Teil 3 Seite 4-46<br />

Parameters Unit Max. Limits Measurement values<br />

COD<br />

BSB5 mg/l 7<br />

10<br />

NH4-N<br />

4.5.3.2.1<br />

mg/l 47 60<br />

Ntot mg/l 11 12<br />

mg/l 3,7 5<br />

Ptot mg/l 0,8 1<br />

Corporate clarification plant of the Kraftisried animal carcass disposal plant, 87647<br />

Unterthingau<br />

Corporate clarification plant of the Eiweiß- und Fettverwertung GmbH & Co, 49191<br />

Belm-Icker, Germany<br />

Rethmann TBA Genthin GmbH, 39<strong>307</strong> Mützel, Germany<br />

Reference literature<br />

ATV-Handbuch Industrieabwasser (Dienstleistungs und Veredelungsindustrie)<br />

ATV-Handbuch Industrieabwasser (Lebensmittelindustrie)<br />

4.5.3.2 Anaerobic methods<br />

In regard to the anaerobic treatment of wastewater and waste from the meat production,<br />

a large number of reports is available, both from industrial plants home and abroad and<br />

from numerous laboratory and semi-technical tests. The following methods have as yet<br />

been used:<br />

- Contact method (anaerobic activation method with sludge recirculation)<br />

- Fully mixed digesters without sludge recirculation (CSTR)<br />

- Anaerobic Filters<br />

- UASB systems<br />

- Periodically fed sludge bed reactor<br />

Description<br />

Anaerobic pretreatment using down-flow or up-flow reactors<br />

Passing waste water from slaughterhouses or ren<strong>der</strong>ing plants over fixed bed reactors<br />

supporting anaerobic micro-organisms on plastic rings or balls or on sintered glass, can<br />

be used as a pretreatment to reduce the COD in waste water. One technique operates as<br />

either as a down-flow or up-flow operation, incorporating recirculation. Biogas is pro-<br />

duced. The technique is unsuitable for reducing either the COD or nitrogen content suffi-