(vi) Zero Gas Cylinder - 2 nos<br />

(vii) One hand held portable intrinsically safe calibrator# for onsite calibration of sensors. This calibrator should<br />

be certified by an accreditation body of National/International repute.<br />

D. An On-line UPS (Uninterrupted Power Supply) of minimum one hour duration to be provided along with the<br />

system. The above UPS should be of portable type & to be installed in Operator Room (Non-Hazardous area)<br />

or Air Compressor Shed, in case the operator room is situated in hazardous area. The approx distance of Air<br />

Compressor Shed may be around 50-100 meters from existing operator room. The UPS should handle<br />

unwanted extra high voltage charge for about few seconds & have protection facility to cut-off power to the<br />

control system cabinet.<br />

E. Cable & other Hardware:<br />

(i) For Sensor, 3C X 1.5 mm2, multistrand copper conductor, shielded armoured.<br />

(ii) For JB to Control System, 12C/24C X 1.5 mm2, multistrand copper conductor, shielded armoured. (DGMS<br />

approved).<br />

(iii) Length of cable:<br />

3-core (signal)= 200 meters (approx.)<br />

12/24 core (signal) = 700 meters (approx)<br />

3-core (power) = 200 meters (approx)<br />

(iv) FLP cable glands: as required<br />

(v) GI cable gland: as required<br />

ITEM 4 - Infrared (IR) On-Line Gas Monitoring System for GCS - Kathalguri<br />

1.0 Detailed Technical Specifications of On-Line Gas Monitoring System for GCS-Kathalguri shall comprise of the<br />

following:<br />

A.Detector/Gas Sensor required for Gas Compr Packages : 18 nos.<br />

Type:IR (Infrared), suitable for Area Detection of compressed/uncompressed Natural Gas (by volume:<br />

CH4:89.538%, N2:1.004%, CO2: 0.543%, C2H6: 4.132%, C3H8:2.491% & others: 2.292%) under ventilated<br />

shed<br />

Range: 0-100% LEL<br />

Wiring: 3-wire non-isolated<br />

Detector/sensor version: SMART<br />

Input Power Supply: +24 V DC<br />

Output: 4-20 mA + HART Digital Signal<br />

Sensor Enclosure material must be: Suitable for use in Hazardous area and corrosion free.<br />

Operating Humidity: 0-100 % RH non condensing<br />

Operating Temperature: 0 to +50 deg C<br />

Detectors must be suitable for hazardous environment i.e. Zone 1 & Zone 2 Hazardous area as per OMR, 1984.<br />

Approval of Detector/Sensor: Valid DGMS approval should be provided along with bid. Else Vendor should<br />

furnish written assurance to provide DGMS approval before dispatch with minimum 6 months validity.<br />

Accessories: Mounting Plate/Mounting Bracket/Splash guard/Cable Gland/Adapter/Explosion proof junction box/<br />

canopy etc to be provided along with the sensors.<br />

Sensor Calibration: Adjustment of Zero & Span on-site Non Intrusive one man calibration, should have facility to<br />

calibrate the instrument on spot without disconnecting from power supply by using any portable hand held<br />

Intrinsically safe calibrator.<br />

Sensor LED: ON- Healthy Condition<br />

OFF-Open/Fault Condition<br />

<strong>Tender</strong> No. SDG7299P13/09 Page 11 of 25