2.7 Multi-functional analogue input setup

2.7.1 Multi-input no. 102

4120 4-20 mA 102.1

No. Setting Range Factory

setting

Description

4121 4-20 mA

102.1

4122

4-20 mA

102.1

Set point 4 to 20 mA 10 mA The multi-input 102 has been

configured as 4-20 mA in menu

10980.

Timer 0.0 to 999.0 s 120.0 s

4123 4-20 mA

102.1

Relay output A

Not used (option

dependent)

Not used

4124 4-20 mA

102.1

Relay output B

Not used (option

dependent)

Not used

4125 4-20 mA

102.1

Enable

OFF

ON

OFF

4126

4-20 mA

102.1

Fail class F1 to F9 F2 (Warning)

4130 4-20 mA 102.2

No. Setting Range Factory

setting

Description

4131 4-20 mA

102.2

4132

4-20 mA

102.2

Set point 4 to 20 mA 10 mA The multi-input 102 has been

configured as 4-20 mA in menu

10980.

Timer 0.0 to 999.0 s 120.0 s

4133 4-20 mA

102.2

Relay output A

Not used (option

dependent)

Not used

4134 4-20 mA

102.2

Relay output B

Not used (option

dependent)

Not used

4135 4-20 mA

102.2

Enable

OFF

ON

OFF

4136

4-20 mA

102.2

Fail class F1 to F9 F2 (Warning)

4140 V DC 102.1

No. Setting Range Factory

setting

Description

4141 V DC 102.1 Set point 0.0 to 40.0 V 20 V The multi-input 102 has been

4142 V DC 102.1 Timer 0.2 to 999.0 s 10.0 s

configured as DC in menu

10980.

4143 V DC 102.1 Relay output A Not used (option

dependent)

Not used

4144 V DC 102.1 Relay output B Not used (option

dependent)

4145 V DC 102.1 Enable OFF

ON

Not used

OFF

4146 V DC 102.1 Fail class F1 to F9 F2 (Warning)