4180 RMI oil 102.1

No. Setting Range Factory

setting

Description

4181 RMI oil 102.1 Set point 0.0 to 145.0 bar 4.0 bar The multi-input 102 has been

4182 RMI oil 102.1 Timer 0.0 to 999.0 s 5.0 s

configured as RMI oil pressure

in menu 10980.

4183 RMI oil 102.1 Relay output A Not used (option

dependent)

Not used Select bar or PSI unit in menu

10970.

4184 RMI oil 102.1 Relay output B Not used (option

dependent)

4185 RMI oil 102.1 Enable OFF

ON

Not used

OFF

4186 RMI oil 102.1 Fail class F1 to F9 F2 (Warning)

4190 RMI oil 102.2

No. Setting Range Factory

setting

Description

4191 RMI oil 102.2 Set point 0.0 to 145.0 bar 5.0 bar The multi-input 102 has been

4192 RMI oil 102.2 Timer 0.0 to 999.0 s 5.0 s

configured as RMI oil pressure

in menu 10980.

4193 RMI oil 102.2 Relay output A Not used (option

dependent)

Not used Select bar or PSI unit in menu

10970.

4194 RMI oil 102.2 Relay output B Not used (option

dependent)

4195 RMI oil 102.2 Enable OFF

ON

Not used

OFF

4196 RMI oil 102.2 Fail class F1 to F9 F2 (Warning)

4200 RMI water 102.1

No. Setting Range Factory

setting

Description

4201 RMI water

102.1

4202

RMI water

102.1

4203 RMI water

102.1

Set point

Timer

-49 to 482 °C

0.0 to 999.0 s

100 °C

5.0 s

The multi-input 102 has been

configured as RMI water

pressure in menu 10980.

Select C or F unit in menu

10970.

Relay output A Not used (option Not used

dependent)

4204 RMI water

102.1

Relay output B

Not used (option

dependent)

Not used

4205 RMI water

102.1

Enable

OFF

ON

OFF

4206

RMI water

102.1

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 92 of 222