8: Internal doors<br />
750mm<br />
300mm<br />
S2.9 An internal lobby accessible to disabled people must comply with S2.5.<br />
9S<br />
S2.6 – S2.9<br />
Amdt: December 1999<br />
S
S<br />
S2.10, S3.1<br />
AREAS OF AUDIENCE AND SPECTATOR FIXED SEATING<br />
S2.10 In an accessible storey which contains fixed seating for spectators, or an audience, accessible level<br />
spaces for wheelchair users must be provided in accordance with the table to this standard and which -<br />
a. are each at least 1.4 metres x 900mm; and<br />
b. are dispersed among the remainder of the seating; and<br />
c. enable wheelchair users to be located next to able-bodied or disabled companions; and<br />
d. are arranged to avoid the extra height of wheelchair users from obstructing sightlines; and<br />
e. are kept clear specifically for wheelchair users or are fitted with seating which can be readily<br />
removed if the space is required for a wheelchair user.<br />
Table to S2.10: Wheelchair space provision in areas of audience and spectator fixed seating<br />
Seated capacity Number of wheelchair spaces<br />
up to 200 2<br />
201-10 000 2 + 1 per 100 above 200<br />
10 001-20 000 100 + 5 per 1 000 above 10 000<br />
20 001-40 000 150 + 3 per 1 000 above 20 000<br />
more than 40 000 210 + 2 per 1 000 above 40 000<br />
S3 Stairs and ramps<br />
GENERAL STANDARDS FOR ALL STAIRS<br />
S3.1 A stair must be constructed in any of the following ways -<br />
a. a straight flight in accordance with S3.2 to S3.11;<br />
b. a flight consisting partly of straight and partly of tapered treads in accordance with S3.2 to S3.8,<br />
and S3.10 to S3.14;<br />
c. a flight consisting wholly of tapered treads in accordance with S3.6 to S3.8, and S3.15;<br />
d. an industrial stair or fixed ladder in accordance with S3.26;<br />
e. a stair or fixed ladder in an agricultural building in accordance with S3.27;<br />
f. a stair forming part of a sloping gangway in a building of purpose group 5 in accordance with<br />
S3.28.<br />
Amdt: December 1999<br />
10S
RULES OF MEASUREMENT<br />
S3.2 The rise and going must be measured in accordance with the diagram to this standard -<br />
Diagram to S3.2: Stair measurement<br />
open rise<br />
treads should<br />
overlap at<br />
least 16mm<br />
going<br />
open rise<br />
riser<br />
going dimension<br />
to be measured<br />
from nosing to nosing<br />
equal equal<br />
nosing<br />
going<br />
top surface of tread<br />
top surface of tread<br />
Note:<br />
1. The number of tapered treads shown is indicative only.<br />
RISE, GOING AND PITCH OF FLIGHTS IN STAIRS<br />
rise<br />
STAIR WIDTH LESS<br />
THAN 1 METRE<br />
50mm minimum tread<br />
width at narrow end<br />
measure going at centre of tread.<br />
measure from curved stair line,even when<br />
tread is in rectangular enclosure<br />
S3.3 The maximum rise, minimum going and pitch of flights in stairs must be in accordance with the table to<br />
this standard -<br />
Table to S3.3: Rise, going and pitch of flights in stairs<br />
Description of stair Maximum Minimum Maximum pitch<br />
rise (mm) going (mm)<br />
[Note 1]<br />
1. Private stair 220 225 42º [Note 2]<br />
2. Any other stair 170 250 34º<br />
Note:<br />
1. In the case of tapered treads, subject to S3.12 to S3.14.<br />
2. The combination of maximum rise and minimum going will result in a pitch steeper than this.<br />
11S<br />
going (not more<br />
than maximum for<br />
stair category)<br />
width<br />
270mm 270mm<br />
going (at least<br />
minimum for stair<br />
catagory)<br />
landing length<br />
measured on<br />
centre line<br />
S3.2, S3.3<br />
STAIR WIDTH<br />
1 METRE<br />
OR MORE<br />
Amdt: September 2001<br />
S
S<br />
S3.4 – S3.10<br />
S3.4 The width of a stair, measured between handrails and clear of obstructions, must be at least 1 metre,<br />
except -<br />
a. the width of a private stair may reduce to at least -<br />
Amdt: December 1999<br />
i. 900mm where it is within the accessible storey, or<br />
ii. 600mm where it serves only sanitary accommodation and/or one room, other than a living<br />
room or kitchen, or<br />
iii. 800mm elsewhere; and<br />
b. stringers and newels may each project not more than 30mm into the width; and<br />
c. a stair lift projecting into the width may be fitted to a stair within a dwelling.<br />
Note::<br />
There are additional stair width requirements for escape stairs in Part E.<br />
S3.5 The aggregate of the going and twice the rise must be at least 550mm and not more than 700mm.<br />
S3.6 A flight must have uniform rises, each at least 75mm.<br />
S3.7 The depth of a tread must not be less than the going.<br />
S3.8 In a flight with open rises the treads must overlap by at least 16mm. Any opening between adjacent<br />
treads in a flight in a building of purpose group 1 or 5 or purpose sub-group 2A must be small enough<br />
to prevent the passage of a 100mm sphere.<br />
S3.9 In a straight flight, or in that part of a flight which is straight, the going measured along the centre line<br />
of the flight must be uniform.<br />
LENGTH OF FLIGHTS<br />
S3.10 A flight must have -<br />
a. not more than 16 rises; and<br />
b. at least 3 rises,<br />
except -<br />
there may be less than 3 rises -<br />
i. between an external door of a building and the ground, balcony, conservatory, porch or<br />
private garage; or<br />
ii. in a stepped ramp; or<br />
iii. wholly within an apartment within a dwelling; or<br />
iv. wholly within sanitary accommodation within a dwelling; or<br />
v. between a landing and an adjoining level where the route of travel from the adjoining level<br />
to the next flight changes direction through 90 degrees.<br />
12S
RISERS AND NOSINGS<br />
S3.11*A stair serving a storey to which access for disabled people is required by S2.6 must have -<br />
a. risers profiled to minimise tripping; and<br />
b. nosings distinguishable through contrasting colour or tone.<br />
Note:<br />
This standard does not apply to a private stair in a dwelling.<br />
FLIGHTS CONSISTING PARTLY OF STRAIGHT AND PARTLY OF TAPERED TREADS<br />
S3.12*In that part of a flight consisting of tapered treads, the going of the tapered treads must be uniform and<br />
must not be less than the going of the straight treads. At the inner end of the tread the going must be at<br />
least 50mm.<br />
S3.13 In a flight less than 1 metre wide the going must be measured at the centre line of the flight as in S3.2.<br />
S3.14 In a flight 1 metre wide or more the going must be measured at the two points 270mm from each end of<br />
the tread as in S3.2 and the minimum going must be at least the going of the straight treads.<br />
FLIGHTS CONSISTING WHOLLY OF TAPERED TREADS<br />
S3.15*A flight consisting wholly of tapered treads must be constructed so as to give safe passage. The<br />
requirements in S3.18 to S3.25 for landings, so far as they apply to intermediate landings between<br />
floors, and for handrails, and for headroom, do not apply to such stairs.<br />
PEDESTRIAN RAMPS<br />
S3.16 The maximum gradient and maximum length of a flight of a ramp for use by pedestrians must be in<br />
accordance with the table to this standard -<br />
Table to S3.16: Gradient and length of a flight in a ramp<br />
Gradient of flight Maximum length of flight<br />
not more than 1 in 20 No limit<br />
not more than 1 in 15 10m<br />
not more than 1 in 12 5m<br />
more than 1 in 12 not permitted<br />
S3.17 A ramp must have -<br />
a. a width at least the minimum required for the equivalent type of stair in S3.4; and<br />
b. a raised kerb at least 100mm high on any exposed side of a flight or landing,<br />
except -<br />
a ramp serving a single dwelling.<br />
13S<br />
S3.11 – S3.17<br />
Amdt: December 1999<br />
S
S<br />
S3.18 – S3.22<br />
LANDINGS<br />
S3.18 A landing, level except for any necessary slope for drainage, must be provided at the top and bottom of<br />
every flight of a stair or ramp,<br />
except -<br />
a. a landing may be common to two or more flights; and<br />
b. a landing is not required to a flight between the external door of -<br />
Amdt: September 2001<br />
i. a building and the ground, balcony, conservatory, porch or private garage, where the door<br />
slides or opens in a direction away from the flight and the aggregate rise is not more than<br />
600mm; or<br />
ii. a dwelling or private garage ancillary to a dwelling and the ground, balcony, conservatory,<br />
or porch, other than a door required to be accessible for disabled people under Part Q,<br />
where the change in level is not more than 170mm.<br />
S3.19 The unobstructed length of a landing, measured along its centre line and clear of any door swing, must<br />
be at least 1.2 metres,<br />
except -<br />
HANDRAILS<br />
a. in a dwelling, the length of a landing may reduce to at least 900 mm; and<br />
b. a door may open onto a landing between flights such that at any angle of swing it does not diminish<br />
the effective width of the landing to less than the width of the stair or ramp; and<br />
c. a door may open onto the bottom landing of a flight such that at any angle of swing a clear length<br />
of at least 400 mm is left across the full width of the landing.<br />
S3.20 A stair or ramp for a change in level of more than 600mm, or a ramp longer than 2 metres, must have a<br />
handrail on both sides of every flight,<br />
except -<br />
a. no handrail is required on a ramp serving a single dwelling where the change of level is no more<br />
than 600mm; and<br />
b. a private stair in a dwelling connecting two or more storeys may have a handrail on only one side.<br />
S3.21 A stair or ramp more than 1.8 metres wide must be divided by a handrail, or handrails, in such a way<br />
that each section is at least 1.1 metres and not more than 1.8 metres wide,<br />
except -<br />
a. a stair or ramp serving a single dwelling; or<br />
b. a stair between an entrance door to a building and ground level which does not form part of an<br />
escape route.<br />
S3.22 A handrail must be fixed at a height of at least 840mm and not more than 1 metre, measured vertically<br />
above the pitch line of the flight or surface of the landing.<br />
14S
S3.23 A handrail must extend at least 300mm beyond the top and bottom of a flight and have a profile and<br />
projection that allows a firm grip.<br />
except -<br />
where the handrail serves a single dwelling.<br />
S3.24 The ends of a handrail must be wreathed when not forming part of a protective barrier,<br />
except -<br />
HEADROOM<br />
where the handrail serves a single dwelling.<br />
S3.25 A stair, ramp or landing must have a clear headroom of at least 2 metres extending over the whole of the<br />
width, measured vertically from the pitch line of the flight or the surface of the landing, as shown in the<br />
diagram to this standard -<br />
Diagram to S3.25: Measuring headroom<br />
INDUSTRIAL STAIRS AND FIXED LADDERS<br />
S3.26*An industrial stair or fixed ladder serving areas requiring limited access in any building must be constructed<br />
so as to offer safe passage.<br />
STAIRS AND FIXED LADDERS IN AGRICULTURAL BUILDINGS<br />
S3.27*A stair or fixed ladder in an agricultural building must be constructed so as to offer safe passage.<br />
STEPS IN SLOPING GANGWAYS<br />
landing<br />
at least<br />
2 metres<br />
flight<br />
at least<br />
2 metres<br />
pitch line<br />
minimum headroom<br />
landing<br />
at least<br />
2 metres<br />
S3.28 In a building of purpose group 5 where steps form part of sloping gangways serving areas for audiences<br />
or spectators each step must have a rise at least 125mm and not greater than 190mm.<br />
15S<br />
S3.23 – S3.28<br />
Amdt: December 1999<br />
S
S<br />
S4.1 – S4.3<br />
S4 Protective barriers<br />
PEDESTRIAN PROTECTIVE BARRIERS<br />
S4.1 A protective barrier for pedestrians must be provided at the edge of -<br />
a. every floor, stair, ramp, raised floor or other raised accessible area where there is a difference in<br />
level of 600mm or more; and<br />
b. a landing where the route of travel from the adjoining level to the next flight changes direction<br />
through 90 degrees,<br />
except -<br />
i. where the barrier would be incompatible with normal use, such as a loading bay or stage; or<br />
ii. where a wall, partition or fixed glazing at the edge of a drop in level meets the requirement of S4.3.<br />
S4.2 In a building of purpose group 1 or 5 or purpose sub-group 2A openings in a protective barrier must be<br />
small enough to prevent the passage of a 100mm diameter sphere,<br />
except -<br />
the space between a rise and the lowest edge of the protective barrier may be larger if the lowest edge is<br />
not more than 50 mm above, and parallel to, the pitch line of a stair or ramp.<br />
S4.3* A protective barrier must be -<br />
a. secure; and<br />
b. capable of resisting appropriate loads; and<br />
c. of a height at least that given in the table to this standard -<br />
Table to S4.3: Height of pedestrian protective barriers<br />
Location Minimum height (mm)<br />
At the edge of a floor in front of walls, partitions,<br />
fixed glazing and opening windows 800<br />
On a flight within or serving a single dwelling 840<br />
In front of or behind fixed seating 800 [Note 1]<br />
On (a) a stair or ramp; or<br />
(b) a gallery or raised area within a single dwelling 900<br />
Elsewhere 1100 [Note 2]<br />
Notes:<br />
1. The protective barrier may be reduced to 750 mm where it has an overall width at the top of at<br />
least 250 mm.<br />
2. Where a handrail forming the top of a protective barrier to a flight meets a protective barrier to a<br />
landing, the height of the latter may be reduced for a distance not more than 300 mm to permit a<br />
smooth junction.<br />
Amdt: December 1999<br />
16S
VEHICLE PROTECTIVE BARRIERS<br />
S4.4 A barrier to provide protection from vehicles must be provided at the edge of a drop in level in every<br />
floor, roof or ramp which is accessible to vehicles, and forms part of a building.<br />
S4.5* A vehicle protective barrier provided in accordance with S4.4 must be capable of resisting appropriate<br />
loads and be of a height at least that given in the table to this standard -<br />
Table to S4.5: Height of vehicle protective barriers<br />
Location Minimum height (mm)<br />
Floor or roof edge 400<br />
Ramp edge 600<br />
17S<br />
S4.4, S4.5<br />
Amdt: December 1999<br />
S
S<br />
(S2.3), (S2.5)<br />
Provisions deemed to satisfy the standards<br />
ACCESS TO BUILDINGS<br />
(S2.3) The requirements of S2.3 as regards a firm surface suitable for disabled people will be met by -<br />
a. 50mm concrete slabs bedded on granular material; or<br />
b. 30mm tarmacadam to BS4987: Parts 1 and 2: 1993 laid on 100 mm of consolidated hardcore<br />
bottoming; or<br />
c. 50mm clay or calcium silicate pavers to BS6677: Part 1: 1986, laid in accordance with BS6677:<br />
Part 2: 1986; or<br />
d. 60mm concrete paving blocks to BS 6717: Part 1: 1993, laid in accordance with BS6677: Part<br />
2: 1986.<br />
PRINCIPAL ENTRANCE<br />
(S2.5) The requirements of S2.5 will be met by a lobby complying with any of the examples in the diagram to<br />
this specification -<br />
Diagram to (S2.5): Entrance lobbies<br />
300mm<br />
1.8m<br />
2m<br />
1.5m<br />
Note:<br />
Doors to lobbies must have a clear opening width of at least 800 mm.<br />
Amdt: December 1999<br />
1.5m<br />
2m<br />
18S<br />
300mm<br />
1.8m<br />
1.8m<br />
2.3m<br />
1.5m<br />
2.4m<br />
300mm 300mm<br />
300mm
MOVEMENT WITHIN BUILDINGS<br />
(S2.6) The requirements of S2.6 for provision of access to storeys above or below the principal entrance<br />
storey will be met by -<br />
a. a passenger lift having -<br />
i. a clear landing at least 1.5 x 1.5 metres in front of the lift entrance door or doors, and<br />
ii. lift door or doors with a clear opening width of at least 800mm, and<br />
iii a lift car at least 1.1 x 1.4 metres, and<br />
iv within the lift car a horizontal rail on 3 sides, or on 2 sides if the lift car has 2 doors,<br />
900mm above the floor; and<br />
v. controls outside sited between 900mm and 1.2 metres above the landing, and within the<br />
lift car on a side wall between 900mm and 1.2 metres above the car floor and at least<br />
400mm from the corner, and<br />
vi. tactile call buttons, and visual and tactile indication of the storey level, on each storey<br />
served, and<br />
vii. within the lift car, tactile storey selector buttons and, in a lift serving more than 2 storeys,<br />
visual and voice indicators of the storey reached, and<br />
viii. a signalling system which gives 5 seconds notification that the lift is answering a landing<br />
call, and a dwell time of 5 seconds before the lift doors close after they are fully open,<br />
except -<br />
the dwell time may be reduced to 3 seconds where the door closing system is over-ridden<br />
by a door re-activating device which relies on photo-eye or infra-red methods, but not a<br />
door edge pressure system; or<br />
b. in the case of exceptions c. and d. of S2.6, by a stair.<br />
(S2.7) The requirements of S2.7b. will be met by a wheelchair platform stairlift in accordance with BS5776:<br />
1996, or a powered lifting platform in accordance with BS6440: 1983.<br />
RISERS AND NOSINGS<br />
(S3.11) The requirements of S3.11b. will be met by rises profiled in accordance with the diagram to this specification<br />
-<br />
Diagram to (S3.11): Step profile examples<br />
15-25mm 15-25mm<br />
19S<br />
60˚min<br />
(S2.6) – (S3.11)<br />
Amdt: September 2001<br />
S
S<br />
(S3.12) – (S4.5)<br />
FLIGHTS CONSISTING PARTLY OF STRAIGHT AND PARTLY OF TAPERED TREADS<br />
(S3.12) The requirements of S3.12 as regards tapered treads will be met where the stair is constructed in<br />
accordance with BS585: Part 1: 1989, Appendices B1 and B3, irrespective of the material of construction<br />
or whether it contains open rises.<br />
FLIGHTS CONSISTING WHOLLY OF TAPERED TREADS<br />
(S3.15) The requirements of S3.15 will be met where the flight consists wholly of tapered treads forming a<br />
helix or spiral and is constructed in accordance with BS5395: Part 2: 1984. Where such a flight forms<br />
an escape stair the category of the stair must be in accordance with the table to this specification -<br />
Table to (S3.15): Helical or spiral flights forming an escape stair<br />
Appropriate capacity not exceeding - [Note 1] Stair category [Note 2]<br />
10 B<br />
25 C [Note 3]<br />
50 D [Note 3]<br />
100 E [Note 3]<br />
Notes:<br />
1. Appropriate capacity to be calculated in accordance with Part E.<br />
2. Refer to Table 2 of BS 5395: Part 2: 1984.<br />
3. Handrails must be provided on both sides.<br />
INDUSTRIAL STAIRS AND FIXED LADDERS<br />
(S3.26) The requirements of S3.26 will be met by the use of industrial stairs or fixed ladders in the circumstances<br />
described in, and constructed in accordance with, BS5395: Part 3: 1985; or BS4211: 1994; or<br />
by a Type A Spiral or Helical Stair constructed in accordance with BS5395: Part 2: 1984.<br />
STAIRS AND FIXED LADDERS IN AGRICULTURAL BUILDINGS<br />
(S3.27) The requirements of S3.27 will be met by the use of stairs or fixed ladders in the circumstances<br />
described in, and constructed in accordance with, BS5502: Part 80: 1990.<br />
PEDESTRIAN PROTECTIVE BARRIERS<br />
(S4.3) The requirements of S4.3 will be met where the loads are calculated in accordance with BS6399: Part<br />
1: 1996.<br />
VEHICLE PROTECTIVE BARRIERS<br />
(S4.5) The requirements of S4.5 will be met where the loads are calculated in accordance with BS6399: Part<br />
1: 1996.<br />
Amdt: December 1999<br />
20S
APPENDIX: LIST OF PUBLICATIONS REFERRED TO<br />
IN THE TECHNICAL STANDARDS
APPENDIX<br />
List of publications referred to in the <strong>Technical</strong> <strong>Standards</strong><br />
BRITISH STANDARDS<br />
Number Title Amendment Context<br />
BS 41 : 1973 (1981) Specification for cast iron spigot and (F4.12)<br />
socket flue or smoke pipes and fittings<br />
BS 449 Specification for the use of<br />
structural steel in building -<br />
: Part 2: 1969 - Metric units AMD 416 (C2.1)<br />
AMD 523<br />
AMD 661<br />
AMD 1135<br />
AMD 1787<br />
AMD 4576<br />
AMD 5698<br />
AMD 6255<br />
AMD 8859<br />
BS 476 Fire tests on building materials<br />
and structures -<br />
: Part 3: 1958 - External fire exposure roof (D9.1)<br />
tests<br />
: Part 4: 1970 (1984) - Non-combustibility test for AMD 2483 (D1.3)<br />
materials AMD 4390<br />
: Part 6: 1981 - Method of test for fire (D1.3)<br />
propagation for products<br />
: Part 6: 1989 - Method of test for fire (D1.3)<br />
propagation for products<br />
: Part 7: 1987 (1993) - Method for classification of AMD 6249 (D1.3)<br />
the surface spread of flame of AMD 7030<br />
products AMD 7612<br />
: Part 11: 1982 (1988)- Method for assessing the heat (D1.3)<br />
emission from building materials<br />
: Part 20: 1987 - Method for determination of the AMD 6487 (D1.3)<br />
` fire resistance of elements of<br />
construction (general principles)<br />
: Part 21: 1987 - Methods for determination of (D1.3)<br />
the fire resistance of loadbearing<br />
elements of construction<br />
3<br />
Amdt: September 2001
Amdt: September 2001<br />
: Part 22: 1987 - Methods for determination of (D1.3)<br />
the fire resistance of non-loadbearing<br />
elements of construction<br />
: Part 23: 1987 - Methods for determination of (D1.3)<br />
the contribution of components to<br />
the fire resistance of a structure<br />
: Part 24: 1987 - Method for determination of the (D1.3)<br />
fire resistance of ventilation ducts<br />
: Part 31: Section -Methods for measuring smoke AMD 8366 (D1.3)<br />
31.1: 1983 penetration through doorsets<br />
and shutter assemblies - method<br />
of measurement under ambient<br />
temperature conditions<br />
BS 585 Wood stairs -<br />
: Part 1: 1989 - Specification for stairs with AMD 6510 (S3.12)<br />
closed risers for domestic use,<br />
including straight and winder<br />
flights and quarter or half landings<br />
BS 715 : 1993 Specification for metal flue pipes, AMD 8413 (F6.11)<br />
fittings, terminals and accessories<br />
for gas-fired appliances with a<br />
rated input not exceeding 60 kW<br />
BS 750 : 1984 Specification for underground AMD 7658 (E10.2)<br />
fire hydrants and surface box<br />
frames and covers<br />
BS 799 : Part 5: 1987 Specification for oil storage tanks (F7.1)<br />
BS 1289 Flue blocks and masonry terminals<br />
for gas appliances<br />
: Part 1: 1986 - Specification for precast AMD 9853 (F3.5)<br />
concrete flue blocks and terminals<br />
: Part 2: 1989 (1996) - Specification for clay flue (F3.5)<br />
blocks and terminals<br />
BS 1377 Methods of test for soils for<br />
civil engineering purposes<br />
:Part 2: 1990 Classification tests (M3.5)<br />
BS 1449 Steel plate, sheet and strip -<br />
: Part 1: 1991 - Specification for carbon and (F4.12)<br />
carbon-manganese plate,<br />
sheet and strip<br />
4
BS 1566 Copper indirect cylinders for<br />
domestic purposes -<br />
: Part 2: 1984 (1990) - Specification for single AMD 5791 (J6.2), (J11.5)<br />
feed indirect cylinders AMD 6601<br />
BS 2782 Methods of testing plastics -<br />
: Part 1: Thermal Properties<br />
Methods - Determination of the Vicat (D9.1)<br />
120A to 120E: softening temperature of<br />
1990 thermoplastics<br />
Method 508A: - Methods of testing plastics (D7.2), (D9.1)<br />
1970 Rate of burning (laboratory method)<br />
BS 3198 : 1981 Specification for copper hot water storage AMD 4372 (J6.2), (J11.5)<br />
combination units for domestic purposes AMD 6599<br />
BS 4211 : 1994 Specification for ladders for (S3.26)<br />
permanent access to chimneys,<br />
other high structures, silos and bins<br />
BS 4514 : 1983 (1998) Specification for unplasticised AMD 4517 (D3.14),(D4.7)<br />
PVC soil and ventilating pipes, AMD 5584 (D5.8), (D6.7)<br />
fittings and accessories<br />
BS 4543 Factory-made insulated chimneys -<br />
: Part 1: 1990 (1996)-Methods of test AMD 8379 (F3.7), (F3.9)<br />
: Part 2: 1990 (1996)-Specification for chimneys AMD8380 (F3.6), (F4.11)<br />
with stainless steel flue linings for<br />
use with solid fuel fixed appliances<br />
: Part 3: 1990 (1996)-Specification for chimneys AMD 8381 (F3.6)<br />
with stainless steel fluelining<br />
for use with oil fired appliances<br />
BS 4987 Coated macadam for roads and<br />
other paved areas -<br />
: Part 1: 1993 - Specification for constituent AMD 8122 (Q2.4)<br />
materials and for mixtures AMD 8400 (S2.3)<br />
: Part 2: 1993 - Specification for transport, AMD 8158 (Q2.4)<br />
laying and compaction AMD 8361 (S2.3)<br />
BS 5041 Fire hydrant systems equipment -<br />
: Part 1: 1987 - Specification for landing AMD 5912 (E10.7)<br />
valves for wet risers<br />
: Part 2: 1987 - Specification for landing AMD 5776 (E10.8)<br />
valves for dry risers<br />
5<br />
Amdt: September 2001
Amdt: September 2001<br />
: Part 3: 1975 (1987) - Specification for inlet AMD 5504 (E10.8)<br />
breechings for dry riser inlets<br />
: Part 4: 1975 (1987) - Specification for boxes for AMD 5503 (E10.8)<br />
landing valves for dry risers<br />
: Part 5: 1974 (1987) - Specification for boxes for AMD 5505 (E10.9)<br />
foam inlets and dry riser inlets<br />
BS 5250 : 1989 (1995) Code of practice for control of G Introduction<br />
condensation in buildings (G4.1)<br />
J Introduction<br />
BS 5262 : 1991 Code of practice for external renderings (G3.1)<br />
