Annexes 1. acetyl cyclohexane sulphonyl peroxide: –10° C 2. succinic acid peroxide: +10° C 3. tert-butyl peroxyisopropylcarbonate (BPIC): room temperature 4. tert.-butyl peroxypivalate: –10° C 5. dibenzoyl peroxide: room temperature 6. dicyclohexyl peroxydicarbonate: +5° C 7. diisopropyl peroxydicarbonate: –15° C. § 2. Peroxides which for reasons of safety must be kept at the establishment at a temperature lower than room temperature, must be stored: 1. either in refrigerators or freezers located in the production building, in which case each refrigerator or freezer may contain a quantity of at most 30 kg non-refrigerated organic peroxides 2. or in refrigerators or freezers located in a detached storage building in which only the said peroxides are stored. In this case each refrigerator or freezer may contain a quantity of at most 150 kg non-refrigerated organic peroxides 3. or in a detached cold store that is solely intended for this purpose. In this case, unless specified otherwise in the environmental licence, per cold store a quantity of at most 500 kg nonrefrigerated organic peroxides may be stored. Art. 5.17.1.20 As regards the construction certificates, inspections and tests prescribed in this chapter, the operator must dispose of certificates in which the codes of good practice applied, the controls carried out and the relevant observations are clearly indicated. He must at all times keep the certificates concerned at the disposal of the supervisory official. Art. 5.17.1.21 Without prejudice to the provisions of this chapter, the transport, the installation and connection of containers must be performed according to the prevailing Belgian or European standards. Section 5.17.2 Storage of hazardous liquids in underground containers Art. 5.17.2.1 § 1. The necessary measures must be taken to give maximum protection to the containers against mechanical damage and corrosion. § 2. It is forbidden to place containers intended for the storage of P1 and/or P2 products directly under a building or under a vertical projection of a building. A lean-to is not considered as a building. § 3. The distance between the container and the boundaries of the parcels of third parties must be at least 3 metres. The distance between the container and the basement space of the company's own buildings must be at least 2 m. The distance between the container and the wall of the establishment's own buildings must amount to at least 0.75 m. The distance between the containers themselves must amount to at least 0.5 m. The distance between containers for P3 and/or P4 products which do not form part of a distribution installation and the boundaries of the parcels of third parties must amount to at least 1 m. 382 Waste Water and Waste Gas Treatment

Annexes § 4. In the event of possible flooding or high water levels, the necessary provisions must be installed to prevent empty containers from being floated upwards. § 5. Without prejudice to the requirements referred to in this section, storage sites for petrol and their associated installations must comply with the provisions of section 5.17.4. Art. 5.17.2.2 § 1. A notice is to be provided in a clearly visible place by the container in accordance with the provisions of appendix 5.17.2. § 2. The following information is to be shown near the filling opening and near the manhole: 1. the number of the container 2. the name or the code numbers or letters of the stored liquid 3. the danger symbols 4. the water content capacity of the container. The information must be clearly readable. The provisions of this paragraph do not apply to storage sites for P3 and/or P4 products which are only intended for the heating of buildings. Art. 5.17.2.3 § 1. The venting pipe must open into the open air at least 3 metres above ground level and at least 3 metres from each opening in a space and the boundaries of the parcels of third parties. Outlets of venting pipes may not be located under construction parts such as, e.g. roof overhangs. § 2. The provisions of § 1 are not applicable to venting pipes belonging to storage sites for P3 and/or P4 products which do not form part of a fuel distribution installation for motor vehicles. For these storage sites it is to be ensured that the place and the height of the outlet of the venting pipe does not excessively cause nuisance to the vicinity, particularly as a result of the filling of the containers § 3. For the storage of P1 and/or P2 products the air supply and discharge system must be shut off by an appliance that prevents the spreading of fire. Art. 5.17.2.4 § 1. Storage in containers directly buried in the ground is only permitted in: 1. double-walled metal containers which have been manufactured according to the provisions of appendix 5.17.2 2. containers of reinforced thermoset synthetics which have been manufactured according to the provisions of appendix 5.17.2 3. stainless steel containers which have been manufactured in accordance with a code of good practice accepted by an environmental expert, accredited in the discipline containers for gases or hazardous substances, or accepted by an authorised expert 4. a storage system which provides the same guarantees of the prevention of soil and/or groundwater pollution as the aforementioned containers this storage system must be accepted by an environmental expert accredited in the discipline of containers for gases or hazardous substances; a certificate of this acceptance is drawn up and Waste Water and Waste Gas Treatment 383

Annexes<br />

§ 4. In the event of possible flooding or high water levels, the necessary provisions must be installed<br />

to prevent empty containers from being floated upwards.<br />

§ 5. Without prejudice to the requirements referred to in this section, storage sites for petrol and<br />

their associated installations must comply with the provisions of section 5.17.4.<br />

Art. 5.17.2.2<br />

§ 1. A notice is to be provided in a clearly visible place by the container in accordance with the<br />

provisions of appendix 5.17.2.<br />

§ 2. The following information is to be shown near the filling opening and near the manhole:<br />

1. the number of the container<br />

2. the name or the code numbers or letters of the stored liquid<br />

3. the danger symbols<br />

4. the water content capacity of the container.<br />

The information must be clearly readable.<br />

The provisions of this paragraph do not apply to storage sites for P3 and/or P4 products which<br />

are only intended for the heating of buildings.<br />

Art. 5.17.2.3<br />

§ 1. The venting pipe must open into the open air at least 3 metres above gro<strong>und</strong> level and at<br />

least 3 metres from each opening in a space and the bo<strong>und</strong>aries of the parcels of third parties.<br />

Outlets of venting pipes may not be located <strong>und</strong>er construction parts such as, e.g. roof overhangs.<br />

§ 2. The provisions of § 1 are not applicable to venting pipes belonging to storage sites for P3<br />

and/or P4 products which do not form part of a fuel distribution installation for motor vehicles.<br />

For these storage sites it is to be ensured that the place and the height of the outlet of the venting<br />

pipe does not excessively cause nuisance to the vicinity, particularly as a result of the filling<br />

of the containers<br />

§ 3. For the storage of P1 and/or P2 products the air supply and discharge system must be shut<br />

off by an appliance that prevents the spreading of fire.<br />

Art. 5.17.2.4<br />

§ 1. Storage in containers directly buried in the gro<strong>und</strong> is only permitted in:<br />

1. double-walled metal containers which have been manufactured according to the provisions of<br />

appendix 5.17.2<br />

2. containers of reinforced thermoset synthetics which have been manufactured according to the<br />

provisions of appendix 5.17.2<br />

3. stainless steel containers which have been manufactured in accordance with a code of good<br />

practice accepted by an environmental expert, accredited in the discipline containers for<br />

gases or hazardous substances, or accepted by an authorised expert<br />

4. a storage system which provides the same guarantees of the prevention of soil and/or gro<strong>und</strong>water<br />

pollution as the aforementioned containers<br />

this storage system must be accepted by an environmental expert accredited in the discipline of<br />

containers for gases or hazardous substances; a certificate of this acceptance is drawn up and<br />

Waste Water and Waste Gas Treatment 383