VCES-HRV-IOM-1 - HRV600i, HRV700i ... - Venmar CES Inc.

VCES-HRV-IOM-1 - HRV600i, HRV700i ... - Venmar CES Inc. VCES-HRV-IOM-1 - HRV600i, HRV700i ... - Venmar CES Inc.

venmarces.com
from venmarces.com More from this publisher

<strong>HRV</strong><br />

Heat Recovery Ventilators<br />

Installation, Operation and Maintenance Instructions Manual<br />

Capacity: 300 to 1,260 cfm<br />

Model: <strong>HRV</strong>600i, <strong>HRV</strong>700i, <strong>HRV</strong>1200i<br />

©2012 <strong>Venmar</strong> <strong>CES</strong> <strong>Inc</strong>.


Table of Contents<br />

Nomenclature......................................................................................................................................................................3<br />

Safety.Considerations..........................................................................................................................................................4<br />

Installation...........................................................................................................................................................................4<br />

Inspection.......................................................................................................................................................................4<br />

Mounting.Location.Requirements................................................................................................................................4<br />

Mounting.Options.........................................................................................................................................................5<br />

Ductwork........................................................................................................................................................................5<br />

Internal.Grilles.and.Diffusers........................................................................................................................................6<br />

Drains.............................................................................................................................................................................6<br />

Electrical.Connections...................................................................................................................................................6<br />

Controls................................................................................................................................................................................6<br />

General.Information......................................................................................................................................................6<br />

Sequence.of.Operation.................................................................................................................................................7<br />

Frost.Control..................................................................................................................................................................7<br />

Airflow.Measurement.and.Balancing.................................................................................................................................8<br />

Flow.Station.Positions...................................................................................................................................................8<br />

Balancing.Procedure......................................................................................................................................................8<br />

System.Service......................................................................................................................................................................9<br />

Bi-monthly.Maintenance...............................................................................................................................................9<br />

Annual.Maintenance.....................................................................................................................................................9<br />

Appendix.A:.Mounting.Diagrams.....................................................................................................................................11<br />

Appendix.B:.Unit.Dimensions...........................................................................................................................................12<br />

Appendix.C:.Flow.Station.Positions..................................................................................................................................17<br />

Appendix.D:.Drain.Connections........................................................................................................................................18<br />

Appendix.E:.Terminal.Control.Diagrams..........................................................................................................................19<br />

Appendix.F:.Electrical.Connection.Diagrams...................................................................................................................21<br />

Appendix.G:.Make-up.Heat.Requirements......................................................................................................................22<br />

Appendix.H:.Troubleshooting...........................................................................................................................................23<br />

Manufacturer reserves the right to discontinue or change specifications or designs without notice or obligation.<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 2


<strong>HRV</strong>600i Nomenclature (300–750 cfm)<br />

1. FROST CONTROL<br />

D – Recirc defrost 1<br />

E – Exhaust only<br />

N – Non-defrost<br />

2. ENERGY RECOVERY<br />

P – Poly core<br />

A – Aluminum core<br />

H – HM core<br />

3. EXTERNAL FINISH<br />

W – White prepaint package<br />

Note:<br />

1 The recirculation defrost damper module is factory installed.<br />

<strong>HRV</strong>700i Nomenclature (300–800 cfm)<br />

1. FROST CONTROL<br />

D – Recirc defrost<br />

N – Non-defrost<br />

<strong>HRV</strong>1200i Nomenclature (700–1,250 cfm)<br />

1. FROST CONTROL<br />

D – Recirc defrost 1<br />

E – Exhaust only<br />

N – Non-defrost<br />

2. ENERGY RECOVERY<br />

P – Poly core<br />

A – Aluminum core<br />

H – HM core<br />

3. EXTERNAL FINISH<br />

W – White prepaint package<br />

C – Corrosion resistance package<br />

Note:<br />

1 The recirculation defrost damper module is factory installed.<br />

Nomenclature<br />

1 2 3 4<br />

1 2<br />

1 2 3 4<br />

©<strong>Venmar</strong> <strong>CES</strong> <strong>Inc</strong>. 2012. All rights reserved throughout the world.<br />

6. LOW SPEED<br />

L – Reduced low speed<br />

N – Normal low speed<br />

5. AC<strong>CES</strong>S DOOR<br />

S – Standard door<br />

R – Reverse door<br />

(right hand flow)<br />

4. MEF FILTRATION<br />

M – MEF supply filtration<br />

X – No MEF supply filtration<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 3<br />

5 6<br />

5 6<br />

2. EXTERNAL FINISH<br />

C – Corrosion resistant package<br />

6. LOW SPEED<br />

L – Reduced low speed<br />

N – Normal low speed<br />

5. AC<strong>CES</strong>S DOOR<br />

S – Standard door<br />

R – Reverse door<br />

(right hand flow)<br />

4. MEF FILTRATION<br />

M – MEF supply filtration<br />

X – No MEF supply filtration<br />

Illustrations cover the general appearance of <strong>Venmar</strong> <strong>CES</strong> products at the time of publication and <strong>Venmar</strong> <strong>CES</strong> reserves the<br />

right to make changes in design and construction at any time without notice.


Warning, Caution and Important notes appear throughout<br />

this manual in specific and appropriate locations to<br />

alert Installing Contractors and maintenance or service<br />

personnel of potential safety hazards, possible equipment<br />

damage or to alert personnel of special procedures or instructions<br />

that must be followed as outlined below.<br />

! WaRnIng<br />

Identifies an instruction which, if not followed, might cause<br />

serious personal injuries including possibility of death.<br />

CautIon<br />

Identifies an instruction which, if not followed, might severely<br />

damage the unit, its components, the assembly or<br />

final installation.<br />

IMpoRtant<br />

Indicates supplementary information needed to fully<br />

complete an instruction or installation.<br />

Inspect the exterior of the unit for shipping damage by ensuring<br />

that there is no damage to the door, door latches,<br />

door hinges, damper, duct collars, cabinet, etc. Inspect the<br />

interior of the unit for damage by ensuring that the fan<br />

motors and housings, heat exchanger, insulation, dampers,<br />

actuators and drain pans are all intact.<br />

When determining an installation location, the unit must<br />

be mounted in a heated area to prevent condensate drain<br />

lines from freezing. The mounting location should be away<br />

from occupied areas to provide quiet operation. The area<br />

should also be easily accessible for maintenance.<br />

IMpoRtant<br />

These Heat Recovery Ventilators have minimum clearance<br />

requirements when mounting. See Appendix B for<br />

specific clearance requirements. Mounting options must<br />

allow 6” [152 mm] clearance in front of control cover for<br />

access.<br />

Safety Considerations<br />

Installation<br />

Inspection<br />

Mounting.Location.Requirements<br />

Hazards may exist within this equipment because it contains<br />

electrical and powerful moving components. Only<br />

qualified service personnel should install or service this<br />

equipment. Untrained personnel can perform basic maintenance<br />

such as maintaining filters. Observe precautions<br />

marked in the literature and on labels attached to the unit.<br />

Follow all safety codes.<br />

! WaRnIng<br />

Disconnect the main power switch to the unit before performing<br />

service or maintenance. Electric shock can cause<br />

personal injury.<br />

If transportation damage is found, file a claim immediately<br />

with the transportation agency. Remove all packaging,<br />

tape, etc. from the cabinet.<br />

A mounting location close to an exterior partition will<br />

minimize the length of insulated duct. The unit should be<br />

close to a drain and 120 volt, 60 Hz power supply. The<br />

unit should be mounted away from hot chimneys, electrical<br />

panels and other hazards. The area should also be easily<br />

accessible for maintenance.<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 4


