COMMUNICATIONS SYSTEMS 18.9<br />

FIGURE 18.1 Lucent 489A-type<br />

multipair building entrance protector<br />

panel. (Copyright � 1999, Lucent<br />

Technologies, used by permission.)<br />

FIGURE 18.2 Typical communications grounding detail. (Nevling.)<br />

c. ANSI/TIA/EIA St<strong>and</strong>ard 607, Commercial <strong>Building</strong> Grounding <strong>and</strong> Bonding<br />

Requirements for Telecommunications.<br />

d. NEC, Article 250 concerning grounding.<br />

e. NEC, Article 800, Section D concerning communications circuits grounding.<br />

f. NFPA 780, Lightning Protection Code.<br />

Typical communications grounding includes bonding all metal frames <strong>and</strong> equipment<br />

in a communications room or closet to a ground bar in the room <strong>and</strong> connecting<br />

all rooms together. At the main communications room, a ground rod is<br />

provided as well as bonding to the electrical system. Protected entrance terminals<br />

(Fig. 18.1) are grounded so that a lightning strike or surge will be taken to ground.<br />

Please note that the diagram in Fig. 18.2 is an example only <strong>and</strong> does not portray<br />

all of the requirements of the above-mentioned codes.