Annexes<br />

Section 5.17.3 Storage of Hazardous Liquids in abovegro<strong>und</strong> containers<br />

Art. 5.17.3.1<br />

§ 1. The containers must be placed in or above a b<strong>und</strong> in order to prevent the spreading of fire,<br />

and to prevent soil and/or gro<strong>und</strong>water pollution. Equivalent collection systems can be permitted<br />

in the environmental licence.<br />

Double-walled containers fitted with a permanent leak detection system do not have to be<br />

placed in or above a b<strong>und</strong>.<br />

§ 2. Unless specified otherwise in the environmental licence, the storage of P1 and/or P2 products<br />

in fixed containers in basements or abovegro<strong>und</strong> spaces is prohibited. It is forbidden to<br />

install storage sites for P1 and/or P2 products in moveable receptacles in basement floors.<br />

Art. 5.17.3.2<br />

§ 1. Fixed containers must be built according to the provisions of appendix 5.17.2.<br />

§ 2. All metal parts of containers intended for the storage of P1 and/or P2 products, including<br />

the floating roof of the containers, must be equipotential.<br />

Art. 5.17.3.3<br />

§ 1. The control of the construction of fixed containers must take place according to the provisions<br />

of appendix 5.17.2.<br />

The control of separately built containers must take place by an environmental expert accredited<br />

in the discipline containers for gases or hazardous substances or by an authorised expert.<br />

The control of containers installed in series may be limited to one prototype; the approval of the<br />

prototype is given by an environmental expert accredited in the discipline containers for gases<br />

or hazardous substances, of which the accreditation allows the approval of prototypes.<br />

The report on this approval mentions the controls carried out and must be signed by the aforementioned<br />

expert.<br />

§ 2. For each container the operator must dispose of a “declaration of conformity of the container”<br />

signed by the constructor, drawn up according to the specimen form in appendix 5.17.2.<br />

The containers must bear the identification plate applied by the constructor.<br />

Art. 5.17.3.4.<br />

Before the installation of the fixed container it must be checked that the container and/or the<br />

fo<strong>und</strong>ations meet the conditions of these regulations.<br />

After installation, but before the bringing into use of the container, it must be checked whether<br />

the container, the ducts and the accessories, the overfilling warning or safety system, the b<strong>und</strong><br />

and the firefighting resources, and where appropriate, the leak detection system and the provisions<br />

for vapour recovery comply with the conditions of these regulations.<br />

The specified controls must be carried out <strong>und</strong>er the supervision of an environmental expert<br />

accredited in the discipline containers for gases or hazardous substances or an authorised expert<br />

for the storage of P3 and/or P4 products intended for the heating of buildings, or an accredited<br />

technician.<br />

390 Waste Water and Waste Gas Treatment