04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

4390 4-20 mA 108.2

No. Setting Range Factory

setting

Description

4391 4-20 mA

108.2

4392

4-20 mA

108.2

Set point 4 to 20 mA 10 mA The multi-input 108 has been

configured as 4-20 mA in menu

11000.

Timer 0.0 to 999.0 s 120.0 s

4393 4-20 mA

108.2

Relay output A

Not used (option

dependent)

Not used

4394 4-20 mA

108.2

Relay output B

Not used (option

dependent)

Not used

4395 4-20 mA

108.2

Enable

OFF

ON

OFF

4396

4-20 mA

108.2

Fail class F1 to F9 F2 (Warning)

4400 V DC 108.1

No. Setting Range Factory

setting

Description

4401 V DC 108.1 Set point 0.0 to 40.0 V 20 V The multi-input 108 has been

4402 V DC 108.1 Timer 0.2 to 999.0 s 10.0 s

configured as DC in menu

11000.

4403 V DC 108.1 Relay output A Not used (option

dependent)

Not used

4404 V DC 108.1 Relay output B Not used (option

dependent)

4405 V DC 108.1 Enable OFF

ON

Not used

OFF

4406 V DC 108.1 Fail class F1 to F9 F2 (Warning)

4410 V DC 108.2

No. Setting Range Factory

setting

Description

4411 V DC 108.2 Set point 0.0 to 40.0 V 20 V The multi-input 108 has been

4412 V DC 108.2 Timer 0.2 to 999.0 s 10.0 s

configured as DC in menu

11000.

4413 V DC 108.2 Relay output A Not used (option

dependent)

Not used

4414 V DC 108.2 Relay output B Not used (option

dependent)

4415 V DC 108.2 Enable OFF

ON

Not used

OFF

4416 V DC 108.2 Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 99 of 222