BS 5266 Emergency lighting -<br />
: Part 1: 1999 - Code of practice for the emergency (E9.2)<br />
lighting of premises other than<br />
cinemas and certain other specified<br />
premises used for entertainment<br />
BS 5268 Structural use of timber -<br />
: Part 2: 1996 - Code of practice for permissible AMD 9451 (C2.1)<br />
stress design, materials and<br />
workmanship<br />
: Part 3: 1998 - Code of practice for trussed (C2.1)<br />
rafter roofs<br />
: Part 4: Sections - Recommendations for calculating (D1.3)<br />
4.1 and 4.2: 1990 fire resistance of timber stud walls<br />
and joisted floor constructions<br />
: Part 6: Section - Dwellings not exceeding four (C2.1)<br />
6.1: 1996 storeys<br />
BS 5306 Fire extinguishing installations and<br />
equipment on premises -<br />
: Part 0: 1986 - Guide for the selection of installed AMD 5695 (D2.1), (D5.1)<br />
systems and other fire equipment AMD 6653 (D5.3), (D5.4)<br />
(D8.1)<br />
: Part 1: 1976 - Hydrant systems, hose reels AMD 4649 (E10.7)<br />
(1988) and foam inlets AMD 5756 (E10.8)<br />
: Part 2: 1990 - Specification for sprinkler AMD 9809 (D2.1), (D5.1)<br />
systems AMD 9985 (D5.3), (D5.4)<br />
(D8.1)(E10.15)<br />
: Part 4: 1986 - Specification for carbon (D2.1), (D5.1)<br />
dioxide systems (D5.3), (D5.4)<br />
(D8.1)<br />
6
: Part 6 Foam systems -<br />
: Section - Specification for low AMD 9808 (D2.1), (D5.1)<br />
6.1: 1988 expansion foam systems AMD 9945 (D5.3), (D5.4)<br />
(D8.1)<br />
: Section - Specification for medium and (D2.1), (D5.1)<br />
6.2: 1989 high expansion foam systems (D5.3), (D5.4)<br />
(D8.1)<br />
: Part 7: 1988 - Specification for powder (D2.1), (D5.1)<br />
systems (D5.3), (D5.4)<br />
(D8.1)<br />
BS 5378 Safety signs and colours -<br />
: Part 3: 1982- Specification for additional signs (P2.8)<br />
to those given in BS 5378: Part 1<br />
BS 5390 : 1976 (1984) Code of practice for stone masonry AMD 4272 (G3.1)<br />
BS 5395 Stairs, ladders and walkways -<br />
: Part 2: 1984 - Code of practice for the AMD 6076 (S3.15), (S3.26)<br />
design of helical and spiral stairs<br />
: Part 3: 1985 - Code of practice for the (E5.11)<br />
design of industrial type stairs, (P2.8),<br />
permanent ladders and walkways (S3.26)<br />
BS 5410 Code of practice for oil firing -<br />
: Part 1: 1997 - Installations up to 45 kW (F3.1), (F3.8)<br />
output capacity for space heating (F3.11), (F5.3)<br />
and hot water supply purposes (F5.4), (F5.7)<br />
(F7.1), (F7.3)<br />
: Part 2: 1978 - Installations of 44 kW and above AMD 3638 (F3.1), (F7.1)<br />
output capacity for space heating, (F7.2), (F7.3)<br />
hot water and steam supply purposes<br />
BS 5422: 1990 Method for specifying thermal (J6.3), (J6.4)<br />
insulating materials on pipes, (J11.6)<br />
ductwork and equipment (in the (J11.7)<br />
temperature range -40ºC to +700ºC)<br />
BS 5438: 1989 (1995) Methods of test for flammability of AMD 6509 (D7.2)<br />
textile fabrics when subjected to a AMD 8308<br />
small igniting flame applied to the<br />
face or bottom edge of vertically<br />
oriented specimens<br />
BS 5440 Installation of flues and<br />
ventilation for gas appliances of<br />
rated input not exceeding 60 kW<br />
(1st, 2nd and 3rd family gases) -<br />
7<br />
Amdt: September 2001
Amdt: September 2001<br />
: Part 1: 1990 - Specification for installation AMD 8819 (F3.8), (F3.11)<br />
of flues (F6.5), (F6.6)<br />
(F6.7), (F6.11)<br />
: Part 2: 1989 - Specification for installation AMD 8128 (F6.3), (F6.4)<br />
of ventilation for gas appliances<br />
BS 5446 Components of automatic fire alarm<br />
systems for residential premises -<br />
: Part 1: 1990 - Specification for AMD 6863 (E11.1)<br />
self-contained smoke alarms AMD 7648<br />
and point-type smoke detectors AMD 9628<br />
BS 5502 Buildings and structures for agriculture -<br />
: Part 22: 1993 - Code of practice for design, (C2.1)<br />
construction and loading<br />
: Part 50: 1993 - Code of practice for design, (R3.2)<br />
construction and use of storage tanks<br />
and reception pits for livestock slurry<br />
: Part 80: 1990 - Code of practice for design (S3.27)<br />
and construction of workshops,<br />
maintenance and inspection facilities<br />
BS 5534 Code of practice for slating and tiling -<br />
: Part 1: 1997 - Design (G3.1)<br />
BS 5588 Fire precautions in the design,<br />
construction and use of buildings -<br />
: Part 4: 1998 - Code of practice for smoke AMD 10019 (D1.3),<br />
control in protected escape (E5.23)<br />
routes using pressurization<br />
: Part 5: 1991 - Code of practice for AMD 7196 (E10.4),<br />
fire-fighting stairs and lifts (E10.9)<br />
(E10.11)<br />
: Part 6: 1991 - Code of practice for AMD 10212 (D11.13)<br />
places of assembly (D11.14)<br />
(D11.15)<br />
: Part 9: 1999 - Code of practice for ventilation (D3.14),(D4.7)<br />
and air conditioning ductwork (E5.8), (D6.7)<br />
BS 5617 : 1985 (1996) Specification for urea-formaldehyde (G3.1)<br />
(UF) foam systems suitable for thermal<br />
insulation of cavity walls with masonry<br />
or concrete inner and outer leaves<br />
8
BS 5618 : 1985 (1996) Code of practice for thermal insulation AMD 6262 (G3.1)<br />
of cavity walls (with masonry or AMD 7114<br />
concrete inner and outer leaves)<br />
by filling with urea-formaldehyde<br />
(UF) foam systems<br />
BS 5628 Code of practice for use of masonry -<br />
: Part 1: 1992 - Structural use of AMD 7745 (C2.1), (C3.1)<br />
unreinforced masonry<br />
: Part 2: 1995 - Structural use of reinforced (C2.1), (C3.1)<br />
and prestressed masonry<br />
: Part 3: 1985 - Materials and components, AMD 4974 (C2.1)<br />
design and workmanship (G3.1)<br />
(H2.1-H2.3)<br />
BS 5720 : 1979 Code of practice for mechanical ventilation (K2.1), (K4.9)<br />
and air conditioning in buildings<br />
BS 5776 : 1996 Specification for powered stairlifts (S2.7)<br />
BS 5839 Fire detection and alarm systems<br />
for buildings -<br />
: Part 1: 1988 - Code of practice for system AMD 6317 (D3.14),(D4.7)<br />
design, installation and AMD 6874 (D5.8), (D6.7)<br />
servicing AMD 9257 (D11.1-D11.5)<br />
(E2.14)<br />
(E11.1-E11.3)<br />
: Part 3: 1988 - Specification for automatic AMD 10207 (D3.14),(D4.7)<br />
release mechanisms for certain (D5.8), (D6.7)<br />
fire protection equipment (D11.1-D11.5)<br />
: Part 6: 1995 - Code of practice for the design AMD 9135 (E11.1)<br />
and installation of fire detection<br />
and alarm systems in dwellings<br />
: Part 8: 1998 - Code of practice for the design, (E11.3)<br />
installation and servicing of<br />
voice alarm systems<br />
BS 5867 Specification for fabrics for curtains<br />
and drapes -<br />
: Part 2: 1980 (1993) - Flammability requirements AMD 4319 (D7.2)<br />
BS 5871 Specification for the installation of gas<br />
fires, convector heaters, fire/back boilers<br />
and decorative fuel effect gas appliances<br />
: Part 1: 1991 - Gas fires, convector heaters (F6.16)<br />
and fire/back boilers<br />
(1st, 2nd and 3rd family gases)<br />
9<br />
Amdt: September 2001
Amdt: September 2001<br />
: Part 2: 1991 - Inset live fuel effect gas fires (F6.3), (F6.7)<br />
of heat input not exceeding 15kW (F6.16)<br />
(2nd and 3rd family gases)<br />
: Part 3: 1991 - Decorative fuel effect gas AMD 7033 (F6.3), (F6.6)<br />
appliances of heat input not (F6.7), (F6.16)<br />
exceeding 15kW<br />
(2nd and 3rd family gases)<br />
BS 5925 : 1991 (1995) Code of practice for ventilation principles AMD 8930 (K2.1)<br />
and designing for natural ventilation<br />
BS 5930 : 1981 Code of practice for site investigations G Appendix<br />
BS 5950 Structural use of steelwork in building -<br />
: Part 1: 1990 - Code of practice for design AMD 6972 (C2.1),<br />
in simple and continuous (C3.1)<br />
construction: hot rolled sections<br />
: Part 2: 1992 - Specification for materials, AMD 7766 (C2.1)<br />
fabrication and erection: hot<br />
rolled sections<br />
: Part 3: Section - Design in composite construction (C2.1)<br />
3.1: 1990 - Code of practice for design of<br />
simple and continuous composite<br />
beams<br />
: Part 4: 1994 - Code of practice for design (C2.1)<br />
of composite slabs with profiled<br />
steel sheeting<br />
: Part 5: 1987 - Code of practice for design AMD 5957 (C2.1)<br />
of cold formed sections<br />
: Part 6: 1995 - Code of practice for design (C2.1)<br />
of light gauge profiled steel sheeting<br />
: Part 7: 1992 - Specification for materials and (C2.1)<br />
workmanship: cold-formed sections<br />
: Part 8: 1990 - Code of practice for fire AMD 8858 (C2.1),<br />
resistant design (D1.3)<br />
BS 5979 : 1993 Code of practice for remote centres AMD 9235 (E11.2)<br />
for alarm systems<br />
BS 6229 : 1982 Code of practice for flat roofs with (G3.1)<br />
continuously supported coverings<br />
BS 6262 : 1982 Code of practice for glazing for AMD 4063 (P2.2)<br />
buildings AMD 4582<br />
AMD 8279<br />
10
BS 6262 Glazing for buildings -<br />
: Part 4: 1994 - Safety related to human impact (P2.2)<br />
BS 6283 Safety devices for use in hot<br />
water systems -<br />
: Part 2: 1991 - Specification for (P3.1)<br />
temperature relief valves for<br />
pressures from 1 bar to 10 bar<br />
: Part 3: 1991 - Specification for combined (P3.1)<br />
temperature and pressure<br />
relief valves for pressures from<br />
1 bar to 10 bar<br />
BS 6297 : 1983 Code of practice for design and AMD 6150 (M3.1)<br />
installation of small sewage<br />
treatment works and cesspools<br />
BS 6387 : 1994 Specification for performance (D3.6), (D3.7)<br />
requirements for cables required<br />
to maintain circuit integrity<br />
under fire conditions<br />
BS 6399 Loading for buildings -<br />
: Part 1: 1996 - Code of practice for dead (C2.1), (S4.3)<br />
and imposed loads (S4.5)<br />
: Part 2: 1997 - Code of practice for wind loads (C2.1)<br />
: Part 3: 1988 - Code of practice for imposed AMD 6033 (C2.1)<br />
roof loads AMD 9187<br />
AMD 9452<br />
BS 6440 : 1983 Code of practice for powered lifting (S2.7)<br />
platforms for use by disabled persons<br />
BS 6461 Installation of chimneys and flues<br />
for domestic appliances burning<br />
solid fuel (including wood and peat) -<br />
: Part 1: 1984 - Code of practice for masonry AMD 5649 (F3.5), (F3.8)<br />
chimneys and flue pipes (F4.11)<br />
BS 6465 Sanitary installations -<br />
: Part 1: 1994 - Code of practice for scale of (M4.5)<br />
provision, selection and<br />
installation of sanitary appliances<br />
11<br />
Amdt: September 2001
BS 6676 Thermal insulation of cavity walls using<br />
man-made mineral fibre batts (slabs) -<br />
Amdt: September 2001<br />
: Part 1: 1986 (1994) - Specification for man-made (G3.1)<br />
mineral fibre batts (slabs)<br />
: Part 2: 1986 (1994) - Code of practice for installation (G3.1)<br />
of batts (slabs) filling the cavity<br />
BS 6677 Clay and calcium silicate pavers<br />
for flexible pavements -<br />
: Part 1: 1986 (1997) - Specification for pavers (Q2.4), (S2.3)<br />
: Part 2: 1986 (1997) - Code of practice for design (Q2.4), (S2.3)<br />
of lightly trafficked pavements<br />
BS 6700 : 1997 Specification for design, installation, (P3.1)<br />
testing and maintenance of services<br />
supplying water for domestic use<br />
within buildings and their curtilages<br />
BS 6717 Precast concrete paving blocks -<br />
: Part 1: 1993 - Specification for paving blocks (Q2.4), (S2.3)<br />
BS 6915 : 1988 Specification for design and (G3.1)<br />
construction of fully supported<br />
lead sheet roof and wall coverings<br />
BS 6999 : 1989 (1996) Specification for vitreous-enamelled AMD 8949 (F4.12)<br />
low-carbon-steel flue pipes, other<br />
components and accessories for<br />
solid-fuel-burning appliances with<br />
a rated output of 45kW<br />
BS 7036 : 1996 Code of practice for safety at (E2.4)<br />
powered doors for pedestrian use (E5.11)<br />
BS 7206 :1990 Specification for unvented hot AMD 9343 (P3.1)<br />
water storage units and packages<br />
BS 7346 Components for smoke and heat<br />
control systems -<br />
: Part 1: 1990 - Specification for natural smoke AMD 7193 (D3.6), (D3.7)<br />
and heat exhaust ventilators<br />
: Part 2: 1990 - Specification for powered smoke AMD 7028 (E10.15)<br />
and heat exhaust ventilators<br />
BS 7435 Fibre cement flue pipes, fittings<br />
and terminals<br />
: Part 1: 1991 - Specification for light quality fibre (F6.11)<br />
cement flue pipes, fittings and terminals<br />
12
BS 7501 : 1989 General criteria for the operation (B2.2)<br />
of testing laboratories<br />
BS 7502 : 1989 General criteria for the assessment (B2.2)<br />
of testing laboratories<br />
BS 7543 : 1992 (1998) Guide to durability of buildings and B Introduction<br />
building elements, products and<br />
components<br />
BS 7566 Installation of factory-made chimneys<br />
to BS4543 for domestic appliances<br />
: Part 1: 1992 - Method of specifying installation (F3.7), (F4.11)<br />
design information<br />
: Part 2: 1992 - Specification for installation design (F3.7), (F4.11)<br />
: Part 3: 1992 - Specification for site installation (F3.7), (F4.11)<br />
: Part 4: 1992 - Recommendations for installation (F3.7), (F3.8)<br />
design and installation (F4.11)<br />
BS 7671 : 1992 Requirements for electrical installations, AMD 8536 N Introduction,<br />
IEE Wiring Regulations, Sixteenth edition AMD 9781 (N2.1)<br />
BS 8000 Workmanship on building sites (B2.1)<br />
Parts 1 to 16<br />
BS 8004 : 1986 Code of practice for foundations (C2.1)<br />
BS 8103 Structural design of low rise buildings<br />
: Part 1: 1995 - Code of practice for stability, AMD 8980 (C2.1)<br />
site investigation, foundations and<br />
ground floor slabs for housing<br />
: Part 2: 1996 - Code of practice for masonry (C2.1)<br />
walls for housing<br />
: Part 3: 1996 - Code of practice for timber (C2.1)<br />
floors and roofs for housing<br />
: Part 4: 1995 - Code of practice for suspended (C2.1)<br />
concrete floors for housing<br />
BS 8104 : 1992 Code of practice for assessing AMD 8358 (G3.1)<br />
exposure of walls to wind-driven rain<br />
13<br />
Amdt: September 2001
BS 8110 Structural use of concrete -<br />
Amdt: September 2001<br />
: Part 1: 1997 - Code of practice for design (C2.1), (C3.1)<br />
and construction<br />
: Part 2: 1985 - Code of practice for special AMD 5914 (C2.1), (C3.1)<br />
: circumstances (D1.3)<br />
: Part 3: 1985 - Design charts for singly reinforced AMD 5918 (C2.1)<br />
beams, doubly reinforced beams<br />
and rectangular columns<br />
BS 8118 Structural use of aluminium -<br />
: Part 1: 1991 - Code of practice for design (C2.1)<br />
: Part 2: 1991 - Specification for materials, (C2.1)<br />
workmanship and protection<br />
BS 8200 : 1985 Code of practice for design of (G3.1)<br />
non-loadbearing external vertical<br />
enclosures of buildings<br />
BS 8208 Guide to assessment of suitability<br />
of external cavity walls for filling<br />
with thermal insulants -<br />
: Part 1: 1985 - Existing traditional cavity AMD 4996 (G3.1)<br />
construction<br />
BS 8213 Windows, doors and rooflights -<br />
: Part 1: 1991 - Code of practice for safety in use (P2.3)<br />
and during cleaning of windows<br />
and doors (including guidance on<br />
cleaning materials and methods)<br />
BS 8214 : 1990 Code of practice for fire door AMD 7438 (D1.3)<br />
(Sections 1 and 2) assemblies with non-metallic leaves<br />
BS 8217 : 1994 Code of practice for built-up felt roofing (G3.1)<br />
BS 8218 : 1998 Code of practice for mastic (G3.1)<br />
asphalt roofing<br />
BS 8297 : 1995 Code of practice for design and (G3.1)<br />
installation of non-loadbearing<br />
precast concrete cladding<br />
BS 8298 : 1994 Code of practice for design and (G3.1)<br />
installation of natural stone<br />
cladding and lining<br />
14
BS 8301 : 1985 Code of practice for building AMD 5904 (G2.2),<br />
drainage AMD 6580<br />
BS 8303 Installation of domestic heating<br />
and cooking appliances burning<br />
solid mineral fuels<br />
: Part 1: 1994 - Specification for the design (F3.1), (F4.8)<br />
of installations (F4.12), (F4.19)<br />
(F4.21)<br />
: Part 2: 1994 - Specification for installing (F3.1)<br />
and commissioning on site<br />
: Part 3: 1994 - Recommendations for design (F3.1), (F4.21)<br />
and on site installation<br />
15<br />
Amdt: September 2001
CODES OF PRACTICE<br />
CP 3 : Chapter V Code of basic data for the design<br />
of buildings - Loading<br />
: Part 2: 1972 - Wind loads AMD 4952 (C2.1)<br />
AMD 5152<br />
AMD 5343<br />
AMD 6028<br />
AMD 7908<br />
CP 102 : 1973 Code of practice for protection of AMD 1511 (G2.2), (G2.3)<br />
buildings against water from the AMD 2196 (G2.5)<br />
ground AMD 2470<br />
CP 143 Code of practice for sheet roof<br />
and wall coverings -<br />
: Part 5: 1964 - Zinc (G3.1)<br />
: Part 10: 1973 - Galvanised corrugated steel. (G3.1)<br />
Metric units<br />
: Part 12: 1970 (1988)- Copper. Metric units AMD 863 (G3.1)<br />
AMD 5193<br />
: Part 15: 1973 (1986)- Aluminium. Metric units AMD 4473 (G3.1)<br />
CP 1007 : 1955 Maintained lighting for cinemas (E9.2)<br />
EUROPEAN STANDARDS<br />
BS EN 115: 1995 Safety rules for the construction (P2.5)<br />
and installation of escalators and<br />
passenger conveyors<br />
BS EN ISO 140 Acoustics. Measurement of sound insulation<br />
in buildings and of building elements<br />
140-4: 1998 Field measurements of airborne sound (H2.1-H2.3)<br />
insulation between rooms<br />
140-7: 1998 Field measurements of impact sound (H2.1-H2.3)<br />
insulation of floors<br />
BS EN 573 Aluminium and aluminium alloys. Chemical<br />
composition and form of wrought products<br />
573-1: 1995 Numerical designation system (F6.9)<br />
BS EN ISO 717 Acoustics. Rating of sound insulation<br />
in buildings and building elements<br />
Amdt: September 2001<br />
717-1: 1997 Airborne sound insulation (H2.1-H2.3)<br />
717-2: 1997 Impact sound insulation (H2.1-H2.3)<br />
16
BS EN 752 Drain and sewer systems outside buildings<br />
752-3: 1997 Planning (M2.1)<br />
(amendment 2)<br />
752-4: 1998 Hydraulic design and environmental considerations (M2.1), (M2.2)<br />
(M2.5), (M2.9)<br />
(M3.6)<br />
BS EN ISO 1182 Reaction to fire tests for building products – (D1.3)<br />
Non-combustibility test<br />
BS EN 1363 Fire resistance tests<br />
1363-1: 1999 General requirements (D1.3)<br />
1363-2: 1999 Alternative and additional procedures (D1.3)<br />
1363-3: 1999 Verification of furnace performance (D1.3)<br />
BS EN 1364 Fire resistance tests for non-loadbearing elements<br />
1364-1: 1999 Walls (D1.3)<br />
1364-2: 1999 Ceilings (D1.3)<br />
BS EN 1365 Fire resistance tests for loadbearing elements<br />
1365-1: 1999 Walls (D1.3)<br />
1365-2: 1999 Floors and roofs (D1.3)<br />
1365-3: 1999 Beams (D1.3)<br />
1365-4: 1999 Columns (D1.3)<br />
BS EN 1366 Fire resistance tests for service installations<br />
1366-1: 1999 Ducts (D1.3)<br />
1366-2: 1999 Fire dampers (D1.3)<br />
BS EN 1610: 1998 Construction and testing of drains and sewers (M2.1)<br />
BS EN 1634 Fire resistance tests for door and shutter assemblies<br />
1634-1: 2000 Fire doors and shutters (D1.3)<br />
1634-3: 2001 Smoke control doors (D1.3)<br />
BS EN ISO 1716 Reaction to fire tests for building products- (D1.3)<br />
Determination of the gross calorific value<br />
BS EN ISO 6946: 1997 Building components and building elements: (J2.1)<br />
Thermal resistance and thermal transmittance J Appendix B<br />
Calculation method J Appendix C<br />
17<br />
Amdt: September 2001
BS EN ISO 8990: 1996 Thermal insulation. Determination of steady-state thermal (J2.1)<br />
transmission properties. Calibrated and guarded hot box<br />
BS EN ISO 9000 Quality management and Quality (B2.1)<br />
assurance standards<br />
BS EN ISO 10077 Thermal performance of windows, doors and shutters<br />
Calculation of thermal transmittance.<br />
Amdt: September 2001<br />
10077-1: 2000 Simplified method (J2.1)<br />
J Appendix A<br />
10077-2: 2000 Numerical method for frames (J2.1)<br />
J Appendix A<br />
BS EN 10088 Stainless steels<br />
10088-1: 1995 List of stainless steels (F4.12), (F6.9)<br />
BS EN 10215: 1995 Continuously hot-dip Zinc-Aluminium (F6.9)<br />
(AZ) coated steel strip and sheet.<br />
<strong>Technical</strong> delivery conditions<br />
BS EN ISO 11925 Reaction to fire tests for building products.<br />
11925-2 Ignitability when subjected to direct impingement of a flame D1.3<br />
BS EN 12056 Gravity drainage systems inside buildings<br />
12056-2: 2000 Sanitary pipework, layout and calculation (M2.1), (M2.2)<br />
(M2.5)<br />
12056-3: 2000 Roof drainage, layout and calculation (M2.1)<br />
12056-4: 2000 Wastewater lifting plants. Layout and calculation (M2.2)<br />
BS EN 12524: 2000 Building materials and their products J Appendix B<br />
Hygrothermal properties – Tabulated design values<br />
BS EN 12566-1: 2000 Small wastewater treatment systems for up to 50PT. (M3.1)<br />
Prefabricated septic tanks.<br />
BS EN ISO 12664: 2001 Thermal performance of building materials and products. (J2.1)<br />
Determination of thermal resistance by means of guarded<br />
hot plate and heat flow meter methods. Dry and moist<br />
products of medium and low thermal resistance.<br />
BS EN ISO 12667: 2000 Thermal performance of building materials and products. (J2.1)<br />
Determination of thermal resistance by means of guarded<br />
hot plate and heat flow meter methods. Products of high<br />
and medium thermal resistance.<br />
BS EN ISO 13370: 1998 Thermal performance of buildings. Heat transfer via (J2.1)<br />
the ground. Calculation methods. J Appendix C<br />
BS EN ISO 13789: 1999 Thermal performance of buildings. Transmission heat loss J2.3, J8.3<br />
co-efficient. Calculation method.<br />
18
BS EN 13823 Reaction to fire tests for building products D1.3<br />
Building products excluding floorings exposed to the thermal<br />
attack by a single burning item<br />
BS EN ISO/IEC 17025: 2000 General requirements for the competence (B2.2)<br />
of testing and calibration laboratories<br />
BS EN 45002: 1989 General criteria for the assessment of testing laboratories (B2.2)<br />
BS EN 45003: 1995 Calibration and testing laboratory (B2.2)<br />
accreditation systems - general<br />
requirements for operation and<br />
recognition<br />
BS EN 45004; 1995 General criteria for the operation of various types of (B2.2)<br />
bodies performing inspection<br />
BS EN 45011: 1998 General requirements for bodies operating product (B2.2)<br />
certification systems<br />
BS EN 45012: 1998 General requirements for bodies operating assessment and (B2.2)<br />
certification/registration of quality systems<br />
BS 7513: EN 45013: 1989 General criteria for certification bodies operating (B2.2)<br />
certification of personnel<br />
BS EN 45014: 1998 General criteria for supplier’s declaration of conformity (B2.2)<br />
DRAFTS FOR DEVELOPMENT<br />
DD 175 : 1988 Code of practice for the identification G Appendix<br />
(1992) of potentially contaminated land and<br />
its investigation<br />
EU DRAFTS FOR DEVELOPMENT<br />
prEN 858 Separator systems for light liquids (e.g. oil and petrol)<br />
858-1: 1999 Principles of product design, performance and testing, (M2.7)<br />
marking and quality control<br />
858-2: 1999 Selection of nominal size, installation, operation (M2.7)<br />
and maintenance<br />
prEN 1825 Grease separators<br />
1825-1: 1999 Principles of design, performance and testing, (M2.7)<br />
marking and quality control<br />
1825-2: 1999 Selection of nominal size, installation, operation (M2.7)<br />
and maintenance<br />
19<br />
Amdt: September 2001
prEN 13501 Fire classification of construction products and building elements<br />
Amdt: September 2001<br />
13501-1: 2000 Classification using data from reaction to fire tests (D1.3)<br />
13501-2: 1999 Classification using data from fire resistance tests (D1.3)<br />
(excluding products for use in ventilation systems)<br />
Note:<br />
Copies of British <strong>Standards</strong> and British <strong>Standards</strong> Codes of Practice, European <strong>Standards</strong>, Drafts for Development<br />
and International <strong>Standards</strong> may be purchased from the British <strong>Standards</strong> Institution. Copies of British<br />
Board of Agrément Certificates may be purchased from the British Board of Agrément.<br />
OTHER PUBLICATIONS<br />
(listed in order of appearance in the text)<br />
Title and Publisher Context<br />
Construction Products Directive 89/106/EEC as amended by B Introduction<br />
CE Marking Directive 93/68/EEC and Fixing and use of CE Marks Directive 93/465/EEC (B2.2)<br />
Electro Magnetic Compatability Directive 89/336/EEC and B Introduction<br />
Electrical Equipment designed for use within certain voltage limitations 73/23/EEC<br />
Small Buildings Guide, second edition (C2.1)<br />
(HMSO, 1994)<br />
NHS in Scotland Firecode D Introduction<br />
E Introduction<br />
“The Behaviour of Steel Portal Frames in Boundary Conditions”, second edition (D1.3)<br />
(The Steel Construction Institute, 1990)<br />
Building Research Establishment Report (BR 128) “Guidelines for the (D1.3)<br />
Construction of Fire Resisting Structural Elements”<br />
(BRE, 1988)<br />
EC Commission Decision 2000/367/EC on 3.5.2000 implementing Council Directive 89/106/EEC (D1.3)<br />
EC Commission Decision 2000/147/EC on 8.2.2000 implementing Council Directive 89/106/EEC<br />
EC Commission Decision 94/611/EC on SEP.1994 implementing Council Directive 89/106/EEC<br />
EC Commission Decision 96/603/EC on 4.10.1996 (amended 26.9.2000) implementing Council Directive<br />
