16. Troubleshooting Guide<br />
16.1 Refrigeration Cycle System<br />
In order to diagnose malfunctions, make sure that there are no<br />
electrical problems before inspecting the refrigeration cycle.<br />
Such problems include insufficient insulation, problem with the<br />
power source, malfunction of a compressor and a fan.<br />
The normal outlet air temperature and pressure of the<br />
refrigeration cycle depends on various conditions, the standard<br />
values for them are shown in the table on the right.<br />
43<br />
Normal Pressure and Outlet Air Temperature (Standard)<br />
Cooling Mode<br />
Heating Mode<br />
Gas Pressure<br />
PSI<br />
(kg/cm 2 G)<br />
130.53 ~ 174.04<br />
(9 ~ 12)<br />
333.58 ~ 420.60<br />
(23 ~ 29)<br />
Outlet air<br />
Temperature<br />
(°F)<br />
53.6 ~ 60.8<br />
96.8 ~ 113<br />
Condition: <strong>Indoor</strong> fan speed = High<br />
<strong>Outdoor</strong> temperature 95°F at cooling mode<br />
and 44.6°F at heating mode.<br />
Compressor operate at rated frequency