general<br />

SPeCifiCaTionS<br />

hitec current sensors as useD with yokoGawa Power meters<br />

macc plus <strong>ch</strong>aracteristic specification<br />

current output type<br />

Input range DC ±600A (±850Apk)<br />

Input range AC ±850Apk (600Arms)<br />

Transfer ratio 1000:1<br />

External burden 0…1Ω (at max. current)<br />

Accuracy DC 0.005% of reading + 0.002% of range<br />

Accuracy AC<br />

voltage output type<br />

0.010% of reading + 0.002% of range<br />

Input range DC ±100, 200 or 500A<br />

Input range AC ±100, 200 or 500Apk (70, 140 or 350Arms)<br />

Transfer ratio 10, 20 or 50A/V<br />

Output voltage 12Vmax with ≥2kΩ load<br />

Accuracy DC 0.020% of reading + 0.005% of range<br />

Accuracy AC<br />

General<br />

0.025% of reading + 0.005% of range<br />

Bandwidth DC … 100kHz (-3dB)<br />

Overload 120% (DC / AC)<br />

Supply voltage ±15Vdc (max. 1Apk)<br />

Dimensions 112x82x45mm<br />

Hole diameter 25mm<br />

sc1000 (split core) <strong>ch</strong>aracteristic specification<br />

current output type<br />

Input range DC ±1000A<br />

Input range AC ±1000Apk (700Arms)<br />

Transfer ratio 2000:1<br />

External burden 0…2Ω (at max. current)<br />

Accuracy DC / AC<br />

voltage output type<br />

0.01% of reading + 0.08% of range<br />

Input range DC ±400 or 1000A<br />

Input range AC ±400 or 1000Apk (280 or 700Arms)<br />

Transfer ratio 40 or 100A/V<br />

Output voltage 12Vmax with ≥2kΩ load<br />

Accuracy DC / AC<br />

General<br />

0.02% of reading + 0.08% of range<br />

Bandwidth DC … 100kHz (-3dB)<br />

Overload 110% (DC / AC)<br />

Supply voltage ±15Vdc (max. 0.6Apk)<br />

Dimensions 163x130x70mm<br />

Hole diameter 45mm<br />

Notes:<br />

Specification for ambient 25±10°C, humidity ≤90% (non condensing) and sinusoidal AC-currents. Junction unit system HUB4MACC available<br />

for supplying up to four MACC plus or four SC1000 with “current-in/current-out” or “current-in/voltage-out” option.<br />

Input currents with f > 1kHz must be de-rated according to the graph on the next page.<br />