There are several options for hanging or floor mounting<br />

the unit.<br />

IMpoRtant<br />

In all cases, the unit must be level. Consult local building<br />

code for restrictions in your area regarding installation.<br />

Hang the unit with the reinforced rubber straps provided<br />

as shown in Appendix A. Check with local building codes<br />

regarding the use of rubber straps in commercial buildings.<br />

Attach the straps to the unit with two #8 screws provided.<br />

Then attach the other end of the strap to the ceiling<br />

joists, trusses, custom frame, etc.<br />

The unit can also be hung with 3/8” [10 mm] threaded<br />

rod and U-channels or angles (not supplied) as shown in<br />

Appendix A.<br />

The supply and exhaust duct connections on the unit are<br />

as follows:<br />

Table 1: Supply and Exhaust Duct Connection Sizes<br />

unit Duct Size<br />

600 CFM or 700 CFM 14” x 8” [356 x 203 mm]<br />

1,200 CFM 20” x 8” [508 x 203 mm]<br />

IMpoRtant<br />

Duct sizes are for connection purposes only. Ducts should<br />

be sized to keep noise and pressure drop to a minimum.<br />

The supply and exhaust ducts connected to outside, as<br />

well as any ducts passing through an unconditioned space,<br />

must have a minimum insulation value of R5. In addition,<br />

a continuous integral vapor barrier over the duct insulation<br />

must be used.<br />

Air balancing dampers are recommended for both supply<br />

and exhaust ducts to allow for adjustment of airflow. Also,<br />

flexible canvas connectors should be installed close to the<br />

unit in the supply duct to the building and the exhaust<br />

duct from the building to reduce noise transmission from<br />

the unit to the building (see Appendix C).<br />

All ports on the 600 and 1,200 cfm units have 1” [25 mm]<br />

flanges to facilitate the installation of the ductwork. Please<br />

note that the outdoor air opening port has a frost control<br />

Mounting.Options<br />

Ductwork<br />

When installing the unit, keep in mind that access to the<br />

control panel may be required. Supply and exhaust ducts<br />

to outside may have 1” to 2” [25 to 51 mm] of insulation<br />

on them. Rubber vibration isolation may be required and is<br />

recommended for quiet operation.<br />

The unit can also be mounted on a metal or wooden<br />

curb (not supplied) bolted to the floor as shown in Appendix<br />

A. Space must be left under the unit to allow<br />

connection of drain lines. A gradual slope is required for<br />

the condensate water to drain by gravity (minimum ¼”<br />

per foot) [6 mm per 305 mm]. If this is not possible, a<br />

pump should be used. If attachment of the unit to the<br />

curb is required, ensure that screws, bolts and mounting<br />

hardware do not interfere with moving parts or that the<br />

integrity of the cabinet insulation is not affected.<br />

damper incorporated with it. Ensure that any mechanical<br />

fasteners used to connect the duct do not interfere with<br />

the operation of the damper. Screws can be installed on<br />

the side of the cabinet rather than the flange for this port<br />

only. For port locations see Appendix B.<br />

All ports on the 700 cfm unit have 2” [51 mm] flanges to<br />

facilitate the installation of the ductwork. Please note the<br />

outdoor air opening connection is factory set to be the left<br />

side upper port. It is possible to reverse the operation of<br />

the frost control damper in order to use the port on top of<br />

the cabinet for outdoor air opening connection.<br />

To change the outdoor air opening from the side to the<br />

top use the following directions. For port locations see Appendix<br />

B.<br />

Remove the cover of the damper motor with a flat screw<br />

driver. Reverse the orange and red wires by moving the orange<br />

from Terminal #2 to Terminal #3 and moving the red<br />

wire from Terminal #3 to Terminal #2. The end result, in<br />

order to have the outdoor air opening connection to the<br />

top port, will be: #1 – white, #2 – red, #3 – orange.<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 5


Locate exhaust grilles and supply diffusers to provide effective<br />

ventilation and avoid short circuiting of airflows.<br />

Adjustable dampers should be provided at every grille and<br />

diffuser location to make balancing of the system possible.<br />

A proper selection of style and size of grilles and diffusers<br />

is required to minimize pressure drop. The velocity of the<br />

airflow should not exceed 400 feet per minute [2 meters<br />

per second] for normal applications.<br />

The drain fittings provided with the unit will accept a ¾”<br />

[19 mm] NPT coupler (supplied by others). The drain line<br />

for the unit must be fabricated on site and connected to<br />

the building main. A loop in the hose or trap in the copper<br />

or plastic pipe must be provided to prevent sewer gases<br />

from entering the unit when connecting to a drain as illustrated<br />

in Appendix D.<br />

power<br />

A terminal block and strain relief bushing or a junction box<br />

is provided for line voltage to make the necessary power<br />

connections.<br />

The electrical requirements are as follows:<br />

Table 2: Electrical Requirements<br />

600 CfM 700 CfM 1,200 CfM<br />

Voltage 120V 120V 120V<br />

MCa 9.5 6.6 14.3<br />

Mop 12.0 9.0 20.0<br />

fan Interlock Switch (ff)<br />

External fan control can be achieved by connecting an<br />

external fan source (G) through dry contacts (FF). These<br />

contacts are closed on a call for ventilation or frost control.<br />

Speed Selection (600 cfm/1,200 cfm only)<br />

There are three speed settings available with the controls,<br />

only two of which can be functional at any one time. The<br />

units are factory set to use the low and high speed taps<br />

Internal.Grilles.and.Diffusers<br />

Drains<br />

Electrical.Connections<br />

Controls<br />

General.Information<br />

The duct system should be designed according to the high<br />

speed flow rate of the unit. In order to keep the noise and<br />

pressure drop to a minimum, a maximum air velocity of<br />

1,100 feet per minute [5.6 meters second] should be used<br />

in calculations in duct design. The duct runs should be<br />

kept as short as possible with the minimum amount of elbows<br />

and transitions. The manufacturer recommends the<br />

use of smooth radius elbows or square elbows with turning<br />

vanes to achieve maximum performance.<br />

IMpoRtant<br />

Consult local building code for plumbing requirements<br />

in your area. If copper pipe is to be used, ensure not to<br />

solder to the ¾” [19 mm] coupler while it is attached to<br />

the plastic drain fitting as deformation may occur. Ensure<br />

adequate slope is present to allow good drainage (minimum<br />

¼” per foot [6 mm per 305 mm]).<br />

Control Box access for Low Speed Setting<br />

(600 cfm/1,200 cfm only)<br />

Disconnect power to the unit. Remove the four screws<br />

securing the cover plate as shown in Appendix F. Lift off<br />

the control cover plate and switch the red wire as shown<br />

in Appendix F.<br />

on the blower motors. If necessary, the medium speed<br />

tap can be used instead of the low speed tap. See Appendix<br />

F for instructions on how to make this change. Units<br />

without the remote wall control option can be shut off by<br />

opening the contact between Low-Com or High-Com as<br />

shown in Appendix E, Terminal Label.<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 6


