Annexes § 9. In existing tank farms which do not dispose of an impervious bund and which are located outside a water abstraction area or a protected zone, within a period of 24 months after the date of the coming into force of this order observation pipes must be installed in accordance with the provisions of article 5.17.3.12. Art. 5.17.3.20 § 1. If leaks are observed the operator will take all the measures required to avoid the danger of explosion and restrict further soil and groundwater pollution to the extent possible. § 2. After professional repairs the container may only be brought back into use if a certificate has been issued by an environmental expert accredited in the discipline containers for gases or hazardous substances or by an authorised expert or by a technician accredited for the storage of P3 and/or P4 products intended for the heating of buildings. From this certificate it must clearly appear that the container and the installation comply with the requirements referred to in this order. § 3. With the final putting out of use of containers, whether or not due to leaks, the container must be emptied, cleaned and removed within a period of 36 months without prejudice to the provisions of the decree of 2 July 1981 concerning the prevention of waste and waste materials management and its implementing decisions. If it is impossible to remove the container within this period, after consultation with an environmental expert accredited in the discipline containers for gases or hazardous substances or with an authorised expert or with a technician accredited for the storage of P3 and/or P4 products intended for the heating of buildings, the container must be emptied, cleaned and filled with sand, foam or an equivalent inert material. Here the necessary measures must be taken for explosion protection and to prevent soil and groundwater pollution. § 4. Liquid leaks which have caused ground pollution or spillage into the sewer system, the surface waters, the groundwater layers or onto adjacent properties must be immediately reported by the operator to the Environmental Inspection Department, to the Governor of the Province and to the Burgomaster. Section 5.17.4 Control of the emission of volatile organic compounds (VOC) with the storage and transferring of petrol Art. 5.17.4.1 The provisions of this section are applicable to the establishments as referred to in the subsection 17.3.4 and the establishments as referred to in subsection 17.3.9 of the classification list, to the extent these establishments concern the collection, storage and transferring of petrol. Art. 5.17.4.2 § 1. Without prejudice to the other conditions in these regulations, the storage installations must comply with the technical regulations of appendix 5.17.9, § 2. § 2. As a derogation from § 1, existing storage installations must comply with the provisions of § 1: 1. from 1 January 1999 for storage installations with a turnover greater than 50000 tonnes per year, measured during the years 1996 and 1997 398 Waste Water and Waste Gas Treatment
Annexes 2. from 1 January 2002 for storage installations with a turnover greater than 25000 tonnes per year, measured during the years 1996 up to and including 2000; if, however, the turnover measured during the years 1998 up to and including 2000 exceeds the limit of 50000 tonnes per year, the provisions of §1 of this article are applicable from 1 January of the second year after the year for which the limit value was exceeded 3. from 1 January 2005 for other storage installations. Art. 5.17.4.3 § 1. Without prejudice to the other conditions in these regulations, transfer installations of mobile tanks at terminals must comply with the technical regulations of appendix 5.17.9, § 3. § 2. All terminals with transfer installations for the loading of tankers must be equipped with at least one loading gantry that meets the specifications for installations for filling on the bottom side in appendix 5.17.9, § 5. § 3. As a derogation from § 1 of this article, existing transfer installations for the loading of tankers, rail tankers and/or ships must comply with the provisions of § 1 and § 2: 1. from 1 January 1999 for transfer installations with a turnover greater than 150000 tonnes per year, measured during the years 1996 and 