4240 Wire fail 102

No. Setting Range Factory

setting

Description

4241 Wire fail 102 Relay output A Not used (option

dependent)

4242 Wire fail 102 Relay output B Not used (option

dependent)

4243 Wire fail 102 Enable OFF

ON

Not used

Not used

OFF

The wire break fault detection

is activated.

4244 Wire fail 102 Fail class F1 to F9 F2 (Warning)

2.7.2 Multi-input no. 105

4250 4-20 mA 105.1

No. Setting Range Factory

setting

Description

4251 4-20 mA

105.1

4252

4-20 mA

105.1

Set point 4 to 20 mA 10 mA The multi-input 105 has been

configured as 4-20 mA in menu

10990.

Timer 0.0 to 999.0 s 120.0 s

4253 4-20 mA

105.1

Relay output A

Not used (option

dependent)

Not used

4254 4-20 mA

105.1

Relay output B

Not used (option

dependent)

Not used

4255 4-20 mA

105.1

Enable

OFF

ON

OFF

4256

4-20 mA

105.1

Fail class F1 to F9 F2 (Warning)

4260 4-20 mA 105.2

No. Setting Range Factory

setting

Description

4261 4-20 mA

105.2

4262

4-20 mA

105.2

Set point 4 to 20 mA 10 mA The multi-input 105 has been

configured as 4-20 mA in menu

10990.

Timer 0.0 to 999.0 s 120.0 s

4263 4-20 mA

105.2

Relay output A

Not used (option

dependent)

Not used

4264 4-20 mA

105.2

Relay output B

Not used (option

dependent)

Not used

4265 4-20 mA

105.2

Enable

OFF

ON

OFF

4266

4-20 mA

105.2

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 94 of 222