Before start-up, check the unit for obstructive packaging,<br />

objects near or in blowers, dampers, heat exchangers, etc.<br />

Once installation is complete, check all modes of operation<br />

to ensure that the unit is working properly. Close the<br />

doors and check for operation on Low, Com and High.<br />

Use a wall control or the dry contact switching to run fan<br />

speeds as shown in Appendix E, Wall Control Connection.<br />

The 700 cfm unit is two-speed. Low speed can be initiated<br />

by creating a closure across Low-Com or high speed can<br />

be initiated by creating a closure across High-Com.<br />

unit Check points<br />

• Power connected, no ventilation call – Both fans<br />

are off, frost control damper (if equipped) closes off<br />

fresh air from outside.<br />

• Power connected, low speed call – Both fans on low<br />

speed, internal frost control damper (if equipped)<br />

opens fresh air from outside. If equipped with recir-<br />

The unit functions are controlled by integrated controls in<br />

the unit which may include exhaust only defrost or recirculation<br />

defrost. During cold outdoor air temperatures, frost<br />

control cycles will remove frost from the heat exchanger to<br />

maintain continuous operation.<br />

Exhaust only Defrost (optional)<br />

Frost removal occurs when the supply blower de-energizes,<br />

the outside air damper and the heat exchanger<br />

damper close and the exhaust fan continues to draw only<br />

warm room air through the flat plate heat exchanger to<br />

maintain ventilation. This process removes the build-up of<br />

ice in the heat exchanger. Frost control is initiated at an<br />

outdoor air temperature of 23°F [−5°C]. The defrost/ventilation<br />

cycle is time based.<br />

! WaRnIng<br />

A negative building pressure may develop during the exhaust<br />

only frost control cycle with possible backdrafting<br />

of fumes from combustion equipment.<br />

Recirculation Defrost (optional)<br />

The recirculation frost control cycle is electronically controlled<br />

in response to the outside air temperature. On a<br />

call for defrost, the outside air damper closes, the exhaust<br />

fan is de-energized and the supply fan circulates warm<br />

air through the flat plate heat exchanger to remove the<br />

build-up of ice. For the <strong>HRV</strong>700i, it is possible to extend<br />

