04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

4330 RMI water 105.1

No. Setting Range Factory

setting

Description

4331 RMI water

105.1

4332

RMI water

105.1

4333 RMI water

105.1

Set point

Timer

-49 to 482 °C

0.0 to 999.0 s

100 °C

5.0 s

The multi-input 105 has been

configured as RMI water

pressure in menu 10990.

Select C or F unit in menu

10970.

Relay output A Not used (option Not used

dependent)

4334 RMI water

105.1

Relay output B

Not used (option

dependent)

Not used

4335 RMI water

105.1

Enable

OFF

ON

OFF

4336

RMI water

105.1

Fail class F1 to F9 F2 (Warning)

4340 RMI water 105.2

No. Setting Range Factory

setting

Description

4341 RMI water

105.2

4342

RMI water

105.2

4343 RMI water

105.2

Set point

Timer

-49 to 482 °C

0.0 to 999.0 s

110 °C

5.0 s

The multi-input 105 has been

configured as RMI water

pressure in menu 10990.

Select C or F unit in menu

10970.

Relay output A Not used (option Not used

dependent)

4344 RMI water

105.2

Relay output B

Not used (option

dependent)

Not used

4345 RMI water

105.2

Enable

OFF

ON

OFF

4346

RMI water

105.2

Fail class F1 to F9 F2 (Warning)

4350 RMI fuel level 105.1

No. Setting Range Factory

setting

Description

4351 RMI fuel

105.1

4352

RMI fuel

105.1

Set point 0 to 100 % 10 % The multi-input 105 has been

configured as RMI fuel level in

menu 10990.

Timer 0.0 to 999.0 s 10.0 s

4353 RMI fuel

105.1

Relay output A

Not used (option

dependent)

Not used

4354 RMI fuel

105.1

Relay output B

Not used (option

dependent)

Not used

4355 RMI fuel

105.1

Enable

OFF

ON

OFF

4356

RMI fuel

105.1

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 97 of 222

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!