Teil 3 Seite 4-8<br />

heat exchangers, pipes and vessels, as well as contamination with oil and the use of<br />

harmful brines (e.g. ethylen glycol etc.) in high concentrations.<br />

b) Emissions: In direct expansion refrigeration plants the amount of refrigerant is<br />

high since not only the (larger) refrigeration plant but all heat exchangers including<br />

pipes are filled with refrigerant and oil. For safety reasons harmful HFC is preferred<br />

(global warming); otherwise toxic ammonia or carbon dioxide must be used, the lat-<br />

ter bringing the risk of suffocation. A leakage would release refrigerant (and oil) to<br />

the environment, and leaks from. Indirect cooling plants with toxic fluids at relatively<br />

high concentrations would be harmful. Binary Ice made from water and alcohol is in<br />

the lowest "water hazard class" and can normally be released to the sewage system<br />

with the permission of the local authorities.<br />

c) Cross-media effects: Binary Ice is an answer to the uncertain future of HFC refrig-<br />

erants and satisfies the requirements for "natural" refrigerants due to the options<br />

available. Binary Ice plants can operate with HFC, ammonia and hydrocarbons.<br />

Operational data<br />

Energy content of the fluid (enthalpy) and resulting advantages for pipes and pumps:<br />

Chilling<br />

Brine (typical) temperature difference 3 K: 11<br />

kJ/kg<br />

Binary Ice 10 % ice crystals; 3,0-fold: 33<br />

Freezing<br />

kJ/kg<br />

20 % ice crystals; 6,0-fold: 66<br />

kJ/kg<br />

Brine (typical) temperature difference 3 K: 9<br />

kJ/kg<br />

Binary Ice 10 % ice crystals; 3,7-fold: 33<br />

kJ/kg<br />

20 % ice crystals; 7,3-fold: 66<br />

kJ/kg<br />

The amount of fluid to be circulated is between 4 and 7 times higher for<br />

brine compared to Binary Ice. This has an immediate effect on pipe diame-<br />

ters, which can be approx. 50 % (!) smaller. The reduced pumping power is<br />

consi<strong>der</strong>ably reduced and is approx. 70 % (!) smaller than brine systems.