the frost control times during very cold weather by removing<br />

the jumper JU1-F on the circuit board. Frost control is<br />

Sequence.of.Operation<br />

Frost.Control<br />

culation module, the internal frost control damper<br />

closes recirculation opening.<br />

• Power connected, high speed call – Both fans on<br />

high speed, frost control damper opens fresh air<br />

from outside. If equipped with recirculation module,<br />

the internal frost control damper closes recirculation<br />

opening.<br />

• Power connected, occupied timer/sensor connection<br />

open (unoccupied mode) – Both fans are off,<br />

frost control damper closes fresh air from outside. If<br />

equipped with recirculation module, the internal frost<br />

control damper opens recirculation opening.<br />

• Power connected, FF control contacts close during<br />

unit ventilation or frost control cycle.<br />

initiated at an outdoor air temperature of 23°F [−5°C]. The<br />

defrost/ventilation cycle is time based.<br />

Table 3: Recirculation and Exhaust Only Defrost<br />

<strong>HRV</strong> type of<br />

Stage<br />

Model Defrost<br />

Initiate<br />

temperature<br />

Ventilation time<br />

(Minutes) Defrost<br />

time/Run time<br />

Standard Extended<br />

Remote Wall Control (optional)<br />

Remote mounted wall control options are solid state controls<br />

that can be used to control the ventilators from a<br />

remote location. The connection from the ventilator to the<br />

control is low voltage and requires a four conductor (24<br />

gauge minimum) LVT cable. Models are available with a<br />

dehumidistat control and speed switching. The following<br />

three options are available:<br />

Standard.Wall.Control<br />

Dehumidistat to engage high speed exchange. Slide switch<br />

operation supporting continuous low exchange and continuous<br />

high exchange.<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 7<br />

600i<br />

1200i<br />

700i<br />

1<br />

2<br />

3<br />

1<br />

2<br />

3<br />

R/E<br />

R/E<br />

R/E<br />

R<br />

R<br />

R<br />

23ºF<br />

5ºF<br />

−21ºF<br />

23ºF<br />

5ºF<br />

−21ºF<br />

−5ºC<br />

−15ºC<br />

−30ºC<br />

−5ºC<br />

−15ºC<br />

−30ºC<br />

12/60<br />

12/24<br />

12/12<br />

6/60<br />

6/32<br />

6/19<br />

N/A<br />

N/A<br />

N/A<br />

10/28<br />

10/28<br />

10/15


Xtra.Wall.Control<br />

Dehumidistat to engage high speed exchange. Electronic<br />

push button operation supporting intermittent (standby)<br />

ventilation, continuous low exchange, continuous high<br />

exchange, maintenance indicator light and exchange indicator<br />

light.<br />

Aqua.Air.Wall.Control<br />

Ideal for pool dehumidification. Dehumidistat to engage<br />

high speed exchange. Electronic push button operation<br />

supporting intermittent (standby) ventilation, continuous<br />

low exchange, continuous high exchange, maintenance<br />

indicator light and exchange indicator light.<br />

Airflow Measurement and Balancing<br />

Once installation is complete, the supply and exhaust airflows<br />

should be balanced to ensure proper operation and<br />

a good quality installation. A well designed duct system<br />

with properly sized duct runs and equal static pressure<br />

losses of both the supply and exhaust will aid in balancing<br />

the unit. However, it will be necessary to take flow<br />

Whether flow stations are permanently installed or used<br />

temporarily, the position they are placed in is very important<br />

to ensure accuracy as shown in Appendix C. The best<br />

locations for mounting the FMS is in the long straight sections<br />

of ducting where airflow has stabilized across the<br />

area of the duct. This position will provide the most accurate<br />

measurements.<br />

The next best location for the FMS is immediately before<br />

or after a 90 degree elbow and 12” [305 mm] from any<br />

damper. In straight sections of pipe, the FMS should be<br />

installed at least 30” [762 mm] from any fan outlet. This<br />

applies to the supply air opening connection on the heat<br />

recovery ventilator and the exhaust air opening connection.<br />

Before proceeding with balancing, all windows, overhead<br />

doors and walk-in doors should be closed and exhaust systems<br />

should be turned off.<br />

The connections between the flow stations and the ducts<br />

must be sealed with tape. Mount the magnehelic gauge in<br />

a convenient location where it is level and will not vibrate<br />

or be bumped. Zero the gauge. Measure the exhaust air<br />

first as it is often the lowest due to a longer duct system.<br />

With the fan speed at maximum, connect the hoses from<br />

the FMS to the magnehelic gauge. If the needle falls<br />

Flow.Station.Positions<br />

Balancing.Procedure<br />

measurements with the proper equipment to ensure a<br />

balanced system. Magnehelic gauges and flow measuring<br />

stations (FMS) are available for 14” x 8” [356 x 203 mm]<br />

or 20” x 8” [508 x 203 mm] rectangular duct and a range<br />

of round duct sizes. Please ask your supplier for more information.<br />

With airflow measuring stations permanently installed,<br />

balancing is done by measuring airflow on one side of the<br />

heat recovery ventilator and then the other. Adjustments<br />

can then be made to the damper to equalize airflows.<br />

When using the temporary method, an FMS is installed in<br />

one air duct of the heat recovery ventilator and the flow<br />

recorded. The FMS is then relocated to the other air duct<br />

and the airflow is recorded again. Dampers can then be<br />

adjusted to equalize airflow. This procedure should be repeated<br />

to ensure that the unit is balanced properly.<br />

below zero, reverse the hose connections. Ensure that the<br />

damper is wide open. Take a reading from the magnehelic<br />

gauge and record it. Remove the FMS and place it in the<br />

supply duct. This process is not necessary if the FMS is to<br />

be permanently mounted.<br />

Repeat the procedure. If the reading is higher in the supply<br />

duct, adjust the damper until the reading is the same.<br />

If the reading is lower, return the FMS to the exhaust duct<br />

and adjust the damper to obtain the same reading as the<br />

supply duct.<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 8


! WaRnIng<br />

Disconnect power before maintaining the unit.<br />

Bi-monthly maintenance should include:<br />

air filters<br />

The standard foam filters are washable. Under normal<br />

conditions it is recommended that they be cleaned every<br />

two months. More frequent cleaning may be required<br />

under extremely dirty operating conditions. Use a vacuum<br />

cleaner to remove the heaviest portion of accumulated<br />

dirt, then wash with warm water.<br />

A medium efficiency filter for the supply airstream is available<br />

from your supplier. This filter is disposable and should<br />

be replaced when it becomes dirty.<br />

MEF filter (optional)<br />

Figure 1: Filters – 600 cfm and 1,200 cfm<br />

Annual maintenance should include:<br />

air filters<br />

Vacuum and wash standard foam filters. Replace medium<br />

efficiency filter if present.<br />

Drain pans and Interior of unit<br />

Wash the foil faced insulation surfaces and wipe the drain<br />

pans with a soft cloth and mild cleaning solution. Check<br />

the drain fittings to ensure they are draining freely.<br />

flat plate Heat Exchanger<br />

! WaRnIng<br />

Hot water and strong cleaning agents could damage the<br />

heat exchanger. Ensure the heat exchanger is returned to<br />

the unit in the correct orientation. Failure to do so may<br />

result in damage to the exchanger. Follow instructions on<br />

the label.<br />

The flat plate heat exchanger must be handled with care.<br />

Remove the flat plate heat exchangers by sliding them out<br />

System Service<br />

Bi-monthly.Maintenance<br />

Washable foam filter<br />

Annual.Maintenance<br />

Drain pans and Interior of unit<br />

With the filters removed from the unit, the foil faced insulation<br />

surfaces and drain pans should be wiped clean with<br />

a soft cloth and mild cleaning solution. Ensure that the<br />

drain fittings are free from dirt and draining freely.<br />

Washable<br />

foam filter<br />

Figure 2: Filters – 700 cfm<br />

Washable foam filter or<br />

MEF filter (optional)<br />

from the tracks holding them in place. In order to ensure<br />

maximum efficiency of the partitions, it is recommended<br />

that the heat exchanger be cleaned once a year following<br />

the season of most intense use. For polypropylene and aluminum<br />

media, allow the heat exchanger to soak for three<br />

hours in warm water and mild soap. Rinse under a heavy<br />

stream of water. For HM heat exchangers, use a vacuum<br />

cleaner or low pressure air. It is not recommended to use<br />

solvents or detergents as these may damage the media<br />

or structure of the heat exchanger. When replacing the<br />

flat plate heat exchanger sections, ensure they are of the<br />

proper vertical orientation. Failure to do so may result in<br />

low airflow on the exhaust airstream due to system pressure<br />

trapping or holding condensate in the flutes.<br />

fans<br />

Blower wheels and fan housing should be checked for<br />

dirt buildup. If they appear dirty, it may be necessary to<br />

remove the blower assembly and then vacuum the dust<br />

out through the fan mouth. See Figure 3 and Figure 4 for<br />

instructions on removing the blower assembly.<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 9


System operation Check<br />

Verification of all control modes should be checked to ensure<br />

proper operation. Refer to Sequence of Operation.<br />

testing and Replacement of the Damper<br />

actuator<br />

Check damper operation by switching between Low-Com<br />

or High-Com on the dry contact terminal or by switching<br />

through the modes on the optional remote wall control.<br />

If the damper does not respond in one or both directions,<br />

check all connections.<br />

700.cfm.Only<br />

Check for 24 volt output between the white/red and the<br />

white/orange wires at the damper motor. If 24 volts can<br />

be measured at the damper motor, the problem is either<br />

in the connections, the frost control relay or the main circuit<br />

board.<br />

600.and.1,200.cfm.Only<br />

CautIon<br />

120 VAC.<br />

With the unit powered but off, check for 120 volt output<br />

across the white/black wires. If 120 volt can be measured<br />

at the motor, replace the motor. If 120 volt cannot be<br />

measured at the motor, check for 120 volts across pins<br />

J1-9 and J1-1 at the printed circuit board.<br />

Main Circuit Board Replacement<br />

The main circuit board must be replaced if an electronic<br />

problem arises. For example, the unit suddenly stops, the<br />

unit stays in frost control mode all the time or if control<br />

functions are not working properly.<br />

Ensure that power is reaching the board. Test the blower<br />

motors and damper actuators for operation when directly<br />

connected to the appropriate power voltage. If the motor<br />

and damper actuators function normally, replace the main<br />

circuit board.<br />

Motor and Blower Removal and Installation<br />

Disconnect power from the unit. To determine if the fan<br />

motor is burned out, disconnect the four-wire service<br />

connector between the motor and cabinet. Connect the<br />

motor directly to a 120 volt power source with an electrical<br />

cable as follows:<br />

Table 4: Motor Connections<br />

Red + White Low speed<br />

Blue + White Medium speed<br />

Black + White High speed<br />

If the motor functions normally, there is a problem with<br />

the wiring connections or the main circuit board. Check all<br />

wiring and replace main circuit board if necessary.<br />

If the blower does not run, it must be replaced. To replace<br />

the motor, remove the flat plate heat exchanger from the<br />

unit. Disconnect the four-wire service connector from the<br />

unit. Remove the fasteners holding the motor assembly<br />

in place. Lift the assembly up and out, using one hand<br />

under the motor and one hand to steady it. Remove the<br />

assembly carefully from the unit to avoid damage to the<br />

insulation, shelf, etc. Install the repaired motor assembly<br />

by following these instructions in reverse.<br />

Remove these<br />

two screws<br />

Locking plate<br />

Capacitor<br />

Figure 3: Blower assembly removal – 600 cfm and 1,200 cfm<br />

Figure 4: Blower assembly removal – 700 cfm<br />

Thumbscrew<br />

Service<br />

connector<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 10


Reinforced<br />

rubber strap<br />

Appendix A: Mounting Diagrams<br />

Recirculation<br />

module<br />

Recirculation<br />

module<br />

Bolt to floor<br />

Space must be left to allow connection of<br />

drain lines with adequate slope for drainage<br />

Figure A1: Mounting – 600 cfm and 1,200 cfm<br />

Dry contacts<br />

Figure A2: Mounting – 700 cfm<br />

U channel<br />

(supplied by others)<br />

Rubber vibration isolator<br />

(supplied by others)<br />

Wooden curb (supplied by others)<br />

3/8” [10 mm]<br />

threaded rod<br />

(supplied by others)<br />

Cabinet mounted<br />

U channel<br />

Rubber vibration<br />

isolator<br />

Note: Diagrams show standard unit configuration.<br />

For units with the reversed door option, the door<br />

will be located here.<br />

Dry contacts<br />

3/8” [10 mm]<br />

threaded rod<br />

(supplied by others)<br />

Bolt to floor<br />

Wooden curb<br />

(supplied by others)<br />

Space must be left to allow<br />

connection of drain lines with<br />

adequate slope for drainage<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 11


