Art. 5.17.3.15<br />

Annexes<br />

§ 1. The operator of a tank farm will keep a file at appropriate places at the establishment for<br />

the authorised fire brigade, with at least the following information:<br />

1. a map of the tank farm and the access roads<br />

2. a description of the firefighting resources with their indication on a map<br />

3. a description of the stored products with the main physical and chemical properties (danger<br />

cards) with the specification of the listing of EC directive 67/548/EEC of 27 June 1967 or<br />

88/379/EEC of 7 June 1988, of the UN number and of the ADR code<br />

4. the water content capacity of the containers<br />

5. the composition of any establishment's own fire service.<br />

Any other equivalent manner of providing information is allowed, providing the consent of the<br />

supervisory official and of the authorised fire brigade has been given.<br />

Art. 5.17.3.16<br />

§ 1. At least every 3 years, without the period between two consecutive examinations being<br />

able to exceed 40 months, the installations must be subjected to a limited inspection.<br />

This inspection comprises, if relevant:<br />

1. perusal of the previous report or certificate<br />

2. the checking of the good state of the overfilling protection<br />

3. an inspection for visible or organoleptically observable pollution of the surface outside the<br />

container according to the provisions of appendix 5.17.4<br />

4. the inspection of the general state of the installation, comprising:<br />

a) the tracing of leaks and indications of leaks<br />

b) the inspection of the state of the plating, the connections and the butts of the container<br />

c) the inspection of the state of accessories such as: valves, temperature, pressure and level<br />

measurement devices and earthing<br />

d) the inspection of the pressure safety and alarm appliances<br />

e) the inspection of the state of the outer cladding, the paintwork and/or the insulation<br />

f) the inspection of the fo<strong>und</strong>ations and/or supporting blocks regarding stability and drainage<br />

g) the inspection of the b<strong>und</strong> for content, sealing, pollution, measuring wells<br />

h) the inspection of the state of the ducts and the accessories inside the b<strong>und</strong>.<br />

also for vertical containers:<br />

a) where appropriate, a non-destructive inspection must be conducted on the cladding and the<br />

roof plating of the containers to determine the plate thickness and any corrosion, both internal<br />

and external<br />

b) at the request of the environmental expert or the authorised expert, any settling will be determined<br />

by measuring the height at a number of points spread evenly over the periphery of<br />

the bottom edge.<br />

§ 2. At least every 20 years the installations must be subjected to a general inspection. Prior to<br />

this inspection the container must be internally cleaned.<br />

This inspection comprises:<br />

1. the limited inspection, as referred to in § 1<br />

2. the inspection of the state of the inner wall<br />

3. for vertical containers the inspection also includes:<br />

a) the inspection of the state of the framework and the internal accessories such as valves,<br />

heating coils, roof and gro<strong>und</strong>water drains and seals in the floating roofs<br />

b) the inspection of the bottom plates for the tracing of internal and external corrosion<br />

c) the inspection of bottom deformation and the possible measuring of the profile<br />

Waste Water and Waste Gas Treatment 395