4360 RMI fuel level 105.2

No. Setting Range Factory

setting

Description

4361 RMI fuel

105.2

4362

RMI fuel

105.2

Set point 0 to 100 % 5 % The multi-input 105 has been

configured as RMI fuel level in

menu 10990.

Timer 0.0 to 999.0 s 10.0 s

4363 RMI fuel

105.2

Relay output A

Not used (option

dependent)

Not used

4364 RMI fuel

105.2

Relay output B

Not used (option

dependent)

Not used

4365 RMI fuel

105.2

Enable

OFF

ON

OFF

4366

RMI fuel

105.2

Fail class F1 to F9 F2 (Warning)

4370 Wire fail 105

No. Setting Range Factory

setting

Description

4371 Wire fail 105 Relay output A Not used (option

dependent)

4372 Wire fail 105 Relay output B Not used (option

dependent)

4373 Wire fail 105 Enable OFF

ON

Not used

Not used

OFF

The wire break fault detection

is activated.

4374 Wire fail 105 Fail class F1 to F9 F2 (Warning)

2.7.3 Multi-input no. 108

4380 4-20 mA 108.1

No. Setting Range Factory

setting

Description

4381 4-20 mA

108.1

4382

4-20 mA

108.1

Set point 4 to 20 mA 10 mA The multi-input 102 has been

configured as 4-20 mA in menu

11000.

Timer 0.0 to 999.0 s 120.0 s

4383 4-20 mA

108.1

Relay output A

Not used (option

dependent)

Not used

4384 4-20 mA

108.1

Relay output B

Not used (option

dependent)

Not used

4385 4-20 mA

108.1

Enable

OFF

ON

OFF

4386

4-20 mA

108.1

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 98 of 222