Notes: Dimensions in [ ] are millimeters.<br />

Center of gravity<br />

Direction of airflow<br />

B<br />

A<br />

12.005”<br />

[305]<br />

HM Core<br />

Kg<br />

19<br />

12<br />

25<br />

16<br />

72<br />

LBS<br />

41<br />

27<br />

56<br />

35<br />

159<br />

PTS<br />

A<br />

B<br />

C<br />

D<br />

Total<br />

Aluminum Core<br />

PTS LBS Kg<br />

A 40 18<br />

B 26 12<br />

C 55 25<br />

D 34 15<br />

Total 155 70<br />

Kg<br />

17<br />

11<br />

24<br />

15<br />

67<br />

<strong>HRV</strong>600i<br />

Poly Core<br />

PTS LBS<br />

A 38<br />

B 25<br />

C 52<br />

D 33<br />

Total 148<br />

Connection Table<br />

Connection Sizes<br />

Line voltage in 14 gauge wire nut<br />

Condensate drain fitting (2x) 3/4” MPT<br />

C D<br />

13.375”<br />

[340]<br />

Appendix B: Unit Dimensions<br />

TOP VIEW<br />

28.005”<br />

[711]<br />

23.500”<br />

[597]<br />

34.000”<br />

[864]<br />

5.859" [149]<br />

A Line voltage<br />

6.500”<br />

[165]<br />

14.000”<br />

[356]<br />

Strap mounting<br />

location<br />

2.750”<br />

[70]<br />

Figure B1: Unit dimensions – 600 cfm (with exhaust only defrost)<br />

A<br />

B<br />

14.000”<br />

[356]<br />

4.000”<br />

[102]<br />

4.028”<br />

[102]<br />

8.000”<br />

[203]<br />

Exhaust air<br />

Exhaust air<br />

opening<br />

8.000”<br />

[203]<br />

Outdoor air<br />

opening<br />

Outdoor air<br />

24.500”<br />

[622]<br />

4.000” [102]<br />

8.000”<br />

[203]<br />

4.000”<br />

[102]<br />

Supply air<br />

Low voltage<br />

terminal strips<br />

8.000”<br />

[203]<br />

Return air<br />

opening<br />

Return air<br />

Supply air<br />

opening<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 12<br />

3.535” [90]<br />

Control box<br />

access<br />

14.103”<br />

[358]<br />

7.705”<br />

[196]<br />

5.125”<br />

[130]<br />

19.207”<br />

[488]<br />

10.005”<br />

[254]<br />

B Condensate drain<br />

Note: For units with the reversed door option, interior<br />

components will appear as a mirror image of the above diagram.<br />

Reversed<br />

door option<br />

RIGHT VIEW<br />

FRONT VIEW<br />

LEFT VIEW<br />

Note: This model has a damper located on the outdoor intake connection. This damper will close during a frost control cycle or when the unit is placed in the ‘Off‘ position with power maintained to the unit. This damper is not designed as a<br />

backdraft damper and will remain open if power is disconnected from the unit for any reason.<br />

Note: A minimum of 15.000” [381] clearance from any obstruction is required for<br />

removal of heat recovery cores, fans, etc.<br />

The access door can be removed from the cabinet with only 2.000” [51] of clearance.<br />

Note: A minimum of 12.000” [305] clearance from any<br />

obstruction is required for removal of the control box.<br />

Access door<br />

Control plate<br />

Heat recovery core<br />

Reversed<br />

door option<br />

15.000”<br />

[381]<br />

12.000”<br />

[305]<br />

RIGHT VIEW<br />

FRONT VIEW


Note: Dimensions in [ ] are millimeters.<br />

600i (with recirculation defrost)<br />

Poly Core 197 LBS [90 kg]<br />

Aluminum Core 204 LBS [93 kg]<br />

HM Core 208 LBS [95 kg]<br />

Connection Table<br />

Connection Sizes<br />

A Line voltage in 14 gauge wire nut<br />

B Condensate drain fitting (2x) ¾” MPT<br />

28.120”<br />

[714]<br />

49.550”<br />

[1,259]<br />

7.100”<br />

[180]<br />

14.000”<br />

[356]<br />

2.750”<br />

[70]<br />

Strap mounting<br />

location<br />

14.000”<br />

[356]<br />

4.000” [102]<br />

1.750”<br />

[44]<br />

34.000”<br />

[864]<br />

Line voltage in<br />

A<br />

8.000”<br />

[203]<br />

Outdoor air<br />

opening<br />

Outdoor air<br />

Exhaust air<br />

8.000”<br />

[203]<br />

Exhaust air<br />

opening<br />

4.000”<br />

[102]<br />

Dry contacts<br />

4.000”<br />

24.500” [102]<br />

[622]<br />

8.000”<br />

[203]<br />

Return air<br />

opening<br />

Return air<br />

Supply air<br />

8.000”<br />

[203]<br />

Supply air<br />

opening<br />

3.530”<br />

[90]<br />

1.750”<br />

[44]<br />

For recirc defrost only<br />

19.207”<br />

[488]<br />

Control box<br />

14.100”<br />

[358]<br />

Access door<br />

5.125”<br />

[130]<br />

Reversed door option<br />

Condensate drain<br />

B<br />

Note:<br />

For units with the reversed door option, interior components will appear<br />

as a mirror image of the above diagram.<br />

Figure B2: Unit dimensions – 600 cfm (with recirculation defrost)<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 13<br />

RIGHT VIEW<br />

FRONT VIEW<br />

LEFT VIEW<br />

Note: A minimum of 15.000” [381] clearance from any obstruction is required for removal<br />

of heat recovery cores, fans, etc.<br />

The access door can be removed from cabinet with only 2.000” [51] of clearance.<br />

Note: A minimum of 12.000” [305] clearance from any obstruction<br />

is required for removal of the control box.<br />

Access<br />

door<br />

Control panel<br />

Heat<br />

recovery core<br />

15.000”<br />

[381]<br />

12.000”<br />

[305]<br />

Reversed<br />

door option<br />

RIGHT VIEW<br />

FRONT VIEW


Notes: Dimensions in [ ] are millimeters.<br />

Center of gravity<br />

Direction of airflow<br />

B<br />

A<br />

HM Core<br />

20.620”<br />

[524]<br />

Kg<br />

27<br />

20<br />

27<br />

20<br />

94<br />

LBS<br />

59<br />

43<br />

59<br />

43<br />

204<br />

PTS<br />

A<br />

B<br />

C<br />

D<br />

Total<br />

Aluminum Core<br />

PTS LBS Kg<br />

A 57 26<br />

B 41 19<br />

C 57 26<br />

D 41 19<br />

Total 196 90<br />

Kg<br />

25<br />

18<br />

25<br />

18<br />

86<br />

<strong>HRV</strong>1200i<br />

Poly Core<br />

PTS LBS<br />

A 54<br />

B 39<br />

C 54<br />

D 39<br />

Total 186<br />

Connection Table<br />

Connection Sizes<br />

Line voltage in 14 gauge wire nut<br />

Condensate drain fitting (2x) ¾” MPT<br />

C D<br />

14.250”<br />

[362]<br />

9.878”<br />

[251]<br />

20.000”<br />

[508]<br />

11.000”<br />

[279]<br />

41.206”<br />

[1,047]<br />

40.326”<br />

[1,024]<br />

Figure B3: Unit dimensions – 1,200 cfm (with exhaust only defrost)<br />

A<br />

B<br />

TOP VIEW<br />

5.715”<br />

[145]<br />

Strap mount<br />

location<br />

34.000”<br />

[864]<br />

20.000”<br />

[508]<br />

10.000”<br />

[254]<br />

Line voltage in<br />

A<br />

8.000”<br />

[203]<br />

Outdoor<br />

air opening<br />

2.750”<br />

[70]<br />

Exhaust air<br />

8.000”<br />

[203]<br />

Outdoor air<br />

4.028”<br />

[102]<br />

Exhaust air<br />

opening<br />

24.500”<br />

[622]<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 14<br />

4.000”<br />

[102]<br />

8.000”<br />

[203]<br />

Return<br />

air opening<br />

4.000”<br />

[102]<br />

Supply air<br />

Low voltage<br />

terminal strips<br />

Return air<br />

Supply air<br />

opening<br />

20.000”<br />

[508]<br />

Access door<br />

B Condensate drain<br />

19.207”<br />

5.125”<br />

[488]<br />

[130]<br />

Note: For units with the reversed door option, interior components<br />

will appear as a mirror image of the above diagram.<br />

Control box<br />

access<br />

11.325”<br />

[288]<br />

Reversed<br />

door option<br />

RIGHT VIEW<br />

FRONT VIEW<br />

LEFT VIEW<br />

Note: This model has a damper located on the outdoor intake connection. This damper will close during a frost control cycle or when the unit is placed in the ‘Off’ position with power maintained to the unit. This damper is not designed as a backdraft damper and<br />

will remain open if power is disconnected from the unit for any reason.<br />

Note: A minimum of 15.000” [381] clearance from any obstruction<br />

is required for removal of heat recovery cores, fans, etc.<br />

The access door can be removed from the cabinet with only 2.000” [51] of clearance.<br />

