Art. 5.17.3.5<br />

Annexes<br />

§ 1. An identification plate must be applied to fixed containers in a visible and easily accessible<br />

place in accordance with the provisions of appendix 5.17.2.<br />

§ 2. The following indications must be applied near the filling opening and in a clearly visible<br />

place on the fixed container:<br />

1. the number of the container<br />

2. the name or the code numbers or letters of the stored liquid<br />

3. the danger symbols<br />

4. the water content capacity of the container.<br />

The provisions of this paragraph are not applicable to storage sites for P3 and/or P4 products<br />

which are only intended for the heating of buildings.<br />

§ 3. On moveable receptacles the name of the product mentioning the main property must be<br />

applied.<br />

Art. 5.17.3.6<br />

§ 1. The b<strong>und</strong> and the fo<strong>und</strong>ations for fixed containers with an individual water content capacity<br />

from 10000 l must be built according to a code of good practice <strong>und</strong>er the supervision of and<br />

according to the directions of an architect, a civil engineering architect, a civil structural engineer<br />

or an industrial architectural engineer.<br />

For storage sites classified in category 1 or 2, the aforementioned expert confirms in a certificate<br />

that he accepts the code of good practice used and that this was adhered to.<br />

§ 2. Fixed containers must be placed on a supporting block or surface of sufficient dimensions<br />

to prevent the load causing uneven slumps, from which a danger of toppling or breakage could<br />

originate. For the installation of containers with an individual water content capacity from<br />

50000 l a stability study is conducted by the expert specified in §1.<br />

§ 3. The b<strong>und</strong> must be resistant to the action of the stored liquids and must be impervious. The<br />

b<strong>und</strong> must be sufficiently strong to withstand the liquid mass which could escape in the event<br />

of the breakage of the largest container placed in the b<strong>und</strong>.<br />

The floor must be provided in such a way that the spreading of the leaked liquids remains minimal<br />

and the leaked liquids can be easily removed.<br />

§ 4. If the b<strong>und</strong> is made of earthen dams, these dams must be made of a very clayish, solid and<br />

strongly compressed earth, of which the gradients are a max. 4/4 and the thickness on the top<br />

side is to be at least 50 centimetres. The floor may be made of the same materials. The dams<br />

must be sown with grass. At the base, carefully calculated supporting walls with a maximum<br />

height of one metre may be constructed.<br />

§ 5. The passage of ducts through the b<strong>und</strong> is only allowed if the sealing of the b<strong>und</strong> remains<br />

assured.<br />

§ 6. If the b<strong>und</strong> is wider than 30 metres, the escape ladders or stairs must be positioned so that a<br />

person fleeing does not have to travel a distance greater than half the width of the b<strong>und</strong> plus<br />

15 metres to reach an escape ladder or stairs.<br />

Waste Water and Waste Gas Treatment 391