1997 2. from 1 January 2002 for transfer installations with a turnover greater than 25000 tonnes per year, measured during the years 1996 up to and including 2000; if, however, the turnover measured during the years 1998 up to and including 2000 exceeds the limit of 150000 tonnes per year, the provisions of §1 of this article are applicable from 1 January of the second year after the year for which the limit value was exceeded 3. from 1 January 2005 for other transfer installations of terminals. § 4. Not later than three months after the date of bringing into use, and then at least once a year, an environmental expert accredited in the discipline air must draw up a report. In this report the results of the measurements conducted to determine the average concentration of vapours in the vapour recovery unit outlet are shown, discussed and compared to the emission condition mentioned in appendix 5.17.9, § 3. The term between two control measurements may in no event exceed 15 months. This report must be sent to the Environmental Licence Department, the Environmental Inspection Department and the Flemish Environmental Agency. Art. 5.17.4.4 § 1. Without prejudice to the other conditions in these regulations, distribution installations for petrol must meet the technical regulations of appendix 5.17.9, § 4. § 2. As a derogation from § 1 of this article, existing distribution installations must comply with the provisions of § 1: 1. from 1 January 1999 for distribution installations with a turnover greater than 1000 m 3 per year, measured during the years 1996 and 1997, as well as for installations, irrespective of their turnover, which are located under permanent living spaces or working spaces 2. from 1 January 2002 for distribution installations with a turnover greater than 500 m 3 per year, measured during the years 1996 up to and including 2000; if, however, the turnover measured during the years 1998 up to and including 2000 exceeds the limit of 1000 m 3 per year, the provisions of § 1 of this article are applicable from 1 January of the second year after the year for which the limit value was exceeded 3. from 1 January 2005 for other distribution installations. Waste Water and Waste Gas Treatment 399
- Seite 383 und 384: (Plant Nr.) Characterisation Hg [µ
- Seite 385 und 386: Example 3 Highly effective SCR to c
- Seite 387 und 388: ) Oil-fired plants Annexes There ar
- Seite 389 und 390: Annexes Luftreinhaltegesetz and
- Seite 391 und 392: Emission standards for the producti
- Seite 393 und 394: Annexes The ordinance “Verordnung
- Seite 395 und 396: Annexes 7. CHEMICALS (see also sect
- Seite 397 und 398: Annexes 17 Hazardous Products 1 (di
- Seite 399 und 400: Annexes 3. with respect to BFCs, no
- Seite 401 und 402: Art. 5.7.2.2 Annexes § 1. The dump
- Seite 403 und 404: Annexes sponding to the conversion
- Seite 405 und 406: Annexes § 2. The waste gases of pl
- Seite 407 und 408: Section 5.7.11 The production of po
- Seite 409 und 410: Annexes From 1 January 2002, and as
- Seite 411 und 412: Art. 5.17.1.3 Annexes § 1. Unless
- Seite 413 und 414: Annexes an equivalent fire-resistan
- Seite 415 und 416: Annexes § 2. The register or alter
- Seite 417 und 418: Annexes a) provide sufficient stren
- Seite 419 und 420: Annexes § 4. In the event of possi
- Seite 421 und 422: Art. 5.17.2.5 § 1. Storage in cont
- Seite 423 und 424: Annexes § 2. Except for containers
- Seite 425 und 426: Annexes 1. single-walled containers
- Seite 427 und 428: Art. 5.17.3.5 Annexes § 1. An iden
- Seite 429 und 430: Annexes 1. the storage must be prot
- Seite 431 und 432: Art. 5.17.3.15 Annexes § 1. The op
- Seite 433: Annexes These containers continue t
- Seite 437 und 438: Art. 5.17.5.5 Annexes Fuelling plac
- Seite 439 und 440: Annexes For new, large heating inst
- Seite 441 und 442: Annexes § 5. To guarantee complian
- Seite 443 und 444: Art. 5.20.3.10 Existing installatio
- Seite 445 und 446: 5. FRANCE The legislation for the c
- Seite 447 und 448: Annexes Specific emission control r
- Seite 449 und 450: Annexes b) more than 750 mg/l, a CO
- Seite 451 und 452: Annexes (4) Notwithstanding part D,
- Seite 453 und 454: Emission Limit Values for Fertilise
- Seite 455 und 456: Annexes d Fugitive solvent emission
- Seite 457 und 458: ANNEX 2 (SPECIFIC EMISSION LIMITS F
