4270 V DC 105.1

No. Setting Range Factory

setting

Description

4271 V DC 105.1 Set point 0.0 to 40.0 V 20 V The multi-input 105 has been

4272 V DC 105.1 Timer 0.2 to 999.0 s 10.0 s

configured as DC in menu

10990.

4273 V DC 105.1 Relay output A Not used (option

dependent)

Not used

4274 V DC 105.1 Relay output B Not used (option

dependent)

4275 V DC 105.1 Enable OFF

ON

Not used

OFF

4276 V DC 105.1 Fail class F1 to F9 F2 (Warning)

4280 V DC 105.2

No. Setting Range Factory

setting

Description

4281 V DC 105.2 Set point 0.0 to 40.0 V 20 V The multi-input 105 has been

4282 V DC 105.2 Timer 0.2 to 999.0 s 10.0 s

configured as DC in menu

10990.

4283 V DC 105.2 Relay output A Not used (option

dependent)

Not used

4284 V DC 105.2 Relay output B Not used (option

dependent)

4285 V DC 105.2 Enable OFF

ON

Not used

OFF

4286 V DC 105.2 Fail class F1 to F9 F2 (Warning)

4290 Pt100 105.1

No. Setting Range Factory

setting

Description

4291 Pt100 105.1 Set point -49 to 482 °C 80 °C The multi-input 105 has been

4292 Pt100 105.1 Timer 0.0 to 999.0 s 5.0 s

configured as Pt100 in menu

10990.

4293 Pt100 105.1 Relay output A Not used (option

dependent)

Not used Select C or F unit in menu

10970.

4294 Pt100 105.1 Relay output B Not used (option

dependent)

4295 Pt100 105.1 Enable OFF

ON

Not used

OFF

4296 Pt100 105.1 Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 95 of 222