Power Supply Unit should be capable of providing power supply to 18 channel cards, 18 nos sensors and alarm<br />

hooter.<br />

Cabinet: 1 NO<br />

Size: 19 inch<br />

Maximum Channel: 18 nos<br />

Mounting: Wall Mounted<br />

Hooter:<br />

Type: Industrial Hooter<br />

Power Supply: 24V DC/230 V AC<br />

Audible Range: 30 meter from control room in all directions<br />

C. Calibration Kit:<br />

A Gas calibration kit consisting of the following are to be provided along with the system.<br />

(i) Pressure Regulator<br />

(ii) Calibration Adapter<br />

(iii) Hose, Flowmeter<br />

(iv) Carrying case<br />

(v) Methane Cylinder- 2 nos<br />

(vi) Zero Gas Cylinder - 2 nos<br />

(vii) One hand held portable intrinsically safe calibrator# for onsite calibration of sensors. This calibrator should<br />

be certified by an accreditation body of National/International repute.<br />

D. An On-line UPS (Uninterrupted Power Supply) of minimum one hour duration to be provided along with the<br />

system. The above UPS should be of portable type & to be installed in Operator Room (Non-Hazardous area)<br />

or Air Compressor Shed, in case the operator room is situated in hazardous area. The approx distance of Air<br />

Compressor Shed may be around 50-100 meters from existing operator room. The UPS should handle<br />

unwanted extra high voltage charge for about few seconds & have protection facility to cut-off power to the<br />

control system cabinet.<br />

E. Cable & other Hardware:<br />

(i) For Sensor, 3C X 1.5 mm2, multistrand copper conductor, shielded armoured.<br />

(ii) For JB to Control System, 12C/24C X 1.5 mm2, multistrand copper conductor, shielded armoured. (DGMS<br />

approved).<br />

(iii) Length of cable:<br />

3-core (signal)= 200 meters (approx.)<br />

12/24 core (signal) = 700 meters (approx)<br />

3-core (power) = 200 meters (approx)<br />

(iv) FLP cable glands: as required<br />

(v) GI cable gland: as required<br />

Special Notes for all items:<br />

1.0 The bidder shall have single point responsibility for the complete package.<br />

2.0 The bidder has to provide detailed technical specifications along with all relevant technical catalogues, statutory<br />

certificates etc for technical evaluation. Otherwise, offers will not be evaluated and same will be rejected.<br />

2.1 Bidder shall also provide guidelines and proposed plans for configuration of sensor locations inside the Gas compressor<br />

shed and also for plant piping areas.<br />

<strong>Tender</strong> No. SDG7299P13/09 Page 13 of 25