- Seite 459 und 460: Benzo(a)anthracene Benzo(b)fl
- Seite 461 und 462: Class III Annexes If the mass flow
- Seite 463 und 464: Class IV If the mass flow equals or
- Seite 465 und 466: Parameter Unit Discharge into surfa
- Seite 467 und 468: Annexes General Environmental Perfo
- Seite 469 und 470: Annexes Classification of organic s
- Seite 471 und 472: GLOSSAR DER BEGRIFFE UND ABKÜRZUNG
- Seite 473 und 474: Ω ohm = Ohm Glossar Abkürzungen /
- Seite 475 und 476: Glossar PSA Pressure-swing Adsorpti
- Seite 477: Fugitive emissions = Emission von f
Annexes<br />
2. from 1 January 2002 for storage installations with a turnover greater than 25000 tonnes per<br />
year, measured during the years 1996 up to and including 2000; if, however, the turnover<br />
measured during the years 1998 up to and including 2000 exceeds the limit of 50000 tonnes<br />
per year, the provisions of §1 of this article are applicable from 1 January of the second year<br />
after the year for which the limit value was exceeded<br />
3. from 1 January 2005 for other storage installations.<br />
Art. 5.17.4.3<br />
§ 1. Without prejudice to the other conditions in these regulations, transfer installations of mobile<br />
tanks at terminals must comply with the technical regulations of appendix 5.17.9, § 3.<br />
§ 2. All terminals with transfer installations for the loading of tankers must be equipped with at<br />
least one loading gantry that meets the specifications for installations for filling on the bottom<br />
side in appendix 5.17.9, § 5.<br />
§ 3. As a derogation from § 1 of this article, existing transfer installations for the loading of<br />
tankers, rail tankers and/or ships must comply with the provisions of § 1 and § 2:<br />
1. from 1 January 1999 for transfer installations with a turnover greater than 150000 tonnes per<br />
year, measured during the years 1996 and 1997<br />
2. from 1 January 2002 for transfer installations with a turnover greater than 25000 tonnes per<br />
year, measured during the years 1996 up to and including 2000; if, however, the turnover<br />
measured during the years 1998 up to and including 2000 exceeds the limit of 150000 tonnes<br />
per year, the provisions of §1 of this article are applicable from 1 January of the second year<br />
after the year for which the limit value was exceeded<br />
3. from 1 January 2005 for other transfer installations of terminals.<br />
§ 4. Not later than three months after the date of bringing into use, and then at least once a year,<br />
an environmental expert accredited in the discipline air must draw up a report. In this report the<br />
results of the measurements conducted to determine the average concentration of vapours in the<br />
vapour recovery unit outlet are shown, discussed and compared to the emission condition mentioned<br />
in appendix 5.17.9, § 3. The term between two control measurements may in no event<br />
exceed 15 months. This report must be sent to the Environmental Licence Department, the Environmental<br />
Inspection Department and the Flemish Environmental Agency.<br />
Art. 5.17.4.4<br />
§ 1. Without prejudice to the other conditions in these regulations, distribution installations for<br />
petrol must meet the technical regulations of appendix 5.17.9, § 4.<br />
§ 2. As a derogation from § 1 of this article, existing distribution installations must comply with<br />
the provisions of § 1:<br />
1. from 1 January 1999 for distribution installations with a turnover greater than 1000 m 3 per<br />
year, measured during the years 1996 and 1997, as well as for installations, irrespective of<br />
their turnover, which are located <strong>und</strong>er permanent living spaces or working spaces<br />
2. from 1 January 2002 for distribution installations with a turnover greater than 500 m 3 per<br />
year, measured during the years 1996 up to and including 2000; if, however, the turnover<br />
measured during the years 1998 up to and including 2000 exceeds the limit of 1000 m 3 per<br />
year, the provisions of § 1 of this article are applicable from 1 January of the second year after<br />
the year for which the limit value was exceeded<br />
3. from 1 January 2005 for other distribution installations.<br />
Waste Water and Waste Gas Treatment 399