89/106/EEC<br />
Loss Prevention Council Rules for Automatic Sprinkler Installations (D2.1), (D5.1)<br />
(LPC, 1994) (D5.2), (D5.3)<br />
(D5.4), (D8.1)<br />
Building Research Establishment Report (BR 368) “Design Methodologies (D3.6), (D3.7)<br />
for smoke and heat exhaust ventilation”<br />
(BRE, 1999)<br />
CIBSE <strong>Technical</strong> Memorandum 19 (D3.6), (D3.7)<br />
(Chartered Institution of Building Services Engineers, 1995)<br />
Health and Safety Executive Guidance Note PM25 “Vehicle (D3.8)<br />
finishing units fire and explosion hazards”<br />
(HSE, 1981)<br />
20
Builders Hardware Industry Federation, Code of Practice (D3.14), (D4.7)<br />
“Hardware for Timber Fire and Escape Doors” (D5.8), (D6.7)<br />
(2000) (D11.1-D11.5)<br />
(E5.19), (E5.20)<br />
Building Research Establishment Housing Defects Prevention Unit “Defect (D3.16), (D5.10)<br />
Action Sheet” (Design), DAS8<br />
(BRE, 1982) 1985?<br />
“Design, Construction, Specification and Fire Management of Insulated Envelopes (D7.4)<br />
For Temperature Controlled Environments”<br />
(International Association of Cold Storage Contractors(European Division) 1999)<br />
Building Research Establishment Report (BR 187) “External Fire Spread: (D8.1)<br />
Building Separation and Boundary Distances”<br />
(BRE, 1991)<br />
Building Research Establishment Fire Note 9: Assessing the fire performance (D10.1)<br />
of external cladding systems<br />
(BRE 1999)<br />
Fire Precautions (Workplace) Regulations 1997 (as amended to June 2001) E Introduction<br />
Health and Safety (Safety Signs and Signals) Regulations 1996<br />
HSE publication: Safety Signs and Signals: Guidance on Regulations<br />
Part 1 of the Cinematographic (Safety) (Scotland) Regulations 1955 E9.1<br />
Fire Services Act 1947 E10.3<br />
CIBSE Design Guides (F2.1)<br />
(Chartered Institution of Building Services Engineers)<br />
IGE Design Guides (F2.1)<br />
(Institute of Gas Engineers)<br />
Gas Appliance (Safety) Regulations 1985 (F3.1), (F6.2)<br />
Gas Safety (Installation and Use) Regulations 1998 (F3.1)<br />
Building Research Establishment Information Paper IP 7/94 (F3.11)<br />
Spillage of flue gases from solid fuel combustion appliances<br />
(BRE 1994)<br />
OFTEC <strong>Technical</strong> Information Note TI/112, Oil fired appliances (F3.11)<br />
and extract fans<br />
(Oil Firing <strong>Technical</strong> Association For The Petroleum Industry 1996)<br />
The official guide to approved solid fuel products and services (F4.2)<br />
(HETAS Ltd, 1999)<br />
OFTEC Applied <strong>Standards</strong> OFS A100, Oil-fired appliance standard heating boilers (F5.2), (F5.8)<br />
with atomising burners, output up to 70kW and maximum operating pressures of 3Bar (F5.10), (F5.11)<br />
(Oil Firing <strong>Technical</strong> Association For The Petroleum Industry 1998) (F5.13)<br />
21<br />
Amdt: September 2001
OFTEC Applied <strong>Standards</strong> OFS A101, Oil-fired appliance standard oil-fired (F5.2), (F5.8)<br />
cookers with atomising and vaporising burners with or without boilers, (F5.10), (F5.11)<br />
heat output up to 45kW (F5.13)<br />
(Oil Firing <strong>Technical</strong> Association For The Petroleum Industry 1998)<br />
Gas Installation in Timber Frame Buildings IGE/UP/7 (F6.6)<br />
(Institute of Gas Engineers, 1998)<br />
OFTEC <strong>Technical</strong> Standard OFS T100, Polyethylene oil tanks and bunds for (F7.1)<br />
distillate fuel<br />
(Oil Firing <strong>Technical</strong> Association For The Petroleum Industry 1999)<br />
OFTEC <strong>Technical</strong> Information Note TI/133, Assessment of the risk of environmental (F7.2)<br />
damage being caused by spillage from domestic oil storage tanks<br />
(Oil Firing <strong>Technical</strong> Association For The Petroleum Industry 1999)<br />
LPG Association Code of Practice 24: Use of LPG cylinders: Parts 1 and 2 (F7.3)<br />
(Liquid Petroleum Gas Association, 1998)<br />
LPG Association Code of Practice 1: Bulk LPG Storage at Fixed Installations: Part 1 (F7.5)<br />
(Liquid Petroleum Gas Association, 1998)<br />
Radon: guidance on protection measures for new dwellings in Scotland (G2.1)<br />
(Building Research Establishment, 1999) G Appendix<br />
Design Guidance on Flood Damage to Dwellings G Appendix<br />
(HMSO, 1996)<br />
National Planning Policy Guidelines ‘Planning and flooding’ G Appendix<br />
(The <strong>Scottish</strong> Office Environment Department, 1995)<br />
Building Research Establishment Report BR 262: “Thermal Insulation: J Introduction,<br />
Avoiding Risks” second edition (J4.1), (J5.1)<br />
(BRE/HMSO, 1994) (J9.1)<br />
J Appendix C<br />
Building Research Establishment Information Paper IP 14/94: “U-Values J Introduction<br />
for Basements” (J2.2), (J3.2)<br />
(BRE, 1994) J Appendix F10<br />
Building (Procedure) (Scotland) Regulations 1981, as amended to June 2001 J Introduction<br />
(HMSO) J Appendix G<br />
Building Research Establishment Report BR 265: “Minimising Air J Introduction<br />
Infiltration in Office Buildings” (J10.1)<br />
(BRE, 1994)<br />
“The <strong>Government</strong>’s Standard Assessment Procedure for energy rating J2.3, J 3.1<br />
of dwellings” – 2001 edition (SAP 2001) J3.11<br />
(BRE, 2001) J Appendix G<br />
CIBSE Guide A: Design Data - Section A3: “Thermal Properties (J2.1)<br />
of Building Structures” J Appendix B<br />
(Chartered Institution of Building Services Engineers, 1999) J Appendix C<br />
Amdt: September 2001<br />
22
CIBSE Building Energy Code: Part 2: “Calculation of Energy Demands and (J3.4)<br />
Targets for the Design of New Buildings and Services:<br />
(a) Heated and Naturally Ventilated Buildings”, Worksheets 1a-1e<br />
(Chartered Institution of Building Services Engineers, 1981)<br />
CIBSE Applications Manual AM1: “Automatic Controls and (J5.1)<br />
their Implications for Systems Design”<br />
(Chartered Institution of Building Services Engineers, 1985)<br />
BRECSU Good Practice Guide GPG 143 Wet Central Heating Systems, 1996 (J6.1)<br />
CIBSE Application Manual AM11: Building Energy and Environmental Modelling (J8.7)<br />
(Chartered Institution of Building Services Engineers, 1998)<br />
Boiler Efficiency Regulations 1993 & 1994 (J11.1)<br />
BRECSU Good Practice Guide GPG 132 Heating controls in small commercial and (J11.3)<br />
multi-residential buildings, November 2000<br />
CIBSE Code for Interior Lighting (J12.1), (J12.3)<br />
(Chartered Institution of Building Services Engineers, 1994)<br />
ECON 19: Energy Use in Offices – Energy Consumption Guide 19 (J13.1)<br />
DETR 1998 J Appendix K<br />
CIBSE and BSRIA Commissioning Guides (J14.1)<br />
Building Research Establishment Information Paper IP 5/98: J Appendix B<br />
Building Research Establishment Information Paper IP 12/94: “Assessing J Appendix D<br />
Condensation Risk and Heat loss at Thermal Bridges around Openings”<br />
(BRE, 1994)<br />
Building Research Establishment Information Paper IP 3/90: “The U-value J Appendix F10<br />
of Ground Floors: Application to Building Regulations”<br />
(BRE, 1990)<br />
Building Research Establishment Information Paper IP 7/93: “The U-Value J Appendix F10<br />
of Solid Ground Floors with Edge Insulation”<br />
(BRE, 1993)<br />
CIBSE Guide: “Energy Efficiency in Buildings” J Appendix K<br />
(Chartered Institution of Building Services Engineers, 1998)<br />
CIBSE <strong>Technical</strong> Memorandum TM22: Energy Assessment and Reporting Methodology: J Appendix K<br />
Office Assessment Method. (Chartered Institution of Building Services Engineers, 1999)<br />
CIBSE Guide A: 1986: Design data: section A4 (K2.1)<br />
CIBSE Guide B: 1986: section B2 (K2.1), (K3.1)<br />
(Chartered Institution of Building Services Engineers, 1986)<br />
Building Research Establishment Digest 398: “Continuous mechanical ventilation (K2.1)<br />
in dwellings: design, installation and operation”<br />
(BRE, 1994)<br />
23<br />
Amdt: September 2001
Code of practice for ground floor, multi-storey and underground car parks, section 4 (K3.1)<br />
(Association for Petroleum and Explosive Administration, 1994)<br />
available from APEA, PO Box 572, Barton-le-Clay, Beds. MK45 4QW<br />
Building Research Establishment Information Paper IP 13/94 (K4.3)<br />
(BRE, 1994)<br />
“The control of legionellosis including legionnaires’ disease” (K4.10)<br />
(HSE 1991)<br />
SEDD Planning Advice Note PAN61 “Planning and Sustainable Urban Drainage Systems M Introduction<br />
Approved Code of Practice to the Workplace (Health, Safety and Welfare) Regulations 1992 M Introduction<br />
Sewage (Scotland) Act 1968 M2.8, M2.9<br />
Sewers for Scotland (M2.1)<br />
(<strong>Scottish</strong> Water Authorities, 2001)<br />
Sustainable Urban Drainage Systems: Design Manual for Scotland and Northern Ireland (M2.2), (M2.9)<br />
(CIRIA, 2000)<br />
BRE Digest 365 “Soakaway design” (M2.9)<br />
(Building Research Establishment 1991)<br />
BRE Good Building Guide GBG 42 Parts 1 and 2 (M3.6)<br />
(Building Research Establishment 2000)<br />
NSF41: “Wastewater recycling/reuse and Water conservation devices (M4.2)<br />
(National Sanitation Federation 1996)<br />
NSF41-1999 “Non-liquid saturated treatment systems” (M4.2)<br />
National Sanitation Federation<br />
School Premises (General Requirements and <strong>Standards</strong>) (Scotland) Regulations 1967 to 1979 (M4.5)<br />
DOE Waste Management Paper No.25 “Clinical Wastes” R Introduction<br />
(Department of the Environment, 19??)<br />
Guide to Safety at Sports Grounds, fourth edition S Introduction<br />
(HMSO, 1997)<br />
Disabled Access Guide S Introduction<br />
(Disability Scotland, October 1993 edition)<br />
Guidance on the use of Tactile Paving Surfaces S Introduction<br />
(The <strong>Scottish</strong> Office/DETR, 1998)<br />
Disability Discrimination Act 1995 S Introduction<br />
Workplace (Health, Safety and Welfare) Regulations 1992 S Introduction<br />
Amdt: September 2001<br />
24
INDEX
A<br />
Absorbent blankets (H2.1-3) floor type 3<br />
Absorbent curtains (H2.1-3) wall type 4<br />
Access S intro, S reg 32<br />
Application of Part S S1<br />
Buildings other than dwellings<br />
Sanitary accommodation (M4.5)<br />
Disabled M4.9, (M4.4-5)<br />
Buildings of purpose groups 2-7 S2, (S2.3), (S2.5-7)<br />
Drainage systems (M2.4)<br />
Dwellings Q intro, Q reg 29(1), Q2, (Q2.1), (Q2.4), (Q2.7), (Q2.10-11)<br />
Application of Part Q Q1<br />
Sanitary facilities (M4.1)<br />
Disabled M intro 6, M4.3<br />
Solid waste storage accommodation R reg 30(2)(a), R2.1<br />
Within and between storeys Q reg 29(1)(b), Q2.11-13, (Q2.11)<br />
Escape stairs from topmost storeys E6.2b<br />
Fire-fighting E intro, E10.1<br />
Indicator panels (E11.3)<br />
Structural fire precautions D intro 2<br />
Vehicles E intro 4, E10.7-8, (E10.1-2, 10.8)<br />
Flues and solid fuel appliances F4.8, (F4.8)<br />
Manual controls for windows and rooflights P intro 2, P reg 27(1)(f), P2.7<br />
Oil storage tanks (F7.2)<br />
Practicable replacement of materials and components B2.2<br />
Roofs P intro 2, P reg 27(1)(g), P2.8, (P2.8)<br />
Wastewater treatment plant<br />
Desludging M3.3, (M3.3)<br />
Inspection and sampling treated water M3.1, (M3.1)<br />
Window and rooflight cleaning P intro 2, P2.3-4, (P2.3-4)<br />
Access balconies<br />
Escape routes E2.2<br />
Open<br />
Downstand from soffit E2.13<br />
Protected lobbies E2.11<br />
Smoke ventilation E10.14<br />
Access corridors see Common access corridors<br />
Access decks D11.11<br />
Buildings of purpose groups 2-7, Escape routes E5.9d<br />
Definition A definitions<br />
Fire resistance periods (D1.3) table 1<br />
Flats and maisonettes<br />
Downstand from soffit E2.13<br />
Escape routes E2.2<br />
Smoke ventilation E10.14<br />
Protected lobbies E2.11<br />
Served by escape stairs D11.8-9<br />
Access hatches<br />
Cavity barriers D6.7<br />
Fire safety performance of suspended ceilings (D1.3)<br />
Rooflights within P2.4<br />
Accessible corridors, Dwellings (Q2.11)<br />
Accessible entrance storeys Q intro 4, Q2.11<br />
Sanitary facilities M4.3<br />
Accessible entrances see Entrances<br />
Accessible storeys see Storeys<br />
Accidents<br />
Disproportionate collapse (C3.1)<br />
Miscellaneous hazards P intro, P2, (P2.2-5), (P2.8)<br />
Amdt: September 2001<br />
2
Accommodation see Sleeping accommodation<br />
Accreditation of installers B2.2<br />
Acoustic tests<br />
Identical dwellings H intro 3<br />
Procedures (H2.1-3) test procedures<br />
Active fire protection measures see Fire control systems<br />
Activity spaces<br />
Sanitary facilities<br />
Dwellings M4.3<br />
Small buildings (M4.4)<br />
Watercloset cubicles (M4.6)<br />
Activity spaces (Dwellings) Q3.1, Q3.3<br />
Adjustable automatic timing devices J6.1b, J11.3b, (J6.2), (J11.5)<br />
Agricultural buildings<br />
Exempted classes A schedule 1<br />
Stairs and fixed ladders S3.1e, S3.27, (S3.27)<br />
Agriculture<br />
Definition A definitions<br />
see also Farm effluent tanks<br />
Aids for hard of hearing N reg 26A, N2.2, (N2.2)<br />
Air changes<br />
Dwellings (K2.1)<br />
Large garages (K3.1)<br />
Reduction in natural air changes K intro 4<br />
Small garages (K3.2)<br />
Air for combustion F intro 3c, 6, F reg 14(d)<br />
Gas-fired appliances F6.3, (F6.3)<br />
Large combustion appliance installations F2.1d<br />
Oil-fired appliances F5.3, (F5.3)<br />
Operation of air extract fans F intro 6, F3.11, (F3.11)<br />
Solid fuel appliances F4.3, (F4.3)<br />
Air conditioning<br />
Conservation of fuel and power J intro 7, J13.1, (J13.1)<br />
Office buildings J Appendix K<br />
Air for cooling<br />
Gas-fired appliances F6.4, (F6.4)<br />
Oil-fired appliances F5.4, (F5.4)<br />
Open-flued combustion appliances F3.11, (F3.11)<br />
Air extract fans<br />
Air for combustion F intro 6<br />
Small combustion appliance installations F3.10-11, (F3.11)<br />
Air gaps see Gaps<br />
Air infiltration J intro 8, J5.1, J10.1, (J5.1), (J10.1)<br />
Air supported structures E5.27<br />
Definition A definitions<br />
Exempted classes of buildings A schedule 1<br />
Airborne sound H reg 19, H2.1, (H2.1-3) standards, test procedures<br />
Alarms see Fire detection and alarm systems; Smoke alarms<br />
Alternative exits<br />
Definition A definitions<br />
Flats and maisonettes E2.14-15, E2.18a<br />
Storey height more than 4.5 m E2.20-23<br />
Houses E3.3a, E3.5, E3.7<br />
Aluminium, Structural work (C2.1)<br />
Amendment of warrants A intro 4<br />
Amplified music, Silenced on operation of fire alarm (E11.3)<br />
Amusement arcades, Occupancy load factors A schedule 4<br />
Ancient monuments, Controlled by other legislation A schedule 1<br />
3<br />
Amdt: September 2001
Ancillary buildings<br />
Classifying buildings and parts by purpose A reg 6(2)<br />
Dwellings<br />
Conservatories<br />
Conservation of fuel and power J intro 5, J7.1<br />
Natural ventilation K4.1a<br />
Duration of fire protection D2.1 table 1<br />
Exempted classes A schedule 1<br />
Fire spread D8.1<br />
Roof coverings D9.1<br />
Animal accommodation<br />
Ancillary to dwellings<br />
Acceptable roof coverings D9.1<br />
Duration of fire protection D2.1 table 1<br />
Exempted classes of buildings A schedule 1<br />
Surfaces of unprotected zones D7.1<br />
Apartments see Dwellings<br />
Appliance compartments, Definition A definitions<br />
Appliance replacements not requiring warrants A schedule 2<br />
Archaeological areas, Controlled by other legislation A schedule 1<br />
Areas<br />
Compartments D2.1 table 2<br />
Single storey buildings D2.1 table 1<br />
Energy calculations J2.5<br />
Target U-value method J3.5, J Appendix F<br />
U-values of ground floors J Appendix C<br />
Windows, doors and rooflights<br />
Buildings of purpose groups 2-7<br />
Carbon emissions calculation method J8.9a<br />
Elemental method J8.3-4<br />
Heat loss method J8.5-6, (J8.5), J Appendix H<br />
Measurement A schedule 5<br />
Arenas see Buildings of purpose group 5<br />
Art galleries<br />
Occupancy load factors A schedule 4<br />
Purpose groups A schedule 3<br />
Artificial lighting see Lighting<br />
Asphalt, Thermal conductivity of materials J Appendix A table A18<br />
Assembly buildings see Buildings of purpose group 5<br />
Atria, U-values of floors above or walls adjoining J2.3<br />
Audiences see Fixed seating<br />
Auditoria<br />
Air movement in event of fire D11.14, (D11.14)<br />
Escape routes E4.5, E5.22b<br />
Hearing aids N2.2a<br />
High level smoke outlet above stage D11.15, (D11.15)<br />
Sanitary facilities (M4.5)<br />
Separated stage and stage area D11.13, (D11.13)<br />
Automatic doors S2.4<br />
Escape routes (E2.4, 5.11)<br />
Buildings of purpose groups 2-7 E5.11e<br />
Flats and maisonettes E2.4e<br />
Automatic heat activated sealing devices (D3.14, 4.7, 5.8, 6.7)<br />
Automatic smoke detectors see Fire detection and alarm systems; Smoke detectors<br />
Automatic timing devices (J11.5)<br />
Hot water service systems J6.2, (J6.2)<br />
Space heating controls J6.1b, J11.3b,<br />
B<br />
Baby changing facilities (M4.5)<br />
Back-entry appliances see Combustion appliances<br />
Balanced flues, Fixtures not requiring warrants A schedule 2<br />
Amdt: September 2001<br />
4
Balconies<br />
Transmission of sound H intro 2<br />
Treated as rooms for purpose of Part E E1.4<br />
see also Access balconies<br />
Ballrooms<br />
Emergency lighting (E9.2)<br />
see also Buildings of purpose sub-group 5A<br />
Bars<br />
Disabled access S2.6h<br />
Occupancy load factors A schedule 4<br />
Sanitary facilities (M4.5)<br />
Basement storeys<br />
Buildings of purpose groups 2-7<br />
Number of exits E4.1<br />
Protected zones enclosing escape stairs E6.12<br />
Width of escape stairs E6.3<br />
Compartments D3.3-4<br />
Definition A definitions<br />
Fire-fighting facilities E10.4 table, E10.10<br />
Flats and maisonettes<br />
Ducted warm air heating E2.24<br />
Inner rooms E2.16<br />
Means of escape E2.18-19<br />
Protected zones E2.10<br />
Houses<br />
Inner rooms E3.1<br />
Means of escape E3.3<br />
Private stairs E3.6<br />
Protected enclosures E3.6<br />
Resistance to moisture from ground (G2.3, 2.5-6)<br />
Smoke ventilation E10.15, (E10.15)<br />
Structural fire protection D2.1 table 2<br />
U-values (J2.1), J Appendix C<br />
Bathrooms<br />
Trickle ventilators K4.1b, (K4.1)<br />
Ventilation for dwellings (K2.1) table<br />
Baths see Sanitary facilities<br />
BBA Certificates see British Board of Agrement Certificates<br />
Bed space, Dwellings Q3.1<br />
Bed-patient care<br />
Means of escape E8.4-6, (E8.6)<br />
Measuring travel distances E5.3<br />
Bedrooms<br />
Cavities above ceilings in buildings of purpose sub-group 2B D6.4<br />
Disabled access S2.6e<br />
Dwellings, Location Q3.2<br />
Means of escape<br />
Buildings of purpose sub-group 2A E5.10<br />
Flats and maisonettes<br />
Alternative exits E2.23<br />
Separation from kitchens and other apartments E2.20d<br />
Hospitals E8.4-6, (E8.6)<br />
Occupancy load factors A schedule 4<br />
Sanitary accommodation for disabled, Buildings of purpose groups 2-7 M4.8, (M4.8)<br />
Smoke alarms in shared residential accommodation (E11.2)<br />
Sub-compartmentation in buildings of purpose sub-group 2A D4.2<br />
Sub-compartmentation in buildings of purpose sub-group 2B D4.6<br />
Bingo halls<br />
Emergency lighting (E9.2)<br />
see also Buildings of purpose sub-group 5A<br />
Blind see Disabled people<br />
5<br />
Amdt: September 2001
Blocks<br />
Density and sound insulation (H2.1-3)<br />
Thermal conductivity of materials J Appendix A table A18<br />
Blockwork<br />
Constructions for sound insulation (H2.1-3) wall types 1-3<br />
Insulation thickness J Appendix A table A10, examples 4-6<br />
Resistance to precipitation (G3.1) wall types<br />
Thermal bridging (J2.1), J Appendix B<br />
Thermal conductivity of materials J Appendix A table A18<br />
Boilers<br />
Conservation of fuel and power<br />
Buildings of purpose groups 2-7<br />
Controls J11.2-4, (J11.5)<br />
Efficiency (J11.1)<br />
Dwellings<br />
Carbon index method J Appendix G<br />
Controls J6.1-2, (J6.1-2)<br />
Elemental method J3.2 table 2<br />
Methods of compliance J3.1<br />
Target U-value method J3.5-6, J Appendix F<br />
see also Combustion appliances<br />
Bore holes<br />
Location of infiltration systems (M3.7)<br />
Location of oil storage tanks (F7.2c) table<br />
Boundaries<br />
Definition A definitions<br />
Distance and exceptions to exempted classes A schedule 1<br />
Fire protection<br />
Duration of external walls D2.1 table 2, D8.1-2<br />
Minimum periods of fire resistance (D1.3) table 1<br />
Single storey buildings D2.1 table 1<br />
Fire spread D intro 6<br />
Buildings ancillary to dwellings D8.1b<br />
From adjoining buildings D9.1<br />
Two buildings on land in same occupation D8.3<br />
Unprotected area calculations (D8.1)<br />
Flue terminals<br />
Gas-fired appliances (F6.10)<br />
Oil-fired appliances (F5.10)<br />
Infiltration systems (M3.7)<br />
LPG storage containers F7.5b, (F7.5)<br />
Oil storage tanks F7.2b, (F7.2b) table<br />
Wastewater treatment systems M3.1e, (M3.1)<br />
Bowling alleys<br />
Emergency lighting (E9.2)<br />
see also Buildings of purpose sub-group 5B<br />
Branch pipes, Service openings in walls and floors (D3.14, 4.7, 5.8, 6.7)<br />
Breather membranes (G3.1) wall type 3, roof type 2<br />
Bricks<br />
Constructions for sound insulation (H2.1-3) wall types 1-3<br />
Thermal conductivity of materials J Appendix A table A18<br />
Brickwork<br />
Density and sound insulation (H2.1-3)<br />
Insulation thickness J Appendix A table A9 examples 4-7<br />
Resistance to precipitation (G3.1) wall types<br />
Thermal conductivity of materials J Appendix A table A18<br />
see also Thermal bridging<br />
Bridges, Exempted classes of buildings A schedule 1<br />
Amdt: September 2001<br />
6
British Board of Agrement Certificates<br />
References A references<br />
Unvented hot water storage systems (P3.1)<br />
British <strong>Standards</strong><br />
Fire reaction D1.3, (D1.3)<br />
Fire resistance D1.3, (D1.3)<br />
Large combustion appliance installations F intro 4, F(2.1)<br />
References A references<br />
Selection and use of materials and components (B2.2)<br />
Structural Eurocodes C intro 4<br />
Workmanship B intro 6, (B2.1)<br />
Building services see Services<br />
Buildings<br />
Attached to dwellings A schedule 1<br />
Classifying by purpose A reg 6<br />
Definitions<br />
Building A definitions<br />
Change of use A intro 4<br />
Exempted classes A reg 3<br />
Agricultural buildings A schedule 1<br />
Buildings ancillary to dwellings A schedule 1<br />
Construction and development buildings A schedule 1<br />
Controlled by other legislation A schedule 1<br />
Maintenance only A schedule 1<br />
Not frequented by people A schedule 1<br />
Small buildings A schedule 1<br />
Specialised buildings A schedule 1<br />
Tanks, cables, sewers and drains A schedule 1<br />
Temporary buildings A schedule 1<br />
Works of civil engineering A schedule 1<br />
Buildings of purpose group 1 see Dwellings<br />
Buildings of purpose group 2<br />
Compartmentation D3.5, D2.1 table 2<br />
Single storey buildings D2.1 table 1<br />
Occupancy capacity A reg 7(2)(a)<br />
Purpose groups A schedule 3<br />
Sanitary facilities M4.5, (M4.5)<br />
Warning of fire E intro 1, reg 13(1A), E11.2, (E11.2)<br />
see also Buildings of purpose sub-group 2A; Buildings of purpose sub-group 2B<br />
Buildings of purpose group 3 see Office buildings<br />
Buildings of purpose group 4<br />
Compartmentation D2.1 table 2<br />
Single storey buildings D2.1 table 1<br />
Occupancy capacity and width of circulation areas E5.22c<br />
Purpose groups A schedule 3<br />
Sanitary facilities M4.5, (M4.5)<br />
Smoke and heat exhaust ventilation system D3.6-7, (D3.6-7)<br />
Buildings of purpose group 5<br />
Artificial lighting J Appendix J<br />
Compartmentation D2.1 table 2<br />
Single storey buildings D2.1 table 1<br />
Occupancy load factors A schedule 4<br />
Openings in protective barriers S4.2<br />
Purpose groups A schedule 3<br />
Sanitary facilities M4.5, (M4.5)<br />
Steps in sloping gangways S3.28<br />
see also Auditoria; Buildings of purpose sub-group 5A; Buildings of purpose sub-group 5B<br />
Buildings of purpose group 6 see Industrial buildings<br />
Buildings of purpose group 7 see Storage buildings<br />
Buildings of purpose sub-group 1A see Flats and maisonettes<br />
7<br />
Amdt: September 2001
Buildings of purpose sub-group 2A A schedule 3<br />
Escape routes<br />
Bed-patient care and travel distances E5.3<br />
Maximum travel distances E5.1<br />
Sub-compartmentation and exits E5.10<br />
Fire detection and alarm systems (E11.2)<br />
Lower roof abutting external wall D10.3<br />
Openings in protective barriers S4.2<br />
Sub-compartments D intro 4, D4.1-3<br />
Buildings of purpose sub-group 2B A schedule 3<br />
Cavities above ceilings D6.4<br />
Fire detection and alarm systems (E11.2)<br />
Sanitary accommodation for disabled M4.8, (M4.8)<br />
Sub-compartments D4.6<br />
Buildings of purpose sub-group 5A A schedule 3<br />
Display lighting J12.2<br />
Buildings of purpose sub-group 5B A schedule 3<br />
Bulk storage see Storage buildings; Storage spaces<br />
C<br />
Cables, Exempted classes of buildings A schedule 1<br />
Calling lifts, Tactile buttons (S2.6)<br />
Canopies (D9.1)<br />
Canteens, Sanitary facilities (M4.5)<br />
Capacity see Occupancy capacity<br />
Car parking<br />
Access to dwellings Q2.1<br />
Disabled access S2.1-3, S2.6g<br />
see also Vehicle parking<br />