NOTE: A minimum of 12.000” [305] clearance from any obstruction<br />

is required for removal of the control box.<br />

Access<br />

door<br />

Control cover<br />

Heat recovery<br />

core<br />

15.000”<br />

[381]<br />

12.000”<br />

[305]<br />

Reversed<br />

door option<br />

RIGHT VIEW<br />

FRONT VIEW


Note: Dimensions in [ ] are millimeters<br />

1200i (with recirculation defrost)<br />

Poly Core 247 LBS [112 kg]<br />

Aluminum Core 257 LBS [117 kg]<br />

HM Core 264 LBS [120 kg]<br />

Connection Table<br />

Connection Sizes<br />

A Line voltage in 14 gauge wire nut<br />

B Condensate drain fitting (2x) ¾” MPT<br />

41.240”<br />

[1,047]<br />

10.000”<br />

[254]<br />

20.000”<br />

[508]<br />

49.550”<br />

[1,259]<br />

20.000”<br />

[508]<br />

10.000”<br />

[254]<br />

Strap mounting<br />

location<br />

2.750”<br />

[70]<br />

A Line voltage in<br />

1.750”<br />

[44]<br />

Dry contacts<br />

8.000”<br />

[203]<br />

8.000”<br />

[203]<br />

Outdoor air<br />

opening<br />

Exhaust air<br />

opening<br />

4.000”<br />

[102]<br />

4.000”<br />

[102]<br />

24.500”<br />

[622]<br />

8.000”<br />

[203]<br />

8.000”<br />

[203]<br />

Return air<br />

opening<br />

Supply air<br />

opening<br />

3.530”<br />

[90]<br />

1.750”<br />

[44]<br />

For recirc defrost only<br />

5.125”<br />

[130]<br />

19.207”<br />

[488]<br />

Control box<br />

20.000”<br />

[508]<br />

Access door<br />

B Condensate drain<br />

Figure B4: Unit dimensions – 1,200 cfm (with recirculation defrost)<br />

Reversed door<br />

option<br />

Note: For units with the reversed door option, interior components<br />

will appear as a mirror image of the above diagram.<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 15<br />

RIGHT VIEW<br />

FRONT VIEW<br />

LEFT VIEW<br />

Note: A minimum of 15.000” [381] clearance from any obstruction is required for removal<br />

of heat recovery cores, fans, etc.<br />

The access door can be removed from cabinet with only 2.000” [51] of clearance.<br />

Note: A minimum of 12.000” [305] clearance<br />

from any obstruction is required for removal<br />

of the control box.<br />

Access<br />

door<br />

Control cover<br />

Heat<br />

recovery<br />

core<br />

15.000”<br />

[381]<br />

12.000”<br />

[305]<br />

Reversed door option<br />

RIGHT VIEW<br />

FRONT VIEW


Notes: Dimensions in [ ] are millimeters.<br />

Center of gravity<br />

Direction of airflow<br />

A B<br />

Kg<br />

15<br />

30<br />

16<br />

34<br />

95<br />

<strong>HRV</strong>700i<br />

LBS<br />

34<br />

67<br />

36<br />

74<br />

211<br />

PTS<br />

A<br />

B<br />

C<br />

D<br />

Total<br />

10.000”<br />

[254]<br />

C D<br />

22.500”<br />

[572]<br />

Connection Table<br />

Connection Sizes<br />

Line voltage in 14 gauge wire nut<br />

Condensate drain fitting (2x) ¾” MPT<br />

TOP VIEW<br />

A<br />

B<br />

47.000”<br />

[1,194]<br />

Figure B5: Unit dimensions – 700 cfm<br />

20.750”<br />

[527]<br />

8.000”<br />

[203]<br />

1.875”<br />

[48]<br />

2.000”<br />

[51]<br />

Defrost air<br />

opening<br />

3.625”<br />

[92]<br />

2.000”<br />

[51]<br />

14.000”<br />

[356]<br />

1.875”<br />

[48]<br />

3.750”<br />

[95]<br />

8.000”<br />

[203]<br />

Exhaust<br />

air opening<br />

Exhaust<br />

air<br />

Outdoor air<br />

Outdoor<br />

air opening<br />

8.000”<br />

[203]<br />

10.750”<br />

[273]<br />

Line voltage in<br />

A<br />

37.000”<br />

[940]<br />

2.000”<br />

[51]<br />

12.250”<br />

[311]<br />

40.500”<br />

[1,029]<br />

2.157”<br />

[55]<br />

8.000”<br />

[203]<br />

Supply<br />

air opening<br />

Supply<br />

air<br />

12.104”<br />

[307]<br />

Return air<br />

Return<br />

air opening<br />

8.000”<br />

[203]<br />

7.500” [191]<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 16<br />

Condensate drain<br />

B<br />

10.605”<br />

[269]<br />

Low voltage<br />

terminal strips<br />

24.736”<br />

[628]<br />

31.080”<br />

[789]<br />

15.250”<br />

[387]<br />

Note: A minimum of 12.000” [305] clearance from any obstruction is<br />

required for power hook-up, low voltage remote connection and control panel access.<br />

51.000”<br />

[1,295]<br />

RIGHT VIEW<br />

FRONT VIEW<br />

LEFT VIEW<br />

Note: A minimum of 21.000” [533] clearance from any obstruction<br />

is required for removal of heat recovery cores, fans and control box access.<br />

The access door can be removed from cabinet with only 2.000” [51] of clearance.<br />

Note: Air is drawn in to the defrost air opening on top of the unit for recirculation defrost from the space or room in which the unit is mounted.<br />

If this air is not suitable for supply air or if a negative pressure is created and is not acceptable, then the defrost air opening should be ducted<br />

