Annexes<br />

Art. 5.17.1.16<br />

§ 1. The drawing off of P1 and/or P2 products into mobile receptacles must be performed either<br />

in the open air or in a well-ventilated space constructed with non-flammable materials. The necessary<br />

measures must be taken to prevent dangerous electrostatic charges from being generated<br />

during the drawing off. This place or space must be provided with signs according to the General<br />

Regulations for Labour Safety indicating a fire hazard.<br />

§ 2. The floor of the space referred to in § 1 must be impervious and made of non-flammable<br />

materials. It must be constructed in such a way that accidentally spilt substances and leaked<br />

liquids are drained into a collection device and subsequently are taken to one or more collection<br />

wells by means of collection channels. This collecting device may in no way be connected indirectly<br />

or directly to a public sewer, a surface water, a collecting basin for surface water, a ditch<br />

or a gro<strong>und</strong>water layer.<br />

§ 3. If P1 and/or P2 products are stored in abovegro<strong>und</strong> containers, the filling of the mobile receptacles<br />

must be performed in a suitable filling area located at least 10 metres from the containers<br />

or completely outside the b<strong>und</strong>.<br />

§ 4. P1 and/or P2 products must be handled in such a way that spillage of the liquids on the<br />

floor is avoided.<br />

§ 5. P1 and/or P2 products must be stored in closed receptacles offering all guarantees of sealing.<br />

In addition, the sealing must be checked immediately after the filling. Receptacles fo<strong>und</strong> to<br />

be defective in this respect must immediately be emptied and removed from the space where<br />

the filling takes place.<br />

§ 6. The maximum quantities of P1 and/or P2 products (number of mobile receptacles, etc.) that<br />

may be present in the spaces where the filling of the mobile receptacles takes place, may be<br />

restricted in the environmental licence.<br />

Art. 5.17.1.17<br />

With respect to the filling of fixed containers and road tankers the following regulations apply:<br />

1. the necessary measures must be taken to prevent spillages of liquids and pollution of the<br />

gro<strong>und</strong>, gro<strong>und</strong>water and surface water<br />

2. the flexible hose used for the filling must be connected to the opening of the container or the<br />

conduit by means of a device with screw coupling or an equivalent system<br />

3. each filling operation must be performed <strong>und</strong>er the supervision of the operator or his appointee;<br />

said supervision must be organised in such a way that the filling operation can be<br />

monitored and that immediate action can be taken in the event of an incident<br />

4. to prevent overfilling all fixed containers must be equipped with an overfilling protection,<br />

which may be:<br />

a) either a warning system, giving an acoustic signal which the supplier must always be able<br />

to hear in the filling area and which informs the supplier that the container to be filled is<br />

95 % full; this system may be mechanical or electronic<br />

b) or a safety system, which automatically shuts off product flow as soon as the container to<br />

be filled is at most 98% full; this system may be mechanical or electronic<br />

c) at storage facilities forming part of a fuel distribution installation for motor vehicles, a<br />

safety system of the type indicated in b) must be used<br />

5. all containers must be equipped with the possibility to measure the level<br />

6. the filling position for the road tanker, the zones where the nozzles of the filling pipes are<br />

grouped and the filling zones at the distribution installation must always be located on the<br />

premises of the establishment and must:<br />

380 Waste Water and Waste Gas Treatment