Car parks<br />
Occupancy load factors A schedule 4<br />
Open-sided<br />
Compartmentation D2.1 table 2<br />
Single storey buildings D2.1 table 1<br />
Steel framed (D1.3)<br />
Purpose groups A schedule 3<br />
U-values of floors above or walls adjoining unheated spaces J2.3<br />
Caravans, Exempted classes of buildings A schedule 1<br />
Carbon dioxide emissions J intro 4<br />
Carbon dioxide systems of fire control (D2.1, 5.1, 5.3-4, 8.1)<br />
Carbon emissions J8.7, (J11.1), J Appendix K<br />
Calculation method J intro 6, J8.7-9, (J8.7)<br />
Carbon index method J intro 3-4, J3.1, J3.11, J Appendix G<br />
Carbon monoxide<br />
Concentration in large garages (K3.1)<br />
Flue gases F intro 6<br />
Carbon performance index (J13.1), J Appendix K2<br />
Caretakers’ flats, Escape stairs from flats and maisonettes E2.14<br />
Carports<br />
Definition A definitions<br />
Exempted classes of buildings A schedule 1<br />
Fire spread D8.1<br />
Catchpits<br />
Definition (F7.2c) table<br />
Oil storage tanks F7.2c, (F7.2c) table<br />
Catwalks<br />
Disabled access 2.6b<br />
Escape stairs E6.6<br />
Structural protection exceptions D2.1<br />
Caulking, Wall joints (H2.1-3) wall types<br />
Cavities see Concealed spaces<br />
Amdt: September 2001<br />
8
Cavity barriers D6.1-10<br />
Definition A definitions<br />
Openings D6.7, (D3.14, 4.7, 5.8, 6.7)<br />
Periods of fire resistance (D1.3) table 1<br />
Cavity fill (Partial)<br />
Insulation thickness J Appendix A example 6<br />
Resistance to precipitation (G3.1) wall type 2<br />
Cavity walls<br />
Concealed spaces D6.1-2<br />
Insulated closers J Appendix D<br />
Non-combustible insulation in buildings over 18 m D10.2<br />
Resistance to precipitation (G3.1) wall type 2<br />
Sealing around joist ends built into inner leafs (J5.1)<br />
Sound insulation constructions (H2.1-3) wall types 1-2<br />
Thermal bridging J Appendix B example 2<br />
Thermal insulation J Appendix A examples 4-6<br />
Ties<br />
Sound insulation constructions (H2.1-3) wall types 1-2<br />
U-value calculations J Appendix B<br />
CE mark of conformity B intro 3<br />
Ceilings<br />
Dispensing with cavity barriers (D1.3) table 1, D6.6-7<br />
Fire safety performance of floors (D1.3) table 2<br />
Fire spread on surfaces D7.1, (D7.1)<br />
Garages ancillary to dwellings D5.2<br />
Independent (H2.1-3) floor type 4<br />
Insulation between and over joists J Appendix A table A4, examples 1-2<br />
Junctions with walls (H2.1-3) wall types 1-3<br />
Openwork and smoke reservoirs (D3.6-7)<br />
Requirements for cavity barriers D6.2-4<br />
Sandwich panels D7.3-4, (D7.4)<br />
Thermoplastic materials D7.1c, D7.2, (D7.2)<br />
Central cores, Escape routes E6.11<br />
Central heating see Space heating<br />
Central monitoring units, Smoke alarms (E11.1)<br />
Change of use see Existing buildings<br />
Changes of level, Disabled access S2.7<br />
Changing cubicles M4.7, (M4.7)<br />
Changing facilities<br />
Hospitals D5.4a<br />
Sub-compartmentation D4.2<br />
Chases, Separating walls and sound transmission (H2.1-3)<br />
Chest of drawers space Q3.1<br />
Chimney stacks, Definition A definitions<br />
Chimneys F intro 3e<br />
Definition A definitions<br />
Fixtures requiring warrants A schedule 2<br />
Gas-fired combustion appliance installations F6.1, F6.6, (F6.6)<br />
Incinerators F3.13<br />
Large combustion appliance installations F2.1e<br />
Oil-fired combustion appliance installations F5.1, F5.7-8, (F5.7)<br />
Openings in compartment walls and compartment floors D3.14<br />
Openings in separating walls and separating floors D5.8<br />
Openings in sub-compartment walls D4.7<br />
Small combustion appliance installations F3.3, F3.5, (F3.5)<br />
Factory-made chimneys F3.5-7, (F3.6-7)<br />
Relationship to combustible materials F3.9, (F3.9)<br />
Solid fuel combustion appliance installations F4.1, F4.11-13, (F4.11)<br />
Separation from combustible materials F4.15-16<br />
Chipboard see Wood based boards<br />
Chutes see Waste chutes<br />
9<br />
Amdt: September 2001
Cinemas<br />
Emergency lighting (E9.2)<br />
Gangways S intro 6<br />
Sanitary facilities (M4.5)<br />
see also Buildings of purpose sub-group 5A<br />
Circuits see Electrical circuits<br />
Circular stairs S3.15, (S3.15)<br />
Escape stairs (S3.15)<br />
Circulation areas<br />
Definition A definitions<br />
Minimum width in buildings of purpose group 4 E5.22c<br />
Civil engineering works, Exempted classes of buildings A schedule 1<br />
Claddings<br />
Concealed spaces and cavity barriers D6.5, D6.8<br />
External wall fire spread D10.1, (D10.1)<br />
To adjoining buildings D8.1-2, (D8.1)<br />
Replacements not requiring warrants A schedule 2<br />
Resistance to precipitation (G3.1)<br />
Sound insulation constructions (H2.1-3) wall type 4<br />
Classes of buildings A intro 4<br />
Exempted A reg 3<br />
Cleaner’s rooms<br />
Escape stair protected zones E6.8<br />
Separation from escape stairs D11.5<br />
Cleaning<br />
Windows and rooflights P intro 2, P reg 27(1)(c), P2.3-4, (P2.3-4)<br />
see also Inspection openings; Maintenance<br />
Coastal flooding see Flood water<br />
Cold deck roofs G intro 5<br />
Cold stores, Ventilation requirements K2.1a<br />
Collapse see Disproportionate collapse<br />
Collapsible buildings, Exempted classes of buildings A schedule 1<br />
Collisions<br />
With glazing P intro 2, P reg 27(1)(b), P2.2, (P2.2)<br />
With projections P intro 2, P reg 27(1)(a), P2.1<br />
Combined heat and power systems, Heating system efficiency (J11.1)<br />
Combined method (J2.1), J Appendix B<br />
Combustible materials<br />
Factory-made chimneys F3.9, (F3.9)<br />
Gas-fired appliances F6.14-17, (F6.16-17)<br />
Oil-fired appliances F5.11-13, (F5.11-13)<br />
Solid fuel appliances F4.14-21, (F4.17-19), (F4.21)<br />
Combustion appliance installations F intro 1, F reg 14<br />
Application of Part F F1<br />
Conservation of fuel and power, Combined heat and power systems (J11.1)<br />
Gas-fired F6, (F6.2-7), (F6.9-11), (F6.13), (F6.16-17)<br />
Energy rating eficiency J Appendix G<br />
Labelling F3.12, (F3.12)<br />
Large installations F2.1, (F2.1)<br />
Location F intro 8<br />
Oil-fired F5, (F5.2-4), (F5.7-8), (F5.10-13)<br />
Small installations F3, (F3.1), (F3.4-9), (F3.11-12)<br />
Solid fuel F4, (F4.2-3), (F4.5), (F4.8), (F4.10-12), (F4.17-19), (F4.21)<br />
see also Hot water; Space heating<br />
Amdt: September 2001<br />
10
Combustion appliances<br />
Conservation of fuel and power<br />
Buildings of purpose groups 2-7<br />
Controls J11.2-4, (J11.5)<br />
Efficiency (J11.1)<br />
Dwellings<br />
Carbon index method J Appendix G<br />
Controls J6.1-2, (J6.1-2)<br />
Elemental method J3.2 table 2<br />
Methods of compliance J3.1<br />
Target U-value method J3.5-6, J Appendix F<br />
Exceptions to exempted classes of buildings A schedule 1<br />
Fixtures not requiring warrants A schedule 2<br />
Gas-fired F6.2, F6.16-17, (F6.2), (F6.16-17)<br />
Condensing mode of operation (F6.11)<br />
Decorative fuel-effect (F3.6), (F6.3), (F6.6-7), (F6.16)<br />
Fixtures not requiring warrants A schedule 2<br />
Flue terminal positions (F6.10)<br />
Live fuel-effect (F6.3), (F6.7), (F.6.16)<br />
Separation from combustible materials F6.16-17, (F6.16-17)<br />
Oil-fired F5.2, (F5.2)<br />
Fixtures not requiring warrants A schedule 2<br />
Room-sealed F5.3, F5.6<br />
Separation from combustible materials F5.13, (F5.13)<br />
Standing F5.11-12, (F5.11-12)<br />
Open-flued<br />
Air for combustion or cooling F3.11, (F3.11)<br />
Definition A definitions<br />
Ventilation of dwellings (K2.1) table<br />
Solid fuel F4.2, (F4.2)<br />
Back entry F4.6<br />
Construction of adjacent parts of buildings (F4.19)<br />
Fixtures not requiring warrants A schedule 2<br />
Positioning on hearths F4.18, (F4.18)<br />
Prefabricated appliance chambers (F4.21)<br />
Removal of products of combustion (F4.5)<br />
Combustion products and their removal F intro 3d, F reg 14(c)<br />
Gas-fired combustion appliance installations F6.5-10, (F6.5-7), (F6.9-10)<br />
Large combustion appliance installations F2.1c<br />
Oil-fired combustion appliance installations F5.5-10, (F5.7), (F5.8), (F5.10)<br />
Small combustion appliance installations F3.3-4, (F3.4)<br />
Solid fuel combustion appliance installations F4.4-10, (F4.5), (F4.8), (F4.10)<br />
Commercial buildings see Buildings of purpose group 4<br />
Commissioning services J6.5-6, J14.1-2, (J14.1-2)<br />
Common access corridors<br />
Flats and maisonettes Q2.8<br />
Smoke ventilation E10.14<br />
Sound insulation H1.4<br />
Common ducts, Mechanical ventilation system K4.7<br />
Communal occupations see Mixed occupations<br />
Communal rooms, Escape routes from flats and maisonettes E2.1b, E2.7<br />
Communal solid waste storage accommodation R2.2, (R2.3)<br />
Compartment floors D3.1<br />
Buildings with basement storeys D3.3<br />
Definition A definitions<br />
Escape stairs E6.4b<br />
Junctions with walls D3.15<br />
Openings D3.14, (D3.14, 4.7, 5.8, 6.7)<br />
Chimneys of small combustion appliance installations F3.7a<br />
Flue-pipes of gas-fired installations F6.12<br />
Periods of fire resistance (D1.3) table 1<br />
11<br />
Amdt: September 2001
Compartment walls D3.1<br />
Definitions<br />
Compartment wall A definitions<br />
Sub-compartment wall A definitions<br />
Enclosure of lift wells D3.12<br />
Junctions with other walls D3.15<br />
Hospitals D3.17<br />
Junctions with roofs D3.16, (D3.16, 5.10)<br />
Measuring travel distances E5.2-3<br />
Openings D3.14, (D3.14, 4.7, 5.8, 6.7)<br />
Chimneys of small combustion appliance installations F3.7a<br />
Flue-pipes of gas-fired installations F6.12<br />
Manual operation of rolling shutters E10.16<br />
Periods of fire resistance (D1.3) table 1<br />
Separated stage and stage area D11.13<br />
Compartments D intro 3, D3.1-17<br />
Definition A definitions<br />
Duration and area D2.1 table 2<br />
Single storey buildings D2.1 table 1<br />
Hospitals E8.1-4<br />
Hospital streets E8.9-10<br />
Rules of measurement A schedule 5<br />
Single buildings having opposing compartments externally D8.3<br />
Travel distances E5.3<br />
Buildings of purpose sub-group 2A E5.8<br />
Unprotected area calculations (D8.1)<br />
see also Sub-compartments<br />
Components, Selection and use B2<br />
Composite floor bases, Sound insulation constructions (H2.1-3)<br />
Composite steel and concrete structural work (C2.1)<br />
Concealed spaces D6.1-10<br />
Definition of cavity A definitions<br />
Junctions D6.8-10, (D3.14, 4.7, 5.8, 6.7, 6.9)<br />
Openings D6.7, (D3.14, 4.7, 5.8, 6.7)<br />
Storeys more than 18 m above ground<br />
Insulation in cavities of external walls D10.2<br />
Rainscreen cladding D6.5<br />
Concentrated loads C intro 3<br />
Concrete<br />
Deck roofs<br />
Insulation thickness J Appendix A example 3<br />
Resistance to precipitation (G3.1)<br />
Floors<br />
Sound insulation constructions (H2.1-3) wall types 2-3, floor types 1-2<br />
Thermal insulation thickness J Appendix A table A16<br />
Flue-block chimneys (F3.5)<br />
Ground floors<br />
Insulation thickness J Appendix A tables A12, A14, example 8<br />
Resistance to moisture from ground (G2.3, 2.5-6)<br />
Lightweight blocks<br />
Thermal bridging (J2.1), J Appendix B<br />
Thermal conductivity of materials J Appendix A table A18<br />
Structural work (C2.1)<br />
Disproportionate collapse (C3.1)<br />
Thermal conductivity of materials J Appendix A table A18<br />
Walls<br />
Resistance to precipitation (G3.1) wall types 1-2<br />
Sound insulation constructions (H2.1-3) wall types 1-3<br />
Thermal insulation thickness J Appendix A table A10<br />
Amdt: September 2001<br />
12
Condensation J intro 8<br />
Air conditioning and ventilation plant management J Appendix K<br />
Risk at edges of openings J Appendix D<br />
Ventilation standards K intro 4<br />
Condensation resistance G intro 5-6, G reg 18, (G3.1)<br />
Interstitial G intro 6, G4.1, (G4.1)<br />
Surface G intro 6, G4.2, (G4.2)<br />
Conference halls<br />
Hearing aids N2.2a<br />
see also Buildings of purpose sub-group 5A<br />
Confined spaces<br />
Means of escape E5.22<br />
Storage areas E5.21<br />
Conservation of fuel and power J intro, J reg 22<br />
Application of Part J J1<br />
Buildings of purpose groups 2-7 J intro 6<br />
Carbon emissions calculation method J8.7-10, (J8.7)<br />
Commissioning services J14.1-2, (J14.1-2)<br />
Efficiency of services systems J13.1, (J13.1)<br />
Offices J Appendix K<br />
Elemental method J8.2-4<br />
Heat loss method J8.5-6, (J8.5), J Appendix H<br />
Heating and hot water services J11.1-7, (J11.1, 11.3, 11.5-7)<br />
Lighting services J12.1-3, (J12.1-3), J Appendix J<br />
Limiting infiltration J10.1, (J10.1)<br />
Limiting thermal bridging J9.1, (J9.1)<br />
<strong>Standards</strong> J8.1<br />
Dwellings J intro 3-5<br />
Carbon index method J3.11, J Appendix G<br />
Conservatories J7.1<br />
Elemental method J3.2-3<br />
Heating and hot water services J6.1-6, (J6.1-4)<br />
Limiting infiltration J5.1, (J5.1)<br />
Limiting thermal bridging J4.1, (J4.1)<br />
Maximum permissible U-values J3.12<br />
<strong>Standards</strong> J 3.1<br />
Target U-value method J3.4-10, J Appendix F<br />
Rules for the use of Part J J2.1-5, (J2.1)<br />
Tables of U-values J Appendix A<br />
Thermal bridging at the edges of openings J Appendix D<br />
U-value calculations using the Combined Method J Appendix B<br />
U-values of ground floors and basements J Appendix C<br />
U-values of windows, doors and rooflights J Appendix E<br />
Ventilation K intro 3<br />
Conservatories<br />
Conservation of fuel and power J intro 5, J7.1<br />
Definition A definitions<br />
Duration of fire protection D2.1 table 1<br />
Exceptions to exemptions A schedule 1<br />
Ventilation of dwellings K4.1a<br />
Construction<br />
Applications for warrants already made A intro 4<br />
Definition A definitions<br />
Construction and development buildings, Exempted classes A schedule 1<br />
Construction Products Directive<br />
Compliance A references<br />
Fitness of materials B intro 3, (B2.2)<br />
Reaction to fire (D1.3)<br />
Constructional hearths see Hearths<br />
Containers, Surface water storage M2.9d<br />
13<br />
Amdt: September 2001
Contamination<br />
Air supply of mechanical ventilation systems K4.9-10, (K4.10)<br />
Contaminants and remedial actions G Appendix<br />
Dungsteads and farm effluent tanks R reg 31, R3.1a, (R3.1)<br />
From contents of fuel tanks F reg 15(1)(b), (F7.2c) table<br />
Solid waste storage from dwellings R reg 30(2)(c), R2.1<br />
Control rooms, Shopping centres with malls (E11.3)<br />
Controlled waters, Oil storage tanks (F7.2c) table<br />
Conversions see Existing buildings<br />
Cookers, Facilities for dwellings Q3.3<br />
Cooling see Air for cooling; Space cooling<br />
Corridors<br />
Access within dwellings (Q2.11)<br />
Division for smoke control E5.23, (E5.23)<br />
Fire safety performance of walls D11.4<br />
Escape from flats and maisonettes E2.12, E10.14, (E2.11-12)<br />
Service corridor escape from shops E7.6-7<br />
see also Common access corridors<br />
Counter battens, Framed walls and resistance to precipitation (G3.1) wall type 3, roof type 2<br />
Course heights, Coordinating for thermal insulation (H2.1-3)<br />
Covered areas<br />
Ancillary to dwellings A schedule 1<br />
Fire spread D8.1<br />
Definition A definitions<br />
Fire safety of roofs and rooflights (D9.1)<br />
Creches in shopping centres with malls E7.8<br />
Cubic capacity, Measurement A schedule 5<br />
Cupboards, Factory-made chimneys F3.7b, (F3.7)<br />
Current leakages see Electrical installations<br />
Curtain walls<br />
Condensation avoidance J Appendix D6<br />
Thermal performance J Appendix B4<br />
Curtilage<br />
Buildings ancillary to dwellings exemptions A schedule 1<br />
Definition A definitions<br />
Exceptions to small buildings exemption A schedule 1<br />
D<br />
Damage by heat, Combustion appliance installations F reg 14(b)<br />
Damp-proof courses, Combustible materials and chimneys F4.11, F4.15a<br />
Damp-proof membranes (G2.3, 2.5-6)<br />
Dance halls<br />
Emergency lighting (E9.2)<br />
Occupancy load factors A schedule 4<br />
see also Buildings of purpose sub-group 5A<br />
Dangerous substances see Harmful or dangerous substances<br />
Day centres, Purpose groups A schedule 3<br />
Day rooms<br />
Occupancy capacity A reg 7(2)(a)<br />
Sub-compartmentation D4.2d<br />
Daylight-linked photo-electric light switching (J12.3)<br />
Dead loads C2.1<br />
Calculation (C2.1)<br />
Definition A definitions<br />
Deaf see Disabled people<br />
Deafening (H2.1-3) floor type 3<br />
Decorative fuel-effect gas appliances (F3.6)<br />
Air for combustion (F6.3)<br />
Definition A definitions<br />
Relationship to combustible materials (F6.16)<br />
Removal of products of combustion (F6.6-7)<br />
Amdt: September 2001<br />
14
Deemed to satisfy compliance with standards A reg 9(2)<br />
Workmanship B intro 6<br />
Definitions A definitions<br />
Density, Masonry units, Sound insulation (H2.1-3)<br />
Desludging, Wastewater treatment plant M3.3, (M3.3)<br />
Development buildings see Construction and development buildings<br />
Different occupation<br />
Definition A definitions<br />
Separating walls and separating floors D5.1<br />
Differential movement, Fire-stopping (D3.14, 4.7, 5.8, 6.7, 6.9)<br />
Directions of travel<br />
Buildings of purpose groups 2-7 E4.2-3<br />
Maximum travel distances E5.1<br />
Multiple exits E5.7<br />
Enclosed shopping centres E7.1<br />
Flats and maisonettes E2.15<br />
Storey heights of more than 4.5 m E2.20-21<br />
Hospital streets E8.9e<br />
Directives see Construction Products Directive; European Community<br />
Disabled people<br />
Access to buildings S intro 1, S2.1-5<br />
Access to dwellings Q intro, Q2.1-12, (Q2.1), (Q2.4), (Q2.7), (Q2.11)<br />
Access to flats and maisonettes Q intro 3, Q2.1, Q2.5-7, Q2.10, (Q2.10)<br />
Entryphone systems Q2.10a, (Q2.10)<br />
Definition A definitions, Q intro 6, S intro 8<br />
Fixed seating accommodation S intro 7, S reg 32(2), S2.6f, S2.10<br />
Wheelchair space provision S2.10 table<br />
Hearing aid systems N2.2, (N2.2)<br />
Impaired sight S intro 1<br />
Internal doors and lobbies S2.8-9<br />
Means of escape from fire<br />
Refuges within protected zones E intro 3c<br />
Wheelchair spaces on escape stair landings E2.9, E6.7<br />
Movement within buildings S intro 1, S2.6-7, (S2.6-7)<br />
Dwellings Q2.11-13, (Q2.11)<br />
Light switches in communal areas of flats and maisonettes Q2.10b<br />
Sanitary facilities<br />
Buildings other than dwellings M intro 6-7, M4.8, (M4.4-5), (M4.8)<br />
Travel distances M4.9<br />
Dwellings M intro 6-7<br />
Accessibility M intro 6, M4.3<br />
Discharges from drainage systems M2.8-9, (M2.9)<br />
Discharges into drainage systems M2.6-7, (M2.6-7)<br />
Discharges of steam or hot water P intro 2, P reg 27(1)(e), P2.6<br />
Installation of discharge pipes (P3.1)<br />
Warnings must not be impeded by insulation J11.7<br />
Display lighting, Energy conservation J12.2, (J12.2-3)<br />
Disproportionate collapse C reg 11(2), C3.1, (C3.1)<br />
Distances between buildings see Boundaries; Separation distances<br />
Docks, Exempted classes of buildings A schedule 1<br />
Domestic garages<br />
Acceptable roof coverings D9.1<br />
Duration of fire protection D2.1 table 1<br />
Exempted classes of buildings A schedule 1<br />
Protected lobbies E2.11<br />
Separating walls and separating floors D5.2b, D5.7<br />
U-values of floors above or walls adjoining unheated spaces J2.3<br />
Door frames<br />
Conservation of fuel and power<br />
Dwellings, Elemental method J3.2 table 1<br />
Indicative U-values J Appendix A tables A1-3<br />
15<br />
Amdt: September 2001
Doors<br />
Conservation of fuel and power<br />
Buildings of purpose groups 2-7<br />
Carbon emissions calculation method J8.9a<br />
Elemental method J8.2-4, J Appendix E<br />
Heat loss method J8.5-6, (J8.5), J Appendix H<br />
Dwellings<br />
Draught seals (J5.1)<br />
Elemental method J3.2-3, J Appendix E<br />
Methods of compliance J3.1<br />
Target U-value method J Appendix F<br />
Indicative U-values J Appendix A tables A1-3<br />
Definition of emergency door A definitions<br />
Escape routes (E2.4, 5.11)<br />
Buildings of purpose groups 2-5, Occupancy capacity more than 60 E5.20<br />
Buildings of purpose groups 2-7 E5.11, E5.17-20<br />
Flats and maisonettes E2.1, E2.4-5<br />
Hospital streets to adjoining compartments E8.10<br />
Internal doors S2.8<br />
Opening onto landings S3.19<br />
Measuring travel distances<br />
Buildings of purpose groups 2-7 E5.2-4<br />
Flats and maisonettes E2.15<br />
see also Entrances; Fire doors; Glazed doors<br />
Doorways<br />
Clear headroom, Escape routes E2.3, E5.12<br />
Clear opening width (Q2.11)<br />
Escape routes E5.15<br />
Double glazing see Glazing<br />
Double-walled flue-pipes<br />
Gas-fired installations<br />
Relationship to combustible materials F6.14-15<br />
Removal of combustion products F6.9, (F6.9)<br />
Drainage systems<br />
Application of Part M M1<br />
Definition A definitions<br />
Discharges from drainage systems M2.8-9, (M2.9)<br />
Discharges into systems M2.6-7, (M2.6-7)<br />
Washing down floors where communal solid waste stored R2.2<br />
Wastewater and surface water M intro 1-4, M reg 24, M2.1-5, (M2.1-5)<br />
see also Site drainage<br />
Drains<br />
Branch pipe through fire resisting construction (D3.14, 4.7, 5.8, 6.7)<br />
Exempted classes of buildings A schedule 1<br />
Existing drains and site preparation G intro 3, G reg 16(2)(c), G2.4<br />
Size and construction M intro 2, (M2.4)<br />
Subsoil G intro 3, (G2.2)<br />
Draught diverters<br />
Gas-fired installations F6.8a, F6.17, (F6.17)<br />
Solid fuel installations F4.7a<br />
Draught seals (J5.1)<br />
Draught stabilisers<br />
Flue openings<br />
Gas-fired installations F6.8a<br />
Solid fuel installations F4.7a, (F4.3)<br />
Dropped kerbs see Kerbs<br />
Dry fire mains see Fire mains<br />
Dry linings see Internal linings<br />
Ducted warm air heating systems<br />
Flats and maisonettes E2.24<br />
Thermostats and time controls J11.4a<br />
Amdt: September 2001<br />
16
Ducts<br />
Conservation of fuel and power<br />
Calculation of areas J2.5c<br />
Thermal insulation J6.3, J11.6, (J6.3-4), (J11.6)<br />
Definition A definitions<br />
Fire resisting construction (D3.14, 4.7, 5.8, 6.7)<br />
Floor penetrations and sound transmission (H2.1-3) floor types<br />
Separating walls and sound transmission (H2.1-3)<br />
see also Common ducts<br />
Dungsteads R intro 1b, R reg 31, R3.1-2, (R3.1-2)<br />
Exceptions to exempted classes A schedule 1<br />
Durability B intro 5, B reg 10, B2.2<br />
Dwell times, Passenger lifts (S2.6)<br />
Dwellings<br />
Above shops or offices D5.6b<br />
Access Q intro, Q reg 29(1), Q2, (Q2.1), (Q2.4), (Q2.7), (Q10-11)<br />
Accessible entrances Q2.5-7, (Q2.7)<br />
Application of Part Q Q1<br />
Within and between storeys Q reg 29(1)(b), Q2.11-13, (Q2.11)<br />
Accommodation Q intro 1, Q reg 29(1)(c), Q3.1<br />
Ancillary or attached buildings<br />
Conservatories<br />
Conservation of fuel and power J intro 5, J7.1<br />
Natural ventilation K4.1a<br />
Duration of fire protection D2.1 table 1<br />
Exemptions A schedule 1<br />
Fire spread D8.1<br />
Roof coverings D9.1<br />
Compartmentation D2.1 table 2<br />
Single storey buildings D2.1 table 1<br />
Conservation of fuel and power<br />
Application of Part J J intro 3-5, J1.2<br />
Area of glazing in extensions J2.5d<br />
Carbon index method J3.1, J3.11, J Appendix G<br />
Elemental method J3.1-3<br />
U-values of windows, doors and rooflights J Appendix E<br />
Heating and hot water services J6.1-6, (J6.1-4)<br />
Limiting air infiltration J5.1, (J5.1)<br />
Limiting thermal bridging J4.1, (J4.1)<br />
Maximum permissible U-values J3.12<br />
<strong>Standards</strong> J3.1<br />
Target U-value method J3.1, J3.4-10, J Appendix F<br />
U-values<br />
Floors or walls adjoining unheated space J2.3<br />
Ground floors J Appendix C<br />
Definitions<br />
Apartment A definitions<br />
Dwelling A definitions, H1.4<br />
Discharge from hot water systems P2.6<br />
Discharges into drainage systems M2.6, (M2.6)<br />
Distance from dungsteads or farm effluent tanks R3.1c, (R3.1)<br />
External walls and risk of fire spread D8.1-2<br />
Facilities Q intro 1, Q reg 29, Q3<br />
Application of Part Q Q1<br />
Kitchens Q reg 29(1)(d), Q3.3-4<br />
Sanitary facilities Q intro 5<br />
Openings in protective barriers S4.2<br />
Protected enclosures D11.3<br />
Purpose groups A schedule 3<br />
Sanitary facilities M intro 2, M4.1-3, (M4.1-2)<br />
Accessibility to disabled M intro 6, M4.3<br />
17<br />
Amdt: September 2001
Separating walls and separating floors D5.2, D5.6-7<br />
Solid waste storage R reg 30(1), R2, (R2.3)<br />
Sound transmission H intro, H regs 19-21<br />
Application of Part H H1<br />
Specified constructions (H2.1-3)<br />
Test procedures (H2.1-3) test procedures<br />
Used for business, Purpose groups A schedule 3<br />
Ventilation K intro 4-5, K4.1a, (K2.1)<br />
Passive stack K2.1c, (K2.1)<br />
Systems serving more than one dwelling K4.6<br />
Warning of fire E intro 1, E reg 13(1A), E11.1<br />
see also Disabled people; Flats and maisonettes; Houses<br />
Dynamic loads C intro 3<br />
E<br />
Edge insulation J Appendix C<br />
Educational establishments, Purpose groups A schedule 3<br />
Effluents see Dungsteads; Farm effluent tanks<br />
Electric shocks N intro 1<br />
Electrical circuits<br />
Definition of protected circuit A definitions<br />
