06.12.2012 Aufrufe

BVT-Merkblatt zu Abwasser- und Abgasbehandlung

BVT-Merkblatt zu Abwasser- und Abgasbehandlung

BVT-Merkblatt zu Abwasser- und Abgasbehandlung

MEHR ANZEIGEN
WENIGER ANZEIGEN

Sie wollen auch ein ePaper? Erhöhen Sie die Reichweite Ihrer Titel.

YUMPU macht aus Druck-PDFs automatisch weboptimierte ePaper, die Google liebt.

Annexes<br />

7.7 Annex VII. Member States’ Legislation on Waste Water<br />

and Waste Gas in the Chemical Sector<br />

Annex VII surveys the chemical sector emission limits for waste water and waste gas in Member<br />

States. Note that there may be different criteria behind the figures, concerning such items as<br />

averaging time, reference conditions, sampling techniques, measurement and analysis and<br />

method of compliance testing.<br />

1. AUSTRIA<br />

Emissions to Air<br />

No special legislation exists in Austria on emission standards for air emissions from the chemical<br />

industry. In general the “Gewerbeordnung” (BGBl. 194/1994) regulates the licensing of<br />

chemical plants and means that plants have to be “state-of-the-art” in their performance. Emission<br />

standards for air emissions from chemical plants are usually based on the German “Technical<br />

Instructions on Air Quality” (TA – Luft).<br />

Combustion plants are regulated with the “Feuerungsanlagenverordnung” (BGBl. II 1997/331),<br />

except for steam boilers including waste heat boilers, afterburners of exhaust gases, gas turbines<br />

and combustion engines.<br />

Emission standards for boiler plants are regulated by the “Luftreinhaltegesetz für Kesselanlagen”<br />

(BGBl. 1988/380 i.d.F. BGBl. 1993/185, BGBl. I 1997/115, BGBl. I 1998/158) and the<br />

“Luftreinhalteverordnung für Kesselanlagen” (BGBl. 1989/19 i.d.F. BGBl. 1990/134, BGBl.<br />

1994/785, BGBl. II 1997/324).<br />

­ Feuerungsanlagenverordnung (Ordinance for Firing Installations) (BGBl. II 1997/331)<br />

The “Feuerungsanlagenverordnung” regulates emissions of combustion plants with a nominal<br />

thermal output of 50 kW or more. This ordinance is based on § 82 Abs. 1 of the Gewerbeordnung.<br />

As mentioned above, steam boilers including waste heat boilers, afterburners of<br />

exhaust gases, gas turbines, combustion engines and plants using waste as fuel are not regulated<br />

by this ordinance.<br />

The “Feuerungsanlagenverordnung” provides different emission standards, depending on<br />

the fuel used and the thermal output. The emission standards for coal- and coke-firing<br />

plants, oil-fired furnaces and combustion plants for gaseous fuels are presented in the following<br />

section.<br />

a) Coal- and coke-fired plants<br />

Emission standards for furnaces using coal or coke<br />

Pollutants Capacity a [MW]<br />

�0.35 >0.35-1 >1–2 >2–10 >10-50 >50<br />

Dust [mg/m³] 150 150 150 50 50 50<br />

SO2 [mg/m³] - - - - 400 200<br />

CO [mg/m³] 1000 1000 150 150 150 150<br />

NOx [mg/m³] - 400 400 400 350 100<br />

a The capacity is defined as the average of the hourly added amount of heat related to the calorific value<br />

of the fuel<br />

The emission standards are related to dry exhaust gas at 0 °C, a pressure of 101.3 kPa and oxygen content<br />

of 6 % in the exhaust gas.<br />

350 Waste Water and Waste Gas Treatment

Hurra! Ihre Datei wurde hochgeladen und ist bereit für die Veröffentlichung.

Erfolgreich gespeichert!

Leider ist etwas schief gelaufen!