Control System EDUS391004-M<br />

8.5.1 Example of Wiring<br />

� In the above system, the longest extension of wiring is 2950ft between (A) and (C), which satisfies the limit of 3280ft.<br />

And the total length is 3610ft, that is the total of 2950ft between (A) and (C) and 656ft between (B) and (D), which also<br />

satisfies the limit of 6560ft. The central controller functions properly, only when both the longest extension and the<br />

total length of wiring satisfies the limitation, as shown above.<br />

Caution:<br />

When designing the system, be sure to check both the longest extension and the total length of wiring. If it exceeds the<br />

limitation, there is no other way but to split into several systems.<br />

8.6 Connection Method<br />

8.6.1 Correct wiring<br />

� Series wiring method only should be used.<br />