Protected lighting circuits E9.1<br />
Separate lighting circuits for protected zones E9.1<br />
Smoke alarms (E11.1)<br />
Smoke and heat ventilation systems (D3.6-7)<br />
Electrical installations N intro, N reg 26, N2.1, (N2.1)<br />
Application of Part N N intro 3, N1<br />
Artificial lighting of escape routes E9.1<br />
Emergency lighting E9.2, (E9.2)<br />
Protection against overcurrents or leakages N2.1b<br />
Smoke alarms (E11.1)<br />
Socket outlets in dwellings Q reg 29(2), Q3.9<br />
Standby power supply<br />
Air supported structures E5.27d<br />
Smoke and heat ventilation systems (D3.6-7)<br />
Electro-magnetic or electro-mechanical devices susceptible to smoke, Definition A definitions<br />
Electromagnetic disturbances, Smoke alarms B intro 4<br />
Elemental method<br />
Buildings of purpose groups 2-7 J intro 6, J8.2-4<br />
Dwellings J intro 3, J3.1-3<br />
U-values of windows, doors and rooflights J Appendix E<br />
Elements of structure<br />
Definition A definitions<br />
Fire safety performance D2.1-3<br />
Emergency doors E5.18<br />
Definition A definitions<br />
Emergency lighting E9.2, (E9.2)<br />
Definition A definitions<br />
Energy use J12.1a<br />
Escape routes E9.1<br />
Emergency stopping of escalators & passenger conveyors P intro 3, P reg 27(1)(d), P2.5, (P2.5)<br />
Emergency support systems, Air supported structures E5.27e<br />
Emergency windows see Windows<br />
Enclosed courtyards, Treated as rooms for purpose of Part E E1.4<br />
Enclosed shopping centres see Shopping complexes<br />
Enclosing rectangles, Unprotected area calculations (D8.1)<br />
Enclosures<br />
Escape stairs<br />
Buildings of purpose groups 2-7 E6.2, E6.6-14<br />
External walls D11.10<br />
Flats and maisonettes E2.8-11<br />
Hospitals E8.7<br />
Separating walls D5.7<br />
Amdt: September 2001<br />
18
Protected D11.3<br />
Definition A definitions<br />
Lift wells D3.12<br />
Means of escape in flats and maisonettes E2.11, E2.19<br />
More than 5 m in height E2.20-21, E2.23a<br />
Means of escape in houses of purpose sub-group 1B E3.4, E3.6<br />
Swimming pools, Ancillary buildings exempted A schedule 1<br />
Energy conservation see Conservation of fuel and power<br />
Energy consumption<br />
Efficiency of system operation J13.1, (J13.1)<br />
Office buildings J Appendix K<br />
Information for occupiers J14.2, (J14.2)<br />
Energy metering J Appendix K<br />
Energy ratings see SAP energy ratings<br />
Entrance lobbies S2.5 (S2.5)<br />
Entrances<br />
Access to dwellings Q intro 3, Q2.1-4<br />
Access to flats and maisonettes Q intro 3, Q2.1, Q2.5-9<br />
Access within dwellings Q2.11, (Q2.11)<br />
Sanitary facilities for disabled M4.3<br />
Accessible entrances to dwellings Q intro 4, Q2.5-7<br />
Thresholds Q2.7, (Q2.7)<br />
Approaches of principal entrances S2.3, (S2.3)<br />
Escape from flats and maisonettes E2.1a, E2.15<br />
More than 4.5 m high E2.20-23<br />
Intensive therapy units D4.5<br />
Principal entrances S2.4-5, (S2.5)<br />
Entryphone systems, Disabled access Q2.10a, (Q2.10)<br />
Equipment malfunctions<br />
Escalators and passenger conveyors P intro 3, P reg 27(1)(d), P2.5, (P2.5)<br />
Hot water storage systems P intro 2, P reg 28(1), P3.1, (P3.1)<br />
Escalators<br />
Emergency stopping mechanisms P intro 3, P reg 27(1)(d), P2.5, (P2.5)<br />
Openings in compartment floors D3.14, (D3.14)<br />
Replacements not requiring warrants A schedule 2<br />
Escape of foul air, Drainage systems M intro 2, M2.3, (M2.3)<br />
Escape routes<br />
Air supported structures E5.27<br />
Buildings containing auditoria E4.5<br />
Buildings of purpose groups 2-7 E4.2-5<br />
Horizontal escape E5.1-27<br />
Height and width E5.12-18<br />
Travel distances E5.1-8<br />
Vertical escape E6.1-14<br />
Buildings of purpose sub-group 2A E5.3<br />
Definitions<br />
Escape route A definitions<br />
Protected zones A definitions<br />
Enclosed shopping centres with malls E7.1-8<br />
Flat roofs or access decks E2.2e, E3.7, E5.9g<br />
Flats and maisonettes E2.1-19, (E2.11-12)<br />
Storey height more than 4.5 m E2.20-24<br />
Hospitals E5.9, E8.3-10, (E8.6)<br />
Houses E3.2-7<br />
Lighting E9.1<br />
Number E intro 2<br />
Protection during fires D intro 2, D11.1-15<br />
Flat roofs or access decks D11.11<br />
Minimum periods of fire resistance (D1.3) table 1<br />
Requirements E intro 3<br />
Revolving, sliding or automatic doors (E2.4, 5.11)<br />
Smoke ventilation E10.13-14<br />
see also Travel distances<br />
19<br />
Amdt: September 2001
Escape stairs E intro 3b<br />
Buildings of purpose groups 2-7 E5.9e<br />
Appropriate capacity E6.4<br />
Measuring travel distances if not in a protected zone E5.6<br />
Protected zones E6.6-14<br />
Width E6.1-5<br />
Buildings of purpose sub-group 2A, Maximum travel distances E5.8<br />
Circular (S3.15)<br />
Definition A definitions<br />
Fire protection<br />
Enclosing rooms D11.5<br />
Enclosure and external walls D11.10<br />
Enclosure and separating walls D5.7<br />
External escape stairs D11.7-8<br />
Flats and maisonettes D11.9<br />
Non-combustible materials D11.12<br />
Fire-fighting facilities E10.4<br />
Flats and maisonettes E2.2d, E2.8-14, (E2.11-12), (E2.14)<br />
Hospitals E8.6-9, (E8.6)<br />
Smoke ventilation E10.13<br />
Eurocodes see Structural Eurocodes<br />
European Community<br />
Directives B intro 4<br />
see also CE mark of conformity; Construction Products Directive<br />
European Economic Area B intro 2<br />
European Pre-standards C intro 4<br />
European <strong>Standards</strong><br />
Durability requirements B intro 5<br />
Fire reaction D1.3, (D1.3)<br />
Fire resistance D1.3, (D1.3)<br />
References A references<br />
European <strong>Technical</strong> Approvals (B2.1-2)<br />
Exempted classes of buildings A reg 3, A schedule 1<br />
Existing buildings<br />
Change of use definition A intro 4<br />
Change of use warrants A intro 4<br />
Determining notional boundaries D8.3<br />
Sound transmission H1.3<br />
Timber bases with independent ceilings (H2.1-3) floor type 4<br />
Exits<br />
Air supported structures E5.27<br />
Buildings of purpose groups 2-7 E4.1-2, E5.7, E5.9<br />
Multiple exits E4.3, E5.7, E5.22b<br />
Buildings of purpose sub-group 2A E5.8, E5.10<br />
Creches in malls E7.8<br />
Definitions<br />
Alternative exit A definitions<br />
Exit A definitions<br />
Flats and maisonettes E2.2d, E2.7a<br />
Alternative exits E2.14-15, E2.18a, E2.20-23<br />
Hospitals E8.3, E8.8-9<br />
Houses, Alternative exits E3.3a, E3.5, E3.7<br />
Shops in malls E7.3-4<br />
Signs E intro 7<br />
Air supported structures E5.27c<br />
Width and rate of discharge E intro 2<br />
Expanded polystyrene slabs, Thermal conductivity of materials J Appendix A table A18<br />
Explosion doors, Flue openings F4.6 diagram, F4.7b<br />
Explosions<br />
LPG storage containers F reg 15(2)(b), F7.4<br />
Unvented hot water storage systems P intro 2<br />
Explosives, Buildings controlled by other legislation A schedule 1<br />
Amdt: September 2001<br />
20
Exposed, Definition A definitions<br />
Extension of warrants A intro 4<br />
Extensions<br />
Determining U-values J Appendix C4<br />
Maximum permitted areas of glazing J2.5d<br />
External renderings, Thermal conductivity of materials J Appendix A table A18<br />
External temperature sensing devices J11.3d<br />
External walls<br />
Calculation of areas J2.5<br />
Claddings, Resistance to precipitation (G3.1) wall type 3<br />
Definition A definitions<br />
Fire safety performance<br />
Concealed spaces D6.2, D6.5, D6.8<br />
Duration D2.1 table 2<br />
Single-storey buildings D2.1 table 1<br />
Escape routes in flats and maisonettes D11.9<br />
Escape stair enclosures D11.10<br />
External escape stairs D11.7-8<br />
Fire spread between buildings D8.1-2, (D8.1)<br />
Fire spread on external walls D10.1-3, (D10.1)<br />
Junctions with separating walls or floors D5.9, D5.11<br />
Junctions with sub-compartment walls D4.8<br />
Periods of fire resistance (D1.3) table 1<br />
Junctions for sound insulation floor types (H2.1-3) floor types<br />
Junctions for sound insulation wall types (H2.1-3) wall types<br />
Sealing around joist ends built into inner leafs (J5.1)<br />
Thermal insulation requiring warrants A schedule 2<br />
see also Walls<br />
Extract fans see Fans<br />
F<br />
Factories Act 1961, Ventilation of buildings K intro 2, K reg 23(2)<br />
Factory waste R intro 4<br />
Fanned draught gas-fired appliances, Flue terminals (F6.10) table 1<br />
Fans<br />
Conservation of fuel and power (J13.1), J Appendix K<br />
Extract, Ventilation of dwellings (K2.1)<br />
Replacement not requiring warrants A schedule 2<br />
Smoke and heat ventilation systems (D3.6-7)<br />
Farm effluent tanks R intro 1b, R reg 31, R3.1-2, (R3.1-2)<br />
Fastenings, Securing doors across escape routes E2.5, E5.19-20, (E5.19-20)<br />
Fat discharges into drainage systems M2.7, (M2.7)<br />
Felt, Thermal conductivity of materials J Appendix A table A18<br />
Fencing<br />
Farm effluent tanks R3.2, (R3.2)<br />
Height and exceptions to exempted classes A schedule 1<br />
Fibre cement (G3.1) wall type 3, roof type 2<br />
Fibreboard, Thermal conductivity of materials J Appendix A table A18<br />
Filling contaminated land G Appendix<br />
Filter stations or beds, Exempted classes of buildings A schedule 1<br />
Filtration systems (M3.6)<br />
Fire alarms see Fire detection and alarm systems; Smoke alarms<br />
Fire Certificates (Special Premises) Regulations E reg 13(2)(b)<br />
Fire control rooms<br />
Overriding controls for smoke and ventilation systems (D3.6-7)<br />
Shopping centres with malls E10.12<br />
Fire control systems (D2.1, 5.1, 5.3-4, 8.1)<br />
Basement storeys E10.15, (E10.15)<br />
Compartment size D intro 3, D2.1 table 2<br />
Single storey buildings D2.1 table 1<br />
Enclosed shopping centres (D2.1, 5.1, 5.3-4, 8.1)<br />
Hospitals D5.3-4<br />
Permitted levels of unprotected areas D8.1 table<br />
21<br />
Amdt: September 2001
Fire detection and alarm systems<br />
Activating self-closing fire doors (D3.14, 4.7, 5.8, 6.7, 11.1-5)<br />
Buildings of purpose group 2 E11.2<br />
Buildings of purpose sub-group 2A (E11.2)<br />
Buildings of purpose sub-group 2B (E11.2)<br />
Dwellings E11.1b, (E11.1)<br />
Flats and maisonettes E2.14b, (E2.14)<br />
Shopping complexes E11.3, (E11.3)<br />
Silencing amplified music (E11.3)<br />
Shutters sealing compartment floors (D3.14)<br />
Smoke alarms compliance with EC Directives B intro 4<br />
Fire doors<br />
Definitions<br />
Fire doors A definitions<br />
Protected door A definitions<br />
Self-closing fire door A definitions<br />
Escape routes E5.19-20, (E5.19-20)<br />
Opening direction E5.18<br />
Smoke control in corridors E5.23<br />
Escape stairs D11.7-9<br />
Fire resistance (D1.3) table 1<br />
Self-closing (D3.14, 4.7, 5.8, 6.7, 11.1-5)<br />
Cavity barriers D6.7<br />
Escape route protection D11.1-5<br />
Openings in compartment walls D3.14<br />
Openings in separating walls D5.8<br />
Openings in sub-compartment walls D4.7<br />
Separating walls between flat or maisonette and protected lobby or protected zone D5.8<br />
Fire loads of compartments D intro 3<br />
Fire mains E10.4-8, (E10.7-8)<br />
Definitions<br />
Dry fire main A definitions<br />
Wet fire mains A definitions<br />
Hospital streets E10.4-5<br />
Shopping malls E10.6<br />
Fire reaction D intro 5, D1.3b, (D1.3)<br />
Internal linings D7.1-4, (D7.1, 7.2, 7.4)<br />
Fire resistance<br />
Ducts of passive stack ventilation systems K4.5<br />
Elements of structure D2.1<br />
Levels of fire safety performance D1.3a, (D1.3)<br />
Fire risk see High risk buildings; Places of special fire risk<br />
Fire spread see Spread of fire; Spread of fire to fuel tanks<br />
Fire tests D intro 8, D1.3, (D1.3)<br />
External cladding systems (D10.1)<br />
Thermoplastic materials (D7.2), (D9.1)<br />
Fire valves, Oil supply pipes F7.3, (F7.3)<br />
Fire-fighting E intro 4, E reg 13(1)(b), E10.1-12, (E10.1-2)<br />
Access E intro 1, E10.1, (E10.1)<br />
Indicator panels in shopping centres (E11.3)<br />
Vehicle access routes E intro 4, (E10.1)<br />
Application of Part E E1<br />
Equipment E intro 1<br />
Manual operation of rolling shutters E10.16<br />
Manual override of automatic opening ventilators (E2.11-12)<br />
Overriding controls for smoke and ventilation systems (D3.6-7)<br />
Structural fire precautions D intro 2<br />
Fire-fighting lifts E10.11, (E10.9, 10.11)<br />
Definition A definitions<br />
Provision E10.4 table<br />
Amdt: September 2001<br />
22
Fire-fighting lobbies E10.9, E10.11a, (E10.4, 10.9), (E10.9, 10.11)<br />
Definition A definitions<br />
Fire-fighting outlets E10.4<br />
Dry fire mains E10.5-6<br />
Fire-fighting shafts E10.9-10, (E10.4, 10.9), (E10.9, 10.11)<br />
Definition A definitions<br />
Enclosure D3.10<br />
Pressure differential control (E10.4, 10.9)<br />
Provision E10.4 table<br />
Wall and ceiling surfaces D7.1<br />
Fire-stops (D3.14, 4.7, 5.8, 6.7, 6.9)<br />
Concealed spaces D6.7, D6.9<br />
Definition A definitions<br />
Junctions between walls and roofs (D3.16, 5.10)<br />
Service openings D3.14, D4.7, D5.8<br />
Sound transmission<br />
Joints between walls and roof (H2.1-3) wall types<br />
Timber frame walls with absorbent curtains (H2.1-3) wall type 4<br />
Fireplace opening areas (F4.5) diagram 2<br />
Flue sizes (F4.5) diagram 1<br />
Fireplace recesses<br />
Gas-fired combustion appliance installations (F6.16)<br />
Oil-fired combustion appliance installations (F5.12)<br />
Solid fuel combustion appliance installations F4.15-16, F4.21, (F4.17-19), (F4.21)<br />
Hearths location within (F4.19)<br />
Fitness of materials B intro, B reg 10<br />
Application of Part B B1<br />
Selection and use of materials and components B2.2, (B2.2)<br />
Fixed ladders see Ladders<br />
Fixed obstructions<br />
Means of escape E5.22<br />
Storage areas E5.21<br />
Fixed plant or machinery, Exempted classes of buildings A schedule 1<br />
Fixed seating<br />
Means of escape E5.22<br />
Pedestrian protective barriers S4.3c<br />
Travel distances E5.5<br />
Wheelchair spaces S intro 7, S reg 32(2), S2.6f, S2.10<br />
Fixtures not requiring warrants A reg 4, A schedule 2<br />
Flanking sound transmission H intro 2<br />
Walls (H2.1-3) wall types 1-2<br />
Flat roofs<br />
Avoiding ventilation of roof voids G intro 5<br />
Definition A definitions<br />
Escape routes<br />
Buildings of purpose groups 2-7 E5.9g<br />
Fire safety performance D11.11<br />
Flats and maisonettes E2.2e<br />
Houses E3.7<br />
Insulation thickness J Appendix A example 3<br />
Resistance to precipitation (G3.1) roof type 1<br />
Flats and maisonettes<br />
Access Q intro 3, Q2.1, Q2.5-10, (Q2.10)<br />
Application of Part E E1.3<br />
Application of Part Q Q1.2<br />
Changing use of elements and sound transmission H1.3<br />
Definitions<br />
Flat A definitions<br />
Maisonette A definitions<br />
External walls past which there is an escape route D11.9<br />
Fire doors in separating walls D5.8<br />
23<br />
Amdt: September 2001
Means of escape E2.1-19<br />
Automatic opening ventilators E2.11-12, (E2.11-12)<br />
Ducted warm air heating E2.24<br />
Fire detection and alarm system (E2.14)<br />
Smoke ventilation of access corridors E10.14<br />
Storey height more than 4.5 m E2.20-23<br />
Non-combustible materials for separating floors D5.6<br />
Non-combustible materials for separating walls D5.7<br />
Unheated parts exempt from Part J J reg 22(2)(b)<br />
Flights see Stairs<br />
Floating layers, Sound insulation (H2.1-3) floor types 2-3<br />
Flood levels of drainage systems (M2.4)<br />
Flood water<br />
Drainage of sites G intro 3, G reg 16(2)(b), G2.2<br />
Reducing damage to buildings G Appendix<br />
Flooring<br />
Combustible material on outer face of chimneys F4.15d<br />
Resistance to impact sound transmission (H2.1-3) floor type 1<br />
Thermal conductivity of materials J Appendix A table A18<br />
Floors<br />
Conservation of fuel and power<br />
Calculation of areas J2.5<br />
Insulation thickness<br />
Ground floors J Appendix A tables A12-14, examples 8-9<br />
Upper floors J Appendix A tables A15-17<br />
Target U-value method J3.5, J Appendix F<br />
Thermal conductivity of materials J Appendix A table A18<br />
U-values<br />
Basement storeys J Appendix C<br />
Floors above unheated spaces J2.3<br />
Ground floors J Appendix C<br />
Carbon emissions calculation method J8.9b<br />
Heat loss method J8.6a, J Appendix H<br />
Definition A definitions<br />
Escape past openings E5.25<br />
Fire safety performance D2.1, (D1.3)<br />
Galleries D11.6<br />
Provision of cavity barriers D6.2, D6.8<br />
Hazards from combustion appliances<br />
Gas-fired F6.16<br />
Oil-fired F5.12<br />
Solid-fuel F4.18<br />
Impact sound transmission H reg 20(1)<br />
Internal transition units (Q2.7)<br />
Openwork and escape stairs E6.6<br />
Resistance to moisture from ground G2.6<br />
Specified constructions (G2.3, 2.5-6)<br />
Sound insulation constructions (H2.1-3) floor types<br />
Walls (H2.1-3) wall types 1-3<br />
Ventilation of sub-floors (G2.3, 2.5-6)<br />
see also Separating floors<br />
Flow control devices, Space heating J11.2b<br />
Flue gases F intro 6<br />
Gas-fired combustion appliance installations F6.14-15<br />
Oil-fired combustion appliance installations F5.8, (F5.8)<br />
Small combustion appliance installations (F3.6)<br />
Flue-pipes F intro 3e<br />
Definition A definitions<br />
Fixtures requiring warrants A schedule 2<br />
Gas-fired combustion appliance installations F6.1, F6.6, F6.9, (F6.6), (F6.9)<br />
Protection from products of combustion F6.11-13, (F6.11), (F6.13)<br />
Relationship to combustible materials F6.14-15<br />
Amdt: September 2001<br />
24
Flues<br />
Incinerators F3.13<br />
Large combustion appliance installations F2.1e<br />
Oil-fired combustion appliance installations F5.1, F5.7-8, (F5.7)<br />
Openings in compartment walls and compartment floors D3.14<br />
Openings in separating walls and separating floors D5.8<br />
Openings in sub-compartment walls D4.7<br />
Penetrations of floors and sound transmission (H2.1-3) floor types<br />
Small combustion appliance installations F3.3<br />
Solid fuel combustion appliance installations F4.1, F4.12-13, (F4.12)<br />
Back-entry appliances F4.6<br />
External fixing F4.9<br />
Separation from combustible materials F4.14<br />
Balanced, Fixtures requiring warrants A schedule 2<br />
Definition A definitions<br />
Gas-fired combustion appliance installations F6.5<br />
Area of flues F6.7, (F6.7)<br />
Intermediate openings F6.8<br />
Outlets F6.10, (F6.10)<br />
Shared flues F6.5, (F6.5)<br />
Liners, Chimneys of small combustion appliance installations F3.5a<br />
Oil-fired combustion appliances installations F5.5<br />
Direction changes F5.10<br />
Outlet position F5.10, (F5.10)<br />
Separating walls and sound transmission (H2.1-3)<br />
Small combustion appliance installations F3.8, (F3.8)<br />
Terminals and guards F3.4, (F3.4)<br />
Solid fuel combustion appliance installations<br />
Protection from combustion products F4.11, (F4.11)<br />
Removal of combustion products F4.4-8, (F4.8)<br />
Flue areas F4.5, (F4.5)<br />
Terminal outlets F4.10, (F4.10)<br />
Separation from combustible materials F4.15-16<br />
Fluorescent lamps see Lamps<br />
Foam systems of fire control (D2.1, 5.1, 5.3-4, 8.1)<br />
Food premises<br />
Distance from dungsteads or farm effluent tanks R3.1c, (R3.1)<br />
Occupancy load factors A schedule 4<br />
Purpose groups A schedule 3<br />
Sanitary facilities (M4.4-5)<br />
Foulwater see Drainage systems; Wastewater<br />
Foundations<br />
Definition A definitions<br />
Structural work (C2.1)<br />
Fuel conservation see Conservation of fuel and power<br />
Fuel oil storage tanks see Liquid fuel storage<br />
Fuels<br />
Small combustion appliances using more than one type F3.2<br />
Solid F reg 14, F4.1<br />
Fusible links, Activating shutters D3.14, (D3.14)<br />
G<br />
Galleries<br />
Definition A definitions<br />
Escape stairs, External walls D11.8-9<br />
Floors<br />
Fire safety performance D11.6<br />
Structural protection D2.1<br />
Means of escape E5.24<br />
Escape stairs E6.6<br />
25<br />
Amdt: September 2001
Gangways S intro 6<br />
Fixed seating E5.22<br />
Floor fixtures E5.22<br />
Steps in sloping gangways S3.28<br />
Storage areas with fixed obstructions E5.21<br />
Gaps<br />
Limiting air infiltration J5.1, J10.1, (J5.1), (J10.1)<br />
Limiting thermal bridging J4.1, J9.1, (J4.1), (J9.1)<br />
Edges of openings J Appendix D<br />
Sound insulation H intro 4, (H2.1-3) wall types<br />
U-value calculations J Appendix B<br />
Garages<br />
Disabled access S2.6g<br />
Purpose groups A schedule 3<br />
Separating walls and separating floors D5.1<br />
U-values of floors above or walls adjoining unheated spaces J2.3<br />
Ventilation of large garages K3.1, (K3.1)<br />
Ventilation of small garages K3.2, (K3.2)<br />
see also Domestic garages<br />
Garden huts<br />
Acceptable roof coverings D9.1<br />
Distance from boundaries D8.1b<br />
Duration of fire protection D2.1 table 1<br />
Exempted classes of buildings A schedule 1<br />
Gas pockets, LPG storage containers F reg 15(2)(b), F7.4<br />
Gas storage see Liquid fuel storage<br />
Gas-fired combustion appliance installations F6, (F6.2-7), (F6.9-11), (F6.13), (F6.16-17)<br />
Energy rating efficiency J Appendix G<br />
Geometric method, Unprotected area calculations (D8.1)<br />
Glazed doors<br />
Avoiding collisions with projections P2.1<br />
Disabled access S2.8c<br />
Dwellings Q3.5<br />
Indicative U-values J Appendix A table A1<br />
Principal entrances S2.4c<br />
Glazed screens, Situations in which hearing aids are necessary N2.2b<br />
Glazing<br />
Collision hazards P intro 2, P reg 27(1)(b), P2.2, (P2.2)<br />
Conservation of fuel and power<br />
Buildings of purpose groups 2-7<br />
Carbon emissions calculation method J8.9a<br />
Elemental method J8.2-4, J Appendix E<br />
Heat loss method J8.5-6, (J8.5), J Appendix H<br />
Dwellings<br />
Conservatories J7.1<br />
Elemental method J3.2-3, J Appendix E<br />
Maximum permitted areas for extensions J2.5d<br />
Methods of compliance J3.1<br />
Target U-value method J3.8-9, J Appendix F<br />
Indicative U-values for windows and rooflights J Appendix A tables A1-3<br />
U-values (J2.1)<br />
Definition A definitions<br />
Plastics D7.1, (D7.1)<br />
Roofs and rooflights (D9.1)<br />
Going see Stairs<br />
Grace periods, Activation of alarms in shops (E11.3)<br />
Grease discharges into drainage systems M2.7, (M2.7)<br />
Amdt: September 2001<br />
26
Greenhouses<br />
Ancillary to dwellings<br />
Acceptable roof coverings D9.1<br />
Exempted classes of buildings A schedule 1<br />
Fire spread D8.1<br />
Definition A definitions<br />
Greywater<br />
Definition A definitions<br />
Discharges to ground M intro 2, M2.8b<br />
Infiltration systems M3.5-6, (M3.5-6)<br />
Grit interceptors M2.6-7, (M2.6-7)<br />
Ground assessment (M3.2), (M3.5)<br />
Ground floors<br />
Junctions with walls (H2.1-3) wall types 1-3<br />
Provision of cavity barriers D6.2<br />
Resistance to moisture from ground (G2.3, 2.5-6)<br />
U-values J Appendix C<br />
Carbon emissions calculation method J8.9b<br />
Heat loss method J8.6a, J Appendix H<br />
Insulation thickness J Appendix A tables A12-14, examples 8-9<br />
Ground hydrants E10.2-3, (E10.2)<br />
Ground storeys see Storeys<br />
Ground water<br />
Drainage of sites G intro 3, G reg 16(2)(a)<br />
Infiltration systems (M3.5)<br />
Gypsum, Thermal conductivity of materials J Appendix A table A18<br />
H<br />
Handrails<br />
Access to buildings S2.3b<br />
Height of pedestrian protective barriers S4.3 table<br />
Measurement of stair width S3.4<br />
Stairs and ramps S3.20-24<br />
Flights of tapered treads S3.15, (S3.15) table<br />
Hangers, Timber floors (H2.1-3) wall types 1-3<br />
Harbours, Exempted classes of buildings A schedule 1<br />
Hardcore G1.5, (G2.3, 2.5-6)<br />
Harmful or dangerous substances<br />
Definition A definitions, G reg 16(4)<br />
Exceptions to exempted classes of buildings A schedule 1<br />
Preparation of sites G intro 2, G reg 16(1)(a), G2.1, G Appendix<br />
Hatches see Access hatches<br />
Hazards P intro, P regs 27-8, P2, P3<br />
Application of Part P P1<br />
see also Accidents; Equipment malfunctions; Explosions<br />
Headroom, Stairs and ramps S3.25<br />
Health centres, Purpose groups A schedule 3<br />
Hearing aid systems N2.2, (N2.2)<br />
Hearing impairments see Disabled people<br />
Hearths F intro 3e<br />
Gas-fired appliances F6.1, F6.16, (F6.16)<br />
Oil-fired appliances F5.1, F5.11-12, (F5.11-12)<br />
Solid fuel appliances F4.17-20, (F4.17-19)<br />
Construction of adjacent parts of buildings F4.18-19, (F4.19)<br />
Superimposed hearths (F4.18) diagram 2<br />
Heat dumping, Combined heat and power systems, Heating system efficiency (J11.1)<br />
Heat exchangers, Hot water service controls (J6.2), (J11.5)<br />
27<br />
Amdt: September 2001
Heat loss<br />
Edges of openings J Appendix D<br />
Method J intro 6, J8.5-6, (J8.5), J Appendix H<br />
Heat pumps, Heating system efficiency (J11.1)<br />
Heating systems see Space heating<br />
Height and depth, Measurement A schedule 5<br />
Helical stairs see Circular stairs<br />
High risk buildings<br />
Compartmentation D2.1 table 2<br />
Single storey buildings D2.1 table 1<br />
see also Places of special fire risk<br />
High-bay storage see Storage buildings; Storage spaces<br />
Horizontal escape in buildings of purpose groups 2-7<br />
Air supported structures E5.27<br />
Circulation in confined spaces E5.21-22<br />