to a branch from the return air duct or from a suitable space.<br />

21.000”<br />

[533]<br />

Heat recovery core<br />

Access door<br />

RIGHT VIEW


Min. 12”<br />

[305 mm]<br />

Appendix C: Flow Station Positions<br />

Balancing damper<br />

Min. 30”<br />

[762 mm]<br />

Flow measuring station (FMS)<br />

Canvas vibration isolator<br />

Figure C1: Flow station position – 600 cfm and 1,200 cfm<br />

Min. 12”<br />

[304 mm]<br />

Flow measuring<br />

station (FMS)<br />

Canvas virbration isolator<br />

Figure C2: Flow station position – 700 cfm<br />

Dry contacts<br />

Reverse door option<br />

Min. 12”<br />

[304 mm]<br />

Min. 12”<br />

[305 mm]<br />

Min. 8” [203 mm]<br />

Min. 12”<br />

[304 mm]<br />

Canvas vibration isolator (optional)<br />

Fresh air<br />

from outside<br />

Exhaust air<br />

from building<br />

Balancing damper<br />

(not supplied)<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 17


Appendix D: Drain Connections<br />

Min. 3”<br />

[76 mm]<br />

Min. 1”<br />

[25 mm]<br />

To drain<br />

Figure D1: Drain connections – 600 cfm and 1,200 cfm<br />

Min..1”<br />

[25.mm]<br />

To.drain<br />

Min..3”<br />

[76.mm]<br />

¾” NPT<br />

coupler<br />

Water trap<br />

Plastic hose<br />

Min. 3”<br />

[76 mm]<br />

Min. 1”<br />

[25 mm]<br />

Note: All hose, pipe and couplers to be supplied by others.<br />

¾”.NPT<br />

coupler<br />

Water.trap<br />

Plastic.hose<br />

Min..3”<br />

[76.mm]<br />

Min..1”<br />

[25.mm]<br />

Plastic.drain.fitting<br />

To.drain<br />

Copper.or<br />

plastic.pipe<br />

note:.All.hose,.pipe.and.couplers.to.be.supplied.by.others.<br />

Figure D2: Drain connections – 700 cfm<br />

Plastic drain fitting<br />

To drain<br />

Copper or<br />

plastic pipe<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 18


terminal Label<br />

Appendix E: Terminal Control Diagrams<br />

A low voltage remote control wiring interface is provided<br />

on the unit. The connections for the low voltage remote<br />

wiring are located on two terminals adjacent to the exhaust<br />

fan outlet (or adjacent to the supply fan outlet on<br />

the 700 cfm unit). All field installed wiring must be low<br />

voltage Class II.<br />

Remote.Wall.Control<br />

Optional wall control requires a four-wire LVT 24 gauge<br />

(or equivalent). This remote wall control runs on 12 VDC.<br />

Low.Voltage.Controls<br />

All other terminals are dry contacts.<br />

Low voltage terminal control consists of the following:<br />

Wall.Control<br />

Four-wire LVT 24 gauge minimum.<br />

Occupied.(Night.Setback).Timer/Sensor<br />

24 VAC, needs dry contact.<br />

Low-Com-High<br />

Remote fan switching requires a single pole, double throw<br />

switch (SPDT).<br />

Fan.Interlock.switch.(FF)<br />

Dry contact closes on ventilation or frost control. Used to<br />

control external fan source (G).<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

BLACK<br />

RED<br />

WALL CONTROL<br />

OCCUPIED<br />

TIMER/<br />

SENSOR<br />

Figure E1: Terminal label<br />

F<br />

F<br />

LOW<br />

COMMON<br />

HIGH<br />

CLASS 2 VOLTAGE<br />

GREEN<br />

YELLOW<br />

NOTE:<br />

Connections are all dry<br />

contacts except wall control<br />

and 24 VAC power supply.<br />

Use of 24 VAC circuit<br />

requires isolating contacts<br />

(ex. thermostat) to prevent<br />

interconnection of Class 2<br />

outputs.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

Wall Control Connection<br />

Three types of remote wall controls are available:<br />

1. Standard wall control with fan switch and dehumidistat<br />

control.<br />

2. Xtra wall control with fan mode selection, dehumidistat<br />

control and maintenance indicator.<br />

3. Aqua Air wall control with fan mode selection, dehumidistat<br />

control and high speed recirculation mode.<br />

4. The remote wall controls work with the integrated<br />

electronic controls within the unit to control ventilation<br />

sequences. Each wall control has different features<br />

and requires four-wire connection to the unit<br />

as shown below. Without the wall control, fans can<br />

be operated with a remote fan switch as shown in<br />

Remote Fan Control.<br />

IMpoRtant<br />

An occupied timer or sensor device cannot be used with<br />

the Xtra wall control.<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 19<br />

JUMPER<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

BLACK<br />

RED<br />

WALL CONTROL<br />

OCCUPIED<br />

TIMER/<br />

SENSOR<br />

F<br />

F<br />

LOW<br />

COMMON<br />

HIGH<br />

CLASS 2 VOLTAGE<br />

GREEN<br />

YELLOW<br />

NOTE:<br />

Connections are all dry<br />

contacts except wall control<br />

and 24 VAC power supply.<br />

Use of 24 VAC circuit<br />

requires isolating contacts<br />

(ex. thermostat) to prevent<br />

interconnection of Class 2<br />

outputs.<br />

Figure E2: Wall control connection<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

WALL<br />

CONTROL


occupied timer/Sensor Connection<br />

Occupancy control is achieved by connection to the terminal<br />

interface shown below. These terminals require a dry<br />

contact which could be provided by a number of types of<br />

controls such as a timer, light sensor, occupancy sensor,<br />

Building Management System or other. The unit will not<br />

operate unless these contacts are closed!<br />

The illustration below shows a factory installed jumper and<br />

programmable timer option.<br />

IMpoRtant<br />

An occupied timer or sensor device cannot be used with<br />

the Xtra wall control.<br />

JUMPER<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

JUMPER<br />

(factory installed)<br />

BLACK<br />

RED<br />

OCCUPIED<br />

TIMER/<br />

SENSOR<br />

F<br />

F<br />

WALL CONTROL<br />

LOW<br />

COMMON<br />

HIGH<br />

CLASS 2 VOLTAGE<br />

GREEN<br />

YELLOW<br />

NOTE:<br />

Connections are all dry<br />

contacts except wall control<br />

and 24 VAC power supply.<br />

Use of 24 VAC circuit<br />

requires isolating contacts<br />

(ex. thermostat) to prevent<br />

interconnection of Class 2<br />

outputs.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

NSB Timer<br />

1 2 3 4 5<br />

24 (+) VAC<br />

24 (−) VAC<br />

Figure E3: Occupied timer/sensor connection<br />

M<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

WALL CONTROL<br />

BLACK<br />

GREEN<br />

RED<br />

OCCUPIED<br />

TIMER/<br />

SENSOR<br />

F<br />

F<br />

OCC. CONTROL<br />

(field installed)<br />

LOW<br />

COMMON<br />

HIGH<br />

YELLOW<br />

CLASS 2 VOLTAGE<br />

NOTE:<br />

Connections are all dry<br />

contacts except wall control<br />

and 24 VAC power supply.<br />

Use of 24 VAC circuit<br />

requires isolating contacts<br />

(ex. thermostat) to prevent<br />

interconnection of Class 2<br />

outputs.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

Remote fan Control<br />

Remote fan control can be achieved by connecting dry<br />

contact controls to the terminal interface at terminals labeled:<br />

Low-Com-High. These controls could be the following:<br />

SPDT switch, dehumidistat, CO2 sensor, light sensor,<br />

timer, Building Management System, etc. The illustration<br />

below represents a switch connected to the unit.<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 20<br />

JUMPER<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

BLACK<br />

RED<br />

WALL CONTROL<br />

OCCUPIED<br />

TIMER/<br />

SENSOR<br />

F<br />

F<br />

LOW<br />

COMMON<br />

HIGH<br />

CLASS 2 VOLTAGE<br />

GREEN<br />

YELLOW<br />

NOTE:<br />

Connections are all dry<br />

contacts except wall control<br />

and 24 VAC power supply.<br />

Use of 24 VAC circuit<br />

requires isolating contacts<br />

(ex. thermostat) to prevent<br />

interconnection of Class 2<br />

outputs.<br />

Figure E4: Remote fan control<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

REMOTE FAN SWITCH<br />

LOW HIGH


Appendix F: Electrical Connection Diagrams<br />

Figure F1: Control box assembly – 600 cfm and 1,200 cfm<br />

FU1015<br />

5A-600i<br />

8A-1200i<br />

PJ2003<br />

PJ2014<br />

PJ1007<br />

PJ1001A<br />

XF1015<br />

415VA<br />

600i<br />

1 2<br />

3 4<br />

5 6<br />

CR1023<br />

PJ2011<br />

PJ1001<br />

FILTRAN<br />

CR1024 CR1026<br />

A B<br />

1<br />

0<br />

1<br />

0<br />

UCB1021<br />

CR1029<br />

NC NO<br />

4<br />

8<br />

2<br />

6<br />

COM<br />

XF1015<br />

855VA<br />

1200i<br />

<strong>HRV</strong> cabinet<br />

Control cover plate<br />

Figure F2: Low speed setting wire connections – 600 cfm and 1,200 cfm<br />

4<br />

8<br />

2<br />

6<br />

Remote control access plate<br />

Remote wiring terminal block<br />

Control box<br />

Note: Low speed motor selection may be<br />

replaced by medium speed. To make<br />

this change, replace the low speed<br />

wires (red) on relay CR1024 with the<br />

medium speed wires (blue).<br />

Note: Autotransformers (if equipped) are<br />

mounted on the back of the control box.<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 21


