Annexes<br />

Art. 5.17.3.7<br />

§ 1. For storage sites in fixed containers or moveable receptacles located inside a water abstraction<br />

area and/or protected zone, the minimum capacity of the b<strong>und</strong> is to be equal to the total<br />

water content capacity of all containers and/or receptacles placed therein.<br />

§ 2. For storage places in fixed containers located outside a water abstraction area and/or protected<br />

zone, the minimum capacity of the b<strong>und</strong> must be determined as follows (double-walled<br />

containers fitted with a permanent leak detection system not included):<br />

1. for the storage of P1, P2, highly toxic, toxic and explosive products, the greatest of the following<br />

values:<br />

a) the water content capacity of the largest container, increased by 25 % of the total water<br />

content capacity of the other containers in the b<strong>und</strong><br />

b) half of the total water content capacity of the containers placed therein;<br />

2. for the storage of P3, harmful, irritating, oxidising, corrosive and environmentally harmful<br />

products: the water content capacity of the largest container;<br />

3. for the storage of P4 products and extra heavy heating oil, irrespective of the flashpoint: only<br />

the presence of a upright edge is required<br />

4. for the storage of P1 and/or P2 products in abovegro<strong>und</strong> spaces and basements: the total water<br />

content capacity of all containers placed therein.<br />

For the storage of products with various main properties the strictest of the regulations must be<br />

adhered to. Here account must also be taken of the flashpoint.<br />

§ 3. For storage sites located outside a water abstraction area and/or protected zone for products<br />

other than P1 and/or P2 products in moveable receptacles, the capacity of the b<strong>und</strong> must be restricted<br />

to 10 % of the total water content capacity of the receptacles stored therein. In each<br />

case the capacity of the b<strong>und</strong> must be at least equal to the capacity of the largest receptacle<br />

placed in the b<strong>und</strong>.<br />

§ 4. For storage sites located outside a water abstraction area and/or protected zone for P1<br />

and/or P2 products in moveable receptacles, the capacity of the b<strong>und</strong> must be 25 % of the total<br />

water content capacity of the receptacles stored therein. The capacity may be reduced to 10% if,<br />

after consultation with the authorised fire brigade, a suitable fire extinguishing installation is<br />

provided. In each case the capacity of the b<strong>und</strong> must be at least equal to the capacity of the<br />

largest receptacle placed in the b<strong>und</strong>.<br />

Art. 5.17.3.8<br />

Unless specified otherwise in the environmental licence, the distance between the containers is<br />

to be at least 0.5 m, and between the containers and the inner walls of the b<strong>und</strong> or the bottom<br />

the dams at least half the height of the containers.<br />

This last obligation does not apply:<br />

1. for the storage of hazardous liquids in double-walled containers or containers with ring cladding<br />

or similar protection which ensures that any leaked liquid stays inside the b<strong>und</strong>, or<br />

2. for the storage of P4 products or extra heavy heating oil, irrespective of the flashpoint.<br />

Art. 5.17.3.9<br />

Without prejudice to other provisions of these regulations, storage sites for P1 and/or P2 products<br />

in moveable receptacles must comply with the following conditions:<br />