Doors across escape routes E5.19-20, (E5.19-20)<br />
Escape past openings in floors E5.25<br />
Escape routes E5.9-11<br />
Height E5.12<br />
Width E5.13-18<br />
Galleries E5.24<br />
Places of special fire risk E5.26<br />
Smoke control in corridors E5.23, (E5.23)<br />
Travel distance E5.1-8<br />
Hospital streets E8.9-10<br />
Definition A definitions<br />
Dry fire mains E10.5<br />
Entrances to intensive therapy units D4.5<br />
Hospitals<br />
Access for fire-fighting (E10.1)<br />
Automatic fire detection and alarm systems (E11.2)<br />
Cavities above operating theatres D6.2-3<br />
Definition A definitions<br />
Fire safety D intro 7<br />
Fire-fighting facilities E10.4-5<br />
Junctions between compartment walls and external walls D3.17<br />
Junctions between sub-compartment walls and external walls D4.8<br />
Means of escape E intro 6, E8.1-10, (E8.6)<br />
Escape routes E5.9, E8.3-5<br />
Number of exits E4.1 table<br />
Travel distances E5.3b<br />
Separating walls and external walls D5.11<br />
Separating walls and separating floors D5.1d, D5.3<br />
Sub-compartmentation D intro 4, D4.4-5<br />
Hot water<br />
Discharges P intro 2, P reg 27(1)(e), P2.6<br />
Service systems<br />
Commissioning J6.5, J14.1-2, (J14.1-2)<br />
Controls J6.2, J11.5, (J6.2), (J11.5)<br />
Information for occupiers J6.6, J14.2<br />
Insulation of pipes J6.3, J11.6, (J6.3-4), (J11.6)<br />
Storage vessels, Thermal insulation J6.4, J11.7, (J6.3-4), (J11.7)<br />
Unvented storage system malfunctions P intro 2, P reg 28, P3.1 (P3.1)<br />
Application of Part P P1.3<br />
Vessels, Definitions of storage packages and units (P3.1)<br />
Hotels see Buildings of purpose sub-group 2B<br />
Houses<br />
Conservation of fuel and power<br />
SAP energy ratings and carbon indexes J Appendix G<br />
Target U-value method illustrated J Appendix F<br />
Window, door and rooflight areas J Appendix E<br />
Amdt: September 2001<br />
28
Definition A definitions<br />
Means of escape from fire E3.1-3<br />
Purpose sub-group 1B E3.4-7<br />
Roofs of detached houses D9.1 table<br />
Separating walls of non-combustible materials D5.7<br />
see also Dwellings<br />
Humidity sensitive ventilation inlet grilles K4.4a<br />
Hydrants see Ground hydrants<br />
I<br />
Illuminated signs see Signs<br />
Illumination levels, Escape routes E9.1<br />
Impact sound H reg 20, H2.2-3, (H2.1-3) standards, test procedures<br />
Impairments see Disabled people<br />
Imposed loads C2.1<br />
Calculation (C2.1)<br />
Definition A definitions<br />
Incinerators, Small combustion appliance installations F3.13<br />
Indicator panels, Fire-fighting accesses (E11.3)<br />
Industrial buildings<br />
Compartmentation D2.1 table 2<br />
Single storey buildings D2.1 table 1<br />
Occupancy load factors for production areas A schedule 4<br />
Purpose groups A schedule 3<br />
Industrial processes, Insulation against heat loss J11.6-7<br />
Industrial stairs S intro 4, S3.1d, S3.26, (S3.26)<br />
Infiltration limitation J intro 8, J5.1, J10.1, (J5.1), (J10.1)<br />
Infiltration systems M3.5-7, (M3.2), (M3.5-7)<br />
Inflation equipment, Air supported structures E5.27d<br />
Inlet breechings, Dry fire mains (E10.8)<br />
Inner rooms<br />
Buildings of purpose groups 2-7 E5.9f<br />
Definition A definitions<br />
Flats and maisonettes E2.16<br />
Emergency escape windows E2.17<br />
Houses E3.1<br />
Emergency escape windows E3.2<br />
Innovative products and processes (B2.2)<br />
Inspection openings (Flues)<br />
Gas-fired installations F6.8b<br />
Solid fuel installations F4.7c<br />
Institutional buildings see Buildings of purpose group 2<br />
Insulation see Sound insulating materials; Thermal insulation<br />
Integrally bunded tanks, Definition (F7.2c) table<br />
Intensive therapy units<br />
Entrances D4.5<br />
Location of hospital departments D5.3-4<br />
Interior lighting see Lighting<br />
Internal linings<br />
Fire spread D7.1-4, (D7.1, 7.2, 7.4)<br />
Sealing gaps (J5.1)<br />
Sound insulation<br />
Inclusion in calculations (H2.1-3)<br />
Inner leafs of external walls (H2.1-3) wall type 3<br />
Thermal conductivity of materials J Appendix A table A18<br />
Internal transition units (Q2.7)<br />
International standards see <strong>Standards</strong><br />
Interstitial condensation G intro 6, G4.1, (G4.1)<br />
Inverted roofs see Warm deck roofs<br />
Isolating switches N2.1c<br />
29<br />
Amdt: September 2001
J<br />
Jambs, Compensating for additional heat losses J Appendix D<br />
Joints<br />
Factory-made chimneys F3.7c<br />
Sound insulation constructions (H2.1-3) wall types 1-3<br />
Thermal bridging (J2.1), J Appendix B<br />
Joists<br />
Roof insulation thickness J Appendix A tables A4-5, examples 1-2<br />
Sealing around ends built into cavity walls (J5.1)<br />
Thermal bridging effects (J2.1)<br />
Projecting beyond surface of insulation J Appendix B2<br />
Use of hangers for support (H2.1-3) wall types 1-3<br />
Junctions between elements<br />
Cavity barriers D6.8-10<br />
Compartment walls and roofs D3.16, (D3.16, 5.10)<br />
Limiting infiltration (J5.1)<br />
Separating and compartment walls and floors D3.15<br />
Separating walls or floors and external walls D5.9, D5.11<br />
Separating walls or floors and separating walls D5.9<br />
Separating walls and roofs D5.10, (D3.16, 5.10)<br />
Sound insulation (H2.1-3) wall types, floor types<br />
Sub-compartment walls and external walls D4.8<br />
Thermal bridging<br />
Buildings of purpose groups 2-7, J9.1, (J9.1)<br />
Dwellings J4.1, (J4.1)<br />
K<br />
Kerbs<br />
Dropped S2.3c<br />
Raised S3.17b<br />
Kiosks E7.1, E7.4<br />
Kitchens<br />
Definition A definitions<br />
Dwellings Q reg 29(1)(d)<br />
Cookers and activity spaces Q3.3<br />
Socket outlets Q3.9a<br />
Storage Q3.4<br />
Ventilation (K2.1) table<br />
Fire control systems in hospitals D5.3<br />
Occupancy load factors A schedule 4<br />
Passive stack ventilation K4.5<br />
Separation from sleeping accommodation in flats and maisonettes E2.20d<br />
Sub-compartmentation D4.2l<br />
L<br />
Laboratories, Sub-compartmentation D4.2g<br />
Ladders S intro 4, S3.1d, S3.26, (S3.26)<br />
Agricultural buildings S3.1e, S3.27, (S3.27)<br />
Buildings of purpose groups 2-7<br />
Escape routes E5.11, (E5.11)<br />
Vertical escape E6.2, E6.6<br />
Flats and maisonettes, Escape routes E2.4g<br />
Portable, Cleaning windows and rooflights P2.4, (P2.4)<br />
Lamps, Luminous efficacies (J12.1-2), J Appendix J<br />
Land in different occupations, Definition A definitions<br />
Landing valves, Fire mains (E10.7-8)<br />
Amdt: September 2001<br />
30
Landings S3.18-19<br />
Escape stairs D11.8-9<br />
Mattress evacuation (E8.6)<br />
Wheelchair spaces E2.9, E6.7<br />
Headroom S3.25<br />
Passenger lifts (S2.6)<br />
Laundries<br />
Fire control systems in hospitals D5.3<br />
Sub-compartmentation D4.2m<br />
Legionella, Contamination in mechanical ventilation systems K4.10, (K4.10)<br />
Legionnaires’ disease see Legionella<br />
Libraries, Purpose groups A schedule 3<br />
Licensed betting offices, Occupancy load factors A schedule 4<br />
Lift wells, Compartmentation of buildings D3.12<br />
Lifts (S2.6)<br />
Avoiding controls affected by fire D3.13<br />
Escape routes E2.4a, E5.11a<br />
Height of entrance doors to flats and maisonettes Q2.9<br />
Replacements not requiring warrants A schedule 2<br />
Sub-compartmentation of motor rooms D4.2h<br />
see also Fire-fighting lifts<br />
Light fittings with diffusers D7.1, D7.2, (D7.2)<br />
Lighting<br />
Conservation of fuel and power J intro 7, J12.1-3, (J12.1-3), J Appendix J<br />
Dwellings<br />
Controlling switches on stairs Q3.8<br />
Points Q reg 29(2), Q3.7-8<br />
Emergency E9.2, (E9.2)<br />
Definition A definitions<br />
Escape routes E9.1<br />
Flats and maisonettes, Communal areas, Switches Q2.10b, (Q2.10)<br />
Lightweight blocks<br />
Thermal bridging (J2.1), J Appendix B<br />
Thermal conductivity of materials J Appendix A table A18<br />
Limestone, Thermal conductivity of materials J Appendix A table A18<br />
Limited life buildings, Definition A definitions, A reg 5<br />
Limiting infiltration see Infiltration limitation<br />
Lintels, Minimum thermal resistance calculations J Appendix D<br />
Liquid fuel storage<br />
Application of Part F F1<br />
Fuel oil storage tanks F intro 1, F reg 15(1), F7.1-3, (F7.1-3)<br />
LPG cylinders not requiring warrants A schedule 2<br />
LPG tanks F intro 1, F reg 15(2), F7.4-5, (F7.4-5)<br />
Liquids retention, Hazardous materials D3.9<br />
Live fuel-effect gas appliances<br />
Air for combustion (F6.3)<br />
Relationship to combustible materials (F6.16)<br />
Removal of products of combustion (F6.7)<br />
Livestock accommodation<br />
Ancillary to dwellings<br />
Acceptable roof coverings D9.1<br />
Duration of fire protection D2.1 table 1<br />
Exempted classes of buildings A schedule 1<br />
Surfaces of unprotected zones D7.1<br />
Loading bays<br />
Conservation of fuel and power J Appendix H<br />
Plastics coverings (D9.1)<br />
Protective barriers not required S4.1b<br />
31<br />
Amdt: September 2001
Loads C intro 3, C reg 11(1), C2.1<br />
Calculation (C2.1)<br />
Definitions<br />
Dead load A definitions<br />
Imposed load A definitions<br />
Wind load A definitions<br />
Lobbies<br />
Entrances to intensive therapy units D4.5<br />
Internal lobbies accessible to disabled S2.9<br />
Protected<br />
Buildings of purpose groups 2-7, Vertical escape E6.2, E6.10, E6.13-14<br />
Definition A definitions<br />
Fire doors in separating walls D5.8<br />
Flats and maisonettes E2.11, (E2.11-12)<br />
Escape stairs in different purpose groups E2.14<br />
Hospitals, Escape stairs E8.7<br />
Non-combustible materials D11.12<br />
Places of special fire risk E5.26<br />
Within protected zones D11.2<br />
see also Entrance lobbies; Fire-fighting lobbies<br />
Lockable doors<br />
Across escape routes (E5.19-20)<br />
Buildings of purpose groups 2-5 E5.20<br />
Buildings of purpose groups 2-7 E5.19<br />
Flats and maisonettes E2.5<br />
Separation of escape stairs D11.5<br />
Log-books, Conservation of fuel and power (J14.2)<br />
Low rise buildings see Single storey buildings; Small buildings<br />
Low-emissivity glazing, Indicative U-values for windows and rooflights J Appendix A tables A1-3<br />
LPG storage see Liquid fuel storage<br />
M<br />
Mains supply see Electrical installations<br />
Maintenance<br />
Access to storeys for plant, Escape stairs from topmost storeys E6.2<br />
Buildings not frequented by people A schedule 1<br />
Drainage systems discharging to wastewater treatment plant (M3.4)<br />
Fitness of materials B intro 1<br />
Flues and gas-fired installations F6.8b<br />
Flues and solid fuel appliances F4.8, (F4.8)<br />
Information for users on services systems J6.6, J14.2, (J14.2)<br />
Requirements affecting fitness for purpose B2.2<br />
Maisonettes see Flats and maisonettes<br />
Malls<br />
Automatic fire control systems (D2.1, 5.1, 5.3-4, 8.1)<br />
Dry fire mains E10.6<br />
Fire control rooms E10.12<br />
Fire detection and alarm systems E11.3, (E11.3)<br />
Fire spread on wall and ceiling surfaces D7.1 table<br />
Means of escape E7.1-8<br />
Smoke and heat exhaust ventilation E6.9e<br />
Travel distances E5.2<br />
Occupancy load factors A schedule 4<br />
Sanitary facilities (M4.5)<br />
Separating walls and separating floors D5.1b, D5.5<br />
Smoke and heat exhaust ventilation D3.7, (D3.6-7)<br />
Manual controls, Windows and rooflights P reg 27(1)(f), P2.7<br />
Amdt: September 2001<br />
32
Manual operation<br />
Automatic opening ventilators (E2.11-12)<br />
Rolling shutters E10.16<br />
Manual override, Smoke and ventilation systems (D3.6-7)<br />
Manufacturing procedures, Selection and use of materials and components (B2.2)<br />
Mark of conformity see CE mark of conformity<br />
Masonry<br />
Joints, Thermal bridging (J2.1), J Appendix B<br />
Mass of leaf (H2.1-3)<br />
Resistance to precipitation (G3.1) wall types<br />
Sound insulation constructions (H2.1-3) wall types<br />
Structural work (C2.1)<br />
Disproportionate collapse (C3.1)<br />
Thermal insulation thickness J Appendix A examples 4-6<br />
Masonry units<br />
Constructions for sound insulation (H2.1-3) wall types 1-3<br />
Density and sound insulation (H2.1-3)<br />
Thermal conductivity J Appendix A table A18<br />
Materials<br />
Claddings (G3.1) wall type 3<br />
Designations for roof coverings (D9.1)<br />
Fire reaction (D1.3)<br />
Flue-pipes (F4.12), (F6.9), (F6.11)<br />
Non-combustible D2.3, (D1.3) table 3<br />
Chimney casings F3.7a<br />
Concealed spaces D6.2<br />
Core of sandwich panels D7.3<br />
Definition A definitions<br />
Escape stairs D11.12<br />
External walls<br />
More than 18 m above ground D10.2<br />
Near to boundaries D8.2<br />
Flue-pipe casings F6.12<br />
Separating floors D5.6<br />
Separating walls D5.7<br />
Supporting fire-stopping materials (D3.14, 4.7, 5.8, 6.7, 6.9)<br />
Properties and safety of structure C intro 1)<br />
Providing firm surface for disabled (S2.3)<br />
Dwellings (Q2.4)<br />
Sound insulating (H2.1-3) wall types, floor types<br />
Thermal conductivity J2.1, (J2.1), J Appendix A table A18<br />
see also Fitness of materials<br />
Means of access see Access<br />
Means of escape from fire E intro, E reg 13<br />
Application of Part E E1<br />
Buildings of purpose groups 2-7<br />
Exits and escape routes E4.1-5<br />
Horizontal escape E5.1-27<br />
Vertical escape E6.1-14<br />
Emergency escape windows E2.17, E3.2, (E2.17, 3.2)<br />
Enclosed shopping centres E7.1-8<br />
Flats and maisonettes E2.1-19, (E2.11-12), (E2.14)<br />
More than 4.5 m in height E2.20-23<br />
Hospitals E8.1-10, (E8.6)<br />
Houses E3.1-7<br />
Lighting E9.1-2<br />
Places of special fire risk E4.4<br />
Revolving, sliding or automatic doors (E2.4, 5.11)<br />
Smoke ventilation of escape routes E10.13-14<br />
33<br />
Amdt: September 2001
Measurement<br />
Clear opening width of doorways E5.15<br />
Operational energy consumption J Appendix K1.3.1<br />
Rules A schedule 5<br />
Sound insulation tests (H2.1-3) test procedures<br />
Stairs<br />
Rise and going S3.2<br />
Width S3.4<br />
Thermal conductivity (J2.1)<br />
Thermal transmittance (J2.1)<br />
Travel distances<br />
Buildings of purpose groups 2-7 E5.2-6<br />
Flats and maisonettes E2.15<br />
Mechanical ventilation see Ventilation<br />
Meeting rooms, Occupancy load factors A schedule 4<br />
Metals<br />
Flat roofs, Specified constructions (G3.1) roof type 1<br />
Lintels and minimum thermal resistance J Appendix D<br />
Pitched roofs, Specified constructions (G3.1) roof type 2<br />
Sheet metal walls and roofs J Appendix B4<br />
Structural work (C2.1)b<br />
Disproportionate collapse (C3.1)<br />
Window frames<br />
Conservation of fuel and power<br />
Buildings of purpose groups 2-7, Elemental method J8.3<br />
Dwellings<br />
Elemental method J3.2 table 1<br />
Methods of compliance J3.1<br />
Indicative U-values J Appendix A tables A2-3<br />
Mineral fibres<br />
Absorbent blankets (H2.1-3) floor type 3<br />
Absorbent curtains (H2.1-3) wall type 4<br />
Resilient layers (H2.1-3) floor types 2-3<br />
Resilient strips (H2.1-3) floor type 3<br />
Mineral wool, Thermal conductivity of materials J Appendix A table A18<br />
Misuse, Disproportionate collapse (C3.1)<br />
Mixed occupations, Separating walls and separating floors D5.1<br />
Mixed use<br />
Escape stairs serving flats and maisonettes and other accommodation E2.14<br />
Minimum number of sanitary facilities (M4.5)<br />
Separating walls and separating floors D5.1c<br />
Mobile homes, Exempted classes of buildings A schedule 1<br />
Moisture resistance G reg 17, G2.5-6<br />
From ground G2.5-6, (G2.3, 2.5-6)<br />
Precipitation G3.1, (G3.1)<br />
Mortar joints<br />
Sound insulation constructions (H2.1-3) wall types 1-3<br />
Thermal bridging (J2.1), J Appendix B<br />
Thermal conductivity of mortar J Appendix A table A18<br />
Motor vehicle repair, Purpose groups A schedule 3<br />
Mould see Condensation<br />
Mound filter systems (M3.6)<br />
Movement within buildings see Access<br />
Multi-storey buildings<br />
Compartments D3.2<br />
Concealed spaces D6.5<br />
Fire safety performance D2.1 table 2<br />
Fire-fighting facilities E intro 4, E10.4 table<br />
Insulation within cavities of external walls D10.2<br />
Amdt: September 2001<br />
34
Means of escape<br />
Buildings of purpose groups 2-7 E6.14<br />
Flats and maisonettes E2.20-24<br />
Hospitals E8.1<br />
Houses E3.1, E3.4-7<br />
see also Storeys<br />
Museums<br />
Occupancy load factors A schedule 4<br />
Purpose groups A schedule 3<br />
N<br />
National Application Document for Eurocodes C intro 4<br />
National standards see British <strong>Standards</strong>; <strong>Standards</strong><br />
Natural air changes see Air changes<br />
Natural draught open-flued gas-fired appliances, Flue terminals (F6.10) tables 1-2<br />
Natural ventilation see Ventilation<br />
Net output ratings, Definition A definitions<br />
Newels see Stairs<br />
Noise see Sound transmission<br />
Non-combustible materials D2.3, (D1.3) table 3<br />
Chimney casings F3.7a<br />
Concealed spaces D6.2<br />
Core of sandwich panels D7.3<br />
Definition A definitions<br />
Escape stairs D11.12<br />
External walls<br />
More than 18 m above ground D10.2<br />
Near to boundaries D8.2<br />
Flue-pipe casings F6.12<br />
Separating floors D5.6<br />
Separating walls D5.7<br />
Used with fire-stopping materials (D3.14, 4.7, 5.8, 6.7, 6.9)<br />
Non-return shutters see Shutters<br />
Nosings see Stairs<br />
Notices served under section 11<br />
Access and facilities for dwellings Q reg 29(3)<br />
Access to and movement within buildings S reg 32(4)<br />
Means of escape from fire E reg 13(2)<br />
Resistance to transmission of sound H reg 21<br />
Sanitary facilities M reg 25(3)<br />
Storage of waste R reg 30(3)<br />
Structural fire precautions D reg 12(2)<br />
Notified bodies, Definition A definitions<br />
Notional boundaries D8.3<br />
Nuclear installations, Controlled by other legislation A schedule 1<br />
O<br />
Occupancy capacity A reg 7<br />
Air supported structures E5.27<br />
Capacity of escape stairs E6.4<br />
Circulation areas in buildings of purpose group 4 E5.22<br />
Communal rooms E2.7<br />
Definition A definitions<br />
Exits from shops E7.2-4<br />
Exits to unprotected zones E4.3<br />
Fire doors across escape routes E5.18, E5.20<br />
Number of escape routes E intro 2<br />
Number of exits E4.1<br />
Travel distances E5.3<br />
Width of escape routes E5.13-14<br />
Shopping centres with malls E7.2-7<br />
35<br />
Amdt: September 2001
Occupancy hours<br />
Air conditioning and ventilation plant operation J Appendix K<br />
Artificial lighting J12.3, (J12.3)<br />
Occupancy load factors A reg 7(1)(a), A schedule 4<br />
Occupations<br />
Definitions<br />
Different occupation A definitions<br />
Land in different occupation A definitions<br />
Two buildings on land in same occupation D8.3<br />
see also Mixed occupations; Mixed use<br />
Occupiers<br />
Definition A definitions<br />
Log-books J14.2, (J14.2)<br />
Office buildings<br />
Compartmentation D2.1 table 2<br />
Single storey buildings D2.1 table 1<br />
Conservation of fuel and power<br />
Energy efficiency (J13.1), J Appendix K<br />
Heat loss method J Appendix H<br />
Purpose groups A schedule 3<br />
Offices<br />
Dwellings above D5.6<br />
Escape stair protected zones E6.8<br />
Occupancy load factors A schedule 4<br />
Separation from escape stairs D11.5<br />
Oil discharges into drainage systems M2.7, (M2.7)<br />
Oil storage see Liquid fuel storage<br />
Oil-fired combustion appliance installations F5, (F5.2-4), (F5.7-8), (F5.10-13)<br />
Open access balconies<br />
Downstand from soffit E2.13<br />
Protected lobbies E2.11<br />
Smoke ventilation E10.14<br />
Open fires, Minimum area of flues (F4.5)<br />
Open spaces see Public open spaces<br />
Open-flued combustion appliances<br />
Air for combustion or cooling F3.11, (F3.11)<br />
Fanned draught (F6.10) table 1<br />
Natural draught (F6.10) tables 1-2<br />
Ventilation of dwellings (K2.1) table<br />
Openings<br />
Cavity barriers D6.7, (D3.14, 4.7, 5.8, 6.7)<br />
Compartment walls and compartment floors D3.14, (D3.14, 4.7, 5.8, 6.7)<br />
Chimneys of small combustion appliance installations F3.7a<br />
Flue-pipes of gas-fired installations F6.12<br />
Manual operation of rolling shutters E10.16<br />
Conservation of fuel and power<br />
Buildings of purpose groups 2-7<br />
Carbon emissions calculation method J8.9a<br />
Elemental method J8.2-4, J Appendix E<br />
Heat loss method J8.5-6, (J8.5), J Appendix H<br />
Thermal bridging J9.1, (J9.1)<br />
Calculations of areas J2.5e<br />
Dwellings<br />
Elemental method J3.2-3, J Appendix E<br />
Limiting infiltration (J5.1)<br />
Methods of compliance J3.1<br />
Target U-value method J3.9, J Appendix F<br />
Thermal bridging J4.1, (J4.1)<br />
Indicative U-values J Appendix A tables A1-3<br />
Thermal bridging at edges of openings, J Appendix D<br />
Doors from hospital street to adjoining compartment E8.10<br />
Escape route protection D11.1-5, D11.7-8<br />
Amdt: September 2001<br />
36
Escape routes<br />
Doorways E5.15<br />
Headroom E2.3, E5.12<br />
Past openings in floors E5.25<br />
Smoke control in corridors E5.23<br />
Smoke ventilation E10.13<br />
Travel distances E5.3-4<br />
Fire safety performance of suspended ceilings (D1.3)<br />
Separating walls and separating floors D5.8<br />
Separation from flue outlets<br />
Gas-fired installations (F6.10)<br />
Oil-fired installations (F5.10)<br />
Sound transmission<br />
External walls and floors (H2.1-3) floor type 1<br />
Separating walls (H2.1-3)<br />
Sub-compartments D4.7<br />
Unprotected areas D8.1<br />
Ventilation of large garages (K3.1)<br />
see also Services<br />
Operating theatres<br />
Cavity barriers D6.2, D6.3<br />
Location of hospital departments D5.3-4<br />
Optimising controls, Space heating J11.3<br />
Organic matter, Preparation of sites G intro 2, G reg 16(1)(c), G2.3<br />
Orientation, Dwellings J3.9, J Appendix F<br />
Outdoor signs see Signs<br />
Outfalls, Discharges from drainage systems M2.9c, (M2.9)<br />
Outlets, Private wastewater treatment plant M3.2, (M3.2)<br />
Over-roof insulation see Thermal insulation<br />
Overcladding, Requirements for cavity barriers D6.2, D6.8<br />
Overcurrents see Electrical installations<br />
P<br />
Paint spray booths D3.8, (D3.8)<br />
Panels<br />
Rainscreen, Ventilated voids D6.5<br />
Solid masonry between (H2.1-3) wall type 3<br />
Parking garages see Garages<br />
Parking spaces see Car parking; Vehicle parking<br />
Partial cavity fill see Cavity fill (Partial)<br />
Particleboard see Wood based boards<br />
Partitions, Sound insulation constructions (H2.1-3) wall types<br />
Passenger conveyors<br />
Definition A definitions<br />
Emergency stopping mechanisms P intro 3, P reg 27(1)(d), P2.5, (P2.5)<br />
Escape routes E2.4b, E5.11b<br />
Passenger lifts see Lifts<br />
Passenger shelters, Exempted classes of buildings A schedule 1<br />
Passive stack ventilation K4.3-5, (K4.3)<br />
Dwellings K2.1c, (K2.1) table<br />
Pathology departments, Fire control systems D5.4e<br />
Paths, Access to dwellings (Q2.4)<br />
Paving materials<br />
Access to buildings (S2.3)<br />
Access to dwellings (Q2.4)<br />
Peak load effects C intro 3<br />
Peat see Fuels<br />
Pedestrian protective barriers see Protective barriers<br />
Pedestrian ramps see Ramps<br />
Pends D5.6<br />
Penetration by services see Services<br />
Percolation tests (M3.2), (M3.5-6)<br />
37<br />
Amdt: September 2001
Performance standards<br />
Fire safety D1.3, (D1.3)<br />
Sound insulation (H2.1-3) standards<br />
Period of validity of warrants A intro 4<br />
Periodic renewal, Practicable replacement B2.2<br />
Periods of fire resistance see Fire resistance<br />
Permanent ventilation see Ventilation<br />
Permanent ventilators see Ventilators<br />
Permissible areas see Areas<br />
Pharmacy departments, Fire control systems D5.4f<br />
Phenolic foam boards, Thermal conductivity of materials J Appendix A table A18<br />
Physical impairments see Disabled people<br />
Piped infiltration systems (M3.6)<br />
Pipelines, Exempted classes of buildings A schedule 1<br />
Pipes<br />
Connections for ground hydrants E10.3<br />
Floor penetrations and sound transmission (H2.1-3) floor types<br />
Outlets from hot water storage systems P intro 2, (P3.1)<br />
Separating walls and sound transmission (H2.1-3)<br />
Service openings in cavity barriers D6.7c<br />
Service openings in walls and floors (D3.14, 4.7, 5.8, 6.7)<br />
Compartment walls and floors D3.14d<br />
Separating walls and floors D5.8d<br />
Sub-compartment walls D4.7c<br />
Thermal insulation J6.3, J11.6, (J6.3-4), (J11.6)<br />
Wastewater and surface water drainage M intro 2, (M2.4)<br />
see also Flue-pipes<br />
Pitch see Stairs<br />
Pitched roofs<br />
Insulation thickness J Appendix A examples 1-2<br />
Resistance to precipitation (G3.1) roof type 2<br />
Slope and calculation of storeys C reg 11(3)<br />
Wall junctions (D3.16, 5.10)<br />
Places of safety E intro 2-3<br />
Definition A definitions<br />
Places of special fire risk D3.8-9<br />
Definition A definitions<br />
Escape routes<br />
Independence E4.4<br />
Inner rooms E5.9f<br />
Separation by protected lobbies E5.26<br />
Location of large combustion appliance installations F intro 8<br />
Smoke outlets from basement storeys (E10.15)<br />
Places of worship, Purpose groups A schedule 3<br />
Plant<br />
Log books (J14.2)<br />
