28.02.2013 Views

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

Building Design and Construction Handbook - Merritt - Ventech!

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

13.88 SECTION THIRTEEN<br />

FIGURE 13.43 Control circuit for a cooling-tower-type HVAC system.<br />

In buildings where one tower <strong>and</strong> pump are used to provide water for many<br />

units, pressure switches may be used in series with the holding coil of each compressor<br />

motor starter. No interconnecting wiring is necessary, for the compressor<br />

will not be able to run unless the pump is in operation <strong>and</strong> provides the necessary<br />

pressure to close the contacts on the pressure switch.<br />

Some city ordinances require that indirect-expansion, or chilled-water, systems<br />

be installed in public buildings, such as theaters, night clubs, hotels, <strong>and</strong> depots.<br />

This type of system is illustrated in Fig. 13.30. The refrigerant is used to cool water<br />

<strong>and</strong> the water is circulated through the cooling coil to cool the air. The water<br />

temperature should be between 40 <strong>and</strong> 45�F, depending on whether the occupancy<br />

is a high latent load or a low latent load. Because the cost of equipment is increased<br />

<strong>and</strong> the capacity decreased as water temperature is lowered, most designers use<br />

45�F water as a basis for design <strong>and</strong> use a much deeper cooling coil for high-latentload<br />

installations.<br />

The amount of chilled water in gallons per minute to be circulated may be<br />

obtained from<br />

24 � tons of refrigeration<br />

Q � (13.37)<br />

�T<br />

where �T is the temperature rise of water on passing through the cooling coil,<br />

usually 8 or 10�F. The smaller the temperature change, the more water to be circulated<br />

<strong>and</strong> the greater the pumping cost, but the better will be the heat transfer<br />

through the water chiller <strong>and</strong> cooling coil.<br />

Coil manufacturers’ catalogs usually give the procedure for picking the number<br />

of rows of coil necessary to do the required cooling with the water temperatures<br />

available.<br />

The water chiller should be sized to cool the required flow of water from the<br />

temperature leaving the cooling coil to that required by the coil at a given suction<br />

temperature.<br />

Assuming 45�F water supplied to the cooling coil <strong>and</strong> a temperature rise of 8�F,<br />

the water leaving the coil would be at 53�F. The chiller would then be picked to<br />

cool the required flow from 53 to 45�F at37�F suction. The lower the suction

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!