04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

4150 V DC 102.2

No. Setting Range Factory

setting

Description

4151 V DC 102.2 Set point 0.0 to 40.0 V 20 V The multi-input 102 has been

4152 V DC 102.2 Timer 0.2 to 999.0 s 10.0 s

configured as DC in menu

10980.

4153 V DC 102.2 Relay output A Not used (option

dependent)

Not used

4154 V DC 102.2 Relay output B Not used (option

dependent)

4155 V DC 102.2 Enable OFF

ON

Not used

OFF

4156 V DC 102.2 Fail class F1 to F9 F2 (Warning)

4160 Pt100 102.1

No. Setting Range Factory

setting

Description

4161 Pt100 102.1 Set point -49 to 482 °C 80 °C The multi-input 102 has been

4162 Pt100 102.1 Timer 0.0 to 999.0 s 5.0 s

configured as Pt100 in menu

10980.

4163 Pt100 102.1 Relay output A Not used (option

dependent)

Not used Select C or F unit in menu

10970.

4164 Pt100 102.1 Relay output B Not used (option

dependent)

4165 Pt100 102.1 Enable OFF

ON

Not used

OFF

4166 Pt100 102.1 Fail class F1 to F9 F2 (Warning)

4170 Pt100 102.2

No. Setting Range Factory

setting

Description

4171 Pt100 102.2 Set point -49 to 482 °C 80 °C The multi-input 102 has been

4172 Pt100 102.2 Timer 0.0 to 999.0 s 10.0 s

configured as Pt100 in menu

10980.

4173 Pt100 102.2 Relay output A Not used (option

dependent)

Not used Select C or F unit in menu

10970.

4174 Pt100 102.2 Relay output B Not used (option

dependent)

4175 Pt100 102.2 Enable OFF

ON

Not used

OFF

4176 Pt100 102.2 Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 91 of 222