Appendix G: Make-up Heat Requirements<br />

Although the 600 cfm, 700 cfm and 1,200 cfm models<br />

have good efficiencies, the supply air could be colder<br />

than the ambient room air. It is possible to eliminate the<br />

discomfort associated with this temperature difference by<br />

installing an electric duct heater. This will temper the air<br />

before it is distributed throughout the building. The table<br />

below gives the heating requirements at different temperatures<br />

and airflows.<br />

IMpoRtant<br />

The data does not reflect a reduction in effectiveness due<br />

to frosting. Based on the standard air at: 1.2 Kg/m 3 and<br />

Cp = 1.0 KJ/Kg°C 13.35 lb/ft 3 and Cp = 0.24 Btu/lbm°F.<br />

Table G1: Make-up Heat Requirements – 600 and 700 cfm Unit<br />

outdoor air outdoor air outdoor air outdoor air outdoor air<br />

−40°f [−40°C] −22°f [−30°C] −4°f [−20°C] 14°f [−10°C] 32°f [0°C]<br />

Desired air Desired air Desired air Desired air Desired air<br />

Supply Supply<br />

temperature temperature temperature temperature temperature<br />

air air<br />

55°f 68°f 73°f 55°f 68°f 73°f 55°f 68°f 73°f 55°f 68°f 73°f 55°f 68°f 73°f<br />

(CfM) (L/s)<br />

[13°C] [20°C] [23°C] [13°C] [20°C] [23°C] [13°C] [20°C] [23°C] [13°C] [20°C] [23°C] [13°C] [20°C] [23°C]<br />

700 330 7.4 10.4 11.5 5.6 8.6 9.7 3.9 6.8 8.0 2.1 5.1 6.2 0.3 3.3 4.4<br />

650 307 6.6 9.4 10.5 5.0 7.8 8.9 3.4 6.2 7.3 1.8 4.6 5.6 0.2 3.0 4.0<br />

600 283 5.9 8.5 9.4 4.5 7.0 8.0 3.0 5.6 6.5 1.6 4.1 5.1 0.1 2.7 3.7<br />

550 259 5.2 7.6 8.5 3.9 6.3 7.2 2.6 5.0 5.9 1.3 3.7 4.6 0.1 2.4 3.3<br />

500 236 4.0 6.1 7.0 3.0 5.1 5.9 1.9 4.0 4.9 0.9 3.0 3.8 — 1.9 2.7<br />

450 212 3.0 4.9 5.6 2.1 4.0 4.8 1.3 3.2 3.9 0.4 2.3 3.1 — 1.5 2.2<br />

400 189 2.2 3.9 4.6 1.5 3.2 3.9 0.9 2.5 3.2 0.2 1.9 2.5 — 1.2 1.8<br />

Table G2: Make-up Heat Requirements – 1,200 cfm Unit<br />

outdoor air outdoor air outdoor air outdoor air outdoor air<br />

−40°f [−40°C] −22°f [−30°C] −4°f [−20°C] 14°f [−10°C] 32°f [0°C]<br />

Desired air Desired air Desired air Desired air Desired air<br />

Supply Supply<br />

temperature temperature temperature temperature temperature<br />

air air<br />

55°f 68°f 73°f 55°f 68°f 73°f 55°f 68°f 73°f 55°f 68°f 73°f 55°f 68°f 73°f<br />

(CfM) (L/s)<br />

[13°C] [20°C] [23°C] [13°C] [20°C] [23°C] [13°C] [20°C] [23°C] [13°C] [20°C] [23°C] [13°C] [20°C] [23°C]<br />

1,250 590 14.6 19.9 21.9 11.2 16.5 18.5 7.8 13.1 15.2 4.4 9.7 11.8 1.0 6.3 8.4<br />

1,200 566 13.5 18.6 20.6 10.4 15.5 17.4 7.2 12.3 14.3 4.0 9.1 11.1 0.8 5.9 7.9<br />

1,150 542 12.6 17.4 19.3 9.6 14.5 16.4 6.6 11.5 13.4 3.6 8.5 10.4 0.7 5.5 7.4<br />

1,100 675 11.2 15.9 17.7 8.5 13.2 15.0 5.8 10.5 12.3 3.1 7.7 9.6 0.4 5.0 6.8<br />

1,050 495 10.7 15.2 16.9 8.1 12.6 14.3 5.5 10.0 11.7 2.9 7.4 9.1 0.4 4.8 6.5<br />

1,000 472 9.9 14.1 15.7 7.4 11.7 13.3 5.0 9.3 10.9 2.6 6.9 8.5 0.2 4.4 6.1<br />

900 425 8.5 12.4 13.8 6.4 10.2 11.7 4.3 8.1 9.6 2.2 6.0 7.5 0.1 3.9 5.4<br />

800 377 7.0 10.4 11.7 5.2 8.6 9.9 3.4 6.8 8.2 1.7 5.0 6.4 — 3.3 4.6<br />

700 330 5.0 8.1 9.3 3.7 6.7 7.9 2.3 5.3 6.5 0.9 3.9 5.1 — 2.5 3.7<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 22


Appendix H: Troubleshooting<br />

Table H1: <strong>HRV</strong>600i, 700i and 1200i Troubleshooting<br />

Symptoms possible Causes Solutions<br />

Over ventilation – speed setting too high. Adjust speed setting.<br />

Inside air is too dry.<br />

Dehumidistat setting too low.<br />

Set dehumidistat control in a higher position<br />

(if applicable).<br />

Adjust dehumidistat control knob to a lower<br />

Improper adjustment of dehumidistat control.<br />

Persistent condensation on windows,<br />

setting.<br />

walls, ceilings, etc.<br />

Improper ventilation rate. Install a dehumisistat (option).<br />

Window frame is too cold or leaky. Repair window frame.<br />

Unit stops functioning. Electrical supply interrupted. Check the unit circuit breaker.<br />

Air from supply diffusers too cold.<br />

Imbalance of supply and exhaust air.<br />

Check filters and heat exchangers for blockage.<br />

Check balance of airflows.<br />

Outdoor temperature very cold. Install electric duct heater if necessary.<br />

Unit makes annoying noise. Blower wheel out of alignment.<br />

Remove the motor/blower assembly and<br />

adjust blower wheel.<br />

Heat exchanger freezing up.<br />

Imbalance of supply and exhaust air.<br />

Frost control damper not functioning.<br />

Check filters and heat exchangers for blockage.<br />

Check balance of airflows.<br />

Check for operation of both frost control<br />

damper actuators.<br />

Heat exchanger flutes are positioned in the<br />

Low exhaust airflow in winter season.<br />

exhaust airstream.<br />

Remove flat plate heat exchanger sections<br />

and re-position the flute side of the heat<br />

exchanger into the supply airstream.<br />

vces-HRv-iom-1 – HRv600i, HRv700i, HRv1200i 23


info@venmarces.com<br />

www.venmarces.com<br />

<strong>Venmar</strong> <strong>CES</strong> <strong>Inc</strong>. has a policy of continuous improvement and reserves<br />

the right to change design and specifications without notice.<br />

©2012 <strong>Venmar</strong> <strong>CES</strong> <strong>Inc</strong>.<br />

<strong>V<strong>CES</strong></strong>-<strong>HRV</strong>-<strong>IOM</strong>-1 (PN 206815)<br />

August 2012

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!