Top storey location, Width of escape stairs E6.2<br />
Plant rooms<br />
Escape routes<br />
Flats and maisonettes E2.1c<br />
Rooftop E5.9g<br />
Plaster<br />
Inclusion in sound insulation calculations (H2.1-3)<br />
Thermal conductivity of materials J Appendix A table A18<br />
Plasterboard<br />
Solid masonry between panels (H2.1-3) wall type 3<br />
Thermal conductivity of materials J Appendix A table A18<br />
Plastics<br />
Roof coverings and rooflights (D9.1)<br />
Windows and internal glazing D7.1, (D7.1)<br />
see also Thermoplastic materials<br />
Platform floors, Sound insulation (H2.1-3) floor type 3<br />
Amdt: September 2001<br />
38
Platt, Accessible entrances Q2.6, (Q2.7)<br />
Polycarbonate sheet<br />
Roof coverings or rooflights (D9.1)<br />
Thermoplastic products (D7.2), (D9.1)<br />
Windows and internal glazing (D7.1)<br />
Polyurethane boards, Thermal conductivity of materials J Appendix A table A18<br />
Porches<br />
Buildings attached to dwellings exemptions A schedule 1<br />
Definition A definitions<br />
Duration of fire protection D2.1 table 1<br />
Portable ladders see Ladders<br />
Portal frames, Fire safety performance (D1.3)<br />
Powder systems of fire control (D2.1, 5.1, 5.3-4, 8.1)<br />
Power supply, Smoke and heat ventilation systems (D3.6-7)<br />
Powered lifting platforms (S2.7)<br />
Precipitation resistance G reg 17(1)(b), G3.1, (G3.1)<br />
Presence detectors, Lighting controls (J12.3), J Appendix J<br />
Pressure jet burners, Removal of products of combustion from oil-fired appliances F5.5, F5.9<br />
Pressurisation, Corridors E5.23, (E5.23)<br />
Prestressed concrete structural work (C2.1)<br />
Disproportionate collapse (C3.1)<br />
Principal entrance storeys<br />
Buildings of purpose groups 2-7 S2.6<br />
Dwellings Q intro 4, Q2.12<br />
Principal entrances see Entrances<br />
Private stairs see Stairs<br />
Products see Construction Products Directive; Fitness of materials<br />
Projecting joists, U-values of structures J Appendix B2<br />
Projections, Collisions P intro 2, P reg 27(1)(a), P2.1<br />
Proscenium openings D11.13, (D11.13)<br />
Protected circuits<br />
Definition A definitions<br />
Lighting escape routes E9.1<br />
Smoke alarms (E11.1)<br />
Protected doors, Definition A definitions<br />
Protected enclosures<br />
Definition A definitions<br />
Fire safety performance D11.3<br />
Flats and maisonettes E2.11, E2.19<br />
More than 5 m in height E2.20-21, E2.23a<br />
Houses of purpose sub-group 1B E3.4, E3.6<br />
Protected lobbies<br />
Buildings of purpose groups 2-7, Vertical escape E6.2, E6.10, E6.13-14<br />
Definition A definitions<br />
Flats and maisonettes D5.8, E2.11, (E2.11-12)<br />
Separation of escape stairs in different purpose groups E2.14<br />
Hospitals, Escape stairs E8.7<br />
Non-combustible materials D11.12<br />
Places of special fire risk E5.26<br />
Within protected zones D11.2<br />
Protected zones E intro 2<br />
Buildings of purpose groups 2-7<br />
Escape routes E4.3-4<br />
Horizontal escape E5.9, E5.24, E5.26<br />
Vertical escape E6.2, E6.6-14<br />
Calculation of unprotected areas (D8.1)<br />
Definition A definitions<br />
Fire safety performance of enclosing structure D11.1<br />
Flats and maisonettes E2.2<br />
Escape stairs E2.8-11<br />
Flats or maisonettes, Separating walls and floors D5.8<br />
39<br />
Amdt: September 2001
Hospitals<br />
Escape stairs E8.7<br />
Hospital streets E8.9a<br />
Separating walls and floors D5.1d<br />
Lighting E9.1-2<br />
Refuges for wheelchair users E intro 3c<br />
Wall dividing protected lobby from rest of protected zone D11.2<br />
Protective barriers S intro 3, S reg 32(3)<br />
Cleaning windows and rooflights (P2.3)<br />
Pedestrians S4.1-3, (S4.3)<br />
Vehicles S4.4-5, (S4.5)<br />
Public houses<br />
Artificial lighting J Appendix J<br />
Purpose groups A schedule 3<br />
Sanitary facilities (M4.5)<br />
Public open spaces, Definition A definitions<br />
Public roads see Roads<br />
Public sewers see Sewers<br />
Public toilets, Purpose groups A schedule 3<br />
Publications, References A references<br />
Pugging see Deafening<br />
Pumping appliances<br />
Alternative sources of water (E10.2)<br />
Dry fire mains E10.8<br />
Wet fire mains E10.7<br />
Purpose groups<br />
Classification A reg 6, A schedule 3<br />
Definition A definitions<br />
PVC<br />
Thermoplastic products (D7.2), (D9.1)<br />
Windows and internal glazing (D7.1)<br />
Q<br />
Queuing areas, Occupancy load factors A schedule 4<br />
Quick response sprinklers see Sprinkler systems<br />
R<br />
Racking, Fixed obstructions and means of escape E5.21<br />
Radiator valves see Thermostats<br />
Radiators, Width of accessible corridors (Q2.11)<br />
Radon protection measures (G2.1), G Appendix<br />
Rafters, Insulation between and over J Appendix A tables A4-5, example 1<br />
Railway stations, Purpose groups A schedule 3<br />
Rainscreen panels D6.5<br />
Rainwater see Surface water<br />
Raised kerbs see Kerbs<br />
Ramps S intro 3, S3.16-17<br />
Access between storeys of dwellings Q2.13<br />
Access to dwellings (Q2.4)<br />
Disabled access S2.7a<br />
Handrails S3.20-24<br />
Headroom S3.25<br />
Landings S3.18-19<br />
Reasonably practicable, Definition A definitions<br />
Reception rooms<br />
Escape stair protected zones E6.8<br />
Separation from escape stairs D11.5<br />
Record stores<br />
Hospitals D5.4d<br />
Sub-compartmentation D4.2<br />
Recycling see Waste management<br />
Reed beds, Infiltration systems (M3.6)<br />
Amdt: September 2001<br />
40
Refrigeration plant, Conservation of fuel and power J13.1, J Appendix K<br />
Refuges for disabled people E intro 3c, E2.9, E6.7<br />
Relevant standards<br />
Compliance A reg 9<br />
Definition A definitions<br />
Relief air openings, Gas-fired installations F6.8a<br />
Remote control of lighting (J12.3)<br />
Removal of contaminants G Appendix<br />
Renders<br />
Inclusion in sound insulation calculations (H2.1-3)<br />
Masonry walls and resistance to precipitation (G3.1)<br />
Thermal conductivity of materials J Appendix A table A18<br />
Replacement practicability B2.2<br />
Replacements of fixtures or appliances not requiring warrants A schedule 2<br />
Rescue see Fire-fighting<br />
Residential accommodation see Buildings of purpose group 2; Dwellings<br />
Resilient materials (H2.1-3) floor types 1-3<br />
Resistance to moisture see Moisture resistance<br />
Restaurants<br />
Disabled access S2.6h<br />
Occupancy load factors A schedule 4<br />
Purpose groups A schedule 3<br />
Sanitary facilities (M4.4-5)<br />
Retailing see Buildings of purpose group 4; Shopping complexes; Shops<br />
Revolving doors S2.4d<br />
Escape routes (E2.4, 5.11)<br />
Buildings of purpose groups 2-7 E5.11e<br />
Flats and maisonettes E2.4e<br />
Ribbed floors, Sound insulation (H2.1-3) floor type 3<br />
Rise see Stairs<br />
Risers see Stairs<br />
Risks see Accidents; Equipment malfunctions; Explosions; Hazards<br />
River flooding see Flood water<br />
Roads<br />
Access to dwellings Q intro 1, Q reg 29(1)(a), Q2.1, (Q2.1)<br />
Definition of public road A definitions<br />
Roof access hatches see Access hatches<br />
Roof coverings<br />
Fire precautions D9.1, (D9.1)<br />
Junctions between walls and roofs (D3.16, 5.10)<br />
Flue terminal outlets (F4.10) diagram 2<br />
Insulation thickness J Appendix A table A7, examples 1-3<br />
Resistance to precipitation (G3.1) roof types<br />
Thermal conductivity of materials J Appendix A table A18<br />
Roof space<br />
Cavity barriers D6.1, D6.3, D6.10<br />
Changes in wall construction (H2.1-3) test procedures<br />
Conservation of fuel and power J3.2, J Appendix A table A7 examples 1-2<br />
Definition A definitions<br />
Dwellings and integral or attached garages D5.2<br />
Factory-made chimneys F3.7b, (F3.7)<br />
Insulation of passive stack ventilation K4.4b<br />
Junctions with walls (H2.1-3) wall types 1-3<br />
Ventilation in flat roofs G intro 5<br />
Rooflights<br />
Access to manual controls P reg 27(1)(f), P2.7<br />
Cleaning P reg 27(1)(c), P2.3-4, (P2.3-4)<br />
Conservation of fuel and power<br />
Buildings of purpose groups 2-7<br />
Carbon emissions calculation method J8.9a<br />
Elemental method J8.2-4, J Appendix E<br />
Heat loss method J8.5-6, (J8.5)<br />
41<br />
Amdt: September 2001
Roofs<br />
Dwellings<br />
Draught seals (J5.1)<br />
Elemental method J3.2-3, J Appendix E<br />
Methods of compliance J3.1<br />
Fire precautions D9.1, (D9.1)<br />
Thermoplastic materials D7.1, D7.2, (D7.2), (D9.1)<br />
Indicative U-values J Appendix A tables A1-3<br />
Access P intro 2, P reg 27(1)(g), P2.8, (P2.8)<br />
Buildings of sub-purpose group 2A with lower roof abutting external wall D10.3<br />
Condensation prevention G intro 5<br />
Definition A definitions<br />
Escape routes<br />
Buildings of purpose groups 2-7 E5.9g<br />
Fire safety performance D11.11<br />
Flats and maisonettes E2.2e<br />
Houses E3.7<br />
Fire resistance periods (D1.3) table 1<br />
Fire spread from adjoining buildings D9.1, (D9.1)<br />
Impact sound transmission H intro 2, H reg 20(2), H1.4<br />
Junctions with compartment walls D3.16, (D3.16, 5.10)<br />
Junctions with separating walls D5.10, (D3.16, 5.10)<br />
Junctions with walls, Sound insulation constructions (H2.1-3) wall types<br />
Resistance to precipitation (G3.1)<br />
Slope and number of storeys C reg 11(3)<br />
Thermal conductivity of materials J Appendix A table A18<br />
Thermal insulation thickness J Appendix A tables A4-7, examples 1-3<br />
Treated as rooms for purpose of Part E E1.4<br />
Two buildings on land in same occupation D8.3b<br />
Ventilators (D3.6-7)<br />
Room thermostats<br />
Central heating controls J6.1a, J11.3a, (J6.2), (J11.5)<br />
Ducted warm air heating E2.24e<br />
Room-sealed appliances<br />
Definition A definitions<br />
Gas-fired (F6.10)<br />
Oil-fired F5.3, F5.6<br />
Rooms, Definition A definitions<br />
Run-off see Surface water<br />
S<br />
Safe-life structures (C2.1)<br />
Safety controls see Equipment malfunctions<br />
Safety curtains D11.13, (D11.13)<br />
Escape from stage and auditorium E4.5<br />
Safety devices, Unvented hot water storage systems P intro 2, P reg 28(1), (P3.1)<br />
Safety factors C intro 2<br />
Sand, Deafening (H2.1-3) floor type 3<br />
Sandstone, Thermal conductivity of materials J Appendix A table A18<br />
Sandwich panels D7.3-4, (D7.4)<br />
Definition A definitions<br />
Sanitary accommodation<br />
Buildings ancillary to dwellings exceptions A schedule 1<br />
Buildings other than dwellings M4.6-9, (M4.4-5)<br />
Bedrooms M4.8, (M4.8)<br />
Changing cubicles M4.7, (M4.7)<br />
Watercloset cubicles M4.6, (M4.6)<br />
Definition A definitions<br />
General requirements for toilets M4.10<br />
Protected enclosures D11.3<br />
see also Bathrooms; Shower-rooms; Toilets; Washrooms<br />
Amdt: September 2001<br />
42
Sanitary facilities M intro 5, M reg 25<br />
Activity space M4.3<br />
Application of Part M M1<br />
Buildings other than dwellings M4.4-5, (M4.4-5)<br />
Minimum facilities for staff M4.4, (M4.4)<br />
Definition A definitions<br />
Disabled people M intro 6<br />
Buildings other than dwellings (M4.4-5)<br />
Dwellings Q intro 5<br />
Accessibility M intro 6, M4.3<br />
Dwellings M4.1-3, (M4.1-2)<br />
Minimum number (M4.1)<br />
Fixtures not requiring warrants A schedule 2<br />
General requirements for toilets M4.10<br />
SAP energy ratings J intro 4, J Appendix G<br />
see also Seasonal efficiency of domestic boilers<br />
Sarking, Combustible material on outer face of chimneys F4.15d<br />
Schools, Sanitary facilities M intro 1, M reg 25(2), (M4.5)<br />
<strong>Scottish</strong> Environment Protection Agency M intro 4, (M2.9), (M3.2), (M3.5-6)<br />
Screeds<br />
Sound insulation constructions (H2.1-3) floor types 1-2<br />
Thermal conductivity of materials J Appendix A table A18<br />
Sealing contaminated land G Appendix<br />
Sealing devices and systems<br />
Fire-stopping (D3.14, 4.7, 5.8, 6.7, 6.9)<br />
Service openings (D3.14, 4.7, 5.8, 6.7)<br />
Seals<br />
Lightweight aggregate blocks (H2.1-3) wall type 3<br />
Limiting air infiltration (J5.1)<br />
Seasonal efficiency of domestic boilers<br />
Conservation of fuel and power<br />
Elemental method J3.2 table 2<br />
Methods of compliance J3.1<br />
Target U-value method J3.5-6, J Appendix F<br />
Seating see Fixed seating<br />
Secondary glazing see Glazing<br />
Selection and use of materials and components B2<br />
Practical replacement B2.2<br />
Self-closing fire doors, Definition A definitions<br />
Separating floors<br />
Chimneys of small combustion appliance installations F3.7a<br />
Definition A definitions<br />
Fire resistance (D1.3) table 1<br />
Flue-pipes of gas-fired installations F6.12<br />
Ignored in calculating U-values J2.4<br />
Junctions with walls D5.9<br />
Non-combustible materials D5.6<br />
Openings D5.8<br />
Provision D5.1-5<br />
Sound transmission H intro 2, H1.3, (H2.1-3) wall types, floor types<br />
Separating walls<br />
Chimneys of small combustion appliance installations F3.7a<br />
Definition A definitions<br />
Fire resistance (D1.3) table 1<br />
Flue-pipes of gas-fired installations F6.12<br />
Garages ancillary to dwellings D5.2b, D5.7c<br />
Ignored in calculating U-values J2.4<br />
Junctions with roofs D5.10, (D3.16, 5.10)<br />
Junctions with walls and floors D5.9, D5.11<br />
Non-combustible materials D5.7<br />
Openings D5.8<br />
Provision D5.1-5<br />
Sound transmission intro 2, H1.3, (H2.1-3) wall types, floor types<br />
43<br />
Amdt: September 2001
Separation distances<br />
Dungsteads or farm effluent tanks from dwellings or food premises R3.1c, (R3.1)<br />
Fire spread D intro 6<br />
Buildings ancillary to dwellings D8.1b<br />
Calculation of unprotected areas (D8.1)<br />
Duration of external walls D2.1 table 2, D8.1-2<br />
From adjoining buildings D9.1<br />
Single storey buildings D2.1 table 1<br />
Two buildings on land in same occupation D8.3<br />
Infiltration systems (M3.7)<br />
LPG storage containers F7.4-5, (F7.5)<br />
Oil storage tanks F7.2, (F7.2)<br />
Wastewater treatment systems M3.1d, (M3.1)<br />
Septic tanks M3.1-4, (M3.1-4)<br />
Discharges from drainage systems M2.8b<br />
Exceptions to exempted classes of buildings A schedule 1<br />
Infiltration systems M3.5-7, (M3.5-7)<br />
Sequence controls, Multiple boiler installations J11.3e<br />
Service corridors, Escape from shops E7.6-7<br />
Services<br />
Commissioning J6.5-6, J14.1-2, (J14.1-2)<br />
Energy efficiency J13.1, (J13.1)<br />
Office buildings J Appendix K<br />
Floor penetrations and sound transmission (H2.1-3) floor types<br />
Information for occupiers J14.2, (J14.2)<br />
Insulation of pipes and ducts J6.3, J11.6, (J6.3-4), (J11.6)<br />
Openings<br />
Cavity barriers D6.7, (D3.14, 4.7, 5.8, 6.7)<br />
Compartment walls and compartment floors D3.14<br />
Definition of service opening A definitions<br />
Separating walls and separating floors D5.8<br />
Sub-compartment walls D4.7<br />
Sealing penetrations (J5.1)<br />
Separating walls and sound transmission (H2.1-3)<br />
Timber frame walls with absorbent curtains (H2.1-3) wall type 4<br />
see also Hot water; Lighting; Space heating<br />
Sewage treatment works<br />
Exempted classes of buildings A schedule 1<br />
see also Wastewater treatment plant<br />
Sewers<br />
Discharges from drainage systems M2.8a, M2.9b<br />
Exempted classes of buildings A schedule 1<br />
Shafts<br />
Smoke venting D3.11<br />
Basement storeys (E10.15)<br />
see also Fire-fighting shafts<br />
Shared residential accommodation<br />
Definition A definitions<br />
Non-combustible materials D5.6, D5.7, D8.2<br />
Protected zones D11.1<br />
Sheathing, Resistance to precipitation (G3.1) wall type 3<br />
Sheds, Exempted classes of buildings A schedule 1<br />
Shelters (Exempted classes)<br />
Road or rail passenger A schedule 1<br />
Within curtilage of dwellings A schedule 1<br />
Shelving, Fixed obstructions and means of escape E5.21<br />
Shielding LPG tanks (F7.5b) table, diagram 1<br />
Shingle roof coverings, Flue terminal outlets (F4.10) diagram 2<br />
Amdt: September 2001<br />
44
Shopping complexes<br />
Creches E7.8<br />
Dry fire mains E10.6<br />
Fire control rooms E10.12<br />
Fire control systems (D2.1, 5.1, 5.3-4, 8.1)<br />
Fire detection and alarm systems E11.3, (E11.3)<br />
Fire spread on wall and ceiling surfaces D7.1 table<br />
Means of escape E7.1-8<br />
Smoke and heat exhaust ventilation E6.9e<br />
Travel distances E5.2<br />
Occupancy load factors A schedule 4<br />
Rules of measurement A schedule 5<br />
Sanitary facilities (M4.5)<br />
Separating walls and separating floors D5.1b, D5.5<br />
Smoke and heat exhaust ventilation D3.7, (D3.6-7)<br />
Warnings of fire E intro 1, reg 13(1A)<br />
Width of circulation areas E5.22c<br />
Shops<br />
Display lighting (J12.3)<br />
Dwellings above D5.6<br />
Sales areas A schedule 4<br />
Occupancy load factors A schedule 4<br />
Sanitary facilities (M4.5)<br />
Width of circulation areas E5.22c<br />
Within enclosed shopping centres<br />
Activation of alarms (E11.3)<br />
Means of escape E7.1-8<br />
Travel distances E5.2<br />
Opposing frontages D5.5<br />
see also Buildings of purpose group 4<br />
Shower-rooms<br />
Trickle ventilators K4.1b, (K4.1)<br />
Ventilation for dwellings (K2.1) table<br />
Showers see Sanitary facilities<br />
Shutters<br />
Compartment floors D3.14, (D3.14)<br />
Compartment walls D3.14<br />
Manual operation of rolling shutters E10.16<br />
Travel distances E5.3a<br />
Escape routes E2.4d, E5.11d<br />
Fire resistance (D1.3) table 1<br />
Sub-compartment walls, Travel distances E5.4a<br />
Sight impairments see Disabled people<br />
Signalling and control centres, Exempted classes of buildings A schedule 1<br />
Signs<br />
Accessibility of roofs P2.8, (P2.8)<br />
Air supported structures E5.27c<br />
Directional E intro 7<br />
Fire exits E intro 7<br />
Fixtures not requiring warrants A schedule 2<br />
Shutters sealing compartment floors (D3.14)<br />
Smoke outlets from basements (E10.15)<br />
Sills, Calculating areas of openings J2.5e<br />
Silt discharges into drainage systems M2.6-7, (M2.6-7)<br />
Simple geometry method, Unprotected area calculations (D8.1)<br />
Single storey buildings<br />
Dry fire mains E10.5-6<br />
Fire safety performance of portal frames (D1.3)<br />
Structural fire protection D2.1 table 1<br />
see also Air supported structures<br />
45<br />
Amdt: September 2001
Site drainage G intro 3, G reg 16(2), G2.2, G2.4, (G2.2)<br />
Sites<br />
Definition A definitions<br />
Preparation G intro 1-3, G reg 16, G2, (G2.1-2), G Appendix<br />
Specified constructions (G2.3, 2.5-6)<br />
Skirtings, Floors with floating layer (H2.1-3) floor type 2<br />
Slates<br />
Roof coverings (G3.1) roof type 2<br />
Wall claddings (G3.1) wall type 3<br />
Sleeper walls, Underfloor ventilation (G2.3, 2.5-6)<br />
Sleeping accommodation<br />
Buildings of purpose group 2, Occupancy capacity A reg 7(2)(a)<br />
Buildings of purpose groups 2-7, Sanitary accommodation for disabled M4.8, (M4.8)<br />
Buildings of purpose sub-group 2A, Sub-compartmentation D4.2-3<br />
Buildings of purpose sub-group 2B A schedule 3<br />
Cavities above ceilings D6.4<br />
Sub-compartmentation D4.6<br />
Dwellings Q reg 29(1)(c), Q3.1-2<br />
Exceptions to exempted classes A schedule 1<br />
Means of escape<br />
Buildings of purpose sub-group 2A E5.10<br />
Flats and maisonettes<br />
Alternative exits for maisonettes E2.23<br />
Separation from kitchens and other apartments E2.20d<br />
Hospitals E8.4-6, (E8.6)<br />
Smoke alarms in shared residential accommodation (E11.2)<br />
Sliding doors<br />
Escape routes (E2.4, 5.11)<br />
Buildings of purpose groups 2-7 E5.11f<br />
Flats and maisonettes E2.4f<br />
Slumber loads, Solid fuel boilers (J11.5)<br />
Small buildings<br />
Artificial lighting J12.1c<br />
Exempted classes A schedule 1<br />
Space heating controls (J11.3)<br />
Structure (C2.1)<br />
see also Single storey buildings<br />
Smoke alarms<br />
Compliance with EC Directives B intro 4<br />
Definition A definitions<br />
Dwellings E11.1a, (E11.1)<br />
Shared residential accommodation (E11.2)<br />
Smoke dampers, Activation in enclosed shopping centres (E11.3)<br />
Smoke detectors<br />
Activating self-closing fire doors (D3.14, 4.7, 5.8, 6.7, 11.1-5)<br />
Automatic opening ventilators (E2.11-12)<br />
Ducted warm air heating in flats and maisonettes E2.24f<br />
Shutters sealing compartment floors (D3.14)<br />
Smoke and fumes D reg 12(1)(b)<br />
Corridor division E5.23<br />
Fire safety performance of walls D11.4<br />
Corridor pressurisation E5.23, (E5.23)<br />
Definitions<br />
Electro-magnetic or electro-mechanical device susceptible to smoke A definitions<br />
Smoke alarm A definitions<br />
Exhaust ventilation<br />
Alternative escape in enclosed shopping centres E6.9e<br />
Basement storeys E10.15, (E10.15)<br />
Emergency lighting and smoke filled reservoirs (E9.2)<br />
Purpose group 4 buildings D3.6-7, (D3.6-7)<br />
Amdt: September 2001<br />
46
Fire detection and alarm systems<br />
Buildings of purpose group 2 E11.2, (E11.2)<br />
Buildings of purpose sub-group 2A (E11.2)<br />
Buildings of purpose sub-group 2B (E11.2)<br />
Dwellings E11.1b, (E11.1)<br />
Flats and maisonettes E2.14b, (E2.14)<br />
Shopping complexes E11.3, (E11.3)<br />
Fire-fighting shafts E10.9b, (E10.4, 10.9)<br />
High level outlet above stage D11.15, (D11.15)<br />
Recirculated air in ducted warm air heating systems E2.24<br />
Smoke venting shafts D3.11<br />
Basement storeys (E10.15)<br />
Ventilation of basement storeys E10.15, (E10.15)<br />
Ventilation of escape routes E10.13-14<br />
Smoke outlets<br />
Basement storeys E10.15, (E10.15)<br />
Exhaust ventilation systems (D3.6-7)<br />
Separated stage and stage area D11.15, (D11.15)<br />
Smoke venting shafts D3.11<br />
Basement storeys (E10.15)<br />
Soakaways, Discharges from drainage systems M2.9, (M2.9)<br />
Socket outlets<br />
Definition A definitions<br />
Dwellings Q reg 29(2), Q3.9<br />
Soffits above open access balconies and access decks E2.13<br />
Soft floor coverings, Resistance to impact sound transmission (H2.1-3) floor type 1<br />
Solar gains, Conservation of fuel and power, Target U-value method J3.4, J3.8-10, J Appendix F<br />
Solid fuel combustion appliance installations F4, (F4.2-3), (F4.5), (F4.8), (F4.10-12), (F4.17-19), (F4.21)<br />
Solid fuels see Fuels<br />
Solid ground floors<br />
Insulation thickness J Appendix A table A12, example 8<br />
U-values J Appendix C table C1<br />
Solid walls<br />
Resistance to precipitation (G3.1) wall type 1<br />
Sound insulation constructions (H2.1-3) wall types 1, 3<br />
Thermal insulation J Appendix A table A10<br />
Solid waste containers, Provision of hard-standing R2.1<br />
Solid waste storage R intro<br />
Application of Part R R1<br />
Dungsteads and farm effluent tanks R reg 31, R3.1-2, (R3.1-2)<br />
Dwellings R reg 30(1), R2, (R2.3)<br />
Escape routes E2.6<br />
Separating walls and separating floors D5.2a, D5.6, D5.7<br />
Solum<br />
Prevention of vegetable growth G2.3<br />
Reducing evaporation from ground G2.5<br />
Specified constructions (G2.3, 2.5-6)<br />
Sound insulating materials<br />
Absorbent blankets (H2.1-3) floor type 3<br />
Absorbent curtains (H2.1-3) wall type 4<br />
Cavity walls (H2.1-3) wall type 2<br />
Floating layers (H2.1-3) floor types 2-3<br />
Resilient (H2.1-3) floor types 1-3<br />
Soft coverings (H2.1-3) floor type 1<br />
Sound transmission H intro, H regs 19-21<br />
Application of Part H H1<br />
Specified constructions (H2.1-3) wall types, floor types<br />
Test procedures (H2.1-3) test procedures<br />
Space cooling<br />
Conservation of fuel and power J13.1, J Appendix K<br />
Insulation of pipes and ducts J11.6, (J11.6)<br />
47<br />
Amdt: September 2001
Space heating<br />
Conservation of fuel and power<br />
Buildings of purpose groups 2-7<br />
Commissioning systems J14.1-2, (J14.1-2)<br />
Controls J11.2-4, (J11.3), (J11.5)<br />
Efficiency of systems J11.1, (J11.1)<br />
Information for occupiers J14.2<br />
Insulation of pipes and ducts J11.6, (J11.6)<br />
Dwellings J intro 3<br />
Commissioning systems J6.5-6<br />
Controls J6.1, (J6.1)<br />
Elemental Method J3.2<br />
Information for occupiers J6.6<br />
Insulation of pipes and ducts J6.3, (J6.3-4)<br />
Methods of compliance J3.1<br />
SAP energy ratings J Appendix G<br />
Target U-value method J3.4-7, J Appendix F<br />
Regulation 22 not applicable J reg 22(2)<br />
Dwellings Q reg 29(1)(f), Q3.6<br />
Flats and maisonettes, Ducted warm air systems E2.24<br />
Regulation 28 not applicable P reg 28(2)(b)<br />
Special care baby units, Location of hospital departments D5.3-4<br />
Special waste R intro 4<br />
Specialised buildings, Exempted classes A schedule 1<br />
Specialist process lighting J12.1<br />
Specifications as standards (B2.2)<br />
Specified constructions<br />
Airborne sound and impact sound (H2.1-3) wall types, floor types<br />
Resistance to moisture from the ground (G2.3, 2.5-6)<br />
Resistance to precipitation (G3.1)<br />
Spectator accommodation see Fixed seating<br />
Spiral stairs S3.15, (S3.15)<br />
Escape stairs (S3.15)<br />
Spirituous liquor stores, Gangways E5.21<br />
Sports stadia<br />
Gangways S intro 6<br />
Purpose groups A schedule 3<br />
Sanitary facilities (M4.5)<br />
see also Buildings of purpose sub-group 5B<br />
Spread of fire D intro 5-6, D reg 12(1), (D1.3) table 3<br />
From adjoining buildings D9.1, (D9.1)<br />
Internal linings D7.1-4, (D7.1, 7.2, 7.4)<br />
On external walls D10.1-3, (D10.1)<br />
To adjoining buildings D8.1-3, (D8.1)<br />
Spread of fire to fuel tanks F reg 15, F7.2-5, (F7.2-5)<br />
Springs<br />
Location of infiltration systems (M3.7)<br />
Oil storage tanks (F7.2c) table<br />
Sprinkler systems (D2.1, 5.1, 5.3-4, 8.1)<br />
Basement storeys (E10.15)<br />
Stability (Structure) C reg 11(1), C2.1, (C2.1)<br />
Fire precautions D reg 12(1)(a)<br />
Stages and stage areas<br />
Direction of air movement in event of fire D11.14, (D11.14)<br />
Escape route independent from that for auditorium E4.5<br />
Escape of smoke and hot gases in event of fire D11.15, (D11.15)<br />
Separation D11.13, (D11.13)<br />
Staggering, Improving sound insulation H intro 3, (H2.1-3) wall type 2<br />
Amdt: September 2001<br />
48
Stair wells<br />
Calculations of floor area J2.5c<br />
U-values of floors above or walls adjoining unheated spaces J2.3<br />
Stairlifts<br />
Fitting to stairs in dwellings S3.4c<br />
Fixtures not requiring warrants A schedule 2<br />
Wheelchair platform (S2.7)<br />
Stairs S intro 3-4<br />
Access between storeys of dwellings Q2.13<br />
Agricultural buildings S3.27, (S3.27)<br />
Application of Part S S3.1<br />
Definitions<br />
Flight A definitions<br />
Private stair or ramp A definitions<br />
Tapered tread A definitions<br />
Disabled access S2.7b, (S2.7)<br />
Handrails S3.20-24<br />
Headroom S3.25<br />
Houses of purpose sub-group 1B E3.4, E3.6<br />
Industrial S3.26, (S3.26)<br />
Landings S3.18-19<br />
Length of flights S3.10<br />
Measurement S3.2, S3.4<br />
Open rises S3.8, (S3.12)<br />
Openings in compartment floors D3.14, (D3.14)<br />
Private stairs<br />
Basement storeys E3.6<br />
Flats at storey height of more than 4.5 m E2.21<br />
Rise, going and pitch of flights S3.3-9<br />
Risers and nosings S3.10-11, (S3.11)<br />
Sound insulation of common stairs (H2.1-3) wall type 4<br />
Tapered treads S3.1-3, S3.12-15, (S3.12), (S3.15)<br />
Width S3.4<br />
see also Escape stairs<br />
Standard Assessment Procedure, Conservation of fuel and power J intro 4, J Appendix G<br />
<strong>Standards</strong><br />
Fire reaction D1.3 (D1.3)<br />
Fire resistance D1.3, (D1.3)<br />
References A references<br />
Selection and use of materials and components (B2.2)<br />
Sound insulation (H2.1-3) standards<br />
Standby power supply see Electrical installations<br />
Standing capacity<br />
Escape stairs E6.4b<br />
see also Occupancy capacity<br />
Steam see Discharges of steam or hot water<br />
Steel<br />
Open-sided car parks (D1.3)<br />
Portal frames, Fire safety performance (D1.3)<br />
Structural work (C2.1)<br />
Disproportionate collapse (C3.1)<br />
Stepped elevation, Improving sound insulation H intro 3, (H2.1-3) wall type 2<br />
Steps<br />
Access to dwellings Q2.1<br />
Profiles (S3.11)<br />
Sloping gangways S3.28<br />
Sterilising and disinfecting units, Fire control systems D5.4c<br />
Stone chippings, Thermal conductivity of materials J Appendix A table A18<br />
49<br />
Amdt: September 2001
Storage buildings<br />
Compartmentation D2.1 table 2<br />
Single storey buildings D2.1 table 1<br />
Purpose groups A schedule 3<br />
Storage spaces<br />
Escape stair protected zones E6.8<br />
Factory-made chimneys F3.7b, (F3.7)<br />
Hospitals D5.3-4<br />
Means of escape where fixed obstructions E5.21<br />
Occupancy load factors A schedule 4<br />
Separation from escape stairs D11.5<br />
Sub-compartmentation D4.2<br />
Stores (Domestic)<br />
Acceptable roof coverings D9.1<br />
Distance from boundaries D8.1b<br />
Duration of fire protection D2.1 table 1<br />
Exempted classes of buildings A schedule 1<br />
Kitchens Q3.4<br />
Storey selector buttons see Tactile storey selector buttons<br />
Storeys<br />
Accessible to disabled<br />
Buildings of purpose groups 2-7 S2.6-7<br />
Dwellings Q intro, Q2.11-13<br />
Accessible entrance storeys Q intro 4, Q2.11-12<br />
Sanitary facilities M4.3<br />
Basement storeys<br />
Compartments D3.3-4<br />
Ducted warm air heating E2.24<br />
Fire-fighting facilities E10.4 table, E10.10<br />
Means of escape<br />
Buildings of purpose groups 2-7<br />
Escape stairs E6.3, E6.12<br />
Number of exits E4.1<br />
Flats and maisonettes E2.16, E2.18<br />
Houses E3.1, E3.3<br />
Protected enclosure E3.6<br />
Smoke ventilation E10.15, (E10.15)<br />
Structural fire protection D2.1 table 2<br />
U-values (J2.1), J Appendix C<br />
Calculating number C reg 11(3)<br />
Definitions<br />
Basement storey A definitions<br />
Ground storey A definitions<br />
Storey A definitions<br />
Upper storey A definitions<br />
Escape stairs connecting multiple levels in a single storey E6.6<br />
Escape stairs only escape route E6.2<br />
Escape stairs serving multiple storeys E6.4b<br />
Maximum areas D2.1 table 2<br />
Number of escape routes E intro 2<br />
Rules of measurement A schedule 5<br />
Separating walls and floors in hospitals D5.1d<br />
Amdt: September 2001<br />
50
Upper storeys<br />
Compartments D3.2<br />
Ducted warm air heating E2.24<br />
Fire spread on external walls D10.2<br />
Fire-fighting facilities E10.4 table<br />
Means of escape<br />
Buildings of purpose groups 2-7<br />
Number of exits E4.1<br />
Protected lobbies E6.14<br />
Flats and maisonettes E2.15-16, E2.20-24<br />
Protected lobbies E2.11<br />
Hospitals E8.1<br />
Houses E3.1<br />
Topmost storeys used for plant maintenance E6.2b<br />
Rainscreen cladding D6.5<br />
Structural fire protection D2.1 table 2<br />
Strapping, Combustible material on outer face of chimneys F4.15d<br />
Stringers see Stairs<br />
Strong rooms, Smoke ventilation of basement storeys E10.15<br />
Structural elements see Elements of structure<br />
Structural Eurocodes C intro 4<br />
Structural fire precautions D intro, D reg 12<br />
Application of Part D D1<br />
Concealed spaces D6<br />
Escape route protection D11.1-15<br />
Buildings of purpose group 2-7 E5.9g<br />
Flats and maisonettes E2.11, E2.19<br />
More than 4.5 m high E2.20-21, E2.23a<br />
Houses of purpose sub-group 1B E3.4, E3.6<br />
Fire spread on external walls D10.1-3, (D10.1)<br />
Fire spread from adjoining buildings D9.1, (D9.1)<br />
Fire spread on internal linings D7, (D7.1, 7.2, 7.4)<br />
Fire spread to adjoining buildings D8, (D8.1)<br />
Protection principles D2.1-2<br />
Use of non-combustible materials D2.3<br />
Structure C reg 11<br />
Application of Part C C1<br />
Disproportionate collapse C reg 11(2), C3.1, (C3.1)<br />
Portal frames, Fire safety performance (D1.3)<br />
Stability C reg 11(1), C2.1, (C2.1)<br />
In fire D intro 1, D reg 12(1)(a)<br />
Steel framed open-sided car parks (D1.3)<br />
Studs<br />
Cavity barriers (D1.3) table 1<br />
Thermal bridging of insulation J Appendix B<br />
Sub-compartment walls<br />
Definition A definitions<br />
Escape routes E5.4<br />
Measuring travel distances E5.2c<br />
Hospitals D4.4, D4.8<br />
Openings D4.7<br />
Ducts (D3.14, 4.7, 5.8, 6.7)<br />
51<br />
Amdt: September 2001
Sub-compartments D intro 4, D4.1-8<br />
Definition A definitions<br />
Escape routes E5.3-4<br />
Buildings of purpose sub-group 2A E5.10<br />
Hospital streets E8.9c<br />
Subsoil drainage of sites see Site drainage<br />
Suitability for purpose B intro 2, B2.2, (B2.2)<br />
Summerhouses<br />
Acceptable roof coverings D9.1<br />
Exempted classes of buildings A schedule 1<br />
Fire spread D8.1<br />
Superimposed hearths see Hearths<br />
Surface condensation G intro 6, G4.2, (G4.2)<br />
Risk at edges of openings J Appendix D6<br />
Surface soil, Preparation of sites G intro 2, G reg 16(1)(b), G2.3<br />
Surface spread of fire<br />
Internal linings D7.1-4, (D7.1, 7.2, 7.4)<br />
Reaction to fire (D1.3) table 3<br />
Surface water, Definition A definitions<br />
Surface water drainage M intro 2-3, M reg 24, M2.2, (M2.2)<br />
Discharges M2.9, (M2.9)<br />
Surgeries, Purpose groups A schedule 3<br />
Suspended ceilings, Fire safety performance of floors (D1.3) table 2<br />
Suspended ground floors<br />
Insulation thickness J Appendix A tables A13-14 example 9<br />
Resistance to moisture from ground (G2.3, 2.5-6)<br />
U-value calculations J Appendix C<br />
Sustainable Urban Drainage Systems M intro 3, M2.2a, (M2.2)<br />
Discharges from drainage systems M2.9a, (M2.9)<br />
Swimming pools<br />
Ancillary to dwellings<br />
Enclosures exempted A schedule 1<br />
Enclosures and fire spread D8.1<br />
Covered by air supported structures E5.27<br />
Plastics roof coverings (D9.1)<br />
Purpose groups A schedule 3<br />
Sanitary facilities (M4.5)<br />
Switching<br />
Artificial lighting<br />
Communal areas of flats and maisonettes Q2.10b, (Q2.10)<br />
Conservation of fuel and power (J12.3), J Appendix J<br />
Controlling points serving stairs Q3.8<br />
Isolating switches N2.1c<br />
T<br />
Tactile call buttons, Passenger lifts (S2.6)<br />
Tactile storey selector buttons, Passenger lifts (S2.6)<br />
Tanks<br />
Exempted classes of buildings A schedule 1<br />
Waste products from waterless closet M2.8b<br />
see also Farm effluent tanks; Liquid fuel storage; Septic tanks<br />
Tapered treads see Stairs<br />
Target U-value method J intro 3, J3.1, J3.4-10, Appendix F<br />
<strong>Technical</strong> <strong>Standards</strong><br />
Definition A definitions<br />
References A references<br />
Telephone kiosks, Exempted classes of buildings A schedule 1<br />
Temperature<br />
Dwellings Q3.6a<br />
Stored hot water P intro 2, P3.1<br />
Temperature controls see Thermostats<br />
Temperature relief valves, Hot water storage systems (P3.1)<br />
Amdt: September 2001<br />
52
Temporary buildings, Exempted classes A schedule 1<br />
Tents, Exempted classes of buildings A schedule 1<br />
Termini (travel), Purpose groups A schedule 3<br />
Tests<br />
Extract fans (F3.11)<br />
Harmonised methods A references<br />
Selection and use of materials and components (B2.2)<br />
Temperature of back, sides and top of oil-fired appliances (F5.13)<br />
Temperature beneath oil-fired appliances (F5.11)<br />
Wastewater and surface water drainage M2.5, (M2.5)<br />
Worksmanship (B2.1)<br />
see also Acoustic tests; Fire tests; Percolation tests<br />
Thatched roof coverings, Flue terminal outlets (F4.10) diagram 2<br />
Theatres see Auditoria; Buildings of purpose sub-group 5A<br />
Thermal breaks<br />
Conservation of fuel and power<br />
Indicative U-values J Appendix A tables A1-3<br />
Target U-value method J3.8<br />
Thermal bridging<br />
Calculating U-values (J2.1), J Appendix B<br />
Limiting at junctions and around openings<br />
At the edges of openings J Appendix D<br />
Buildings of purpose groups 2-7 J9.1, (J9.1)<br />
Dwellings J4.1, (J4.1)<br />
Thermal conductivity J2.1, (J2.1)<br />
Common building materials J Appendix A table A18<br />
Thermal cut-outs, Hot water storage systems (P3.1)<br />
Thermal insulation J intro 8<br />
Basement floors J Appendix C<br />
Cavity closers J Appendix D<br />
Ceilings instead of cavity barriers D6.6<br />
External walls<br />
More than 18 m above ground D10.2<br />
Near to boundaries D8.2<br />
Fixtures not requiring warrants A schedule 2<br />
Ground floors J Appendix C<br />
Heat loss method J Appendix H<br />
Hot water storage vessels J6.4, J11.7, (J6.3-4), (J11.7)<br />
Materials J Appendix A table A18<br />
Over-roof G intro 5<br />
Passive stack ventilation K4.4b<br />
Pipes and ducts J6.3, J11.6, (J6.3-4), (J11.6)<br />
Specified constructions for roofs (G3.1) roof type 1<br />
Specified constructions for walls (G3.1)<br />
Structures with repeating thermal bridges J Appendix B<br />
Thicknesses for U-values J2.1, (J2.1), J Appendix A<br />
Thermal resistance<br />
Difference between bridged and bridging materials (J2.1)<br />
Minimum path at openings J Appendix D<br />
U-value calculations<br />
Elements containing repeating thermal bridges J Appendix B<br />
Ground floors and basements J Appendix C<br />
Thermal transmittances see U-values<br />
Thermoplastic materials<br />
Ceilings D7.1c, D7.2, (D7.2)<br />
Light diffusers D7.1, D7.2, (D7.2)<br />
Roof coverings (D9.1)<br />
Rooflights D7.1, D7.2, (D7.2), (D9.1)<br />
Thermostats J6.2b, J11.4, (J6.2), (J11.5)<br />
Room thermostats J6.1a, J11.3a, (J6.2), (J11.5)<br />
Ducted warm air heating E2.24e<br />
Thermostatic radiator valves J6.1, J11.2b, J11.3a<br />
53<br />
Amdt: September 2001
Thresholds see Entrances<br />
Throats (combustion appliances), Definition (F4.3) table<br />
Ties<br />
Disproportionate collapse (C3.1)<br />
Timber frame wall with absorbent curtain (H2.1-3) wall type 4<br />
see also Cavity walls<br />
Tiles<br />
Roof coverings (G3.1) roof type 2<br />
Thermal conductivity of materials J Appendix A table A18<br />
Wall claddings (G3.1) wall type 3<br />
Timber<br />
Flat roof structures (G3.1) roof type 1<br />
Floating layers, Sound insulation constructions (H2.1-3) floor type 2<br />
Floors<br />
Sound insulation constructions (H2.1-3) floor types 3-4<br />
Thermal insulation thickness J Appendix A table A15<br />
Framed buildings, Chimneys or flue-pipes for gas installations (F6.6)<br />
Framed walls<br />
Resistance to precipitation (G3.1) wall type 3<br />
Sound insulation constructions (H2.1-3) wall type 4<br />
Floors (H2.1-3) floor type 3<br />
Thermal bridging of insulation J Appendix B example 1<br />
Thermal insulation thickness J Appendix A table A11, example 7<br />
Inner leafs of cavity walls, Sound insulation constructions (H2.1-3) wall type 1<br />
Joists<br />
Supported by hangers (H2.1-3) wall types 1-3<br />
Thermal bridging (J2.1)<br />
Projecting beyond surface of insulation J Appendix B2<br />
Pitched roofs (G3.1) roof type 2<br />
Structural work (C2.1)<br />
Studs<br />
Cavity barriers (D1.3) table 1<br />
Thermal bridging of insulation J Appendix B<br />
Suspended ground floors<br />
Insulation thickness J Appendix A table A13, example 9<br />
Resistance to moisture (G2.3, 2.5-6)<br />
Thermal conductivity of materials J Appendix A table A18<br />
Time switching, Lights (J12.3)<br />
Tobacco smoke K intro 6<br />
Toilets M4.10<br />
Definition A definitions<br />
Escape stair protected zones E6.8<br />
Ventilation for dwellings (K2.1) table<br />
Transmission of sound see Sound transmission<br />
Travel distances<br />
Air supported structures E5.27a<br />
Buildings of purpose groups 2-7 E5.1-8<br />
Independence of escape routes E4.3<br />
Flats and maisonettes E2.15<br />
More than 4.5 m in height E2.20-21<br />
Hospitals E8.8-9<br />
Number of escape routes E intro 2<br />
Treads see Stairs<br />
Trickle ventilators see Ventilators<br />
Troughed metal deckings, Specified roof constructions (G3.1)<br />
Turnstiles, Escape routes E2.4c, E5.11c<br />
Amdt: September 2001<br />
54
U<br />
U-values J2.1, (J2.1), J Appendix A<br />
Basement storeys J Appendix C<br />
Buildings of purpose groups 2-7<br />
Carbon emissions calculation method J8.8-9<br />
Elemental method J8.3<br />
Heat loss method J8.5-6, (J8.5), J Appendix H<br />
Calculations using the Combined Method J Appendix B<br />
Definition A definitions<br />
Dwellings<br />
Conservatories J7.1<br />
Elemental method J3.2-3<br />
Maximum permissible J3.12<br />
Methods of compliance J3.1<br />
Target U-value method J3.4-10, J Appendix F<br />
Floors above or walls adjoining unheated space J2.3<br />
Ground floors J8.6a, J8.9b, J Appendix C<br />
Measurement (J2.1)<br />
Windows, doors and rooflights in the elemental method J Appendix E<br />
Underfloor space, Ventilation (G2.3, 2.5-6)<br />
Underground buildings<br />
Exempted buildings ancillary to dwellings A schedule 1<br />
U-values of floors above or walls adjoining unheated spaces J2.3<br />
Underground drainage see Drainage systems<br />
Underground structures (G2.3, 2.5-6)<br />
see also Basement storeys<br />
Unheated buildings, Conservation of fuel and power J reg 22(2)(a)<br />
Unheated spaces<br />
Conservation of fuel and power J reg 22(2)(b)<br />
Floor areas J Appendix C4<br />
U-values of floors above or walls adjoining J2.3<br />
Unprotected areas D intro 6<br />
Calculations (D8.1)<br />
Permitted levels D8.1<br />
Unprotected zones<br />
Definition A definitions<br />
Emergency lighting E9.2 table<br />
Exits from rooms with occupancy capacity of no more than 100 persons E4.3<br />
Horizontal escape E5.9-10<br />
Unvented hot water storage systems see Hot water<br />
Upper storeys see Storeys<br />
Use see Existing buildings; Mixed use; Purpose groups<br />
Used water see Greywater<br />
Utility rooms, Ventilation for dwellings (K2.1) table<br />
V<br />
Vapour control layers (G3.1) wall type 3, roof types<br />
Vapour control membranes, Sealing (J5.1)<br />
Vegetable matter see Organic matter<br />
Vehicle parking<br />
Pumping appliances E10.7-8, (E10.2, 10.8)<br />
Ventilation K1.3<br />
see also Car parking; Car parks<br />
Vehicle protective barriers see Protective barriers<br />
Ventilated voids<br />
Framed walls and resistance to precipitation (G3.1) wall type 3<br />
Rainscreen panels D6.5<br />
55<br />
Amdt: September 2001
Ventilation K intro, K reg 23<br />
Air for combustion F intro 6<br />
Oil-fired appliances F5.3, (F5.3)<br />
Open-flued combustion appliances F3.11, (F3.11)<br />
Solid fuel appliances F4.3, (F4.3)<br />
Air for cooling<br />
Oil-fired appliances F5.4, (F5.4)<br />
Open-flued combustion appliances F3.11, (F3.11)<br />
Application of Part K K1<br />
Auditoria air movements in event of fire D11.14, (D11.14)<br />
Buildings other than garages K2.1, (K2.1)<br />
Conservation of fuel and power K intro 3<br />
Drainage systems M2.3, (M2.3)<br />
Ducts through fire resisting construction (D3.14, 4.7, 5.8, 6.7)<br />
Fan replacements not requiring warrants A schedule 2<br />
Fire-fighting shafts (E10.4, 10.9)<br />
Garages<br />
Large K3.1, (K3.1)<br />
Small K3.2, (K3.2)<br />
Mechanical K4.6-10, (K2.1), (K4.9-10)<br />
Conservation of fuel and power J intro 7, J13.1, (J13.1)<br />
Office buildings J Appendix K<br />
Mixed modes of natural and mechanical J Appendix K<br />
Natural K4.1-5, (K2.1), (K4.1), (K4.3)<br />
Roof void in flat roofs G intro 5<br />
Smoke and fumes<br />
Basement storeys E10.15, (E10.15)<br />
Corridors providing escape from flats and maisonettes E2.12, E10.14, (E2.11-12)<br />
Escape routes E10.13-14<br />
Escape stairs E10.13<br />
Fire-fighting shafts (E10.4, 10.9)<br />
Protected lobbies in flats and maisonettes E2.11, (E2.11-12)<br />
Smoke and heat exhaust systems D3.6-7, (D3.6-7)<br />
Alternative escape E6.9e<br />
Basement storeys E10.15f, (E10.15)<br />
Emergency lighting (E9.2)<br />
Smoke venting shafts D3.11<br />
Basement storeys (E10.15)<br />
Solid waste storage (R2.3)<br />
Sub-floors (G2.3, 2.5-6)<br />
Underfloor space (G2.3, 2.5-6)<br />
Volume K1.3<br />
Ventilators<br />
Basement storeys (E10.15)<br />
Calculation of unprotected areas (D8.1)<br />
Corridors providing escape from flats and maisonettes E2.12, E10.14, (E2.11-12)<br />
Definition A definitions<br />
Escape stairs E10.13a<br />
Fan replacements not requiring warrants A schedule 2<br />
Grilles in ceilings (D3.6-7)<br />
Height K4.2<br />
Opening areas (K2.1)<br />
Permanent (K3.2)<br />
Definition A definitions<br />
Protected lobbies in flats and maisonettes E2.11, (E2.11-12)<br />
Rooms opening into conservatories K4.1a<br />
Smoke reservoirs (D3.6-7)<br />
Trickle K4.1b, (K2.1), (K4.1)<br />
Definition A definitions<br />
Vermin, Securing solid waste storage R2.3, (R2.3)<br />
Amdt: September 2001<br />
56
Vertical escape in buildings of purpose groups 2-7<br />
Protected zones E6.6-14<br />
Width of escape stairs E6.1-5<br />
Vision panels P2.1<br />
Voice alarm systems, Mall areas (E11.3)<br />
Volatile substances discharged into drainage systems M2.7, (M2.7)<br />
Volume<br />
Measurement A schedule 5<br />
Ventilation K1.3<br />
W<br />
Waiting rooms, Occupancy load factors A schedule 4<br />
Walkways, Impact sound transmission H reg 20(2), H1.4<br />
Walls<br />
Cavity barriers D6.1-2, D6.8<br />
Conservation of fuel and power<br />
Adjoining unheated space J2.3<br />
Insulation thickness J Appendix A tables A8-11, examples 4-7<br />
Target U-value method J3.5, J Appendix F<br />
Thermal bridging (J2.1), J Appendix B<br />
Thermal conductivity of materials J Appendix A table A18<br />
U-values of basement storeys J Appendix C<br />
Construction differing only in roof space (H2.1-3) test procedures<br />
Corridor division for smoke control E5.23<br />
Fire safety performance D11.4<br />
Definition A definitions<br />
Dividing protected lobby from rest of protected zone D11.2<br />
Escape across flat roofs or access decks D11.11, E3.7, E5.9g<br />
Fire resistance periods (D1.3) table 1<br />
Fire spread on internal linings D7.1, (D7.1)<br />
Sandwich panels D7.3-4, (D7.4)<br />
Height and exceptions to exempted classes A schedule 1<br />
Mass of leaf (H2.1-3)<br />
Openings for ventilation of large garages (K3.1)<br />
Protected enclosures D11.3<br />
Resistance to moisture from ground (G2.3, 2.5-6)<br />
Resistance to precipitation (G3.1)<br />
Separation of rooms from escape stairs D11.5<br />
Sound insulation constructions (H2.1-3) wall types<br />
Floors (H2.1-3) floor types<br />
see also Cavity walls; Compartment walls; External walls; Separating walls<br />
Wardrobe space Q3.1<br />
Warehousing see Storage buildings; Storage spaces<br />
Warm air ducts, Thermal insulation J6.3, J11.6, (J6.3-4), (J11.6)<br />
Warm deck roofs G intro 5<br />
Specified constructions (G3.1)<br />
Warnings<br />
Activation of shutters sealing compartment floors (D3.14)<br />
Discharges of hot water J11.7<br />
Fire E intro 1, E reg 13(1A), E2.14b, E11.1-3, (E2.14, 11.1-3)<br />
Application of Part E E1<br />
Roof access P2.8, (P2.8)<br />
Warrants A intro 4<br />
Not required for fixtures A reg 4, A schedule 2<br />
Staged applications M intro 5<br />
Washbasins see Sanitary facilities<br />
Washrooms, Escape stair protected zones E6.8<br />
Waste chutes, Sound insulation H1.4<br />
Waste containers R2.1, (R2.3)<br />
Waste management R intro 2, R2.1<br />
57<br />
Amdt: September 2001
Wastewater<br />
Definition A definitions<br />
Inspection and sampling treated water M3.1, (M3.1)<br />
see also Drainage systems<br />
Wastewater treatment plant<br />
Discharges from drainage systems M2.8<br />
Exempted classes of buildings A schedule 1<br />
Private systems M3.1-4, (M3.1-4)<br />
Infiltration systems M3.5-7, (M3.5-7)<br />
Water<br />
Contamination prevention<br />
Dungsteads and farm effluent tanks R reg 31, R3.1b, (R3.1)<br />
Oil storage F reg 15(1)(b), (F7.2c) table<br />
Storage of solid waste from dwellings R reg 30(2)(c)<br />
Locating infiltration systems (M3.5), (M3.7)<br />
Supply for fire-fighting E intro 4, E10.2-3, (E10.2)<br />
see also Hot water<br />
Water service pipes<br />
Connections for ground hydrants E10.3<br />
Service openings in walls and floors (D3.14, 4.7, 5.8, 6.7)<br />
Water works, Exempted classes of buildings A schedule 1<br />
Watercloset compartments see Toilets<br />
Watercloset cubicles M4.6, (M4.6)<br />
Waterclosets see Sanitary facilities<br />
Waterless closets M intro 2, M4.2, (M4.2)<br />
Waste products M2.8b<br />
see also Sanitary facilities<br />
Weather compensating controls J11.3d<br />
Weatherboarding (G3.1) wall type 3<br />
Weighted impact sound improvement (H2.1-3) floor type 1<br />
Wet fire mains see Fire mains<br />
Wetland infiltration systems (M3.6)<br />
Wheelchair platform stairlifts (S2.7)<br />
Wheelchair users see Disabled people<br />
Wind loads C2.1<br />
Calculation (C2.1)<br />
Definition A definitions<br />
Winders see Stairs<br />
Window access systems P2.3c, (P2.3)<br />
Window frames<br />
Conservation of fuel and power<br />
Buildings of purpose groups 2-7, Elemental method J8.3<br />
Dwellings<br />
Elemental method J3.2 table 1<br />
Methods of compliance J3.1<br />
Target U-value method J3.9, J Appendix F<br />
Indicative U-values J Appendix A tables A1-3<br />
Amdt: September 2001<br />
58
Windows<br />
Access to manual controls P intro 2, P reg 27(1)(f), P2.7<br />
Cleaning P intro 2, P reg 27(1)(c), P2.3-4, (P2.3-4)<br />
Conservation of fuel and power<br />
Buildings of purpose groups 2-7<br />
Carbon emissions calculation method J8.9a<br />
Combining natural and mechanical ventilation J Appendix K<br />
Elemental method J8.2-4, J Appendix E<br />
Heat loss method J8.5-6, (J8.5), J Appendix H<br />
Monitoring daylight (J12.3)<br />
Dwellings<br />
Draught seals (J5.1)<br />
Elemental method J3.2-3, J Appendix E<br />
Methods of compliance J3.1<br />
Target U-value method J Appendix F<br />
Indicative U-values J Appendix A tables A1-3<br />
Thermal bridging at edges of openings J Appendix D<br />
Dwellings Q reg 29(1)(e), Q3.5<br />
Emergency escape (E2.17, 3.2)<br />
Flats and maisonettes E2.17-18<br />
Houses E3.1-3<br />
Escape stair ventilation E10.13<br />
Plastics D7.1<br />
Replacements not requiring warrants A schedule 2<br />
see also Rooflights<br />
Wood based boards<br />
Expansion of chipboard (H2.1-3) floor type 3<br />
Floating layers of cement bonded particleboard (H2.1-3) floor type 3<br />
Thermal conductivity of materials J Appendix A table A18<br />
Wood fuel see Fuels<br />
Wood wool slabs, Thermal conductivity of materials J Appendix A table A18<br />
Workmanship B intro 6, B reg 10, B2.1 (B2.1)<br />
Application of Part B B1<br />
Safety of structure C intro 1)<br />
Sound insulation H intro 4, (H2.1-3) floor type 3<br />
Works of civil engineering, Exempted classes of buildings A schedule 1<br />
Workshops see Industrial buildings<br />
Z<br />
Zoos, Purpose groups A schedule 3<br />
59<br />
Amdt: September 2001
Amdt: September 2001<br />
60